0% found this document useful (0 votes)
220 views

Power System Protection Lectures - Instrument Transformers

This document provides information about instrument transformers used in power systems, including their types, fundamentals, specifications, and applications for metering and protection. It covers current transformers, potential transformers, and their roles in stepping down currents and voltages for measurement and relaying purposes.

Uploaded by

avishek
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
220 views

Power System Protection Lectures - Instrument Transformers

This document provides information about instrument transformers used in power systems, including their types, fundamentals, specifications, and applications for metering and protection. It covers current transformers, potential transformers, and their roles in stepping down currents and voltages for measurement and relaying purposes.

Uploaded by

avishek
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 56

Power system Protection Lectures

By
Pratap Mysore, P.E.

Instrument Transformers
Current Transformer (CT)
• Steps down high currents to relay
input levels.
• Applications – Metering and

Copyright@2014
Power System Protection -
Instrument Transformers -
Relaying.

2
CT Types
• Bushing CT

• Free Standing CT

Copyright@2014
Power System Protection -
Instrument Transformers -
• Auxiliary CT

• Optical CT

3
Transformer Fundamentals

VP*IP =VS*IS - PowerIN = PowerOUT


IPNP =ISNS : Ampere-Turns are balanced

Copyright@2014
Power System Protection -
Instrument Transformers -
IP IS

IP NS VP NP
VP NP NS VS = =
IS NP VS NS

4
Transformer – Magnetizing current
Due to magnetic core, magnetizing current is needed to maintain flux.

IP IS
Voltage Transformer:
Current in the primary winding is
determined by the load connected VP IM
NP NS VS
to the secondary winding.

Copyright@2014
Power System Protection -
Instrument Transformers -
Total Primary Current, IP = (NS/NP)IS + IM

With secondary winding open, The primary current is magnetizing current – around 1% of the
full load current in power transformers.

If secondary is shorted, the primary current is determined by the system impedance and the
transformer impedance - The current magnitude is much higher than the full load rating of the
transformer – Short circuit results in damaging the transformer.
5
Current Transformer (CT)
• Steps down high currents to relay input levels.

IS

IP VS
NS ZB
IM

Power System Protection -


Instrument Transformers -
Copyright@2014
Bushing CT
Primary current is determined by the external
load
NP =1; IP = NS*IS ; VS = IS*ZB
Secondary Voltage = IS*ZB
ZB, load connected to the secondary winding
- also called “Burden”
IS = IP(1/NS) -IM 6
Power System Protection -
Instrument Transformers -
7

Copyright@2014
Bushing CT
Internally or Externally mounted on the Bushing

Copyright@2014
Power System Protection -
Instrument Transformers -
CT rating- If primary is not an integral part of the CT,
The CT should be rated for the equipment ratings.
Ex: Transformer or breaker bushing CT. 8
Free Standing CT
• Used in systems up to UHV levels.

Air
Oil
Nitrogen

The cores can be either at

Copyright@2014
Power System Protection -
Instrument Transformers -
Insulator
the bottom or at the top
Primary
winding
of the bushing.

Secondary
Core & winding

Tank 9
Current Transformer Classification
Metering Class Protection Class
 Used with Meters –  Used with protective relays
Indication or Billing  Required to replicate scaled
 Current Range of interest- down secondary currents
Up to Full load ratings of close to the primary fault

Copyright@2014
Power System Protection -
Instrument Transformers -
equipment or customer currents – Could be as high
load. as 20 -25 times the full load
current

10
Auxiliary CT

Used for Ratio Matching

Power System Protection -


Instrument Transformers -
11

Copyright@2014
Metering CT Specification
Accuracy is defined at 10% and 100% of rated current
at a specified burden

Specified as “##B## - %accuracy B Burden in ohms”.

Copyright@2014
Power System Protection -
Instrument Transformers -
 2000/5 0.3 B 1.0
 Error will not exceed 0.3% at full rated current of
2000A on the primary with 1.0 ohms burden
connected to the secondary.
 As per ANSI standard, error should not exceed 0.6%
12
at 10% of the rated current ( 200 primary amperes)
Metering Accuracy of CTS

Power System Protection -


Instrument Transformers -
13

Copyright@2014
Metering CT Burden (0.9 PF)
• Accuracy is defined at a rated connected load (referred to as Burden)
• Example:
Burden Resistance (Ω) Inductance (mH) Impedance (Ω) Power factor
Designation @ 60 HZ

Copyright@2014
Power System Protection -
Instrument Transformers -
B-0.1 0.09 0.116 0.1 0.9

B-0.5 0.45 0.58 0.5 0.9

B –1.8 1.62 2.08 1.8 0.9

14
Protection Class - CT Designation
• C-Class low leakage flux, The ratio can be
calculated.

• T- Class – high leakage ratio cannot be calculated

Copyright@2014
Power System Protection -
Instrument Transformers -
and has to be determined by tests.
• X- Class – 1% accuracy at rated current and user
defined accuracy at 20 times the rated current. Refer
C57.13 to specify.

