ALE75-100AV Specification EN 3A40ZS1199P1-04

This document provides product specifications for Kobe Steel's ALE75AV and ALE100AV air compressor models. It includes details on: - Model specifications such as frequency, voltage, discharge air volume, control system, pressure and temperature conditions. - Safety features including safety valve settings and insulation class. - Component details like motor type, drive system, and pipe diameters. - Physical dimensions, weights and noise levels. - Installation guidelines concerning ventilation, ambient temperature, and recommended lubricating oil. The document contains technical specifications, guidelines and warnings for the proper installation and use of these air compressor units.

Uploaded by

Thanh Barca
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
217 views27 pages

ALE75-100AV Specification EN 3A40ZS1199P1-04

This document provides product specifications for Kobe Steel's ALE75AV and ALE100AV air compressor models. It includes details on: - Model specifications such as frequency, voltage, discharge air volume, control system, pressure and temperature conditions. - Safety features including safety valve settings and insulation class. - Component details like motor type, drive system, and pipe diameters. - Physical dimensions, weights and noise levels. - Installation guidelines concerning ventilation, ambient temperature, and recommended lubricating oil. The document contains technical specifications, guidelines and warnings for the proper installation and use of these air compressor units.

Uploaded by

Thanh Barca
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 27

ALE75AV ALE100AV

ALE75AV-H ALE100AV-H

SPECIFICATIONS

KOBE STEEL,LTD.

 DWG. No. 3A40ZS1199P1


Printed 2016.02 ISSUE 04
P1

CONTENTS

〔CONTENTS〕

Contents 1
Product Specifications 2
Installation Conditions 5
Electric Power Facilities 10
Lubricating Oil 12
Tips For Sound Control Measures 14
After-Sales Service 16
Warranty Conditions / Indemnity 18

〔Attached Drawings〕
(1) ITCS Controller 19
(2) External Drawing 20
(3) Installation Process 22
(4) System Diagram 23
(5) Wiring Diagram 24
(6) Outside Terminal Diagram 26

  WARNING
RESPIRATORY DISORDER
   Do not breathe in nonclean compressed air or do
   not use it for any respiratory equipment; otherwise,
   a respiratory disorder may be caused.
P2

PRODUCT SPECIFICATIONS
◆ 0.75MPa{7.5bar} Specifications
Model
ALE75AV ALE100AV
Item
Frequency (Hz) 50
Voltage (V) 380
Discharge air volume (m3/min) 11.6 17.0
Consumption gas quantity between about 40~100%;
the constant pressure control by the inverter
Control system
Consumption gas quantity less than about 40%;
load and unload control

Pressure (MPa{bar}) 0.1{1.0}


Suction
Temperature (℃) 20
condition
Humidity (%) 0

Gauge pressure 0.75 {7.5}(The setup of the constant pressure control is less
(MPa{bar}) than 0.73{7.3})
Discharge
condition
Below ambient temperature Below ambient temp.
Temperature (℃)
+20 +15

Safety valve setting press. [After-cooler]


0.83 {8.3}
(Gauge pressure) (MPa{bar})

Output (kW) 75 (SF=1.1) 100 (SF=1.1)


Main motor

Type Permanent magnet type 3-phase synchronism


Starting system Inverter

Totally enclosed, Insulation class F,


Specification
Continuous rating

Driving system step-up gear


Fan motor output (kW) 2.2 3.0
Oil pump motor output (kW) 1.5 2.2
Discharge pipe diameter JIS10k-40A RF JIS10k-50A RF
Initial charge of lubricating oil (L) 30 50
Dimensions
2385× 1400× 1783 2466× 1500× 2160
(Width×Depth×Height) (mm)

Weight (kg) 2160 2980


Noise level (dB(A)) 70 69
P3

◆ 0.88MPa{8.8bar} Specifications
Model
ALE75AV-H ALE100AV-H
Item
Frequency (Hz) 50
Voltage (V) 380
Discharge air volume (m3/min) 10.1 15.7
Consumption gas quantity between about 50~100%;
the constant pressure control by the inverter
Control system
Consumption gas quantity less than about 50%;
load and unload control
Pressure (MPa{bar}) 0.1{1.0}
Suction
Temperature (℃) 20
condition
Humidity (%) 0

