01 Risk Category
01 Risk Category
Minimum Design Loads and Associated Criteria for Buildings and Other Structures 245
Table 26.13-1 Main Wind Force Resisting System and Components and Cladding (All Heights): Internal Pressure Coefficient, (GC pi ), for
Enclosed, Partially Enclosed, Partially Open, and Open Buildings (Walls and Roof)
Enclosure Classification Criteria for Enclosure Classification Internal Pressure Internal Pressure Coefficient, (GC pi )
EXCEPTION: Other testing methods and/or performance 26.15 CONSENSUS STANDARDS AND OTHER
criteria are permitted to be used when approved. REFERENCED DOCUMENTS
Glazing and impact-protective systems in buildings and other
This section lists the consensus standards and other documents
structures classified as Risk Category IV in accordance with
that shall be considered part of this standard to the extent
Section 1.5 shall comply with the “enhanced protection” require-
referenced in this chapter.
ments of Table 3 of ASTM E1996. Glazing and impact-protective
AAMA 512, Voluntary Specifications for Tornado Hazard
systems in all other structures shall comply with the “basic
Mitigating Fenestration Products, American Architectural Man-
protection” requirements of Table 3 of ASTM E1996.
ufacturers Association, 2011.
26.12.4 Multiple Classifications. If a building by definition Cited in: C26.14.4
complies with both the “open” and “partially enclosed” ANSI A58.1, Minimum Design Loads for Buildings and Other
definitions, it shall be classified as an “open” building. Structures, American National Standards Institute, 1982.
Cited in: Section C26.5.2
ASTM E1886, Standard test method for performance of
26.13 INTERNAL PRESSURE COEFFICIENTS exterior windows, curtain walls, doors, and impact protective
systems impacted by missile(s) and exposed to cyclic pressure
Internal pressure coefficients, (GCpi ), shall be determined from differentials, ASTM International, 2013.
Table 26.13-1 based on building enclosure classifications deter- Cited in: Section 26.12.3.2, C26.12, C26.14.4.
mined from Section 26.12. ASTM E1996, Standard specification for performance of
exterior windows, curtain walls, doors, and impact protective
26.13.1 Reduction Factor for Large-Volume Buildings, Ri . systems impacted by windborne debris in hurricanes, ASTM
For a partially enclosed building containing a single, International, 2014.
unpartitioned large volume, the internal pressure coefficient, Cited in: Section 26.12.3.2, C26.12, C26.14.4.
(GC pi ), shall be multiplied by the following reduction factor, Ri : ANSI/DASMA 115, Standard Method for Testing Sectional
Garage Doors: Determination of Structural Performance
Ri = 1.0 or under Missile Impact and Cyclic Wind Pressure, Door and
0 1 Access Systems Manufacturers Association International, 2005.
Cited in: Section 26.12.3.2, C26.12.
B 1 C ASTM E330, Standard Test Method for Structural Performance
Ri = 0.5@1 þ qffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiA < 1.0 (26.13-1)
1 þ 22,800Aog Vi of Exterior Windows, Doors, Skylights, and Curtain Walls by
Uniform Static Air Pressure Difference, ASTM International, 2014.
where Cited in: Section C26.5.1
CAN/CSA A123.21, Standard test method for the dynamic wind
Aog = total area of openings in the building envelope (walls and uplift resistance of membrane-roofing systems, CSA Group, 2014.
roof, in ft2 ); and Cited in: Section C26.5.1
V i = unpartitioned internal volume, in ft3 . ICC 500, ICC/NSSA Standard for the Design and Construc-
26.14 TORNADO LIMITATION tion of Storm Shelters, International Code Council and National
Storm Shelter Association, 2014.
