Data Sheet Janitza-Umg96pql-Db-En
Data Sheet Janitza-Umg96pql-Db-En
Power Analyzer
02/2023
UMG 96-PQ-L
Doc. no. 2.061.071.3.c
Data sheet
DEVICE VIEWS
The figures are for illustration purposes only and are not to scale.
UMG 96-PQ-L
4,9 mm
0.19 in
Bottom view
0.24 in
6 mm
96 mm
3.78 in
3.78 in
96 mm
87,2 mm
3.43 in
96 mm Cut-out dimension:
3.78 in
92+0.8 mm x 92+0.8 mm
(3.62+0.03 in x 3.62+0.03 in)
Side view
87,2 mm 6 mm
3.43 in 0.24 in
UMG 96-PQ-L
The UMG 96 PQ-L measurement devices are The UMG 96 PQ-L of class S additionally records
available in different variants: the power quality characteristics of class S ac-
· Both AC and DC voltage in two different voltage cording to IEC 61000-4-30.
ranges are suitable for the power supply of the
device1). The class-S-specific performance characteris-
tics are provided in the GridVis® software and in
· As a special feature of the UMG 96 PQ-L, Modbus addresses:
variants are also available for measurement in · Interharmonics
unearthed three-phase 3-conductor systems
(IT networks) up to 600 V AC. · Flicker
· Frequency events
INFORMATION
Detailed information on the device functions can be found in the usage information enclosed with the
device or is available for download at www.janitza.com.
General
Net weight (with attached plug-in connectors) approx. 250 g (0.55 lbs)
Package weight (incl. accessories) approx. 500 g (1.1 lbs)
Battery Type Lithium CR2032, 3 V, (UL 1642 approved)
Data memory 64 MB
Backlight service life 40000 h
(backlight reduces to approx. 50% over this period)
Impact resistance IK07 according to IEC 62262
Supply voltage
Option 230 V Nominal range AC 90 V - 277 V (50/60 Hz) or
DC 90 V - 250 V, 300 V CATIII
Power consumption max. 4.5 VA / 2 W
Option 24 V Nominal range AC 24 V - 90 V (50/60Hz) or
DC 24 V - 90 V, 150 V CATIII
Power consumption max. 4.5 VA / 2 W
Operating range +-10% of nominal range
Internal fuse, not replaceable Type T1A / 250 V DC / 277 V AC according to IEC 60127
Recommended overcurrent protective device for the Option 230 V: 6 - 16 A (Char. B)
line protection (UL approval) Option 24 V: 1 - 6 A (Char. B)
1) The device only determines measured values if a voltage L1-N of greater than 20 Veff (4-conductor measurement) or a
voltage L1-L2 of greater than 34 Veff (3-conductor measurement) is applied to voltage measurement input V1.
Current measurement
Nominal current 5 A
Measuring range 0.005 .. 6 Arms
Crest factor 2 (relative to 6 Arms)
Overvoltage category 300 V CAT II
Rated surge voltage 2 kV
Power consumption approx. 0.2 VA (Ri=5 mΩ)
Overload for 1 s 60 A (sinusoidal)
Resolution 0.1 mA (display 0.01 A)
Sampling frequency 13.67 kHz
Sampling frequency (IT variant) 13.98 kHz
Fourier analysis 1st - 65th harmonic
Serial interface
RS-485 - Modbus RTU/client device 9.6 kbps, 19.2 kbps, 38.4 kbps, 57.6 kbps, 115.2 kbps
Digital outputs
3 digital outputs, solid state relays, not short-circuit proof.
Switching voltage max. 33 V AC, 40 V DC
Switching current max. 50 mAeff AC/DC
Response time approx. 200 ms
Pulse output max. 50 Hz (energy pulses)
Digital inputs
3 digital inputs, solid state relays, not short-circuit proof.
Maximum counter frequency 20 Hz
Input signal applied 18 V .. 28 V DC (typically 4 mA)
Input signal not applied 0 .. 5 V DC, current less than 0.5 mA
Analog outputs
External power supply max. 33 V
Current 0 .. 20 mA
Update time 1s
Load max. 300 Ω
Resolution 10 bit
UMG 96-PQ-L
Function Symbol Accuracy class Measuring range Display range
Total reactive power QA, Qv 1 (IEC61557-12) 0 var .. 16.6 kvar 0 var .. 999 Gvar *
Total apparent power SA, Sv 0.51) (IEC61557-12) 0 VA .. 12.6 kVA 0 VA .. 999 GVA *
Total reactive energy ErA, ErV 1 (IEC61557-12) 0 varh .. 999 Gvarh 0 varh .. 999 Gvarh *
Neutral conductor current calcu- INc 1.0 (IEC61557-12) 0.03 A .. 25 A 0.03 A .. 999 kA
lated
Power factor PFA, PFV 0.5 (IEC61557-12) 0.00 .. 1.00 0.00 .. 1.00
THD of voltage 3)
THD-Ru - - -
Accuracy of events - - -
Short-term flicker, long-term Pst, Plt Class 1 (IEC61000-4-15) 0.4 Pst ... 10.0 Pst 0 .. 10
flicker
1) Accuracy class 0.2/0.2S with ../5A transformer. * When the maximum total energy values are
Accuracy class 0.5/0.5S with ../1A transformer. reached, the display returns to 0 W.
2) Referenced to the fundamental oscillation.
3) Referenced to the effective value.