0% found this document useful (0 votes)
110 views

Data Sheet Janitza-Umg96pql-Db-En

The document provides technical specifications for the UMG 96-PQ-L power analyzer. It details device variants, supply voltage options, environmental conditions, and measurement capabilities for voltage, current, power, harmonics and power quality analysis in accordance with related standards.

Uploaded by

Maciel
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
110 views

Data Sheet Janitza-Umg96pql-Db-En

The document provides technical specifications for the UMG 96-PQ-L power analyzer. It details device variants, supply voltage options, environmental conditions, and measurement capabilities for voltage, current, power, harmonics and power quality analysis in accordance with related standards.

Uploaded by

Maciel
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 8

Smart Energy & Power Quality Solutions

Part no. 3303826

The device fronts can deviate!

Power Analyzer
02/2023

UMG 96-PQ-L
Doc. no. 2.061.071.3.c

(from firmware 3.42)

Data sheet
DEVICE VIEWS

The figures are for illustration purposes only and are not to scale.
UMG 96-PQ-L

Front view Rear view

4,9 mm
0.19 in

Bottom view

0.24 in
6 mm
96 mm
3.78 in
3.78 in
96 mm

87,2 mm
3.43 in

96 mm Cut-out dimension:
3.78 in
92+0.8 mm x 92+0.8 mm
(3.62+0.03 in x 3.62+0.03 in)

Side view

87,2 mm 6 mm
3.43 in 0.24 in

2 – UMG 96-PQ-L data sheet • 02/2023


DEVICE VARIANTS

Network system and supply "Class S" variant

UMG 96-PQ-L
The UMG 96 PQ-L measurement devices are The UMG 96 PQ-L of class S additionally records
available in different variants: the power quality characteristics of class S ac-
· Both AC and DC voltage in two different voltage cording to IEC 61000-4-30.
ranges are suitable for the power supply of the
device1). The class-S-specific performance characteris-
tics are provided in the GridVis® software and in
· As a special feature of the UMG 96 PQ-L, Modbus addresses:
variants are also available for measurement in · Interharmonics
unearthed three-phase 3-conductor systems
(IT networks) up to 600 V AC. · Flicker

· Unbalances of voltage and current

· Rapid voltage change

· Frequency events

· Mains signal voltages (ripple control signal)

Subsequent class S activation for devices that


have already been installed is possible for a
fee through the GridVis® software (part number
5236020).

Variant Network system, supply Part number

TN / TT networks, 230 V option 1) 5236001


UMG 96-PQ-L
TN / TT networks, 24 V option 1) 5236002
(without class S)
TN / TT / IT networks, 230 V option 1) 5236005

TN / TT networks, 230 V option 1) 5236021


UMG 96-PQ-L
TN / TT networks, 24 V option 1) 5236022
Class S according to IEC 61000-4-30
TN / TT / IT networks, 230 V option 1) 5236025

Subsequent class S activation of a UMG 96-PQ-L 5236020

1) See „Supply voltage“ on page 4

INFORMATION
Detailed information on the device functions can be found in the usage information enclosed with the
device or is available for download at www.janitza.com.

02/2023 • UMG 96-PQ-L data sheet – 3


TECHNICAL DATA
UMG 96-PQ-L

General
Net weight (with attached plug-in connectors) approx. 250 g (0.55 lbs)
Package weight (incl. accessories) approx. 500 g (1.1 lbs)
Battery Type Lithium CR2032, 3 V, (UL 1642 approved)
Data memory 64 MB
Backlight service life 40000 h
(backlight reduces to approx. 50% over this period)
Impact resistance IK07 according to IEC 62262

Transport and storage


The following information applies to devices that are transported or stored in their original packaging.
Free fall 1 m (39.37 in)
Temperature -25 °C (-13 °F) to +70 °C (158 °F)
Relative air humidity (non-condensing) 0 to 90% RH

Environmental conditions during operation


Install the device in a weather-protected and stationary location.
Protection class II according to IEC 60536 (VDE 0106, Part 1).
Rated temperature range -10 °C (14 °F) ... +55 °C (131 °F)
Relative air humidity (non-condensing) 0 to 75% RH
Operating elevation 0 .. 2000 m (6562 ft) above sea level
Pollution degree 2
Mounting orientation As desired
Ventilation No forced ventilation required.
Protection against foreign matter and water
- Front IP40 according to EN60529
- Rear IP20 according to EN60529
- Front with seal IP54 according to EN60529
Electromagnetic environmental conditions Class E2 (MID 2014/32/EU)
Mechanical environmental conditions Class M1 (MID 2014/32/EU)

