TN47 - Overall Building Envelope U-Values (9 PP)
TN47 - Overall Building Envelope U-Values (9 PP)
This Technical Note is one of four on the effect of building envelope performance on energy
use in buildings. The series comprises:
Energy use in buildings is heavily governed The Building Regulations (England and
by energy transfer through the building Wales) give three methods for showing
envelope. Reducing the energy lost by compliance. All of these methods require
conduction through the building envelope is knowledge of the overall U-value of the
an important aspect in the design of energy building envelope or of separate zones of
efficient buildings. the building envelope.
The ‘Elemental method’ allows This method also gives greater design
assessment of compliance of the building flexibility and has the same advantages as
envelope alone. This method is based on: the ‘whole-building’ method. The carbon
emissions calculation method is described
a) U-values of the building envelope in CIBSE TM32.
elements
2/9
Overall building envelope U-values TN 47
Table 1 U-values of building elements from Part L2 of the Building Regulations (England and
Wales) (See Appendix A for values to be used in Scotland and Northern Ireland)
• Other aspects of the building envelope This method of calculation is called the
when using the ‘elemental method’ area-weighted method for calculating U-
• All aspects of energy transfer and values.
energy use when using the ‘whole
building method’ or ‘carbon emissions Consider a façade zone comprising 30
calculation method percent glazing with U-value 2.8 W/m2K
and 70 percent wall with U-value 0.28
W/m2K. The overall U-value of the zone is
U-value of an entire façade given by:
Energy loss through a facade or any zone 2.8 × 0.3 + 0.28 × 0.7
U zone =
of a façade can be calculated by summing 0.3 + 0.7
the energy loss through the individual
elements. The heat flow is: U zone = 1.04 W/m2K
Q = ∆t × ∑ U element × A element
3/9
Overall building envelope U-values TN 47
Selection of components to achieve the those in contact with both the internal and
required overall U-value external environments.
3 The window area may have to be Consider the building shown in Figure 1,
limited to reduce the adverse effect of comprising wall and roof zones as shown
solar gain. in Table 3.
4/9
Overall building envelope U-values TN 47
U average =
∑U × A
window window
calculate annual energy use due to
conduction losses for use in the ‘whole
∑A window building method’ or ‘carbon emissions
calculation method’. The annual energy
Some windows may have higher U-values loss will depend on the internal and
if others have lower U-values. external temperatures. Calculation
requires knowledge of the number of
degree-heating days (TN46).
Opaque Window
Area area U-value U×A area U-value U×A ∑U × A
Zone (m2) (%) (W/m2K) (W/K) (%) (W/m2K) (W/K) (W/K)
Wall 1 15 x 10 = 150 100 0.30 45 0 - 0 45
Wall 2 20 x 10 = 200 50 0.35 35 50 2.8 280 315
Wall 3 15 x 10 = 150 100 0.30 45 0 - 0 45
Wall 4 20 x 10 = 200 50 0.35 35 50 2.8 280 315
Roof 20 x 15 = 300 100 0.20 60 - - 0 60
5/9
Overall building envelope U-values TN 47
The notional building is defined by the the allowable areas of elements are
standard U-values given in Table 1 and shown in Table 4.
When calculating the overall energy use of The overall U-value of the building
the notional building it is only allowable to envelope (excluding the floor) is then
take into account roof lights up to 10 per given by:
cent of the roof area in excess of any
rooflights in the proposed building, up to a
maximum of 20 per cent rooflights in the U overall =
∑U × A = 896.5 = 0.90 W/m2K
notional building. If a roof will actually ∑ A 1000
contain 5 per cent rooflights then the
notional building will contain 15 per cent It can be seen that the U-value of the
rooflights. notional building is greater than that of the
building proposed in example 1 which
For the building shown in Figure 1 the therefore complies with Part L of the
notional building will be defined as four Building Regulations (England and
walls each with 40 per cent glazing Wales).
(assuming it is an office building) and a
roof with 10 per cent rooflights (assuming The overall U-value of 0.90 W/m2K is used
they will not be included in the actual when calculating the annual energy use
building). as an input to the ‘Carbon emission
calculation method’ or the ‘Whole building
The appropriate fabric properties are method’.
shown in Table 5.
