AN0037 Replacing An SM Ethernet Module Rev 04

This document provides instructions for replacing an SM-Ethernet module in a Unidrive SP or Digitax ST drive. The key steps are: 1. Log into the new module using the default username and password. 2. Upload any saved Ethernet configuration files from the original module to the replacement module. 3. Reset the module for the new configuration to take effect. The Ethernet configuration is stored in the module, not the drive, so it must be reloaded when replacing the module. Following these steps will restore the system to its pre-failure state.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
35 views

AN0037 Replacing An SM Ethernet Module Rev 04

This document provides instructions for replacing an SM-Ethernet module in a Unidrive SP or Digitax ST drive. The key steps are: 1. Log into the new module using the default username and password. 2. Upload any saved Ethernet configuration files from the original module to the replacement module. 3. Reset the module for the new configuration to take effect. The Ethernet configuration is stored in the module, not the drive, so it must be reloaded when replacing the module. Following these steps will restore the system to its pre-failure state.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

Control Techniques

Application Note Unidrive SP,


Division of Nidec Motor Corporation
Digitax ST & SM-Ethernet
7078 Shady Oak Road
AN0037
Eden Prairie, MN 55344-3505 USA
Rev.04, 1/11/18
T: +1 952 995-8000
www.controltechniques.com

This Application Note applies to UnidriveSP and DigitaxST series drives

Reprogramming a replaced SM-Ethernet module

This application note will describe the procedure needed to replace an SM-Ethernet module in a
Unidrive SP or a Digitax ST with or without SM- EZMotion.

The most important thing to note is that the webpage Produced/Consumed setup details are saved in
the Ethernet module, not the drive. So if the Ethernet module is replaced, the user will need to reload
the Ethernet configuration by performing a few steps to in order to bring the system back to its
pre-failure state. This is also the case when there is a SM-EZMotion involved. The Ethernet
configuration is not saved in the PowerToolsPro program.

1. Log into the Module by typing the Ethernet Address on the browser’s address bar and entering
the default Username “root” and Password of “ut72”. The user will be prompted to change the

password; however you are never required to change it.

2. If there is a saved .pkg file Ethernet configuration, it was done by accessing the
Configuration/Backup options on the toolbar. There are 4 potential boxes to choose.

7078 Shady Oak Road, Eden Prairie, MN 55344-3505


+1 952 995-8000 www.controltechniques.com
1
Application configuration data: Contains information such as the drive name and the information
from the Current Application Configuration pages

Saved module parameter values: All the internal menus, Pr60.xx, 61.xx, 62.xx, and MM.xxx.

Module specific security settings: Are all usernames, passwords, and security related functions
related to the Ethernet module and if the Decrypt option is not selected, these values may only be used
on the module they came from.

Decrypted module security settings: Allows the security settings above to be restored to any
module. This option is only available to administrative users.

3. Click on Submit, then the user will be prompted to Right Click on the Download option

4. To send the configuration file to the new module, click on the Configuration/Update options on the
toolbar and then click Browse to select the .pkg file. Press Upload.

7078 Shady Oak Road, Eden Prairie, MN 55344-3505


+1 952 995-8000 www.controltechniques.com
2
5. A progress bar will appear then after the bar clears, a reset is then required. Press Apply.

6. Wait until process is complete

Resources: can be found on our website: www.controltechniques.com


For help contact [email protected], or
call Technical Support at 952-995-8000, 24/7/365

7078 Shady Oak Road, Eden Prairie, MN 55344-3505