Supply voltage
Option 230 V Nominal range AC 90 V - 277 V (50/60 Hz) or
DC 90 V - 250 V, 300 V CATIII
Power consumption max. 4.5 VA / 2 W
Option 24 V Nominal range AC 24 V - 90 V (50/60Hz) or
DC 24 V - 90 V, 150 V CATIII
Power consumption max. 4.5 VA / 2 W
Operating range +-10% of nominal range
Internal fuse, not replaceable Type T1A / 250 V DC / 277 V AC according to IEC 60127
Recommended overcurrent protective device for the Option 230 V: 6 - 16 A (Char. B)
line protection (UL approval) Option 24 V: 1 - 6 A (Char. B)

4 – UMG 96-PQ-L data sheet • 02/2023


UMG 96-PQ-L
Voltage measurement
Three-phase 4-conductor systems with rated voltages up to 417 V / 720 V (+-10%) according to IEC
347 V / 600 V (+-10%) according to UL
Three-phase 3-conductor systems with rated voltages up to 600 V (+10%)
Single-phase 2-conductor system with rated voltages up to 480 V (+-10%)
Overvoltage category 600 V CAT III, 300 V CAT IV
Rated surge voltage 6 kV
Protection of the voltage measurement 1 - 10 A tripping characteristic B(with IEC/UL approval)
Measuring range L-N 01) .. 600 Vrms (max. overvoltage 800 Vrms)
Measuring range L-L 01) .. 1040 Vrms (max. overvoltage 1350 Vrms)
Resolution 0.01 V
Crest factor 2.45 (related to the measuring range)
Impedance 3 MΩ/phase
Power consumption approx. 0.1 VA
Sampling frequency 13.67 kHz
Sampling frequency (IT variant) 13.98 kHz
Frequency of the fundamental oscillation 45 Hz .. 65 Hz
- Resolution 0.01 Hz
Fourier analysis 1st - 65th harmonic

1) The device only determines measured values if a voltage L1-N of greater than 20 Veff (4-conductor measurement) or a
voltage L1-L2 of greater than 34 Veff (3-conductor measurement) is applied to voltage measurement input V1.

Current measurement
Nominal current 5 A
Measuring range 0.005 .. 6 Arms
Crest factor 2 (relative to 6 Arms)
Overvoltage category 300 V CAT II
Rated surge voltage 2 kV
Power consumption approx. 0.2 VA (Ri=5 mΩ)
Overload for 1 s 60 A (sinusoidal)
Resolution 0.1 mA (display 0.01 A)
Sampling frequency 13.67 kHz
Sampling frequency (IT variant) 13.98 kHz
Fourier analysis 1st - 65th harmonic

Serial interface
RS-485 - Modbus RTU/client device 9.6 kbps, 19.2 kbps, 38.4 kbps, 57.6 kbps, 115.2 kbps

Digital outputs
3 digital outputs, solid state relays, not short-circuit proof.
Switching voltage max. 33 V AC, 40 V DC
Switching current max. 50 mAeff AC/DC
Response time approx. 200 ms
Pulse output max. 50 Hz (energy pulses)

Digital inputs
3 digital inputs, solid state relays, not short-circuit proof.
Maximum counter frequency 20 Hz
Input signal applied 18 V .. 28 V DC (typically 4 mA)
Input signal not applied 0 .. 5 V DC, current less than 0.5 mA

Cable length (digital inputs/outputs)


Up to 30 m (32.81 yd) Unshielded
Greater than 30 m (32.81 yd) Shielded

02/2023 • UMG 96-PQ-L data sheet – 5


UMG 96-PQ-L

Analog outputs
External power supply max. 33 V
Current 0 .. 20 mA
Update time 1s
Load max. 300 Ω
Resolution 10 bit

Connecting capacity of the terminals (supply voltage)


Connectible conductors. Only connect one conductor per terminal point!
Single core, multi-core, fine-stranded 0.2 - 4.0 mm2, AWG 28-12
Wire ferrules (non-insulated) 0.2 - 2.5 mm2, AWG 26-14
Wire ferrules (insulated) 0.2 - 2.5 mm2, AWG 26-14
Tightening torque 0.4 - 0.5 Nm (3.54 - 4.43 lbf in)
Strip length 7 mm (0.2756 in)

Connecting capacity of the terminals (voltage measurement)


Connectible conductors. Only connect one conductor per terminal point!
Single core, multi-core, fine-stranded 0.2 - 4.0 mm2, AWG 28-12
Wire ferrules (non-insulated) 0.2 - 2.5 mm2, AWG 26-14
Wire ferrules (insulated) 0.2 - 2.5 mm2, AWG 26-14
Tightening torque 0.4 - 0.5 Nm (3.54 - 4.43 lbf in)
Strip length 7 mm (0.2756 in)

Connecting capacity of the terminals (current measurement)


