CR CF - 50 60Hz MS0124A 0121 - Lo

Dunham-Bush manufactures low noise fan coil units with cooling capacities from 100 to 1940 cfm. As a 120-year-old global manufacturer of HVAC/R equipment, Dunham-Bush offers a wide range of products and has manufacturing facilities around the world. The document provides details on Dunham-Bush's fan coil units, including their materials, efficiency features, options, and history of innovations.

Uploaded by

MARCOS
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
557 views20 pages

CR CF - 50 60Hz MS0124A 0121 - Lo

Dunham-Bush manufactures low noise fan coil units with cooling capacities from 100 to 1940 cfm. As a 120-year-old global manufacturer of HVAC/R equipment, Dunham-Bush offers a wide range of products and has manufacturing facilities around the world. The document provides details on Dunham-Bush's fan coil units, including their materials, efficiency features, options, and history of innovations.

Uploaded by

MARCOS
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 20

Low Noise Fan Coil Units

CR Series 50/60Hz
Air Volume: 100 to 1940 cfm (176 to 3300 m3/hr)

Dunham-Bush Air Conditioning

CR-CB/CF

CR-CC

CR-WM

CR-CE
CR-FB
MILESTONE

UNITED KINGDOM

SAUDI ARABIA INDIA


UNITED ARAB
EMIRATES
GUATEMALA USA

ECUADOR

PERU
BRAZIL
BOLIVIA
SOUTH AFRICA
URUGUAY

Dunham-Bush Profile
Dunham-Bush, one of the world’s top commercial air conditioning manufacturers, has long been
committed to offering creative solutions for the customer’s requirements over its 120 years history in
the HVAC/R. Dunham-Bush offers a complete range of HVAC/R products such as large chillers,
unitary, airside system and thermal energy storages for residences, commercial buildings and
industrial facilities. Dunham-Bush is striving to be the leader in the commercialization of green
technologies. Today, by utilizing our global network of sales and service offices, Dunham-Bush is
offering our value-added products and solutions to all corners of the world.

Manufactured the
air conditioner.

Developed the first reciprocating


compressor.
Developed the first air compressor system.

1894
Built in USA as a professional manufacturer of
HVAC/R equipments.
Today
and Innovations...
Beyond never ends

2019 Dunham-Bush built factory in


CHINA Miami, USA

2014 Dunham-Bush launched


oil free magnetic bearing
chiller.

2013 New compressor R&D center was


founded in UK to engage in high
tier compressor technology.

2008 Dunham-Bush launched its


new logo to match its new global
MALAYSIA brand & business strategy.

2007 Dunham-Bush launched


high efficiency dual stage
centrifugal chiller.

Dunham-Bush built factory in Kajang, Malaysia.


Later built Global Headquarters there in 2000.

Hartford Compressors Incorporated


was built in USA.

Dunham-Bush built factory in


Yantai, China.

Patented the technology to use


a screw compressor for
refrigeration / cooling.
Dunham-Bush built factory in
Connecticut, USA.

Dunham-Bush built factory in


Havant, United Kingdom.

first air cooled


DUNHAM-BUSH MALAYSIA
Dunham-Bush Malaysia; founded in 1987, adhered to the innovation system of focusing
on customers’ demands to drive global research & design, and superior quality
manufacturing. Nowadays Dunham-Bush Malaysia are creating innovative cooling
solutions appropriate to the individual requirements of commercial building, schools,
hospitals, airports, factories and residences. No matter where you are, what we deliver
is the same: high performing, highly engineered cooling solutions developed to take on
the challenges of the 21st century.
INTRODUCTION
CR

Dunham-Bush's fan coil unit are high performance, low noise, large air volume and cooling capacity, and flexible left and right water
connections. Currently there are more than 500 types of models with a wide cooling capacity selection. All fan coils have undergone rigorous
testing before leaving the factory. Dunham Bush fan coil continue to lead the market in the air conditioning and refrigeration industry with
cutting edge design, precise manufacturing and excellent performance.

Meticulously Made With High-Quality Materials Energy Efficiency


The unit are made using high-quality galvanized steel sheets US patented computer selection technology to ensure an
and are carefully processed by precision CNC machine tools.The efficient operation. The fan coil fan is a forward multi-blade
structure is compact and beautiful designed. PE centrifugal fan, which is manufactured by a well-known fan
insulation strips added to enhance the sealing and shock manufacturer who expertly designed according to the
absorption, allow easy maintenance and detachability. aerodynamic principle to ensure the fan is light weight, high
efficiency and low noise.

Coil
All coils are of seamless copper tubes, with corrugated Options And Accessories
hydrophilic coated fin for improved condensed draining and
1) Thermostat- LCD or Mechanical
giving excellent heat transfer. The surface design of this
2) Filter - Nylon Mesh Filter or Carbon Filter
“self-cleaning” corrugated fin create a vortex flow which make
3) 2-way motorized valve (shipped loose)
dust difficult to accumulate, and its heat exchange efficiency
4) Flexible pipe connector - For easy connection, eliminate
will not be affected even after used for a long time. All coil are
vibration and reduce noise level
leak tested at 2.4 MPa air pressure and are suitable for up to 1.6
5) UV light - Produce germicidal effects to remove airborne
MPa working pressure. The water inlet and outlet hexagonal
bacteria and germs
connectors are of brass material. The water flow connection
6) Extended Drain Pan
are easy to install on site.

Nomenclature
6 CR H 03 CB 3 DW

6 : 60Hz
AC Motor (3 Speed)
Blank : 50Hz

Fan Coil Unit


Coil Rows
2 - 2 Rows
H : High Static
3 - 3 Rows
Blank : Standard
4 - 4 Rows

Unit Model
Notes:
Type 1. Left hand or Right hand piping connection is determined by
CB - Ceiling concealed (12Pa) facing the supply air.
CBP - Ceiling concealed with back return air plenum (0Pa) 2. Standard unit coil inlet and outlet are in the same
CBPD - Ceiling concealed with bottom return air plenum (0Pa) direction as drain pipe. Concealed unit, the water inlet and
HB - Ceiling concealed (30Pa) outlet same direction as the junction box. For exposed
HBP - Ceiling concealed with back return air plenum (20Pa) unit, the water inlet outlet is opposite direction to the
HBPD - Ceiling concealed with bottom return air plenum (20Pa) junction box.
HBS - Ceiling concealed (50Pa) 3. The unit with return air box can be equipped with a filter, and
HBSP - Ceiling concealed with back return air plenum (40Pa) the filter can be based on customer requirements.
HBSPD - Ceiling concealed with bottom return air plenum (40Pa)
- Ceiling concealed (70Pa) 4. High static pressure type (CRH) includes: CBP / CBPD (2 rows
HBZ
- Ceiling concealed with back return air plenum (60Pa) / 3 rows / 4 rows)Among them, the height of the high static
HBZP
pressure fan coil (CRH series) has increased, its allow
HBZPD - Ceiling concealed with bottom return air plenum (60Pa)
Higher air pressure and larger air volume, able to supply
FB - Vertical concealed
air to long-distance , and allow multi-channel air
CE - Ceiling exposed
supply, multi-channel return air, this fan coil is
WM - Wall mounted
especially suitable for household centralize air conditioning.
CCIIH1-Y - Ceiling Cassette
5. Motor is 220V (±10%) / 1PH/ 50-60Hz.

