Power System Protection Lectures - Instrument Transformers
Power System Protection Lectures - Instrument Transformers
By
Pratap Mysore, P.E.
Instrument Transformers
Current Transformer (CT)
• Steps down high currents to relay
input levels.
• Applications – Metering and
Copyright@2014
Power System Protection -
Instrument Transformers -
Relaying.
2
CT Types
• Bushing CT
• Free Standing CT
Copyright@2014
Power System Protection -
Instrument Transformers -
• Auxiliary CT
• Optical CT
3
Transformer Fundamentals
Copyright@2014
Power System Protection -
Instrument Transformers -
IP IS
IP NS VP NP
VP NP NS VS = =
IS NP VS NS
4
Transformer – Magnetizing current
Due to magnetic core, magnetizing current is needed to maintain flux.
IP IS
Voltage Transformer:
Current in the primary winding is
determined by the load connected VP IM
NP NS VS
to the secondary winding.
Copyright@2014
Power System Protection -
Instrument Transformers -
Total Primary Current, IP = (NS/NP)IS + IM
With secondary winding open, The primary current is magnetizing current – around 1% of the
full load current in power transformers.
If secondary is shorted, the primary current is determined by the system impedance and the
transformer impedance - The current magnitude is much higher than the full load rating of the
transformer – Short circuit results in damaging the transformer.
5
Current Transformer (CT)
• Steps down high currents to relay input levels.
IS
IP VS
NS ZB
IM
Copyright@2014
Bushing CT
Internally or Externally mounted on the Bushing
Copyright@2014
Power System Protection -
Instrument Transformers -
CT rating- If primary is not an integral part of the CT,
The CT should be rated for the equipment ratings.
Ex: Transformer or breaker bushing CT. 8
Free Standing CT
• Used in systems up to UHV levels.
Air
Oil
Nitrogen
Copyright@2014
Power System Protection -
Instrument Transformers -
Insulator
the bottom or at the top
Primary
winding
of the bushing.
Secondary
Core & winding
Tank 9
Current Transformer Classification
Metering Class Protection Class
Used with Meters – Used with protective relays
Indication or Billing Required to replicate scaled
Current Range of interest- down secondary currents
Up to Full load ratings of close to the primary fault
Copyright@2014
Power System Protection -
Instrument Transformers -
equipment or customer currents – Could be as high
load. as 20 -25 times the full load
current
10
Auxiliary CT
Copyright@2014
Metering CT Specification
Accuracy is defined at 10% and 100% of rated current
at a specified burden
Copyright@2014
Power System Protection -
Instrument Transformers -
2000/5 0.3 B 1.0
Error will not exceed 0.3% at full rated current of
2000A on the primary with 1.0 ohms burden
connected to the secondary.
As per ANSI standard, error should not exceed 0.6%
12
at 10% of the rated current ( 200 primary amperes)
Metering Accuracy of CTS
Copyright@2014
Metering CT Burden (0.9 PF)
• Accuracy is defined at a rated connected load (referred to as Burden)
• Example:
Burden Resistance (Ω) Inductance (mH) Impedance (Ω) Power factor
Designation @ 60 HZ
Copyright@2014
Power System Protection -
Instrument Transformers -
B-0.1 0.09 0.116 0.1 0.9
14
Protection Class - CT Designation
• C-Class low leakage flux, The ratio can be
calculated.
Copyright@2014
Power System Protection -
Instrument Transformers -
and has to be determined by tests.
• X- Class – 1% accuracy at rated current and user
defined accuracy at 20 times the rated current. Refer
C57.13 to specify.
15
Protection Class CT
Specified as “C### C-voltage” Rating
Copyright@2014
Power System Protection -
Instrument Transformers -
burden.
C800 - CT secondary winding can develop at least
800V across secondary to push 100 amps through 8
ohms burden.
16
Protection Class CT Accuracy
• C-Class – Error will not exceed 3% at rated current and 10% at 20
times the rated current. This is based on designated burden.
