CR Series 50/60Hz
Air Volume: 100 to 1940 cfm (176 to 3300 m3/hr)
CR-CB/CF
CR-CC
CR-WM
CR-CE
CR-FB
MILESTONE
UNITED KINGDOM
ECUADOR
PERU
BRAZIL
BOLIVIA
SOUTH AFRICA
URUGUAY
Dunham-Bush Profile
Dunham-Bush, one of the world’s top commercial air conditioning manufacturers, has long been
committed to offering creative solutions for the customer’s requirements over its 120 years history in
the HVAC/R. Dunham-Bush offers a complete range of HVAC/R products such as large chillers,
unitary, airside system and thermal energy storages for residences, commercial buildings and
industrial facilities. Dunham-Bush is striving to be the leader in the commercialization of green
technologies. Today, by utilizing our global network of sales and service offices, Dunham-Bush is
offering our value-added products and solutions to all corners of the world.
Manufactured the
air conditioner.
1894
Built in USA as a professional manufacturer of
HVAC/R equipments.
Today
and Innovations...
Beyond never ends
Dunham-Bush's fan coil unit are high performance, low noise, large air volume and cooling capacity, and flexible left and right water
connections. Currently there are more than 500 types of models with a wide cooling capacity selection. All fan coils have undergone rigorous
testing before leaving the factory. Dunham Bush fan coil continue to lead the market in the air conditioning and refrigeration industry with
cutting edge design, precise manufacturing and excellent performance.
Coil
All coils are of seamless copper tubes, with corrugated Options And Accessories
hydrophilic coated fin for improved condensed draining and
1) Thermostat- LCD or Mechanical
giving excellent heat transfer. The surface design of this
2) Filter - Nylon Mesh Filter or Carbon Filter
“self-cleaning” corrugated fin create a vortex flow which make
3) 2-way motorized valve (shipped loose)
dust difficult to accumulate, and its heat exchange efficiency
4) Flexible pipe connector - For easy connection, eliminate
will not be affected even after used for a long time. All coil are
vibration and reduce noise level
leak tested at 2.4 MPa air pressure and are suitable for up to 1.6
5) UV light - Produce germicidal effects to remove airborne
MPa working pressure. The water inlet and outlet hexagonal
bacteria and germs
connectors are of brass material. The water flow connection
6) Extended Drain Pan
are easy to install on site.
Nomenclature
6 CR H 03 CB 3 DW
6 : 60Hz
AC Motor (3 Speed)
Blank : 50Hz
Unit Model
Notes:
Type 1. Left hand or Right hand piping connection is determined by
CB - Ceiling concealed (12Pa) facing the supply air.
CBP - Ceiling concealed with back return air plenum (0Pa) 2. Standard unit coil inlet and outlet are in the same
CBPD - Ceiling concealed with bottom return air plenum (0Pa) direction as drain pipe. Concealed unit, the water inlet and
HB - Ceiling concealed (30Pa) outlet same direction as the junction box. For exposed
HBP - Ceiling concealed with back return air plenum (20Pa) unit, the water inlet outlet is opposite direction to the
HBPD - Ceiling concealed with bottom return air plenum (20Pa) junction box.
HBS - Ceiling concealed (50Pa) 3. The unit with return air box can be equipped with a filter, and
HBSP - Ceiling concealed with back return air plenum (40Pa) the filter can be based on customer requirements.
HBSPD - Ceiling concealed with bottom return air plenum (40Pa)
- Ceiling concealed (70Pa) 4. High static pressure type (CRH) includes: CBP / CBPD (2 rows
HBZ
- Ceiling concealed with back return air plenum (60Pa) / 3 rows / 4 rows)Among them, the height of the high static
HBZP
pressure fan coil (CRH series) has increased, its allow
HBZPD - Ceiling concealed with bottom return air plenum (60Pa)
Higher air pressure and larger air volume, able to supply
FB - Vertical concealed
air to long-distance , and allow multi-channel air
CE - Ceiling exposed
supply, multi-channel return air, this fan coil is
WM - Wall mounted
especially suitable for household centralize air conditioning.