Gauge pressure 0.88 {8.8}(The setup of the constant pressure control is less
(MPa{bar}) than 0.86{8.6})
Discharge
condition
Below ambient temperature Below ambient temperature
Temperature (℃)
+20 +20

Safety valve setting press. [After-cooler]


0.97 {9.7}
(Gauge pressure) (MPa{bar})

Output (kW) 75 (SF=1.1) 100 (SF=1.1)


Main motor

Type Permanent magnet type 3-phase synchronism


Starting system Inverter

Totally enclosed, Insulation class F,


Specification
Continuous rating

Driving system step-up gear


Fan motor output (kW) 2.2 3
Oil pump motor output (kW) 1.5 2.2
Discharge pipe diameter JIS10k-40A RF JIS10k-50A RF
Initial charge of lubricating oil (L) 30 50
Dimensions
2385× 1400× 1783 2466× 1500× 2160
(Width×Depth×Height) (mm)

Weight (kg) 2160 2980


Noise level (dB(A)) 72 71
P4

◆Inverter Specifications
Model
Inverter
Item
Frequency (HZ) 50
Power supply
Voltage (V) Three phase 380

Cooling system Air-cooled


Control mode Sine wave PWM system(Electric current vector control)
Details
Control function PID control
Harmonic restraint DC reactor built in

Notes)
(1) The discharge air volume is the value obtained when the compressor is in the above
mentioned suction condition.
(2) As for the guaranteed values, consult with us separately.
(3) The discharge pressure shows a value after the check valve of compressor.
(4) SF is the meaning of the service factor.
(5) The noise level is measured at 1.5 m away from the machine front and 1 m from the
floor in the anechoic room, with the machine being operated at its full load. As for
the noise level of side and rear face, consult with us separately.
(6) The discharge air must not be used for respiratory equipment from which aspiration
is directly made.
(7) The inside of the unit is cooled down by the ambient air of the compressor installation
site; provide good ventilation to keep the ambient temperature below 45℃.
(8) As for the discharge temperature exceeding the standard condition, consult with
us separately.
(9) Flanges are not included for end of the air pipe.
(10) Make sure to fill the tank with the recommended lubricating oil before operation.
P5

INSTALLATION CONDITIONS

1.Caution in installing the unit


1) Installation site
○ Install the unit indoors where good ventilation is provided. Do not install the unit
outdoors since it is designed for indoor use.

○ The cleaner the suction air is, the longer the machine life is. Avoid such installation
sites subjected to dust, chlorine gas, hydrogen sulfide gas, sulfur dioxide gas, highly
concentration of ozone or any other toxic gas. Also avoid underground or highly
humid place.

○ Keep the machine ambient temperature 45 ℃ or lower. Operation in a room at a


temperature higher than 45 ℃ causes thermal trip or other troubles. Install a
ventilation fan in the room where the compressor is installed to keep the ambient
temperature 45 ℃ or lower.

○ When the indoor temperature that the compressor was installed is lower than 0 ℃,
the oil viscosity is raised, and it is expected to become a starter failure. As for such
case, consult the manufacture separately.

○ Make spaces for maintenance around a machine.


Make a space for opening and closing of covers, operation and maintenance on the
front side, and for exhausting normally on the topside, and for suction air and piping
on the rear side, and on the left side and the right side alike.
(Refer to the external drawing on further details as to spaces.)

2) Caution in installation
○ Perform foundation works on 2 positions, the compressor front and rear, with the
foundation bolts and foundation bolt's set plates attached (see the Exterior Drawing).
Always set cauls for foundation bolts, which is effective for noise prevention.

○ Be sure to connect the ground cable to the terminal installed on the operation panel.