15
Protection Class CT
Specified as “C### C-voltage” Rating

The CT secondary will be able to push 100A (20 times


the rated secondary) through a specified connected

Copyright@2014
Power System Protection -
Instrument Transformers -
burden.
C800 - CT secondary winding can develop at least
800V across secondary to push 100 amps through 8
ohms burden.

16
Protection Class CT Accuracy
• C-Class – Error will not exceed 3% at rated current and 10% at 20
times the rated current. This is based on designated burden.

Burden Resistance (Ω) Inductance (mH) Impedance (Ω) Power factor

Copyright@2014
Power System Protection -
Instrument Transformers -
Designation @ 60 HZ
B-1.0 0.5 2.3 1.0 0.5

B - 2.0 1.0 4.6 2.0 0.5

B - 4.0 2.0 9.2 4.0 0.5

B – 8.0 4.0 18.4 8.0 0.5

17
CT Secondary Voltage required to push
100A through the burden

• CT winding Resistance- Value provided by CT manufacturer –


typical value: 0.002 ohms/turn –
• Ex: 1200/5 CT , C400

Copyright@2014
Power System Protection -
Instrument Transformers -
• Winding resistance = 0.002(1200/5) =0.48 ohms
• CT Burden – 4 ohms ( Assume resistive)
• At 100A, CT terminal voltage = 4*100 =400V
• Voltage drop due to winding resistance =0.48*100 =48 V
• CT internal Voltage =400V+48 =448V

18
CT selection
• Select a CT that can develop at least 448 V with 10% error at
100A (Max. Error=10A)
• CT manufacturers publish curves known as “Excitation
Curves”

Copyright@2014
Power System Protection -
Instrument Transformers -
19
C400 CT Excitation Curves

Power System Protection -


Instrument Transformers -
20

Copyright@2014
Voltage Knee point – a term used by
relay engineers
45 deg. Line intersection with the excitation curve.
Voltage developed by CT

Copyright@2014
Power System Protection -
Instrument Transformers -
Knee-Point

10% error at 100A

21
10A
IEC Terminology
• IEC defines the Knee point as the voltage at which
10% increase in voltage results in 50% increase in
excitation current.
• IEC Classification –P: 5P20, 10P20 – 5% error at 20

Copyright@2014
Power System Protection -
Instrument Transformers -
times the nominal current or 10% error at 20 times
the nominal current.
• Other Classification as TPS, TPX,TPY and TPZ
• Refer IEC 61869 series or/and IEC60044 series

22
CT Specifications – Rating Factor
• Rating Factor determines the overload capability of a CT
• Example: 2000/5 CT with rating factor of 2.0
• Maximum continuous current – 4000A
• Maximum secondary current -10A

Power System Protection -


Instrument Transformers -
Copyright@2014
• Rating Factor of 3.0 allows 6000A on the primary and 15 A on the
secondary
• Ex: Emergency loading of a power Transformer up to 160% of the
Maximum normal rating – CT should also be rated to allow the
overload rating.

23
Multi Ratio CT
2000/5 CT built as per ANSI standard will
have three taps as shown;

The relay is connected the following taps


based on the required ratio.

Power System Protection -


Instrument Transformers -
Copyright@2014
• 300/5 X3-X4
•400/5 X1-X2
•500/5 X4-X5
•800/5 X2-X3
•1100/5 X2-X4
•1200/5 X1-X3
•1500/5 X1-X4
•1600/5 X2-X5
•2000/5 X1-X5
2000/5 CT will have 400
24
turns in the secondary
winding
Effect of Tap on the Rating Factor
2000/5 with Rating Factor: 2.0 Nominal primary current: 2000A

 Iprimary cannot exceed 4000A

Isecondary cannot exceed 10A

Power System Protection -


Instrument Transformers -
Copyright@2014
X1-X2 (80:1 or 400/5)
 Secondary current cannot exceed 10A
Primary current cannot exceed 800A
X2-X5 (320:1 or 1600/5)
Secondary current cannot exceed 10A
Primary current cannot exceed 3200A
Effective overload capability will be
3200/2000 = 1.6

25
Polarity Marking
H
IPrimary 1
ISecondary
X1

Copyright@2014
Power System Protection -
Instrument Transformers -
X2

•Sec. Winding X3
Designation –X,Y, Z, U,W X4
and V.
X5
•Ratio Designated as
xxxx:5A (ex: 1200:5A) 26
Bushing CT designation

Power System Protection -


Instrument Transformers -
27

Copyright@2014
CT circuit- Electrical representation

Cable impedance

Excitation
Current Relay
Burden

Copyright@2014
Power System Protection -
Instrument Transformers -
Cable impedance

• Cable- #10 gauge – 1.0 ohms per 1000 ft.