04
INTRODUCTION
CR-CF

Dunham-Bush low noise fan coil unit not only have the advantages of standard fan coil units, it also processes large air volume, high cooling
capacity , convenient left and right water pipes connection, ultra quiet operation and high efficiency.These units are widely use in luxury
hotels, offices, business centres, hospital, high-end villas, apartments and condominium. With the technology advancement and excellent
performance, Dunham-Bush Fan Coil Units has been continuously maintaining its leading position in the air-conditioning industry.

CRCF-AW Variable Speed DC Motor CRCF-BW Three Speed DC Motor


40% less power consumption than 40% less power consumption than
conventional AC motors. conventional AC motors.
Using 0-10V signal control. The With the analog voltage control
controller provides different voltage method, users can manually select
signals to the motor to adjust the air automatic mode or the three speeds
flow through the room temperature high, medium and low speed. When
feedback to smoother the temperature automatic mode is selected, the
transition and provide comfortable controller automatically switches
experience for the user. The picture is for reference between high, middle and low speed The picture is for reference
only. The thermostat design through room temperature feedback. only. The thermostat design
Indoor temperature requirement can might be different for might be different for
be meet by changing the high and low function. Adjust the airflow by dialing the code to function.
speeds. meet the indoor temperature
requirements.
Indoor temperature requirement can
Ultra Quiet Operation be meet by changing the airflow using
Ultra-low noise. Specially studies and research to ensure the code.
unit's operating noise is 1-3dB (A) lower than other
conventional fan coil unit.

Nomenclature
6 CR 04 CF 3 DW

6 : 60Hz DW - AC Motor (3 Speed)


Blank : 50Hz BW - DC Motor (3 Speed)
AW - DC Motor (Variable Speed)
Fan Coil Unit
Coil Rows
Unit Model 2 - 2 Rows
3 - 3 Rows
4 - 4 Rows
Type
CF - Ceiling concealed (12Pa)
CFP - Ceiling concealed with back return air plenum (0Pa)
CFPD - Ceiling concealed with bottom return air plenum (0Pa)
HF - Ceiling concealed (30Pa)
HFP - Ceiling concealed with back return air plenum (20Pa)
HFPD - Ceiling concealed with bottom return air plenum (20Pa)
HFS - Ceiling concealed (50Pa)
HFSP - Ceiling concealed with back return air plenum (40Pa) Notes:
HFSPD - Ceiling concealed with bottom return air plenum (40Pa) 1. Left hand or Right hand piping connection is determined by facing the supply
HFZ - Ceiling concealed (70Pa) air.
HFZP - Ceiling concealed with back return air plenum (60Pa) 2. Standard unit coil inlet and outlet are in the same direction as drain pipe.
HFZPD - Ceiling concealed with bottom return air plenum (60Pa) 3. Motor is 220V (±10%) / 1PH/ 50-60Hz.