○ The noise level changes by the size of the room where the compressor is installed,
the position, the reflective rating of the wall and so on.

○ Install the compressor on the horizontal floor, and don't install it on the shape steel
and the block. Installation on the shape steels or the blocks may cause increased noise.

○ In the case of installing the compressor's charge's and its discharge's mouth in
the room, pay attention to its mouth's position and direction.
P6

3) Installation of air tank


○ The machine starts load/unload operation at the minimum rated speed.
As to the discharge piping, be sure to install an air tank in the discharge line in order
to control the pressure fluctuation.

Item ※
Air tank capacity ( m3 )
Model
 ALE75AV Min. 1.9
 ALE75AV-H Min. 2.1
 ALE100AV Min. 2.8
 ALE100AV-H Min. 3.2

※) In case of load rate is 20~22%, differential pressure of upper and lower limit pressure is
0.05MPa {0.5bar}, a cycle time (load → unload → load) is 23 seconds.
The capacity shown above is for the constant pressure operation.
And also the capacity shall be selected so as to keep pressure of the discharge line over
0.29MPa {2.9bar} . When operating some machines, or to perform group control operation,
it is necessary to also examine set pressure.

○ Selection of air tank considering cycle time (example)

(t1+t2)× Qs × Pa × x(1-x)
VR=
D

PH
VR :Air tank capacity (m3 )
t1 :Unload time (sec.)
t2 :Load time (sec.)
t1+t2 ≧ 23sec. (more than 23sec.)
Qs :Discharge air volume (m3/s)
PL
t1 t2 Pa :Suction absolute pressure (MPa {bar})
D :Difference of high pressure from
low pressure (MPa {bar})
x :Load rate (Air consumption to volume Qs)
(Air tank capacity is surely made the
biggest at the time of load rate of 50%.)
P7

2.Caution in piping

1) Discharge-air piping
○ The pipe diameter is DN50 or bigger. The discharge air pipe shall be as short as
possible so as to minimize the pressure drop in the pipe. When deciding the pipe
diameter, allow for the piping resistance.

○ An unsupported long piping may cause for vibration and, as a result, the devices
to which such piping is connected may be damaged. The piping must be properly
supported (using hangers, fasteners, columns, etc.).

○ Slope the pipes in the air flow direction to prevent the drain from remaining in pipes.

○ When two or more screw compressor units are to be connected to the same main
discharge pipe, equip a stop valve in every discharge pipe from the unit to close
the valve while either compressor unit is in rest. Set up a drain outlet valve between
the screw compressor, and set up the stop valve of the same size in that point as well
separately. It is necessary at the time of the trial run and the maintenance.

○ For the piping extended up to the air tank, install a drain outlet, for easy draining.

○ Don't equip a check valve between a compressor and the air tank.

○ When a screw type compressor and a reciprocating type compressor are to be installed
together, the discharge pipe from a screw compressor shall be connected to
the downstream of the air tank to keep the pulsation from the reciprocating type
compressor away.
P8

2) Other piping
○ For drain discharge from the inter-cooler and the after-cooler, use a DN10 pipe.

3.Ventilation
○ Install a ventilating fan such a place where the ventilated air is never sucked again.

Item Heat quantity to generate Unit displacement


Model (kJ/h) (m3/min)
 ALE75AV
316,250 200
 ALE75AV-H
 ALE100AV
423,950 300
 ALE100AV-H

Item Ventilation with


Ventilation with
General ventilation exhaust duct
exhaust duct
and exhaust fan
Model (m3/min) (m3 /min ) 3
(m /min )
 ALE75AV
439 15 215
 ALE75AV-H
 ALE100AV
589 15 315
 ALE100AV-H
Note) The unit displacement is displacement on the compressor side.

○ Refer to the next page for the installing a ventilating duct.

WARNING

RESPIRATORY DISORDER
Do not breathe in nonclean compressed air or do not use it for any respiratory equipment;
otherwise, a respiratory disorder may be caused.