• E/M relay burden generally published as Volt Ampere (VA)
– Depends on the relay and the setting – as high as 15.68
ohms – 3.92 VA @0.5 A
• Microprocessor Relays-
• 1-5 VA at 5A. 28
• Max. Z=0.2 ohms.
CT Transient Performance

Voltage developed across the CT secondary = IS*ZB;


where; IS-Secondary Current and ZB-Burden(=cable
resistance+CT resistance+Burden)

Copyright@2014
Power System Protection -
Instrument Transformers -
Flux in the core,φ is given by φ = ∫ VS dt

Fault current may contain DC offset

29
Fault current with DC offset

Power System Protection -


Instrument Transformers -
30

Copyright@2014
Flux
Core
Waveform

ωt
Asymmetrical Fault Current –Core Flux

Power System Protection -


Instrument Transformers -
31

Copyright@2014
φS/A

-φS/A

Power System Protection -


Instrument Transformers -
32

Copyright@2014
Effect of DC offset
• The Flux increases by a factor of X/R with D.C
offset.
• There will always be a residual flux if the fault
current had DC offset.

Copyright@2014
Power System Protection -
Instrument Transformers -
• Resultant flux with DC offset, will be (1+X/R) times
the flux due to sinusoidal steady state current.

33
CT C-Rating to avoid saturation
• V = (1 +X/R)*IF*ZB; IF-CT Secondary current and ZB -
burden

• Fault current 20,000A, X/R=17; CT ratio-2000/5; total burden


= 2 ohms ( cable Resistance-1.0 ohms, CT resistance 0.8 ohms

Power System Protection -


Instrument Transformers -
Copyright@2014
and relay burden 0.2 ohms)
V = (1+17)*(20,000/400)*2 = 1800V
If C800 is used, it will saturate for few cycles.
This can be verified using Excel spread sheet of IEEE Power
Systems Relaying Committee

34
IEEE Power Systems Relaying Committee
(PSRC) Documents
• http://www.pes-psrc.org/. published reports
• CT SAT Calculator (PSRC).xls

Copyright@2014
Power System Protection -
Instrument Transformers -
35
Protection CT Selection
• Maximum continuous Current for primary current rating.
• Use rating factor for emergency rating or select emergency
rating as the primary rating
• Determine the burden – Add cable impedance and the connected
relay impedance.

Copyright@2014
Power System Protection -
Instrument Transformers -
• Determine the max. fault current
• Select the C Class (100, 200, 400 or 800) so that
C-Class V > (1+X/R)*If*(ZBurden)) to avoid saturation.
• C rating- try to select the maximum rating- C800. This may not
be possible due to space constraints.

36
Other Factors –CT Selection
• Max. secondary current <Microprocessor relay A/D limit
(Typical - 100Apk).

Copyright@2014
Power System Protection -
Instrument Transformers -
37
Will CTs Always Saturate?
• It depends on the burden, X/R and C-rating and also on the point of
fault incidence.

• Use Excel spread sheet on IEEE-PSRC website.

Copyright@2014
Power System Protection -
Instrument Transformers -
38
Faults
• Majority of faults are single line to ground.
• D.C offset is maximum if θ - ϕ =900
• System angle, ϕ is around 700 –850
• Fault should occur around zero on the voltage

Copyright@2014
Power System Protection -
Instrument Transformers -
waveform.
• Most of the faults due to insulation failure are around
the voltage peak.
• D.C. offset Probability is low for line to ground faults.
• This is different for three phase faults - at least one of
the phases will have significant offset. 39
CT Saturation Calculator
• Examine the time to saturate, effective current calculated by the
relay

Copyright@2014
Power System Protection -
Instrument Transformers -
40
Other types of CTs-Linear Coupler
• These are CTs without magnetic core.

Copyright@2014
Power System Protection -
Instrument Transformers -
41
Further Reading/ References
• C.R. Mason- Chapters 7 and 8 (CT standards referred to as
“ASA” standards is now superseded by new IEEE standards
classification – C, T ratings
• NPAG – Chapter 6

Copyright@2014
Power System Protection -
Instrument Transformers -
42
Current Transformers References
-Books and Papers
• Stanley E. Zocholl, “Analyzing and Applying Current
transformers” SEL Publication, 2004.
• IEEE WG, “Transient response of Current Transformers”,
IEEE Trans. PAS, VOL.PAS-91, 1977.