05
SPECIFICATIONS
CR

CR-CB/ HB/ HBS/ HBZ/ FB - 1 Row, 2 Rows, 3 Rows


Model 02 03 04 05 06 07 08 10 12 14
1 Row
Heating (kW) 1.9 2.6 3.3 3.6 4.3 5.2 6.1 6.9 8.3 9.7
Water Flowrate (l/min) 3.4 4.7 6.0 5.9 7.3 9.1 11.0 12.8 14.6 17.5
Water Pressure Drop (kPa) 6.6 13.2 23.7 3.7 6.2 10.2 17.0 23.1 11.6 17.9
2 Rows
High Speed 340 510 680 850 1020 1190 1360 1700 2040 2380
Air Flow
Medium Speed 270 406 518 661 770 893 1016 1307 1552 1770
(m³/h)
Low Speed 176 261 348 447 509 595 687 880 1009 1173
CB- 12Pa, CBP/ CBPD- 0Pa 35.5 36.5 38.5 42 44.2 46 45.5 48 49 52
Noise Level HB- 30Pa, HBP/ HBPD- 20Pa 39.5 41 42.5 45.5 46 48 47 50 52 54
dB(A) HBS- 50Pa, HBSP/ HBSPD- 40Pa 42 44 45 47 48 50 49 52 54 56
HBZ- 70Pa, HBZP/ HBZPD- 60Pa 44 46.5 48 49 50 53 53 54 56 58
Sensible Cooling (kW) 1.2 1.7 2.1 2.6 3.0 3.6 4.0 4.7 5.8 6.8
Total Cooling (kW) 1.8 2.5 3.2 4.1 4.5 5.5 6.0 7.0 9.0 10.7
Heating (kW) 3.0 4.3 5.4 6.7 7.7 9.3 10.4 12.0 14.9 17.4
Water Flowrate (l/min) 5.0 7.3 9.3 11.6 13.0 16.0 17.1 20.1 25.7 30.9
Water Pressure Drop (kPa) 5.1 11.1 19.7 30.0 14.8 23.9 14.6 20.1 37.8 50.0
Blower Qty 1 2 2 2 2 2 4 4 4 4
Motor Qty 1 1 1 1 1 1 2 2 2 2
Power Supply 220V/1P/50-60Hz
CB- 12Pa, CBP/ CBPD- 0Pa 27 40 60 74 94 112 132 148 191 230
Power Input HB- 30Pa, HBP/ HBPD- 20Pa 43 57 72 85 109 118 148 173 206 257
(W) HBS- 50Pa, HBSP/ HBSPD- 40Pa 48 65 81 97 116 128 171 193 243 293
HBZ- 70Pa, HBZP/ HBZPD- 60Pa 55 71 92 111 126 180 183 230 277 330
Vertical Concealed 19 22.7 24.5 26.5 28.3 30.6 39.1 41.2 47.9 62.6
Unit Weight
Ceiling Concealed without R/A Plenum 9.3 10.9 15.8 16.6 17.5 20.0 25.6 28.2 32.8 34.6
(kg)
Ceiling Concealed with R/A Plenum 13.4 15.4 20.7 21.9 23.2 26.3 32.7 35.6 41.5 44.1
3 Rows
High Speed 340 510 680 850 1020 1190 1360 1700 2040 2380
Air Flow
Medium Speed 270 406 518 661 770 893 1016 1307 1552 1770
(m³/h)
Low Speed 176 261 348 447 509 595 687 880 1009 1173
CB- 12Pa, CBP/ CBPD- 0Pa 35.5 36.5 38.5 42 44.2 46 45.5 48 49 52
Noise Level HB- 30Pa, HBP/ HBPD- 20Pa 39.5 41 42.5 45.5 46 48 47 50 52 54
dB(A) HBS- 50Pa, HBSP/ HBSPD- 40Pa 42 44 45 47 48 50 49 52 54 56
HBZ- 70Pa, HBZP/ HBZPD- 60Pa 44 46.5 48 49 50 53 53 54 56 58
Sensible Cooling (kW) 1.4 2.0 2.6 3.1 3.5 4.4 5.1 6.0 7.1 8.4
Total Cooling (kW) 2.2 3.2 4.1 4.8 5.4 6.7 7.9 9.4 11.1 13.1
Heating (kW) 3.6 5.1 6.4 7.9 9.3 11.1 12.5 14.9 17.9 20.9
Water Flowrate (l/min) 6.5 9.0 11.6 13.9 15.7 19.3 22.6 27.0 31.7 37.8
Water Pressure Drop (kPa) 11.8 24.3 30.0 22.1 27.2 22.6 34.2 40.0 25.8 39.5
Blower Qty 1 2 2 2 2 2 4 4 4 4
Motor Qty 1 1 1 1 1 1 2 2 2 2
Power Supply 220V/1P/50-60Hz
CB- 12Pa, CBP/ CBPD- 0Pa 27 40 60 74 94 112 132 148 191 230
Power Input HB- 30Pa, HBP/ HBPD- 20Pa 43 57 72 85 109 118 148 173 206 257
(W) HBS- 50Pa, HBSP/ HBSPD- 40Pa 48 65 81 97 116 128 171 193 243 293
HBZ- 70Pa, HBZP/ HBZPD- 60Pa 55 71 92 111 126 180 183 230 277 330
Vertical Concealed 19.9 23.7 25.5 27.7 30 32.8 41.1 43.2 50.4 66.1
Unit Weight
Ceiling Concealed without R/A Plenum 10.2 11.9 16.8 17.8 19.2 22.2 27.6 30.2 35.3 38.1
(kg)
Ceiling Concealed with R/A Plenum 14.3 16.4 21.7 23.1 24.9 28.5 34.7 37.6 44.0 47.6

Notes: 1) High speed air flow corresponds to the respective external static pressure which is measured with unit without R/A plenum.
2) Cooling capacity is based on entering air temperature 27°C DB/ 19.5°C WB and water inlet/ outlet temperature 7°C/ 12°C, at high speed airflow.
3) Heating capacity is based on entering air temperature 21°C and water entering temperature 60°C. Water flowrate and airflow are identical to cooling mode.
4) Refer to Page 23: Total Capacity Correction Factor for other airflow.
5) Noise data is based on high speed under lab testing condition.

PAGE 06 Products that perform...By people who care


SPECIFICATIONS
CR

CR-CB/ HB/ HBS/ HBZ - 4 Rows


Model 02 03 04 05 06 07 08 10 12 14
CB- 12Pa, CBP/ CBPD- 0Pa 36.5 37 41 43 44 46 46 48 50 52
Noise Level HB- 30Pa, HBP/ HBPD- 20Pa 40 41 43 46 46 47 48 50 52 54
dB(A) HBS- 50Pa, HBSP/ HBSPD- 40Pa 42 44 46 47 49 50 50 52 54 56
HBZ- 70Pa, HBZP/ HBZPD- 60Pa 43.5 46.4 46.4 48.5 49.7 52 53 54.3 55.1 57
Power Supply 220V/1P/50-60Hz
CB- 12Pa, CBP/ CBPD- 0Pa 35 46 59 76 98 114 132 152 189 228
Power Input HB- 30Pa, HBP/ HBPD- 20Pa 42 59 72 87 108 125 144 174 212 253
(W) HBS- 50Pa, HBSP/ HBSPD- 40Pa 48 63 84 100 118 136 164 210 250 300
HBZ- 70Pa, HBZP/ HBZPD- 60Pa 53 79 91 106 183 174 182 263 256 299
Unit Weight Ceiling Concealed without R/A Plenum 11.1 12.9 17.8 19 20.4 23.8 29.8 32.2 37.8 41.6
(kg) Ceiling Concealed with R/A Plenum 15.2 17.4 22.7 24.3 26.1 30.1 36.9 39.6 46.5 51.1
Notes: 1) 4 Rows model includes type 2+2 and 3+1. Refer to respective tables of 1 row, 2 rows and 3 rows cooling/ heating coils for the airflow, capacity, water flowrate and
water pressure drop.
2) Noise data is based on high speed under lab testing condition.

CR-CCIIH1-Y
Model 02 03 04 05 06 08 10 12 14
Cooling kW 1.8 2.7 3.6 4.5 5.4 7.2 9.0 10.8 12.6
Heating kW 2.7 4.1 5.4 6.8 8.1 10.8 13.9 16.2 18.9
Capacity
Water Flowrate l/min 0.3 0.5 0.6 0.8 0.9 1.2 1.7 1.9 2.2
Water Pressure Drop kPa 30 30 30 30 40 40 40 40 50
High Speed m³/h 340 510 680 850 1020 1360 1700 2040 2380
Air Flow Medium Speed m³/h 255 383 510 638 765 1020 1275 1530 1785
Low Speed m³/h 170 255 340 425 510 680 950 1020 1190
Noise Level dB (A) 37 39 41 43 45 46 48 50 52
Blower Quantity 1 1 1 1 1 1 1 1 1
Power Supply 220V/1Ph/50-60Hz
Quontity 1 1 1 1 1 1 1 1 1
Motor
Power Input w 36 50 60 74 93 130 147 183 221
Net Weight kg 20 20 20 26 26 26 36 36 36
Notes: 1) Air volume is defined as external pressure 0 Pa.
2) Cooling capacity is based in water inlet/outlet temperature of 7°C/ 12°C, air entering temperature 27°C DB/ 19.5°C WB, and air volume during high speed (external
pressure as 0Pa) standard.
3) Heating capacity is based on water entering temperature of 60°C and air entering temperature 21°C.
4) Total cooling load, sensible heating cooling load and total heating load under different air volume can be obtained according to correction factor chart.
5) Noise data is based on high speed testing condition.