Opaque Window
Area area U-value U×A area U-value U×A ∑U × A
Zone (m2) (%) (W/m2K) (W/K) (%) (W/m2K) (W/K) (W/K)
Wall 1 15 x 10 = 150 60 0.35 31.5 40 2.2 132 163.5
Wall 2 20 x 10 = 200 60 0.35 42 40 2.2 176 218
Wall 3 15 x 10 = 150 60 0.35 31.5 40 2.2 132 163.5
Wall 4 20 x 10 = 200 60 0.35 42 40 2.2 176 218
Roof 20 x 15 = 300 90 0.25 67.5 10 2.2 66 133.5
6/9
Overall building envelope U-values TN 47
Note that the overall U-value of the U-values than allowed by the ‘elemental
proposed building may be greater than method’.
that for the notional building if other
aspects of the proposed buildings lead to Using the ‘carbon emissions calculation
greater efficiency than required by the method’ the energy saved through
notional building. This may arise from: reduced air leakage can be used to
balance energy lost through the building
• The use of more efficient heating envelope by conduction.
and/or cooling systems
• Reduced air leakage Taking the notional building of Table 5, the
• Improved shading or the use of higher total surface area of the building envelope
performance glazing to reduce solar is 1000 m2. If the building can be
gain constructed to have a whole building air
leakage rate of 8 m3/m2hr this will be 2
Single wall m3/m2hr less than the allowable air
When considering only a single wall, leakage of 10 m3/m2hr. The rates of
without any knowledge of the other walls energy use are shown in Table 6.
and roof, it is necessary to assume the
worst conditions for those other elements Rate of energy
of the building and consider only a Notional building use (W/K)
notional wall. This will often lead to a Conduction losses 896.5
more onerous U-value requirement for the Air leakage losses 177.0
wall. Total 1073.5
7/9
Overall building envelope U-values TN 47
Curtain
Opaque wall
Area area U-value U×A area U-value U×A ∑U × A
Zone (m2) (%) (W/m2K) (W/K) (%) (W/m2K) (W/K) (W/K)
Wall 1 15 x 10 = 150 100 0.30 45 0 - 0 45
Wall 2 20 x 10 = 200 0 - 0 100 3.0 600 600
Wall 3 15 x 10 = 150 100 0.30 45 0 - 0 45
Wall 4 20 x 10 = 200 0 - 0 100 3.0 600 600
Roof 20 x 15 = 300 100 0.20 60 - - 0 60
Double skin walls and atria check should be carried out. This also
applies to small components such as
If the components of the building envelope aluminium mullions and transoms.
do not have surfaces in contact with the
internal and external environments the
temperature difference across them will be References
lower than the full temperature between
the internal and external environments. Building Regulations (England and Wales):
Part L2, Conservation of fuel and power in
This may occur where: buildings other than dwellings (2002
edition), http://www.odpm/gov.uk/
• An atrium is at a lower temperature
Building Regulations (Scotland): Part J,
than the shops or offices opening on to
Conservation of fuel and power,
it http://www.scotland.gov.uk/build_regs/sect-
• The internal skin of a double skin j.pdf.
façade is not in contact with the
external environment Building Regulations (Northern Ireland): Part
F, Conservation of fuel and power,
Energy transfer through these areas of the http://www.buildingcontrol.org/bcni/legislation/r
envelope will depend on the actual egulations.asp.
temperature drop across the zone and it is
necessary to calculate the temperature TN46 Introduction to building envelope energy
transfer, CWCT, 2004.
within the atrium or the plenum between
the inner and outer skins of a double skin TN48 Energy loss through curtain walls,
façade. CWCT 2004.
8/9
Overall building envelope U-values TN 47
Allowable U-values used in this Technical In Northern Ireland the appropriate values
Note are those included in the Part L2 of are given in Schedule F. Table A shows
the Building Regulations (England and the values used in each case.
Wales). In Scotland the appropriate
values are given in Schedule J.
England and
Component Wales Scotland Ireland
Pitched roof with insulation between rafters 0.20 0.20
Pitched roof with insulation between joists 0.16 0.16 ?
Flat roof or roof with integral insulation 0.25 0.25 ?
Walls 0.35 0.30 ?
Windows (metal) 2.20 2.20 ?
Windows (timber and plastic) 2.00 2.00 ?
© CWCT 2004
9/9