CCIIH1-Y - Ceiling Cassette
5. Motor is 220V (±10%) / 1PH/ 50-60Hz.
04
INTRODUCTION
CR-CF
Dunham-Bush low noise fan coil unit not only have the advantages of standard fan coil units, it also processes large air volume, high cooling
capacity , convenient left and right water pipes connection, ultra quiet operation and high efficiency.These units are widely use in luxury
hotels, offices, business centres, hospital, high-end villas, apartments and condominium. With the technology advancement and excellent
performance, Dunham-Bush Fan Coil Units has been continuously maintaining its leading position in the air-conditioning industry.
Nomenclature
6 CR 04 CF 3 DW
05
SPECIFICATIONS
CR
Notes: 1) High speed air flow corresponds to the respective external static pressure which is measured with unit without R/A plenum.
2) Cooling capacity is based on entering air temperature 27°C DB/ 19.5°C WB and water inlet/ outlet temperature 7°C/ 12°C, at high speed airflow.
3) Heating capacity is based on entering air temperature 21°C and water entering temperature 60°C. Water flowrate and airflow are identical to cooling mode.
4) Refer to Page 23: Total Capacity Correction Factor for other airflow.
5) Noise data is based on high speed under lab testing condition.
CR-CCIIH1-Y
Model 02 03 04 05 06 08 10 12 14
Cooling kW 1.8 2.7 3.6 4.5 5.4 7.2 9.0 10.8 12.6
Heating kW 2.7 4.1 5.4 6.8 8.1 10.8 13.9 16.2 18.9
Capacity
Water Flowrate l/min 0.3 0.5 0.6 0.8 0.9 1.2 1.7 1.9 2.2
Water Pressure Drop kPa 30 30 30 30 40 40 40 40 50
High Speed m³/h 340 510 680 850 1020 1360 1700 2040 2380
Air Flow Medium Speed m³/h 255 383 510 638 765 1020 1275 1530 1785
Low Speed m³/h 170 255 340 425 510 680 950 1020 1190
Noise Level dB (A) 37 39 41 43 45 46 48 50 52
Blower Quantity 1 1 1 1 1 1 1 1 1
Power Supply 220V/1Ph/50-60Hz
Quontity 1 1 1 1 1 1 1 1 1
Motor
Power Input w 36 50 60 74 93 130 147 183 221
Net Weight kg 20 20 20 26 26 26 36 36 36
Notes: 1) Air volume is defined as external pressure 0 Pa.
2) Cooling capacity is based in water inlet/outlet temperature of 7°C/ 12°C, air entering temperature 27°C DB/ 19.5°C WB, and air volume during high speed (external
pressure as 0Pa) standard.
3) Heating capacity is based on water entering temperature of 60°C and air entering temperature 21°C.
4) Total cooling load, sensible heating cooling load and total heating load under different air volume can be obtained according to correction factor chart.
5) Noise data is based on high speed testing condition.
CR-CE
Model 03 04 05 06 08 10 12
Total Cooling kW 2.7 3.6 4.5 5.5 7.4 9.0 10.8
Heating kW 4.1 5.4 6.8 8.1 10.8 13.5 16.2
Capacity
Water Flowrate l/min 0.5 0.6 0.8 0.9 1.2 1.7 1.9
Water Pressure Drop kPa 30 30 30 40 40 40 40
High Speed m³/h 510 680 850 1020 1360 1700 2040
Air Flow Medium Speed m³/h 383 510 638 765 1020 1275 1530
Low Speed m³/h 255 340 425 510 680 850 1020
Noise Level dB (A) 39 41 43 45 46 48 50
Blower Quantity. 1 2 2 2 3 4 4
Power Supply 220V/ 1P/ 50-60Hz
Quantity 1 1 1 1 2 2 2
Motor
Power Input W 50 60 74 93 130 147 183
Net Weight kg 21 26 26 38 38 44 44
Notes: 1) Air volume is defined as external pressure 0 Pa.