CR-CE
Model 03 04 05 06 08 10 12
Total Cooling kW 2.7 3.6 4.5 5.5 7.4 9.0 10.8
Heating kW 4.1 5.4 6.8 8.1 10.8 13.5 16.2
Capacity
Water Flowrate l/min 0.5 0.6 0.8 0.9 1.2 1.7 1.9
Water Pressure Drop kPa 30 30 30 40 40 40 40
High Speed m³/h 510 680 850 1020 1360 1700 2040
Air Flow Medium Speed m³/h 383 510 638 765 1020 1275 1530
Low Speed m³/h 255 340 425 510 680 850 1020
Noise Level dB (A) 39 41 43 45 46 48 50
Blower Quantity. 1 2 2 2 3 4 4
Power Supply 220V/ 1P/ 50-60Hz
Quantity 1 1 1 1 2 2 2
Motor
Power Input W 50 60 74 93 130 147 183
Net Weight kg 21 26 26 38 38 44 44
Notes: 1) Air volume is defined as external pressure 0 Pa.
2) Cooling capacity is based on water inlet/outlet temperature of 7°C/ 12°C, air entering temperature 27°C DB/ 19.5°C WB, and air volume during high speed (external
pressure as 0Pa) standard
3) Heating capacity is based on water entering temperature of 60°C and air entering temperature 21°C.
4) Total cooling load, sensible heating cooling load and total heating load under different air volume can be obtained according to correction factor chart.
5) Noise data is based on high speed testing condition.

Products that perform...By people who care 07 PAGE


SPECIFICATIONS
CR

CR-WM
Model 03 05 06 08
High Speed kW 2.7 4.5 5.4 7.2
Cooling Capacity Medium Speed kW 2.3 3.8 4.6 6.1
Low Speed kW 1.8 2.9 3.5 4.7
High Speed kW 4.1 6.8 8.2 10.8
Heating Capacity Medium Speed kW 3.5 5.8 7.0 9.2
Low Speed kW 2.6 4.4 5.3 7.0
High Speed m³/h 510 850 1020 1360
Air Flow Medium Speed m³/h 383 638 765 1020
Low Speed m³/h 255 425 510 680
Water Flowrate l/min 10.2 15.8 18.0 23.2
Water Pressure Drop kPa 30 30 40 40
Blower Fan Qty 1 1 1 1
Power Supply 220V/1Ph/50-60Hz
Motor Input Power W 52 76 96 134
Qty 1 1 1 1
Noise Level dB(A) 42 47 47 49
Control Mode Remote control or wired wall pad
Unit Dimension WxDxH mm 850x300x198 970x315x235 970x315x235 1100x330x235
Net Weight kg 11 15 16 20
In Inch RC1/2” RC1/2” RC1/2” RC1/2”
Water Connection Out inch RC1/2” RC1/2” RC1/2” RC1/2”
Drain Pipe inch R1/2” R1/2” R1/2” R1/2”
Notes: 1) Cooling capacity is based on water inlet/outlet temperature of 7°C/ 12°C, air entering temperature 27°C DB/ 19.5°C WB.
2) Heating capacity is based on water entering temperature of 60°C and air entering temperature 21°C.
3) External Static Pressure: 50Pa is optional.
4) Noise level is tested in full-anechoic room.

CRH-CBP/ CBPD
Air Flow (m³/h) Capacity Motor
External
Noise Unit Net
Static Water Blower Power
Model Level Total Sensible Water Weight
Pressure High Hi Med Medium Low Heating Pressure Qty Supply Power
dB(A) Cooling Heating Flowrate Qty (kg)
(Pa) Speed Speed Speed Speed (kW) Drop Input (W)
(kW) (kW) (l/min)
(kPa)
110 1500 1200 970 - 60 5.22 3.90 9.87 15.00 6.72 2 1 303 38
08
80 - 1500 1150 960 60 5.22 3.90 9.87 15.00 6.72 2 1 287 38
2Rows 130 2400 2000 1700 - 62 8.32 6.15 15.35 24.00 12.38 2 1 502 50
CBP 14
CBPD 100 - 2400 1900 1700 62 8.32 6.15 15.35 24.00 12.38 2 1 485 50
165 3300 2900 2200 - 64 12.04 8.67 21.10 34.20 29.00 3 2 781 65
18
125 - 3300 2600 2200 64 12.04 8.67 21.10 34.20 29.00 3 2 738 65
100 1500 1200 970 - 60 7.76 5.30 13.19 22.20 18.71 2 1 303 40
08
70 - 1500 1200 960 60 7.76 5.30 13.19 22.20 18.71 2 1 287 40
3Rows 115 2400 2000 1700 - 62 10.81 7.76 19.87 31.20 9.86 2 1 502 52
220V/ 1P/
CBP 14
85 - 2400 1900 1700 62 10.81 7.76 19.87 31.20 9.86 2 50- 60Hz 1 485 52
CBPD
150 3300 2900 2200 - 64 16.03 11.13 27.45 46.20 24.16 3 2 781 69
18
110 - 3300 2600 2200 64 16.03 11.13 27.45 46.20 24.16 3 2 738 69
90 1500 1200 970 - 60 9.43 6.24 15.32 27.00 34.47 2 1 303 43
08
60 - 1500 1150 960 60 9.43 6.24 15.32 27.00 34.47 2 1 287 43
4Rows 100 2400 2000 1700 - 62 12.66 8.91 22.94 36.60 8.02 2 1 502 55
CBP 14
CBPD 70 - 2400 1900 1700 62 12.66 8.91 22.94 36.60 8.02 2 1 485 55
135 3300 2900 2200 - 64 17.90 12.39 31.59 51.60 18.16 3 2 781 73
18
95 - 3300 2600 2200 64 17.90 12.39 31.59 51.60 18.16 3 2 738 73
Notes: 1) Air volume is based on unit nominal external static pressure.
2) Cooling capacity is based on water inlet/outlet temperature of 7°C/ 12°C and entering air temperature 27°C DB/ 19.5°C WB
3) Heating capacity is based on water entering temperature of 60°C and air entering temperature of 21°C.
4) Total cooling load, sensible heating cooling load and total heating load under different air volume can be obtained according to correction factor chart.
5) Noise level data is based on nominal air pressure testing condition.
6) Customer can opt for 2 rows hot water coil install at unit air outlet.