Copyright@2014
Power System Protection -
Instrument Transformers -
Designation @ 60 HZ
B-1.0 0.5 2.3 1.0 0.5
17
CT Secondary Voltage required to push
100A through the burden
Copyright@2014
Power System Protection -
Instrument Transformers -
• Winding resistance = 0.002(1200/5) =0.48 ohms
• CT Burden – 4 ohms ( Assume resistive)
• At 100A, CT terminal voltage = 4*100 =400V
• Voltage drop due to winding resistance =0.48*100 =48 V
• CT internal Voltage =400V+48 =448V
18
CT selection
• Select a CT that can develop at least 448 V with 10% error at
100A (Max. Error=10A)
• CT manufacturers publish curves known as “Excitation
Curves”
Copyright@2014
Power System Protection -
Instrument Transformers -
19
C400 CT Excitation Curves
Copyright@2014
Voltage Knee point – a term used by
relay engineers
45 deg. Line intersection with the excitation curve.
Voltage developed by CT
Copyright@2014
Power System Protection -
Instrument Transformers -
Knee-Point
21
10A
IEC Terminology
• IEC defines the Knee point as the voltage at which
10% increase in voltage results in 50% increase in
excitation current.
• IEC Classification –P: 5P20, 10P20 – 5% error at 20
Copyright@2014
Power System Protection -
Instrument Transformers -
times the nominal current or 10% error at 20 times
the nominal current.
• Other Classification as TPS, TPX,TPY and TPZ
• Refer IEC 61869 series or/and IEC60044 series
22
CT Specifications – Rating Factor
• Rating Factor determines the overload capability of a CT
• Example: 2000/5 CT with rating factor of 2.0
• Maximum continuous current – 4000A
• Maximum secondary current -10A
23
Multi Ratio CT
2000/5 CT built as per ANSI standard will
have three taps as shown;
25
Polarity Marking
H
IPrimary 1
ISecondary
X1
Copyright@2014
Power System Protection -
Instrument Transformers -
X2
•Sec. Winding X3
Designation –X,Y, Z, U,W X4
and V.
X5
•Ratio Designated as
xxxx:5A (ex: 1200:5A) 26
Bushing CT designation
Copyright@2014
CT circuit- Electrical representation
Cable impedance
Excitation
Current Relay
Burden
Copyright@2014
Power System Protection -
Instrument Transformers -
Cable impedance
Copyright@2014
Power System Protection -
Instrument Transformers -
Flux in the core,φ is given by φ = ∫ VS dt
29
Fault current with DC offset
Copyright@2014
Flux
Core
Waveform
ωt
Asymmetrical Fault Current –Core Flux
Copyright@2014
φS/A
-φS/A
Copyright@2014
Effect of DC offset
• The Flux increases by a factor of X/R with D.C
offset.
• There will always be a residual flux if the fault
current had DC offset.
Copyright@2014
Power System Protection -
Instrument Transformers -
• Resultant flux with DC offset, will be (1+X/R) times
the flux due to sinusoidal steady state current.
33
CT C-Rating to avoid saturation
• V = (1 +X/R)*IF*ZB; IF-CT Secondary current and ZB -
burden
34
IEEE Power Systems Relaying Committee
(PSRC) Documents
• http://www.pes-psrc.org/. published reports
• CT SAT Calculator (PSRC).xls
Copyright@2014
Power System Protection -
Instrument Transformers -
35
Protection CT Selection
• Maximum continuous Current for primary current rating.
• Use rating factor for emergency rating or select emergency
rating as the primary rating
• Determine the burden – Add cable impedance and the connected
relay impedance.
Copyright@2014
Power System Protection -
Instrument Transformers -
• Determine the max. fault current
• Select the C Class (100, 200, 400 or 800) so that
C-Class V > (1+X/R)*If*(ZBurden)) to avoid saturation.
• C rating- try to select the maximum rating- C800. This may not
be possible due to space constraints.
36
Other Factors –CT Selection
• Max. secondary current <Microprocessor relay A/D limit
(Typical - 100Apk).
Copyright@2014
Power System Protection -
Instrument Transformers -
37
Will CTs Always Saturate?
• It depends on the burden, X/R and C-rating and also on the point of
fault incidence.
Copyright@2014
Power System Protection -
Instrument Transformers -
38
Faults
• Majority of faults are single line to ground.