2) Cooling capacity is based on water inlet/outlet temperature of 7°C/ 12°C, air entering temperature 27°C DB/ 19.5°C WB, and air volume during high speed (external
pressure as 0Pa) standard
3) Heating capacity is based on water entering temperature of 60°C and air entering temperature 21°C.
4) Total cooling load, sensible heating cooling load and total heating load under different air volume can be obtained according to correction factor chart.
5) Noise data is based on high speed testing condition.
CR-WM
Model 03 05 06 08
High Speed kW 2.7 4.5 5.4 7.2
Cooling Capacity Medium Speed kW 2.3 3.8 4.6 6.1
Low Speed kW 1.8 2.9 3.5 4.7
High Speed kW 4.1 6.8 8.2 10.8
Heating Capacity Medium Speed kW 3.5 5.8 7.0 9.2
Low Speed kW 2.6 4.4 5.3 7.0
High Speed m³/h 510 850 1020 1360
Air Flow Medium Speed m³/h 383 638 765 1020
Low Speed m³/h 255 425 510 680
Water Flowrate l/min 10.2 15.8 18.0 23.2
Water Pressure Drop kPa 30 30 40 40
Blower Fan Qty 1 1 1 1
Power Supply 220V/1Ph/50-60Hz
Motor Input Power W 52 76 96 134
Qty 1 1 1 1
Noise Level dB(A) 42 47 47 49
Control Mode Remote control or wired wall pad
Unit Dimension WxDxH mm 850x300x198 970x315x235 970x315x235 1100x330x235
Net Weight kg 11 15 16 20
In Inch RC1/2” RC1/2” RC1/2” RC1/2”
Water Connection Out inch RC1/2” RC1/2” RC1/2” RC1/2”
Drain Pipe inch R1/2” R1/2” R1/2” R1/2”
Notes: 1) Cooling capacity is based on water inlet/outlet temperature of 7°C/ 12°C, air entering temperature 27°C DB/ 19.5°C WB.
2) Heating capacity is based on water entering temperature of 60°C and air entering temperature 21°C.
3) External Static Pressure: 50Pa is optional.
4) Noise level is tested in full-anechoic room.
CRH-CBP/ CBPD
Air Flow (m³/h) Capacity Motor
External
Noise Unit Net
Static Water Blower Power
Model Level Total Sensible Water Weight
Pressure High Hi Med Medium Low Heating Pressure Qty Supply Power
dB(A) Cooling Heating Flowrate Qty (kg)
(Pa) Speed Speed Speed Speed (kW) Drop Input (W)
(kW) (kW) (l/min)
(kPa)
110 1500 1200 970 - 60 5.22 3.90 9.87 15.00 6.72 2 1 303 38
08
80 - 1500 1150 960 60 5.22 3.90 9.87 15.00 6.72 2 1 287 38
2Rows 130 2400 2000 1700 - 62 8.32 6.15 15.35 24.00 12.38 2 1 502 50
CBP 14
CBPD 100 - 2400 1900 1700 62 8.32 6.15 15.35 24.00 12.38 2 1 485 50
165 3300 2900 2200 - 64 12.04 8.67 21.10 34.20 29.00 3 2 781 65
18
125 - 3300 2600 2200 64 12.04 8.67 21.10 34.20 29.00 3 2 738 65
100 1500 1200 970 - 60 7.76 5.30 13.19 22.20 18.71 2 1 303 40
08
70 - 1500 1200 960 60 7.76 5.30 13.19 22.20 18.71 2 1 287 40
3Rows 115 2400 2000 1700 - 62 10.81 7.76 19.87 31.20 9.86 2 1 502 52
220V/ 1P/
CBP 14
85 - 2400 1900 1700 62 10.81 7.76 19.87 31.20 9.86 2 50- 60Hz 1 485 52
CBPD
150 3300 2900 2200 - 64 16.03 11.13 27.45 46.20 24.16 3 2 781 69
18
110 - 3300 2600 2200 64 16.03 11.13 27.45 46.20 24.16 3 2 738 69
90 1500 1200 970 - 60 9.43 6.24 15.32 27.00 34.47 2 1 303 43
08
60 - 1500 1150 960 60 9.43 6.24 15.32 27.00 34.47 2 1 287 43
4Rows 100 2400 2000 1700 - 62 12.66 8.91 22.94 36.60 8.02 2 1 502 55
CBP 14
CBPD 70 - 2400 1900 1700 62 12.66 8.91 22.94 36.60 8.02 2 1 485 55
135 3300 2900 2200 - 64 17.90 12.39 31.59 51.60 18.16 3 2 781 73
18
95 - 3300 2600 2200 64 17.90 12.39 31.59 51.60 18.16 3 2 738 73
Notes: 1) Air volume is based on unit nominal external static pressure.