PAGE 08 Products that perform...By people who care


SPECIFICATIONS
CR

CR Series - AHRI
Model 02 03 04 05 06 07 08 10 12 14
2 Rows
High Speed 340 510 680 850 1020 1190 1360 1700 2040 2380
Air Flow (m³/h) Medium Speed 270 406 518 661 770 893 1016 1307 1552 1770
Low Speed 176 261 348 447 509 595 687 880 1009 1173
Sensible Cooling (kW) 1.1 1.6 2.0 2.5 2.9 3.5 3.8 4.6 5.7 6.7
Total Cooling (kW) 1.5 2.1 3.3 4.1 4.5 4.6 6.0 7.0 9.1 10.7
Heating (kW) 3.0 4.1 5.3 6.6 7.5 8.9 10.2 12.0 14.9 17.3
Water Flowrate (l/min) 4.2 5.3 7.2 9.1 9.8 12.0 13.3 15.9 20.1 23.9
Water Pressure Drop (kPa) 4.4 7.4 14.2 23.7 10.7 17.9 11.2 15.6 28.0 41.7
Blower Qty 1 2 2 2 2 2 4 4 4 4
Motor Qty 1 1 1 1 1 1 2 2 2 2
Power Supply 220V/1P/50Hz
12Pa 27 40 60 74 94 112 132 148 191 230
30Pa 43 57 72 85 109 118 148 173 206 257
Power Input (W)
50Pa 48 65 81 97 116 128 171 193 243 293
70Pa 55 71 92 111 126 180 183 230 277 330
Power Supply 220V/1P/60Hz
12Pa 44 56 70 109 124 152 147 195 239 294
30Pa 45 65 75 115 117 168 156 195 247 303
Power Input (W)
50Pa 49 76 102 126 131 188 197 224 278 315
70Pa 58 77 101 121 156 182 192 243 293 366
Ceiling Concealed without R/A Plenum 9.3 10.9 15.8 16.6 17.5 20.0 25.6 28.2 32.8 34.6
Unit Weight (kg)
Ceiling Concealed with R/A Plenum 13.4 15.4 20.7 21.9 23.2 26.3 32.7 35.6 41.5 44.1
3 Rows
High Speed 340 510 680 850 1020 1190 1360 1700 2040 2380
Air Flow (m³/h) Medium Speed 270 406 518 661 770 893 1016 1307 1552 1770
Low Speed 176 261 348 447 509 595 687 880 1009 1173
Sensible Cooling (kW) 1.4 1.9 2.5 3.0 3.6 4.1 4.8 5.8 6.9 8.0
Total Cooling (kW) 2.1 2.8 3.6 4.2 5.1 5.7 6.9 8.2 9.6 11.3
Heating (kW) 3.8 5.1 6.5 8.0 9.5 10.8 12.7 15.1 18.0 20.9
Water Flowrate (l/min) 5.8 7.2 9.1 11.0 13.3 15.0 17.8 21.2 25.0 29.2
Water Pressure Drop (kPa) 11.0 18.2 31.0 16.8 25.9 18.0 26.9 37.0 20.8 30.1
Blower Qty 1 2 2 2 2 2 4 4 4 4
Motor Qty 1 1 1 1 1 1 2 2 2 2
Power Supply 220V/1P/50Hz
12Pa 27 40 60 74 94 112 132 148 191 230
30Pa 43 57 72 85 109 118 148 173 206 257
Power Input (W)
50Pa 48 65 81 97 116 128 171 193 243 293
70Pa 55 71 92 111 126 180 183 230 277 330
Power Supply 220V/1P/60Hz
12Pa 44 56 70 109 124 152 147 195 239 294
30Pa 45 65 75 115 117 168 156 195 247 303
Power Input (W)
50Pa 49 76 102 126 131 188 197 224 278 315
70Pa 58 77 101 121 156 182 192 243 293 366
Ceiling Concealed without R/A Plenum 10.2 11.9 16.8 17.8 19.2 22.2 27.6 30.2 35.3 38.1
Unit Weight (kg)
Ceiling Concealed with R/A Plenum 14.3 16.4 21.7 23.1 24.9 28.5 34.7 37.6 44.0 47.6

Notes: 1) High speed air flow corresponds to the respective external static pressure which is measured with unit without R/A plenum.
2) Cooling capacity is based on entering air temperature 26.7°C DB/ 19.4°C WB and water inlet/ outlet temperature 7.2°C/ 12°C, at high speed airflow.
3) Heating capacity is based on entering air temperature 21.1°C and water entering temperature 60°C. Water flowrate and airflow are identical to cooling mode.