Tornadoes have not been considered in the wind load provisions. Cited in: Section C26.14.1, C26.14.3, C26.14.4
Minimum Design Loads and Associated Criteria for Buildings and Other Structures 271
conditions and locations of buildings and other structures meet Table 26.10-1 Velocity Pressure Exposure Coefficients,
all of the following conditions: K h and K z
1. The hill, ridge, or escarpment is isolated and unobstructed Height above Ground Level, z Exposure
upwind by other similar topographic features of comparable
height for 100 times the height of the topographic feature ft m B C D
(100H) or 2 mi (3.22 km), whichever is less. This distance
shall be measured horizontally from the point at which the 0–15 0–4.6 0.57 (0.70)a 0.85 1.03
height H of the hill, ridge, or escarpment is determined. 20 6.1 0.62 (0.70)a 0.90 1.08
2. The hill, ridge, or escarpment protrudes above the height of 25 7.6 0.66 (0.70)a 0.94 1.12
upwind terrain features within a 2-mi (3.22-km) radius in 30 9.1 0.70 0.98 1.16
any quadrant by a factor of 2 or more. 40 12.2 0.76 1.04 1.22
3. The building or other structure is located as shown in 50 15.2 0.81 1.09 1.27
Fig. 26.8-1 in the upper one-half of a hill or ridge or near 60 18.0 0.85 1.13 1.31
the crest of an escarpment. 70 21.3 0.89 1.17 1.34
4. H∕Lh ≥ 0.2. 80 24.4 0.93 1.21 1.38
5. H is greater than or equal to 15 ft (4.5 m) for Exposure C 90 27.4 0.96 1.24 1.40
and D and 60 ft (18 m) for Exposure B. 100 30.5 0.99 1.26 1.43
120 36.6 1.04 1.31 1.48
26.8.2 Topographic Factor. The wind speed-up effect shall be 140 42.7 1.09 1.36 1.52
included in the calculation of design wind loads by using the 160 48.8 1.13 1.39 1.55
factor K zt : 180 54.9 1.17 1.43 1.58
K zt = ð1 þ K 1 K 2 K 3 Þ2 (26.8-1) 200 61.0 1.20 1.46 1.61
250 76.2 1.28 1.53 1.68
where K 1 , K 2 , and K 3 are given in Fig. 26.8-1. 300 91.4 1.35 1.59 1.73
If site conditions and locations of buildings and other struc- 350 106.7 1.41 1.64 1.78
tures do not meet all the conditions specified in Section 26.8.1, 400 121.9 1.47 1.69 1.82
then K zt = 1.0. 450 137.2 1.52 1.73 1.86
500 152.4 1.56 1.77 1.89
26.9 GROUND ELEVATION FACTOR a
Use 0.70 in Chapter 28, Exposure B, when z < 30 ft (9.1 m).
Notes
The ground elevation factor to adjust for air density, K e , shall be 1. The velocity pressure exposure coefficient K z may be determined from
determined in accordance with Table 26.9-1. It is permitted to the following formula:
take K e = 1 for all elevations. For 15 ft ð4.6 mÞ ≤ z ≤ zg K z = 2.01ðz∕zg Þ2∕α
For z < 15 ft ð4.6 mÞ K z = 2.01ð15∕zg Þ2∕α
26.10 VELOCITY PRESSURE 2. α and zg are tabulated in Table 26.11-1.
3. Linear interpolation for intermediate values of height z is acceptable.
26.10.1 Velocity Pressure Exposure Coefficient. Based on the 4. Exposure categories are defined in Section 26.7.
exposure category determined in Section 26.7.3, a velocity
pressure exposure coefficient, K z or K h , as applicable, shall be
determined from Table 26.10-1. For a site located in a transition between those shown in Table 26.10-1 are permitted provided
zone between exposure categories that is near to a change in that they are determined by a rational analysis method defined in
ground surface roughness, intermediate values of K z or K h , the recognized literature.
26.10.2 Velocity Pressure. Velocity pressure, qz , evaluated at
Table 26.9-1 Ground Elevation Factor, K e
height z above ground shall be calculated by the following
equation:
Ground Elevation above Sea Level
Ground Elevation
Factor
ft m Ke qz = 0.00256K z K zt K d K e V 2 ðlb∕ft2 Þ; V in mi∕h (26.10-1)
Notation
B = Horizontal dimension of building, in ft (m), measured normal to wind direction.
L = Horizontal dimension of building, in ft (m), measured parallel to wind direction.
h = Mean roof height, in ft (m), except that eave height shall be used for θ ≤ 10 degrees.
z = Height above ground, in ft (m).
G = Gust-effect factor.
qz , qh = Velocity pressure, in lb∕ ft2 (N∕ m2 ), evaluated at respective height.
θ = Angle of plane of roof from horizontal, in degrees.