2) Cooling capacity is based on water inlet/outlet temperature of 7°C/ 12°C and entering air temperature 27°C DB/ 19.5°C WB
3) Heating capacity is based on water entering temperature of 60°C and air entering temperature of 21°C.
4) Total cooling load, sensible heating cooling load and total heating load under different air volume can be obtained according to correction factor chart.
5) Noise level data is based on nominal air pressure testing condition.
6) Customer can opt for 2 rows hot water coil install at unit air outlet.
CR Series - AHRI
Model 02 03 04 05 06 07 08 10 12 14
2 Rows
High Speed 340 510 680 850 1020 1190 1360 1700 2040 2380
Air Flow (m³/h) Medium Speed 270 406 518 661 770 893 1016 1307 1552 1770
Low Speed 176 261 348 447 509 595 687 880 1009 1173
Sensible Cooling (kW) 1.1 1.6 2.0 2.5 2.9 3.5 3.8 4.6 5.7 6.7
Total Cooling (kW) 1.5 2.1 3.3 4.1 4.5 4.6 6.0 7.0 9.1 10.7
Heating (kW) 3.0 4.1 5.3 6.6 7.5 8.9 10.2 12.0 14.9 17.3
Water Flowrate (l/min) 4.2 5.3 7.2 9.1 9.8 12.0 13.3 15.9 20.1 23.9
Water Pressure Drop (kPa) 4.4 7.4 14.2 23.7 10.7 17.9 11.2 15.6 28.0 41.7
Blower Qty 1 2 2 2 2 2 4 4 4 4
Motor Qty 1 1 1 1 1 1 2 2 2 2
Power Supply 220V/1P/50Hz
12Pa 27 40 60 74 94 112 132 148 191 230
30Pa 43 57 72 85 109 118 148 173 206 257
Power Input (W)
50Pa 48 65 81 97 116 128 171 193 243 293
70Pa 55 71 92 111 126 180 183 230 277 330
Power Supply 220V/1P/60Hz
12Pa 44 56 70 109 124 152 147 195 239 294
30Pa 45 65 75 115 117 168 156 195 247 303
Power Input (W)
50Pa 49 76 102 126 131 188 197 224 278 315
70Pa 58 77 101 121 156 182 192 243 293 366
Ceiling Concealed without R/A Plenum 9.3 10.9 15.8 16.6 17.5 20.0 25.6 28.2 32.8 34.6
Unit Weight (kg)
Ceiling Concealed with R/A Plenum 13.4 15.4 20.7 21.9 23.2 26.3 32.7 35.6 41.5 44.1
3 Rows
High Speed 340 510 680 850 1020 1190 1360 1700 2040 2380
Air Flow (m³/h) Medium Speed 270 406 518 661 770 893 1016 1307 1552 1770
Low Speed 176 261 348 447 509 595 687 880 1009 1173
Sensible Cooling (kW) 1.4 1.9 2.5 3.0 3.6 4.1 4.8 5.8 6.9 8.0
Total Cooling (kW) 2.1 2.8 3.6 4.2 5.1 5.7 6.9 8.2 9.6 11.3
Heating (kW) 3.8 5.1 6.5 8.0 9.5 10.8 12.7 15.1 18.0 20.9
Water Flowrate (l/min) 5.8 7.2 9.1 11.0 13.3 15.0 17.8 21.2 25.0 29.2
Water Pressure Drop (kPa) 11.0 18.2 31.0 16.8 25.9 18.0 26.9 37.0 20.8 30.1
Blower Qty 1 2 2 2 2 2 4 4 4 4
Motor Qty 1 1 1 1 1 1 2 2 2 2
Power Supply 220V/1P/50Hz
12Pa 27 40 60 74 94 112 132 148 191 230
30Pa 43 57 72 85 109 118 148 173 206 257
Power Input (W)
50Pa 48 65 81 97 116 128 171 193 243 293
70Pa 55 71 92 111 126 180 183 230 277 330