Products that perform...By people who care 09 PAGE


SPECIFICATIONS
CR-CF

CR-CF/ HF/ HFS - 2 Rows, 3 Rows


DW - AC Motor (3 Speed)
Model 02 03 04 05 06 08

2 Rows
High Speed 340 510 680 850 1020 1360
Air Flow
Medium Speed 270 406 510 637 765 1020
(m³/h)
Low Speed 176 261 340 425 510 680
CF- 12Pa, CFP/ CFPD- 0Pa 35.5 36.5 38.5 40.3 43.2 42.6
Noise Level
HF- 30Pa, HFP/ HFPD- 20Pa 39.5 41 41.4 43 45.3 45.9
dB(A)
HFS- 50Pa, HFSP/ HFSPD- 40Pa 42 44 44 44.7 47 48.1
Sensible Cooling (kW) 1.2 1.7 2.2 2.6 2.8 4.0
Total Cooling (kW) 1.8 2.5 3.4 3.9 4.3 6.0
Heating (kW) 3.0 4.3 5.4 6.8 7.1 10.2
Water Flowrate (l/min) 5.0 7.3 9.6 12.6 14.4 18.6
Water Pressure Drop (kPa) 5.1 11.1 23.7 30.0 23.0 20.0
Blower Qty 1 2 2 2 2 4
Motor Qty 1 1 1 1 1 2
Power Supply 220V/1P/50-60Hz
CF- 12Pa, CFP/ CFPD- 0Pa 27 40 60 72 93 130
Power Input
HF- 30Pa, HFP/ HFPD- 20Pa 43 57 67 82 100 146
(W)
HFS- 50Pa, HFSP/ HFSPD- 40Pa 48 64 79 97 114 167
Unit Weight Ceiling Concealed without R/A Plenum 9.3 10.9 16.0 17.9 19.1 26.4
(kg) Ceiling Concealed with R/A Plenum 13.4 15.4 21.1 23.2 25.5 33.8
3 Rows
High Speed 340 510 680 850 1020 1360
Air Flow
Medium Speed 270 406 510 637 765 1020
(m³/h)
Low Speed 176 261 340 425 510 680
CF- 12Pa, CFP/ CFPD- 0Pa 35.5 36.5 38.5 40.3 43.2 42.6
Noise Level
HF- 30Pa, HFP/ HFPD- 20Pa 39.5 41 41.4 43 45.3 45.9
dB(A)
HFS- 50Pa, HFSP/ HFSPD- 40Pa 42 44 44 44.7 47 48.1
Sensible Cooling (kW) 1.4 2.0 2.8 3.4 4.1 5.4
Total Cooling (kW) 2.2 3.2 4.2 4.7 5.4 7.7
Heating (kW) 3.6 5.1 6.5 7.9 8.5 12.3
Water Flowrate (l/min) 6.5 9.0 12.6 13.6 15.7 24.0
Water Pressure Drop (kPa) 11.8 24.3 30.0 28.0 40.0 40.0
Blower Qty 1 2 2 2 2 4
Motor Qty 1 1 1 1 1 2
Power Supply 220V/1P/50-60Hz
CF- 12Pa, CFP/ CFPD- 0Pa 27 40 60 72 93 130
Power Input
HF- 30Pa, HFP/ HFPD- 20Pa 43 57 67 82 100 146
(W)
HFS- 50Pa, HFSP/ HFSPD- 40Pa 48 64 79 97 114 167
Unit Weight Ceiling Concealed without R/A Plenum 10.2 11.9 17.0 19.1 20.8 28.0
(kg) Ceiling Concealed with R/A Plenum 14.3 16.4 22.1 24.5 27.2 35.8

Notes: 1) High speed air flow corresponds to the respective external static pressure which is measured with unit without R/A plenum.
2) Cooling capacity is based on entering air temperature 27°C DB/ 19.5°C WB and water inlet/ outlet temperature 7°C/ 12°C, at high speed airflow.
3) Heating capacity is based on entering air temperature 21°C and water entering temperature 60°C. Water flowrate and airflow are identical to cooling mode.
4) Refer to Page 23: Total Capacity Correction Factor for other airflow.
5) Noise data is based on high speed under lab testing condition.

