SINAMICS SINAMICS V20 Inverter - Fault and Warning Codes
SINAMICS SINAMICS V20 Inverter - Fault and Warning Codes
Note
If there are multiple active faults and alarms, the BOP first displays all faults one after another.
Once all faults are displayed, it displays all alarms in succession.
Faults
Immediately when a fault occurs the fault icon
shows and the display transitions to the faults screen. The faults screen displays the fault
number proceeded by "F".
Acknowledging / clearing faults
• To navigate through the current list of faults, press
or
After you acknowledge or ignore the fault, the screen returns to the previous display. The fault
icon remains active until the fault is cleared / acknowledged.
Note
Under the following circumstances, the faults screen displays again:
• If the fault has not been cleared and the
If a fault is active and there has been no key press for 60 seconds, the backlight (P0070) flashes.
This document constitutes a free excerpt compiled by the user himself/herself from the documentation provided by Siemens for this product. Siemens disclaims
all liability for the completeness of this document. It shall only be used for the user's own internal purposes. It shall not be passed on to third parties. The complete
documentation can be found at:
https://www.automation.siemens.com/mdm/default.aspx?DocVersionId=50755607819&Language=en-US&TopicId=50508976395 8/8/2014
SINAMICS SINAMICS V20 Inverter
Fault and warning codes
This document constitutes a free excerpt compiled by the user himself/herself from the documentation provided by Siemens for this product. Siemens disclaims
all liability for the completeness of this document. It shall only be used for the user's own internal purposes. It shall not be passed on to third parties. The complete
documentation can be found at:
https://www.automation.siemens.com/mdm/default.aspx?DocVersionId=50755607819&Language=en-US&TopicId=50508976395 8/8/2014
SINAMICS SINAMICS V20 Inverter
Fault and warning codes
F20 The calculated DC ripple level has Check the mains supply wiring.
DC ripple too high exceeded the safe threshold. This is
commonly caused by loss of one of the
mains input phases.
This document constitutes a free excerpt compiled by the user himself/herself from the documentation provided by Siemens for this product. Siemens disclaims
all liability for the completeness of this document. It shall only be used for the user's own internal purposes. It shall not be passed on to third parties. The complete
documentation can be found at:
https://www.automation.siemens.com/mdm/default.aspx?DocVersionId=50755607819&Language=en-US&TopicId=50508976395 8/8/2014
SINAMICS SINAMICS V20 Inverter
Fault and warning codes
F51 Read or write failure while access to • Must be power-cycled to cancel this bug as
Parameter EEPROM fault EEPROM. This can also be caused by some parameters may not be read correct.
the EEPROM being full, too many
parameters have been changed.
• Factory reset and new parameterization, if
power-cycle does not remove fault.
• Change some parameters back to default
values if the EEPROM is full, then power-cycle.
• Change inverter.