Power Supply 220V/1P/60Hz
12Pa 44 56 70 109 124 152 147 195 239 294
30Pa 45 65 75 115 117 168 156 195 247 303
Power Input (W)
50Pa 49 76 102 126 131 188 197 224 278 315
70Pa 58 77 101 121 156 182 192 243 293 366
Ceiling Concealed without R/A Plenum 10.2 11.9 16.8 17.8 19.2 22.2 27.6 30.2 35.3 38.1
Unit Weight (kg)
Ceiling Concealed with R/A Plenum 14.3 16.4 21.7 23.1 24.9 28.5 34.7 37.6 44.0 47.6
Notes: 1) High speed air flow corresponds to the respective external static pressure which is measured with unit without R/A plenum.
2) Cooling capacity is based on entering air temperature 26.7°C DB/ 19.4°C WB and water inlet/ outlet temperature 7.2°C/ 12°C, at high speed airflow.
3) Heating capacity is based on entering air temperature 21.1°C and water entering temperature 60°C. Water flowrate and airflow are identical to cooling mode.
2 Rows
High Speed 340 510 680 850 1020 1360
Air Flow
Medium Speed 270 406 510 637 765 1020
(m³/h)
Low Speed 176 261 340 425 510 680
CF- 12Pa, CFP/ CFPD- 0Pa 35.5 36.5 38.5 40.3 43.2 42.6
Noise Level
HF- 30Pa, HFP/ HFPD- 20Pa 39.5 41 41.4 43 45.3 45.9
dB(A)
HFS- 50Pa, HFSP/ HFSPD- 40Pa 42 44 44 44.7 47 48.1
Sensible Cooling (kW) 1.2 1.7 2.2 2.6 2.8 4.0
Total Cooling (kW) 1.8 2.5 3.4 3.9 4.3 6.0
Heating (kW) 3.0 4.3 5.4 6.8 7.1 10.2
Water Flowrate (l/min) 5.0 7.3 9.6 12.6 14.4 18.6
Water Pressure Drop (kPa) 5.1 11.1 23.7 30.0 23.0 20.0
Blower Qty 1 2 2 2 2 4
Motor Qty 1 1 1 1 1 2
Power Supply 220V/1P/50-60Hz
CF- 12Pa, CFP/ CFPD- 0Pa 27 40 60 72 93 130
Power Input
HF- 30Pa, HFP/ HFPD- 20Pa 43 57 67 82 100 146
(W)
HFS- 50Pa, HFSP/ HFSPD- 40Pa 48 64 79 97 114 167
Unit Weight Ceiling Concealed without R/A Plenum 9.3 10.9 16.0 17.9 19.1 26.4
(kg) Ceiling Concealed with R/A Plenum 13.4 15.4 21.1 23.2 25.5 33.8
3 Rows
High Speed 340 510 680 850 1020 1360
Air Flow
Medium Speed 270 406 510 637 765 1020
(m³/h)
Low Speed 176 261 340 425 510 680
CF- 12Pa, CFP/ CFPD- 0Pa 35.5 36.5 38.5 40.3 43.2 42.6
Noise Level
HF- 30Pa, HFP/ HFPD- 20Pa 39.5 41 41.4 43 45.3 45.9
dB(A)
HFS- 50Pa, HFSP/ HFSPD- 40Pa 42 44 44 44.7 47 48.1
Sensible Cooling (kW) 1.4 2.0 2.8 3.4 4.1 5.4
Total Cooling (kW) 2.2 3.2 4.2 4.7 5.4 7.7
Heating (kW) 3.6 5.1 6.5 7.9 8.5 12.3
Water Flowrate (l/min) 6.5 9.0 12.6 13.6 15.7 24.0
Water Pressure Drop (kPa) 11.8 24.3 30.0 28.0 40.0 40.0
Blower Qty 1 2 2 2 2 4
Motor Qty 1 1 1 1 1 2
Power Supply 220V/1P/50-60Hz
CF- 12Pa, CFP/ CFPD- 0Pa 27 40 60 72 93 130
Power Input
HF- 30Pa, HFP/ HFPD- 20Pa 43 57 67 82 100 146
(W)
HFS- 50Pa, HFSP/ HFSPD- 40Pa 48 64 79 97 114 167