WARNING

Grease is not used in the compression section of an oil-free compressor, so discharged


air and drainage water essentially contain no oil. However, a small amount of oil, held in
the atmosphere or attached on the parts at the time of manufacturing, may be contained.
P9

 General ventilation
 This ventilating capacity is provided when the compressor
 is installed in a small room to be ventilated generally
 (assuming that the allowable rise in interior temperature
 Δt is 10℃). Install an exhaust fan on the upper part of
 the wall at the compressor outlet side, and inlet on the lower
 part of the wall at the compressor suction side. Provide such
 a size of inlet opening as to keep the velocity of airflow to be
 2 m/s or less.
 Ventilation with exhaust duct
 When the pressure loss of the exhaust duct is calculated to
 be 0.2 mbar or less based on the compressor airflow quantity,
 the exhaust duct can be directly connected to the compressor
 outlet. When connecting the exhaust duct to the outlet,
 make use of the mounting mark on the top. The exhaust duct
 shall be removable. Install the exhaust fan and the inlet
 according to the same procedure as in the general ventilation.
 Provide such a size of inlet opening as to keep the velocity of
 airflow to be 2 m/s or less.
 Ventilation with exhaust duct and exhaust fan
 When the pressure loss of the exhaust duct is 0.2 mbar or
 more, install such an exhaust fan inside the duct as to
 maintain the fan airflow quantity as above. At this time,
 provide a 200-300 mm of clearance (H) between the exhaust
 duct inlet and the compressor outlet. During running
 the compressor, run the exhaust fan as well. On stopping
 the compressor, stop the exhaust fan as well. Provide such a
 size of inlet opening as to keep the velocity of airflow to be
 2 m/s or less.
Note) Be careful of the position for the exhaust duct opening; noise may leak out of the duct.

●How to obtain the ventilation air H :Heat amount to be generated (kJ/h)


 quantity to be required γ :Specific gravity (1.2kg/m3 )
H Cp :Specific heat (1.0kJ/kg・℃)
Q =
γ×Cp×Δt×60 Δt :t1-t2
3
Q :Airflow quantity to be required (m /min) t1 :Allowable interior temperature (℃)
t2 :Outside-air temperature (℃)
●How to obtain the effective opening area
Q+QC Q :Airflow quantity to be required (m3/min)
A =
V×60 Qc :Discharge air quantity of compressor (m3/min)
A :Effective opening area (m2) V :Velocity of airflow at air inlet (m/s)
P10

ELECTRIC POWER FACILITIES

○ The starter panel of this machine is installed inside front of the unit.
○ Connection to the power source must be carried out correctly referring to the attached
electrical wiring diagram and in accordance with the rules and regulations applied to
each customer.

1. The inverter unit electric characteristics

Item Input electric current Input electric current Input electric current
Voltage
at the rated time at the max. rated in the motor max.
Model (V)
(A) time (A) rated output(A)
 ALE75AV
142 156 156
 ALE75AV-H
380
 ALE100AV
176 194 194
 ALE100AV-H
Note) The change in the allowable voltage of the inverter is±10%

2.Selection of the earth leakage breaker

○ As a short-circuit protective device for the power source, be sure to install an earth
leakage breaker instead of a knife switch with fuse which will burn the motor due to
an open-phase operation.
Considering harmonic, use the earth leakage breaker corresponding to harmonic·surge
in the following list or to harmonic·surge of other makers.

(Sensitive current:200mA, Time extend time: 0.3sec)


Item Voltage
MITSUBISHI(Production since 1988)
Model (V)
 ALE75AV
NV225-SW/225A 3P
 ALE75AV-H
380
 ALE100AV
NV400-SP/300A 3P
 ALE100AV-H
P11

3. Selection of the power cables


○ For the power cables, select CV cables insulated by the polyvinyl chloride.
CV cable:crosslinked-polyethylene insulated vinyl sheath power cable

Item Diameter(mm2) screw size


Voltage(V)
Model Max.30m Max.60m Max.100m of terminal
 ALE75AV
60 60 100 M6
 ALE75AV-H
380
 ALE100AV
100 100 150 M12
 ALE100AV-H
Notes)
1.In case the wiring distance exceeds 100m, thicker cabels are required.
2. When you connect two or more cables per pole, please carry out by two.