Note:
• r0949 = 1: EEPROM full
• r0949 = 1000 + block No: reading data block
failed
• r0949 = 2000 + block No: reading data block
timeout
• r0949 = 3000 + block No: reading data block
CRC failed
• r0949 = 4000 + block No: writing data block
failed
• r0949 = 5000 + block No: writing data block
timeout
• r0949 = 6000 + block No: writing data block
verify failed
• r0949 = 7000 + block No: reading data block at
wrong time
• r0949 = 8000 + block No: writing data block at
wrong time
• r0949 = 9000 + block No: factory reset did not
work because restart or power failure
This document constitutes a free excerpt compiled by the user himself/herself from the documentation provided by Siemens for this product. Siemens disclaims
all liability for the completeness of this document. It shall only be used for the user's own internal purposes. It shall not be passed on to third parties. The complete
documentation can be found at:
https://www.automation.siemens.com/mdm/default.aspx?DocVersionId=50755607819&Language=en-US&TopicId=50508976395 8/8/2014
SINAMICS SINAMICS V20 Inverter
Fault and warning codes
This document constitutes a free excerpt compiled by the user himself/herself from the documentation provided by Siemens for this product. Siemens disclaims
all liability for the completeness of this document. It shall only be used for the user's own internal purposes. It shall not be passed on to third parties. The complete
documentation can be found at:
https://www.automation.siemens.com/mdm/default.aspx?DocVersionId=50755607819&Language=en-US&TopicId=50508976395 8/8/2014
SINAMICS SINAMICS V20 Inverter
Fault and warning codes
This document constitutes a free excerpt compiled by the user himself/herself from the documentation provided by Siemens for this product. Siemens disclaims
all liability for the completeness of this document. It shall only be used for the user's own internal purposes. It shall not be passed on to third parties. The complete
documentation can be found at:
https://www.automation.siemens.com/mdm/default.aspx?DocVersionId=50755607819&Language=en-US&TopicId=50508976395 8/8/2014
SINAMICS SINAMICS V20 Inverter
Fault and warning codes
F61 Parameter cloning failed. • r0949 = 0: Use an MMC / SD card with FAT16
MMC / SD card parameter • r0949 = 0: MMC / SD card not or FAT32 format , or fit an MMC / SD card to the
inverter.
cloning failed connected or incorrect card type or
the card failed to initialize for • r0949 = 1: Check the MMC / SD card (e.g., is the
automatic cloning card memory full?) - format the card again to
• r0949 = 1: Inverter data cannot write FAT16 or FAT32.
to the card. • r0949 = 2: Put the correct named file in the
• r0949 = 2: Parameter cloning file not correct directory /USER/SINAMICS/DATA.
available • r0949 = 3: Make sure file is accessible - recreate
• r0949 = 3: The MMC / SD card file if possible.
cannot read the file • r0949 = 4: File has been changed - recreate file.
• r0949 = 4: Reading data from the
clone file failed (e.g., reading failed,
data or checksum wrong)
F62 File exists but the contents are not valid Recopy and ensure operation completes.
Parameter cloning control word corruption.
contents invalid
F63 File exists but was not the correct inverter Ensure clone from compatible inverter type.
Parameter cloning type.
contents incompatible
F72 No setpoint values from USS / MODBUS Check USS / MODBUS master
USS / MODBUS setpoint during telegram off time
fault
This document constitutes a free excerpt compiled by the user himself/herself from the documentation provided by Siemens for this product. Siemens disclaims
all liability for the completeness of this document. It shall only be used for the user's own internal purposes. It shall not be passed on to third parties. The complete
documentation can be found at:
https://www.automation.siemens.com/mdm/default.aspx?DocVersionId=50755607819&Language=en-US&TopicId=50508976395 8/8/2014
SINAMICS SINAMICS V20 Inverter
Fault and warning codes
F101 Software error or processor failure. Contact service department or change inverter.
Stack overflow
F350 During startup the inverter checks if the Internal failures cannot be fixed.
Configuration vector for the configuration vector (SZL vector) has r0949 = 13 - Make sure the right power module is
inverter failed been programmed correctly and if fitted.
hardware matches the programmed
Note:
vector. If not the inverter will trip.
Fault needs power-cycle to be acknowledged.
• r0949 = 1: Internal failure - no
hardware configuration vector
available.
• r0949 = 2: Internal failure - no
software configuration vector
available.
• r0949 = 11: Internal failure - inverter
code not supported.
• r0949 = 12: Internal failure -
software vector not possible.
• r0949 = 13: Wrong power module
fitted.
• r0949 > 1000: Internal failure -
wrong I/O board fitted.
F395 This fault occurs after a startup clone. It The current parameter set needs to be checked and
Acceptance test / can also be caused by a faulty read from confirmed by clearing the fault.
confirmation pending the EEPROM, see F51 for more details.
A startup clone could have changed and
might not match the application.
This parameter set needs to be checked
before the inverter can start a motor.