Unit Weight Ceiling Concealed without R/A Plenum 10.2 11.9 17.0 19.1 20.8 28.0
(kg) Ceiling Concealed with R/A Plenum 14.3 16.4 22.1 24.5 27.2 35.8
Notes: 1) High speed air flow corresponds to the respective external static pressure which is measured with unit without R/A plenum.
2) Cooling capacity is based on entering air temperature 27°C DB/ 19.5°C WB and water inlet/ outlet temperature 7°C/ 12°C, at high speed airflow.
3) Heating capacity is based on entering air temperature 21°C and water entering temperature 60°C. Water flowrate and airflow are identical to cooling mode.
4) Refer to Page 23: Total Capacity Correction Factor for other airflow.
5) Noise data is based on high speed under lab testing condition.
CR-FB
CR-CE
Model A B C
03 905 625 600
04 1105 825 800
05 1105 825 800
CE 06 1605 1325 1300
08 1605 1325 1300
10 1905 1625 1600
12 1905 1625 1600
CR-WM
A B
Model A B C
03 850 198 300
05 970 235 315
WM
06 970 235 315
C 08 1100 235 330
CR-CCIIH1-Y
Model A B C D E F G H L1 L2
02 680 582 400 614 265 225 51 137 85 92.5
03 680 582 400 614 265 225 51 137 85 92.5
04 680 582 400 614 265 225 51 137 85 92.5
05 830 712 544 744 290 220 89 142 85 106
CCIIH1-Y 06 830 712 544 744 290 220 89 142 85 106
08 830 712 544 744 290 220 89 142 85 106
10 980 827 655 859 290 220 88 146 105 106
12 980 827 655 859 290 220 88 146 105 106
14 980 827 655 859 290 220 88 146 105 106
CRH-CBP/ CBPD
1.0
PERCENTAGE OF TOTAL .
COOLING CAPACITY
0.8
0.6
0.4
0.2
0.0
0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4
1.0
HEAT CAPACITY
0.8
0.6
0.4
0.2
0.0
0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4
1.0
PERCENTAGE OF TOTAL .
COOLING CAPACITY
0.8
0.6
0.4
0.2
0.0
0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4
1.0
HEAT CAPACITY
0.8
0.6
0.4
0.2
0.0
0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4
CR
CRH
Note:
Terminal No. 1, 2, 3 for low static pressure of low, medium, high speed connection.
Terminal No. 2, 3. 4 for high static pressure of low, medium, high speed connection.
Terminal No. 2, 3, 4 are standard connection.
Caution: Wrong termination may cause motor damage.
AC Motor (3 Speed)
DC Motor (3 Speed)
Thailand Vietnam
48/39 Soi Praditmanutham 19 10th Floor, Nam A Bank Tower,
Praditmanutham Road, 201-203 Cach Mang Thang 8 Street,
Lat Pharo, Bangkok 10230 District 3, Ho Chi Minh City,
Thailand Vietnam
[email protected]
www.dunham-bush.com
R
The manufacturer reserves the right to change specifications without prior notice. M-S-0124A-0121
©Dunham-Bush. All rights reserved.