• D.C offset is maximum if θ - ϕ =900
• System angle, ϕ is around 700 –850
• Fault should occur around zero on the voltage
Copyright@2014
Power System Protection -
Instrument Transformers -
waveform.
• Most of the faults due to insulation failure are around
the voltage peak.
• D.C. offset Probability is low for line to ground faults.
• This is different for three phase faults - at least one of
the phases will have significant offset. 39
CT Saturation Calculator
• Examine the time to saturate, effective current calculated by the
relay
Copyright@2014
Power System Protection -
Instrument Transformers -
40
Other types of CTs-Linear Coupler
• These are CTs without magnetic core.
Copyright@2014
Power System Protection -
Instrument Transformers -
41
Further Reading/ References
• C.R. Mason- Chapters 7 and 8 (CT standards referred to as
“ASA” standards is now superseded by new IEEE standards
classification – C, T ratings
• NPAG – Chapter 6
Copyright@2014
Power System Protection -
Instrument Transformers -
42
Current Transformers References
-Books and Papers
• Stanley E. Zocholl, “Analyzing and Applying Current
transformers” SEL Publication, 2004.
• IEEE WG, “Transient response of Current Transformers”,
IEEE Trans. PAS, VOL.PAS-91, 1977.
Copyright@2014
Power System Protection -
Instrument Transformers -
• Arthur Wright, “ Current Transformers, their transient and
steady state Performance”, Chapman and Hall, 1968.
• Brian D. Jenkins, “Introduction to Instrument-Transformers”,
CRC Press, 1967.
43
Current Transformers – IEEE Documents
• IEEE C57.13-2008, “IEEE standard requirements for instrument
Transformers”.
• IEEE C57.13.1-2006, “ IEEE guide for Field Testing of Relaying Current
Transformers.
• IEEE C57.13.3-2005, “ IEEE guide for Grounding of Instrument
Transformer secondary circuits and Cases”.
Copyright@2014
Power System Protection -
Instrument Transformers -
• IEEE C57.13.5-2009, “ IEEE Standard for Performance and Test
Requirements for Instrument Transformers of a Nominal System voltage
of 115 kV and above”.
• IEEE C57.13.2 –2005 – This standard covers tests required for CT from
600V up to 38kV.
• IEEE C37.110-2007 “IEEE Guide for the Application of Current
Transformers for Protective Relaying Purposes”.
44
44
CT Selection
1. Rating Factor: Always referred to the primary current
• Ex: 2000/5 CT, RF:2.0
• Maximum Primary current = RF*2000 =4000 A
2. C-Rating shows how much voltage the CT secondary can
45
Effect of tapping the CT to a Lower Ratio
2000/5 CT built as per ANSI
standard will have three taps as
shown;
47
C-Rating –Ex-C-800
200 V
800 V
Copyright@2014
Power System Protection -
Instrument Transformers -
600 V
48
Potential Transformer
Copyright@2014
Power System Protection -
Instrument Transformers -
Metering Accuracy –0.3, 0.6, 1.2 at 90% to110% of the nominal
rating.
C57.13.6 – 0.15 Accuracy Class specified.
49
Voltage Transformer Ratings
Copyright@2014
Power System Protection -
Instrument Transformers -
• 40250V/ 115V/67V on 69 kV system – Secondary
has a tap.
• Relays (legacy relays) are normally connected to 67 V
tap.
• Modern relays can withstand at least up to 150V.
50
VT Burdens
Copyright@2014
Power System Protection -
Instrument Transformers -
X 25.0 0.7
M 35.0 0.2
Y 75.0 0.85
Z 200.0 0.85
ZZ 400.0 0.85
51
Polarity
H1
Y-Winding
X2
X1
X3
Copyright@2014
Capacitor Coupling Voltage Transformer
Copyright@2014
Power System Protection -
Instrument Transformers -
C1
Compensating
Reactor
Transformer
C2
53
CCVT Transient Performance
Copyright@2014
CCVT Transient Performance
Copyright@2014
CCVT –Effect of Load on Transients
Copyright@2014
Power System Protection -
Instrument Transformers -
56