• r0949 = 3/4: Inverter data change
• r0949 = 5: Startup clone via an
MMC / SD card has been performed
• r0949 = 10: Previous startup clone
was aborted
F410 Conditions exist for cavitation damage. If cavitation is not occurring, reduce the cavitation
Cavitation protection failure Cavitation damage is damage caused to threshhold P2361, or increase the cavitation
a pump in pumping systems when the protection delay. Ensure sensor feedback is working.
fluid is not flowing sufficiently. This can
lead to heat build up and subsequent
damage to the pump.
This document constitutes a free excerpt compiled by the user himself/herself from the documentation provided by Siemens for this product. Siemens disclaims
all liability for the completeness of this document. It shall only be used for the user's own internal purposes. It shall not be passed on to third parties. The complete
documentation can be found at:
https://www.automation.siemens.com/mdm/default.aspx?DocVersionId=50755607819&Language=en-US&TopicId=50508976395 8/8/2014
SINAMICS SINAMICS V20 Inverter
Fault and warning codes
Alarms
If an alarm is activated the alarm icon
shows immediately and then the display shows the alarm code proceeded by "A".
Note
Note that alarms cannot be acknowledged. They are cleared automatically once the warning
has been rectified.
This document constitutes a free excerpt compiled by the user himself/herself from the documentation provided by Siemens for this product. Siemens disclaims
all liability for the completeness of this document. It shall only be used for the user's own internal purposes. It shall not be passed on to third parties. The complete
documentation can be found at:
https://www.automation.siemens.com/mdm/default.aspx?DocVersionId=50755607819&Language=en-US&TopicId=50508976395 8/8/2014
SINAMICS SINAMICS V20 Inverter
Fault and warning codes
• Small motors (120 W) under FCC Use V/f operation for very small motors
and light load may cause a high
current
A502 Overvoltage limit is reached. This If this warning is displayed permanently, check
Overvoltage limit warning can occur during ramp down, if inverter input voltage.
the Vdc controller is disabled (P1240 =
0).
A505 Warning level exceeded, current will be Check that load cycle lies within specified limits.
Inverter I2t reduced if parameterized (P0610 = 1).
A506 Overload warning. Difference between Check that load steps and shock loads lie within
IGBT junction temperature heat sink and IGBT junction temperature specified limits.
rise warning exceeds warning limits.
A507 Inverter heat sink temperature signal Contact service department or change inverter.
Inverter temperature signal loss. Possible sensor fallen off.
lost
This document constitutes a free excerpt compiled by the user himself/herself from the documentation provided by Siemens for this product. Siemens disclaims
all liability for the completeness of this document. It shall only be used for the user's own internal purposes. It shall not be passed on to third parties. The complete
documentation can be found at:
https://www.automation.siemens.com/mdm/default.aspx?DocVersionId=50755607819&Language=en-US&TopicId=50508976395 8/8/2014
SINAMICS SINAMICS V20 Inverter
Fault and warning codes
A535 The braking energy is too large. Reduce the braking energy.
Braking resistor overload The braking resistor is not suited for the Use a braking resistor with a higher rating.
application.
This document constitutes a free excerpt compiled by the user himself/herself from the documentation provided by Siemens for this product. Siemens disclaims
all liability for the completeness of this document. It shall only be used for the user's own internal purposes. It shall not be passed on to third parties. The complete
documentation can be found at:
https://www.automation.siemens.com/mdm/default.aspx?DocVersionId=50755607819&Language=en-US&TopicId=50508976395 8/8/2014
SINAMICS SINAMICS V20 Inverter
Fault and warning codes
A922 No Load is applied to the inverter. Check that motor is connected to inverter.
No load applied to inverter As a result, some functions may not work
as under normal load conditions.
A923 Both JOG right and JOG left (P1055 / Do not press JOG right and left simultaneously.
Both JOG left and JOG P1056) have been requested. This
right are requested freezes the RFG output frequency at its
current value.
A936 PID autotuning (P2350) selected or Warning disappears when PID autotuning has
PID autotuning active running finished.