4.Selection of earth cable


○ Connect the earth cable to the fixed bolt(marked E) of the starter panel. Apply the groundin
of 10Ω or less to the compressor.
Never fail to connect the ground, or it causes the electrical shock accidents and the compres
troubles.
When the length of the earth cable is less than 5m,its diameter is generally required the si
in the following list.

Item
Voltage(V) Diameter(mm2)
Model
ALE75AV
38
ALE75AV-H
380
ALE100AV
60
ALE100AV-H

5.Phase advancing condenser


○ Never install phase advancing condenser, otherwise burnt could be result.
If the existing power or motor circuit has a phase advancing condenser,
a reactor should be installed in the upstrem of the condenser.
When installing a reactor, please consult the manufaturer of the existed condenser.
P12

LUBRICATING OIL

1.Control of Lubricating Oil

○ For the long and good use of the compressor, proper control of the lubricating oil is
necessary.

○ Lubricating oil shall not be mixed with that of a different brand.


Mixing oil may cause deterioration of oil or adherents which may shorten the life of
bearing extremely.

○ If you change the brand of oil, drain the oil completely, and clean the oil line by
flushing oil, and supply new oil.

○ Lubricating oil should be changed the entire quantity in 1 year or 8000 hours,
whichever comes first. But conduct sampling of every half year only in the first year,
and confirm the effectiveness of the exchange at 1 year (or 8000 hours).

○ You must use the lubricating oil of the brands recommended in the following table.
The machine has been designed for the following brands of lubricating oil.
The use of unrecommended brands could shorten the life of bearings extremely as
proper oil quantity and film cannot be maintained.

2.Recommended lubricating oil brand

Brand name    Viscosity : ISO VG 68


Oil manufacturer    Type of oil: Turbine oil with additives
Idemitsu Kosan  Daphne Turbine Oil 68
Exxon Mobil  Teresso 68
 Teresstic T 68
 Mobil DTE Oil Heavy Medium
COSMO OIL Cosmo Turbine Super 68
JX Nippon Oil & Energy  JOMO RIX Turbine 68
 FBK Turbine 68
Shell Oil  Turbo Oil T 68
P13

3.Replenish of motor grease

○ Since the grease valve system is adopted in the shaft seal part of the main motor.
Replenish the new grease to two places in the load-side and the fan-side according to
the following table. Undercharge or overcharge of motor grease could cause problem
on the bearing of main motor. The replenishment must be performed in an appropriate
amount (as per the specification) for every replenishment interval. Use grease gun to
replenish grease under pressure while the motor is in operation.

◆ Grease
Amount of replenishment Replenishment
Recommended grease brand interval
Load side Fan side
ALE75AV
ALE75AV-H
45g 60g 1500h
ALE100AV KOBELCO TOUGH GREASE

ALE100AV-H

○ Never mix different types of greases. Mixture of greases of different quality or brand,
or with different additives could cause deterioration and insufficient lubrication.
As a result, bearings could be damaged and extremely short-lived.

○ Do not fill the grease except the above one. The main motor is designed on the basis
of the above mentioned grease. If you use other grease, the bearing temperature will
rise and lead to damage of the bearing. It will also shorten the bearing life.

○ Please refer to the operation manual about other precautions.


P14

TIPS FOR SOUND CONTROL MEASURES

The sound level on this machine is measured at the point 1.5m from the front of
the machine and 1m above the floor in an anechoic chamber. The sound level
depends on the measuring position. It also changes according to the circumstances
and conditions under which the machine is installed. To install the machine, special
consideration should be given to sound control measures. The following are just
samples for sound control measures to be done by customers.

<Case 1>

If the discharge piping is securely


attached to the wall, vibration may
transmit to the building.