Copyright@2014
Power System Protection -
Instrument Transformers -
• Arthur Wright, “ Current Transformers, their transient and
steady state Performance”, Chapman and Hall, 1968.
• Brian D. Jenkins, “Introduction to Instrument-Transformers”,
CRC Press, 1967.

43
Current Transformers – IEEE Documents
• IEEE C57.13-2008, “IEEE standard requirements for instrument
Transformers”.
• IEEE C57.13.1-2006, “ IEEE guide for Field Testing of Relaying Current
Transformers.
• IEEE C57.13.3-2005, “ IEEE guide for Grounding of Instrument
Transformer secondary circuits and Cases”.

Copyright@2014
Power System Protection -
Instrument Transformers -
• IEEE C57.13.5-2009, “ IEEE Standard for Performance and Test
Requirements for Instrument Transformers of a Nominal System voltage
of 115 kV and above”.
• IEEE C57.13.2 –2005 – This standard covers tests required for CT from
600V up to 38kV.
• IEEE C37.110-2007 “IEEE Guide for the Application of Current
Transformers for Protective Relaying Purposes”.
44

44
CT Selection
1. Rating Factor: Always referred to the primary current
• Ex: 2000/5 CT, RF:2.0
• Maximum Primary current = RF*2000 =4000 A
2. C-Rating shows how much voltage the CT secondary can

Power System Protection -


Instrument Transformers -
Copyright@2014
produce to push current through the connected load not exceeding
10% error
• Ex: C800. Can push 100A through 8 ohms burden with 10% error or
less.

45
Effect of tapping the CT to a Lower Ratio
2000/5 CT built as per ANSI
standard will have three taps as
shown;

The relay is connected the following


taps based on the required ratio.

Power System Protection -


Instrument Transformers -
Copyright@2014
• 300/5 X3-X4
•400/5 X1-X2
•500/5 X4-X5
•800/5 X2-X3
•1100/5 X2-X4
•1200/5 X1-X3
2000/5 CT will have •1500/5 X1-X4
400 turns in the •1600/5 X2-X5
secondary winding •2000/5 X1-X5
46
Rating Factor
• Secondary current limit may reduce the primary rating.
• Ex: 2000/5 RF 2.0
• Max. primary current= 4000A;
• Max. secondary current=10A

Power System Protection -


Instrument Transformers -
Copyright@2014
• If tapped at 800/5, max. current on the primary is limited to
1600A.

47
C-Rating –Ex-C-800
200 V

800 V

Copyright@2014
Power System Protection -
Instrument Transformers -
600 V

The C-rating reduces with lower CT ratio

48
Potential Transformer

 Steps down the voltage to 120V or less.


 C57.13 specifies the ratings.

Copyright@2014
Power System Protection -
Instrument Transformers -
 Metering Accuracy –0.3, 0.6, 1.2 at 90% to110% of the nominal
rating.
 C57.13.6 – 0.15 Accuracy Class specified.

49
Voltage Transformer Ratings

• Typically connected –Phase to ground.


• Standard Ratios as per Table 12 of IEEE C57.13-
2008.

Copyright@2014
Power System Protection -
Instrument Transformers -
• 40250V/ 115V/67V on 69 kV system – Secondary
has a tap.
• Relays (legacy relays) are normally connected to 67 V
tap.
• Modern relays can withstand at least up to 150V.
50
VT Burdens

Designation BURDEN At 120V and at 69.3V basis


VA Power Factor
W 12.5 0.1

Copyright@2014
Power System Protection -
Instrument Transformers -
X 25.0 0.7

M 35.0 0.2
Y 75.0 0.85
Z 200.0 0.85
ZZ 400.0 0.85

51
Polarity

H1

Y-Winding
X2
X1

X3

Power System Protection -


Instrument Transformers -
52

Copyright@2014
Capacitor Coupling Voltage Transformer

• CCVTs are more economical at higher voltages instead of


wound transformers.

Copyright@2014
Power System Protection -
Instrument Transformers -
C1

Compensating
Reactor

Transformer
C2
53
CCVT Transient Performance

Power System Protection -


Instrument Transformers -
54

Copyright@2014
CCVT Transient Performance

Power System Protection -


Instrument Transformers -
55

Copyright@2014
CCVT –Effect of Load on Transients

• Transients are higher if CCVT is loaded.


• Fault Point on the waveform also has an effect.

Copyright@2014
Power System Protection -
Instrument Transformers -
56

You might also like