Connectible conductors. Only connect one conductor per terminal point!
Single core, multi-core, fine-stranded 0.2 - 4 mm2, AWG 28-12
Wire ferrules (non-insulated) 0.2 - 2.5 mm2, AWG 26-14
Wire ferrules (insulated) 0.2 - 2.5 mm2, AWG 26-14
Tightening torque 0.4 - 0.5 Nm (3.54 - 4.43 lbf in)
Strip length 7 mm (0.2756 in)

Terminal connection capacity (serial interface)


Connectible conductors. Only connect one conductor per terminal point!
Single core, multi-core, fine-stranded 0.2 - 1.5 mm2, AWG 28-16
Wire ferrules (non-insulated) 0.2 - 1.5 mm2, AWG 26-16
Wire ferrules (insulated) 0.2 - 1.5 mm2, AWG 26-16
Tightening torque 0.2 - 0.25 Nm (1.77 - 2.21 lbf in)
Strip length 7 mm (0.2756 in)

Connecting capacity of the terminals (digital inputs/outputs, analog output)


Connectible conductors. Only connect one conductor per terminal point!
Single core, multi-core, fine-stranded 0.2 - 1.5 mm2, AWG 28-16
Wire ferrules (non-insulated) 0.2 - 1.5 mm2, AWG 26-16
Wire ferrules (insulated) 0.2 - 1.5 mm2, AWG 26-16
Tightening torque 0.2 - 0.25 Nm (1.77 - 2.21 lbf in)
Strip length 7 mm (0.2756 in)

6 – UMG 96-PQ-L data sheet • 02/2023


PERFORMANCE CHARACTERISTICS OF FUNCTIONS

UMG 96-PQ-L
Function Symbol Accuracy class Measuring range Display range

Total active power P 0.5 (IEC61557-12)


1)
0 W .. 12.6 kW 0 W .. 999 GW *

Total reactive power QA, Qv 1 (IEC61557-12) 0 var .. 16.6 kvar 0 var .. 999 Gvar *

Total apparent power SA, Sv 0.51) (IEC61557-12) 0 VA .. 12.6 kVA 0 VA .. 999 GVA *

Total active energy Ea 0.21) (IEC61557-12) 0 Wh .. 999 GWh 0 Wh .. 999 GWh *


0.2S1) (IEC62053-22)
0.2 (ANSI C12.20)

Total reactive energy ErA, ErV 1 (IEC61557-12) 0 varh .. 999 Gvarh 0 varh .. 999 Gvarh *

Total apparent energy EapA, EapV 0.5 (IEC61557-12)


1)
0 VAh .. 999 GVAh 0 VAh .. 999 GVAh *

Frequency f 0.05 (IEC61557-12) 42.5 Hz .. 69 Hz 42.50 Hz .. 69.00 Hz

Phase current I 0.2 (IEC61557-12) 0 Arms .. 7 Arms 0 A .. 999 kA

Neutral conductor current calcu- INc 1.0 (IEC61557-12) 0.03 A .. 25 A 0.03 A .. 999 kA
lated

Voltage U L-N 0.2 (IEC61557-12) 10 Vrms .. 600 Vrms 0 V .. 999 kV

Voltage U L-L 0.2 (IEC61557-12) 18 Vrms .. 1040 Vrms 0 V .. 999 kV

Power factor PFA, PFV 0.5 (IEC61557-12) 0.00 .. 1.00 0.00 .. 1.00

Transient overvoltages Utr - - -

Voltage harmonics Uh Cl. 1 (IEC61000-4-7) 1 .. 65 0 V .. 999 kV

THD of voltage 2) THDu 1.0 (IEC61557-12) 0% .. 999% 0% .. 999%

THD of voltage 3)
THD-Ru - - -

Current harmonics Ih Cl. 1 (IEC61000-4-7) 1 .. 65 0 A .. 999 kA

THD of current 2) THDi 1.0 (IEC61557-12) 0% .. 999% 0% .. 999%

THD of current 3) THD-Ri - - -

Accuracy of events - - -

Short-term flicker, long-term Pst, Plt Class 1 (IEC61000-4-15) 0.4 Pst ... 10.0 Pst 0 .. 10
flicker

1) Accuracy class 0.2/0.2S with ../5A transformer. * When the maximum total energy values are
Accuracy class 0.5/0.5S with ../1A transformer. reached, the display returns to 0 W.
2) Referenced to the fundamental oscillation.
3) Referenced to the effective value.

02/2023 • UMG 96-PQ-L data sheet – 7


Smart Energy & Power Quality Solutions

Janitza electronics GmbH


Vor dem Polstück 6 | 35633 Lahnau
Germany

Tel.: +49 6441 9642-0


[email protected] | www.janitza.com

You might also like