<Case 2>

There may be gap between the Fill up the gap to avoid resonance.
compressor base plate and the floor.

<Case 3>

The sound level is increased due to Install sound absorbing material to


reverberation against the wall behind the wall to reduce the sound level.
the machine.
P15

<Case 4>

The piping is resonant with the air tank. ・Lag the piping
・Please install the silencer between the
 compressor and the air tank. Set up
 the support in consideration of weight
 when installing the silencer.
<Case 5>

The opening position of exhaust duct To reduce the sound level in the vicinity
can influence the sound level. of compressor room, install sound
absorbing material to the inner surface
of exhaust ducting.
Note) In constructing the exhaust ducting,
always maintain the static pressure at
20Pa or below.

<Others>
The sound level also varies according to the number of operating compressors.
For example, if three 85dB compressors operate, the sound level will be as calculated
by the following equation:
85 85 85
 10 log(10 10 +10 10 +10 10 )=90dB

There are other factors that may increase the sound level.
When installing the compressor, take effective sound control measures with adequate
consideration.

If there are unclear points, please consult separately.


P16

AFTER-SALES SERVICE

Proper maintenance is necessary to keep the compressor in good condition for long
periods. Inside the compressor, there are various heavy equipments such as the motor,
and many of them need removing or replacing at the time of maintenance. As shown
below, the installation of the I-beam will make it safer and easier to do
the maintenance work.

<Installation of the I-beam>

ting

420

<Precaution>

(1) Select the I-beam with enough load capacity to lift the heavy load listed above.
Take the joint strength between the building and I-beam into account.

(2) The compressor’s maintenance needs specialized knowledge and skill.


The maintenance work by the Customer yourself or other companies may
cause an unexpected accident.
Please be sure to contact us for the maintenance work.
P17

AFTER-SALES SERVICE

Proper maintenance is necessary to keep the compressor in good condition for long
periods. Inside the compressor, there are various heavy equipments such as the motor,
and many of them need removing or replacing at the time of maintenance. As shown
below, the installation of the I-beam will make it safer and easier to do
the maintenance work.

<Installation of the I-beam>

2nd-stage

《Lifting weight》 maintenance i-beam Main motor

810
maintenance i-beam

Name Weight(kg)
1st-stage 160
compressor unit

690
2nd-stage 80 1st-stage Compressor unit
compressor unit maintenance i-beam

Main motor 500


845
Building ceiling

1630 2030
MIN.1300

570 480 450

900 2010 750


1500

Main motor
Compressor
1st-stage 2-stage
unit
2160

<Precaution>

(1) Select the I-beam with enough load capacity to lift the heavy load listed above.
Take the joint strength between the building and I-beam into account.

(2) The compressor’s maintenance needs specialized knowledge and skill.


The maintenance work by the Customer yourself or other companies may
cause an unexpected accident.
Please be sure to contact us for the maintenance work.
P18

WARRANTY CONDITIONS

1.Warranty conditions

The warranty period shall be 12 month after completion of the test run or 18 months
after shipment, whichever comes first.
※“After completion of the test run”shall mean
[At the time when the test run (procedure and activities of receiving materials
test) is completed after installation at site.]

2.Contents of warranty

In case a trouble should occur during the warranty period and when it is determined
that the trouble is caused clearly by our defective design, manufacture and/or
execution of work, we repair or replace the parts free of change without delay.

3.Exceptions to the application of warranty

Even during the warranty period of this machine, we refuse warranty in the following
cases:
① Trouble caused by the natural disasters or accidents beyond human control.

② Trouble caused by a defective material selected or supplied by you, or caused by


a defect resulted from the design designated by you.

③ Trouble caused by a repair or modification conducted by you without notifying


us of the fact.

④ Trouble caused by not adhering to the operating procedures, periodical inspections,


maintenance and storage, etc. described in the specification sheets and instruction
manuals issued by us.

⑤ Trouble caused by defective foundation, building and/or equipment other than


this machine.