PAGE 10 Products that perform...By people who care


SPECIFICATIONS
CR-CF

CR-CF/ HF/ HFS/ HFZ - 2 Rows, 3 Rows, 4 Rows


AW - DC Motor (Variable Speed), BW - DC Motor (3 Speed)
Model 02 03 04 05 06 07 08 10 12 14
2 Rows
High Speed 340 510 680 850 1020 1190 1360 1700 2040 2380
Air Flow
Medium Speed 270 406 510 637 765 893 1020 1307 1552 1770
(m³/h)
Low Speed 176 261 340 425 510 595 680 880 1009 1173
CF- 12Pa, CFP/ CFPD- 0Pa 35.5 36.5 38.5 40.3 43.2 46 42.6 48 49 52
Noise Level HF- 30Pa, HFP/ HFPD- 20Pa 39.5 41 41.4 43 45.3 48 45.9 50 52 54
dB(A) HFS- 50Pa, HFSP/ HFSPD- 40Pa 42 44 44 44.7 47 50 48.1 52 54 56
HFZ- 70Pa, HFZP/ HFZPD- 60Pa 44 46.5 48 49 50 53 53 54 56 58
Sensible Cooling (kW) 1.2 1.7 2.2 2.6 2.8 3.6 4.0 4.7 5.8 6.8
Total Cooling (kW) 1.8 2.5 3.4 3.9 4.3 5.5 6.0 7.0 9.0 10.7
Heating (kW) 3.0 4.3 5.4 6.8 7.1 10.2 10.2 12.0 14.9 17.4
Water Flowrate (l/min) 5.0 7.3 9.6 12.6 14.4 18.6 18.6 20.1 25.7 30.9
Water Pressure Drop (kPa) 5.1 11.1 23.7 30.0 23.0 23.9 20.0 20.1 37.8 50.0
Blower Qty 1 2 2 2 2 2 4 4 4 4
Motor Qty 1 1 1 1 1 1 2 2 2 2
Power Supply 220V/1P/50-60Hz
CF- 12Pa, CFP/ CFPD- 0Pa 13 15 26 36 53 63 57 88 114 139
Power Input HF- 30Pa, HFP/ HFPD- 20Pa 16 24 36 46 65 73 74 101 140 166
(W) HFS- 50Pa, HFSP/ HFSPD- 40Pa 20 32 48 61 80 90 94 125 165 208
HFZ- 70Pa, HFZP/ HFZPD- 60Pa 39 42 56 82 99 127 123 165 210 238
Unit Weight Ceiling Concealed without R/A Plenum 9.8 11.4 16.5 18.4 19.6 21 26.9 29.2 33.8 35.6
(kg) Ceiling Concealed with R/A Plenum 13.9 15.9 21.6 23.7 26.0 27.3 34.3 36.6 42.5 45.1
3 Rows
High Speed 340 510 680 850 1020 1190 1360 1700 2040 2380
Air Flow
Medium Speed 270 406 510 637 765 893 1020 1307 1552 1770
(m³/h)
Low Speed 176 261 340 425 510 595 680 880 1009 1173
CF- 12Pa, CFP/ CFPD- 0Pa 35.5 36.5 38.5 40.3 43.2 46 42.6 48 49 52
Noise Level HF- 30Pa, HFP/ HFPD- 20Pa 39.5 41 41.4 43 45.3 48 45.9 50 52 54
dB(A) HFS- 50Pa, HFSP/ HFSPD- 40Pa 42 44 44 44.7 47 50 48.1 52 54 56
HFZ- 70Pa, HFZP/ HFZPD- 60Pa 44 46.5 48 49 50 53 53 54 56 58
Sensible Cooling (kW) 1.4 2.0 2.8 3.4 4.1 4.4 5.4 6.0 7.1 8.4
Total Cooling (kW) 2.2 3.2 4.2 4.7 5.4 6.7 7.7 9.4 11.1 13.1
Heating (kW) 3.6 5.1 6.5 7.9 8.5 11.1 12.3 14.9 17.9 20.9
Water Flowrate (l/min) 6.5 9.0 12.6 13.6 15.7 19.3 24 27.0 31.7 37.8
Water Pressure Drop (kPa) 11.8 24.3 30.0 28.0 40.0 22.6 40 40.0 25.8 39.5
Blower Qty 1 2 2 2 2 2 4 4 4 4
Motor Qty 1 1 1 1 1 1 2 2 2 2
Power Supply 220V/1P/50-60Hz
CF- 12Pa, CFP/ CFPD- 0Pa 13 15 26 36 53 63 57 88 114 139
Power Input HF- 30Pa, HFP/ HFPD- 20Pa 16 24 36 46 65 73 74 101 140 166
(W) HFS- 50Pa, HFSP/ HFSPD- 40Pa 20 32 48 61 80 90 94 125 165 208
HFZ- 70Pa, HFZP/ HFZPD- 60Pa 39 42 56 82 99 127 123 165 210 238
Unit Weight Ceiling Concealed without R/A Plenum 10.7 12.4 17.5 19.6 21.3 23.2 28.4 31.2 36.3 39.1
(kg) Ceiling Concealed with R/A Plenum 14.8 16.9 22.6 25.0 27.7 29.5 36.3 45.0 45.0 48.6
4 Rows
CF- 12Pa, CFP/ CFPD- 0Pa 36.5 37 41 43 44 46 46 48 50 52
Noise Level HF- 30Pa, HFP/ HFPD- 20Pa 40 41 43 46 46 47 48 50 52 54
dB(A) HFS- 50Pa, HFSP/ HFSPD- 40Pa 42 44 46 47 49 50 50 52 54 56
HFZ- 70Pa, HFZP/ HFZPD- 60Pa 43.5 46.4 46.4 48.5 49.7 52 53 54.3 55.1 57
Power Supply 220V/1P/50-60Hz
CF- 12Pa, CFP/ CFPD- 0Pa 15 21 28 41 55 61 70 88 114 139
Power Input HF- 30Pa, HFP/ HFPD- 20Pa 19 28 39 51 65 73 87 101 140 166
(W) HFS- 50Pa, HFSP/ HFSPD- 40Pa 27 37 49 61 80 90 101 125 168 208
HFZ- 70Pa, HFZP/ HFZPD- 60Pa 35 44 62 87 99 130 134 185 210 251
Unit Weight Ceiling Concealed without R/A Plenum 12.1 13.9 18.8 20.2 22.4 24.8 30.8 33.2 38.8 42.6
(kg) Ceiling Concealed with R/A Plenum 16.2 18.4 23.7 25.3 29.0 31.1 38.7 40.6 47.5 52.1
Notes: 1) High speed air flow corresponds to the respective external static pressure which is measured with unit without R/A plenum.
2) Cooling capacity is based on entering air temperature 27°C DB/ 19.5°C WB and water inlet/ outlet temperature 7°C/ 12°C, at high speed airflow.
3) Heating capacity is based on entering air temperature 21°C and water entering temperature 60°C. Water flowrate and airflow are identical to cooling mode.
4) Refer to Page 23: Total Capacity Correction Factor for other airflow.
5) Noise data is based on high speed under lab testing condition.

Products that perform...By people who care 11 PAGE


DIMENSIONS
CR

CR-CB/ HB/ HBS/ HBZ

Model A B C C* Air Outlet


02 560 530 755 955 560x136
03 640 610 835 1035 640x136
04 740 710 935 1135 740x136
CB 05 840 810 1035 1235 840x136
HB 06 950 920 1145 1345 950x136
HBS 07 1076 1046 1270 1470 1076x136
HBZ 08 1280 1250 1475 1675 1280x136
10 1330 1300 1525 1725 1330x136
12 1635 1605 1830 2030 1635x136
14 1838 1808 2035 2235 1838x136
C* is extended drain pan size (optional).

CR-CBP/ CBPD/ HBP/ HBPD/ HBSP/ HBSPD/ HBZP/ HBZPD

Model A B C C* Air Outlet Air Inlet


02 560 530 755 955 560x136 530x180
CBP 03 640 610 835 1035 640x136 610x180
CBPD 04 740 710 935 1135 740x136 710x180
HBP 05 840 810 1035 1235 840x136 810x180
HBPD 06 950 920 1145 1345 950x136 920x180
HBSP 07 1076 1046 1270 1470 1076x136 1046x180
HBSPD 08 1280 1250 1475 1675 1280x136 1250x180
HBZP 10 1330 1300 1525 1725 1330x136 1300x180
HBZPD 12 1635 1605 1830 2030 1635x136 1605x180
Note: All dimensions are in mm. 14 1838 1808 2035 2235 1838x136 1808x180

PAGE 12 Products that perform...By people who care


DIMENSIONS
CR

CR-FB

Model A B C H W Air Outlet


02 658 500 558 621 234 500x120
03 738 580 638 621 234 580x120
04 838 680 738 621 234 680x120
05 938 780 838 621 234 780x120
06 1048 890 948 621 234 890x120
FB
07 1174 1016 1074 621 234 1016x120
08 1378 1220 1278 621 234 1220x120
10 1428 1270 1328 621 234 1270x120
12 1733 1575 1633 621 234 1575x120
14 1936 1778 1836 621 234 1778x120

CR-CE

Model A B C
03 905 625 600
04 1105 825 800
05 1105 825 800
CE 06 1605 1325 1300
08 1605 1325 1300
10 1905 1625 1600
12 1905 1625 1600

CR-WM
A B
Model A B C
03 850 198 300
05 970 235 315
WM
06 970 235 315
C 08 1100 235 330

Note: All dimensions are in mm.

