AN0037 Replacing An SM Ethernet Module Rev 04
AN0037 Replacing An SM Ethernet Module Rev 04
This application note will describe the procedure needed to replace an SM-Ethernet module in a
Unidrive SP or a Digitax ST with or without SM- EZMotion.
The most important thing to note is that the webpage Produced/Consumed setup details are saved in
the Ethernet module, not the drive. So if the Ethernet module is replaced, the user will need to reload
the Ethernet configuration by performing a few steps to in order to bring the system back to its
pre-failure state. This is also the case when there is a SM-EZMotion involved. The Ethernet
configuration is not saved in the PowerToolsPro program.
1. Log into the Module by typing the Ethernet Address on the browser’s address bar and entering
the default Username “root” and Password of “ut72”. The user will be prompted to change the
2. If there is a saved .pkg file Ethernet configuration, it was done by accessing the
Configuration/Backup options on the toolbar. There are 4 potential boxes to choose.
Saved module parameter values: All the internal menus, Pr60.xx, 61.xx, 62.xx, and MM.xxx.
Module specific security settings: Are all usernames, passwords, and security related functions
related to the Ethernet module and if the Decrypt option is not selected, these values may only be used
on the module they came from.
Decrypted module security settings: Allows the security settings above to be restored to any
module. This option is only available to administrative users.
3. Click on Submit, then the user will be prompted to Right Click on the Download option
4. To send the configuration file to the new module, click on the Configuration/Update options on the
toolbar and then click Browse to select the .pkg file. Press Upload.