INDEMNITY

Under no circumstances shall, including any illegality, Kobe Steel, Ltd. be liable for special,
indirect, incidental, or consequential damages, including, but not limited to, loss of
production, loss of anticipated profits, loss of operational profits, loss of material and
products, or indirect losses, however same shall be caused.
P19

KOBE STEEL,LTD.
KOBE STEEL,LTD.
KOBE STEEL,LTD.
KOBE STEEL,LTD.
P23

KOBE STEEL,LTD.
KOBE STEEL,LTD.
KOBE STEEL,LTD.
P26

OUTSIDE TERMINAL DIAGRAM


Outside terminal
Usage : TB2 Signal Kind Motion Remark
T.No.
Notes)
3 Input signal for a compressor's remote stop. 1. The input signal means the signal to be input by compressor operating panel.
Remote stop Input b (N.C)
4 (one shot signal) The current of 11mA at AC 100V flows through the terminals.
Remote operating panel and group control panel

5 Input signal for a compressor's remote start. Input on no-voltage contact in order not to damage the controller in taking voltage.
Remote start Input a (N.O)
6 (one shot signal) Select the contacts which can flow faint current.
7 Input for a compressor's remote loading.
Remote load Input a (N.O)
8 (status signal) 2. The output signal means the signal to be output from the compressor operating
9 + Input from the pressure sensor to control the outside panel. Use the receive circuit at AC 100-250V below 2A or at DC 30V below 2A.
Input
10 Outside start condition (option) - pressure(line pressure). (AC 100/110V below 2A is suitable)
11 LOCAL SD (4~20mA)
12 - - - - 3. The input signals of start and stop are necessary for remote operation.
13 - - - - The terminal number 3-4 is short-circuited at factory shipments.
14 - - - - Remove a short circuit wire in the case of using this terminal by remote operation.
15 Emergency stop Output a (N.O) General output on a compressor's emergency stop.
16 Caution Output a (N.O) General output on a compressor's caution. 4. Input longer than 500ms signal as to one shot signal.
17 Maintenance Output a (N.O) General output on a compressor's maintenance. In the case of a short pulse signal, a signal may be unable to be recognized.
18 Remote mode Output a (N.O) Output on a compressor's remote operation.
19 Loading Output a (N.O) Output during a compressor's loading. 5. The start orders of dryer, cooling tower and exhaust duct-ventilating fan interlock
20 Common (Output) - The common line of terminal number 15 ~19. with the auxiliary device start/stop in the unit.
21 It is possible to select the preceding operation (for 3 minutes) about the dryer.
Running Output a (N.O) Output during a compressor's running (main motor running).
22 And these terminals can be used for other auxiliary devices.
23 - - - -
24 - - - - 6. Refer to the following drawing as to the connection for the group control
25 (alternative) operation. In this case, the terminals of No.3 to No.20 can not be
Dryer Failure Input a (N.O) Input signal to display the dryer failure on the controller.
26 used for the original purpose shown in the left table.
27 Output signal to start the dryer on the compressor operating
Dryer start Output a (N.O)
28 panel. (ON: Start, OFF: Stop)
The first machine The second machine
29 Output signal to start the cooling tower on the compressor
Cooling tower start Output a (N.O)
30 operating panel. (ON: Start, OFF: Stop) TB2 TB2
31 Exhaust duct ventilating fan Output signal to start the exhaust duct-ventilating fan on the 3 3
Output a (N.O)
Auxiliary device

32 start compressor operating panel. (ON: Start, OFF: Stop) 4 4


33 - 5 5  Remote start
34 -
- - -
6 6
- - -
35 7 7  Remote load
36 - - - - 8 8
37 - - - -
9 9
38 - - - -
10 10
39 - - - -
11 11
40 - - - -
12 12
41 - - - -
42 - - - -
13 13
43 - - - -
14 14
15 15
16 16
17 17
18 18  Remote mode
19 19  Loading
20 20  Common
21 21
22 22

ISSUE

KOBE STEEL,LTD. DRAWING No.