FIGURE 27.3-1 Main Wind Force Resisting System, Part 1 (All Heights): External Pressure Coefficients, C p , for Enclosed and Partially
Enclosed Buildings—Walls and Roofs
continues
Minimum Design Loads and Associated Criteria for Buildings and Other Structures 275
Wall Pressure Coefficients, C p
Windward Leeward
Wind
Direction h∕L 10 15 20 25 30 35 45 ≥60c 10 15 ≥20
Notes
1. Plus and minus signs signify pressures acting toward and away from the surfaces, respectively.
2. Linear interpolation is permitted for values of L∕ B, h∕ L, and θ other than shown. Interpolation shall only be carried out between
values of the same sign. Where no value of the same sign is given, assume 0.0 for interpolation purposes.
3. Where two values of C p are listed, this indicates that the windward roof slope is subjected to either positive or negative pressures
and the roof structure shall be designed for both conditions. Interpolation for intermediate ratios of h∕ L in this case shall only be
carried out between C p values of like sign.
4. For monoslope roofs, entire roof surface is either a windward or leeward surface.
5. Refer to Fig. 27.3-2 for domes and Fig. 27.3-3 for arched roofs.
6. For mansard roofs, the top horizontal surface and leeward inclined surface shall be treated as leeward surfaces from
the table.
7. Except for MWFRSs at the roof consisting of moment-resisting frames, the total horizontal shear shall not be less than that
determined by neglecting wind forces on roof surfaces.
FIGURE 27.3-1 (Coninued ). Main Wind Force Resisting System, Part 1 (All Heights): External Pressure Coefficients, C p , for Enclosed and
Partially Enclosed Buildings—Walls and Roofs
Notation
L = Horizontal dimension of roof, measured in the along-wind direction, ft (m).
h = Mean roof height, ft (m).
γ = Direction of wind, degrees.
θ = Angle of plane of roof from horizontal, degrees.
Clear Wind Flow Obstructed Wind Flow Clear Wind Flow Obstructed Wind Flow
Notes
1. C NW and C NL denote net pressures (contributions from top and bottom surfaces) for windward and leeward half of roof surfaces,
respectively.
2. Clear wind flow denotes relatively unobstructed wind flow with blockage less than or equal to 50%. Obstructed wind flow denotes
objects below roof inhibiting wind flow (>50% blockage).
3. For values of θ between 7.5° and 45°, linear interpolation is permitted. For values of θ less than 7.5°, use load coefficients for 0°.
4. Plus and minus signs signify pressures acting toward and away from the top roof surface, respectively.
5. All load cases shown for each roof angle shall be investigated.
FIGURE 27.3-4 Main Wind Force Resisting System, Part 1 (0.25 ≤ h∕L ≤ 1.0): Net Pressure Coefficient, C N , for Open Buildings with
Monoslope Free Roofs, θ ≤ 45°, γ = 0°, 180°)
Minimum Design Loads and Associated Criteria for Buildings and Other Structures 279
Diagrams
Notation
L = Horizontal dimension of roof, measured in the along-wind direction, ft (m).
h = Mean roof height, ft (m). See Figs. 27.3-4, 27.3-5, or 27.3-6 for a graphical depiction of this dimension.
γ = Direction of wind, degrees.
θ = Angle of plane of roof from horizontal, degrees.
Notes
1. C N denotes net pressures (contributions from top and bottom surfaces).
2. Clear wind flow denotes relatively unobstructed wind flow with blockage less than or equal to 50%. Obstructed wind flow denotes
objects below roof inhibiting wind flow (>50% blockage).
3. Plus and minus signs signify pressures acting toward and away from the top roof surface, respectively.
4. All load cases shown for each roof angle shall be investigated.
5. For monoslope roofs with θ less than 5 degrees, CN values shown apply also for cases where γ = 0 degrees and 0.05 less than or
equal to h∕ L less than or equal to 0.25. See Fig. 27.3-4 for other h∕ L values.
FIGURE 27.3-7 Main Wind Force Resisting System, Part 1 (0.25 ≤ h∕L ≤ 1.0): Net Pressure Coefficient, C N ,
for Open Buildings with Free Roofs, θ ≤ 45°, γ = 90°, 270°