Products that perform...By people who care 13 PAGE


DIMENSIONS
CR

CR-CCIIH1-Y

Model A B C D E F G H L1 L2
02 680 582 400 614 265 225 51 137 85 92.5
03 680 582 400 614 265 225 51 137 85 92.5
04 680 582 400 614 265 225 51 137 85 92.5
05 830 712 544 744 290 220 89 142 85 106
CCIIH1-Y 06 830 712 544 744 290 220 89 142 85 106
08 830 712 544 744 290 220 89 142 85 106
10 980 827 655 859 290 220 88 146 105 106
12 980 827 655 859 290 220 88 146 105 106
14 980 827 655 859 290 220 88 146 105 106

CRH-CBP/ CBPD

Model A B C D E F G H I J K Air Outlet Air Inlet


08 930 990 1374 270 310 680 320 660 200 180 490 960x200 930x270
CBP
14 1120 1180 1544 320 360 730 370 710 250 230 540 1150x250 1120x320
CBPD
18 1460 1520 1894 320 360 730 370 710 250 230 540 1490x250 1460x320
Note: All dimensions are in mm.

PAGE 14 Products that perform...By people who care


DIMENSIONS
CR-CF

CR-CF/ HF/ HFS/ HFZ

Model A B C C* Air Outlet


02 560 530 755 955 560x136
03 640 610 835 1035 640x136
04 775 745 970 1170 775x136
CF 05 900 870 1095 1295 900x136
HF 06 1076 1046 1270 1470 1076x136
HFS 07* 1076 1046 1270 1470 1076x136
HFZ 08 1330 1300 1525 1725 1330x136
10* 1330 1300 1525 1725 1330x136
12* 1635 1605 1830 2030 1635x136
C* is extended drain pan size (optional). 07*, 10*, 12*, 14* for DC motor fan coil unit only 14* 1838 1808 2035 2235 1838x136

CR-CFP/ CFPD/ HFP/ HFPD/ HFSP/ HFSPD/ HFZP/ HFZPD

Model A B C C* Air Outlet Air Inlet


02 560 530 755 955 560x136 530x180
CFP 03 640 610 835 1035 640x136 610x180
CFPD 04 775 745 970 1175 775x136 745x180
HFP 05 900 870 1095 1295 900x136 870x180
HFPD 06 1076 1046 1270 1470 1076x136 1046x180
HFSP 07* 1076 1046 1270 1470 1076x136 1046x180
HFSPD 08 1330 1300 1525 1725 1330x136 1300x180
HFZP 10* 1330 1300 1525 1725 1330x136 1300x180
HFZPD 12* 1635 1605 1830 2030 1635x136 1605x180
C* is extended drain pan size (optional). 07*, 10*, 12*, 14* for DC motor fan coil unit only 14* 1838 1808 2035 2235 1838x136 1808x180

Products that perform...By people who care 15 PAGE


PERFORMANCE
CR

Total Cooling Capacity


1.2

1.0
PERCENTAGE OF TOTAL .
COOLING CAPACITY

0.8

0.6

0.4

0.2

0.0
0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4

PERCENTAGE OF NOMINAL AIRFLOW

Total Heating And Sensible Heat


1.2
PERCENTAGE OF TOTAL HEATING AND SENSIBLE

1.0
HEAT CAPACITY

0.8

0.6

0.4

0.2

0.0
0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4

PERCENTAGE OF NOMINAL AIRFLOW

PAGE 16 Products that perform...By people who care


PERFORMANCE
CR-CF

Total Cooling Capacity


1.2

1.0
PERCENTAGE OF TOTAL .
COOLING CAPACITY

0.8

0.6

0.4

0.2

0.0
0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4

PERCENTAGE OF NOMINAL AIRFLOW

Total Heating And Sensible Heat


1.2
PERCENTAGE OF TOTAL HEATING AND SENSIBLE

1.0
HEAT CAPACITY

0.8

0.6

0.4

0.2

0.0
0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4

PERCENTAGE OF NOMINAL AIRFLOW

Products that perform...By people who care 17 PAGE


WIRING DIAGRAM
CR

CR

CRH

Note:
Terminal No. 1, 2, 3 for low static pressure of low, medium, high speed connection.
Terminal No. 2, 3. 4 for high static pressure of low, medium, high speed connection.
Terminal No. 2, 3, 4 are standard connection.
Caution: Wrong termination may cause motor damage.

PAGE 18 Products that perform...By people who care


WIRING DIAGRAM
CR-CF

AC Motor (3 Speed)

DC Motor (3 Speed)

DC Motor (Variable Speed)

Products that perform...By people who care 19 PAGE


Malaysia China United Kingdom
Lot 5755-6, No.1 Dunham-Bush Road, 8 Downley Road,
Kidamai lndustrial Park, Laishan District, Havant,
Bukit Angkat, Yantai, Hampshire,
43000 Kajang, Shandong Province, England PO9 2JD
Selangor, Malaysia China 264003
Tel: +44-23-9247 7700
Tel: +603-8924 9000 Tel: +86-535-739 7888 Fax:+44-23-9245 0396
Fax:+603-8739 5020 Fax:+86-535-739 7999

Uni ted States of America United Arab Emirates South Africa


1800 SE 38th Avenue, Office # 2606, No.57 Sovereign Drive
Homestead, Fortune Executive Towers, Route 21 Corporate Park
Florida 33035 Cluster T1, Jumeirah Lake Tower Irene, Pretoria
United States of America Dubai, UAE South Africa

Tel: +1(786)-800 9999 Tel: +971-4-443 9207 Tel: +27-12-345 4202


Fax: +1(786)-527 3539 Fax:+971-4-443 9208 Fax:+27-12-345 4203

India Indonesia Singapore


957D, 9th Floor, Tower B-1, The Boulevard Office, 2, Kallang Pudding Road
Spaze i-Tech Park, Sohna Road, 3F2 Jl. Fachrudin No.5, #07-07 Mactech Building,
Sector-49, Gurugram Kp. Bali, Tanah Abang Singapore 349307
Haryana-122018, India Jakarta Pusat - 10250, Indonesia
Tel: +65-6842 2012
Tel: +91-124-414 4430 Tel: +62-21-2123 1392 Fax:+65-6842 2013

Thailand Vietnam
48/39 Soi Praditmanutham 19 10th Floor, Nam A Bank Tower,
Praditmanutham Road, 201-203 Cach Mang Thang 8 Street,
Lat Pharo, Bangkok 10230 District 3, Ho Chi Minh City,
Thailand Vietnam

Tel: +66-0-2610 3749 Tel: +84-8-6290 3108


Fax:+66-0-2610 3601 Fax:+84-8-6290 3109

[email protected]
www.dunham-bush.com
R

The manufacturer reserves the right to change specifications without prior notice. M-S-0124A-0121
©Dunham-Bush. All rights reserved.