THERMO KING TK 61377-18-MM TKV500 and TKV600 Maintenance Manual Rev. A 01-19
THERMO KING TK 61377-18-MM TKV500 and TKV600 Maintenance Manual Rev. A 01-19
Truck Edition
V-500/V-600 Series
Revision A
Revision History
Revision A (02/19) Original release
Recover Refrigerant
At Thermo King®, we recognize the need to preserve the environment and limit the potential harm to the ozone layer
that can result from allowing refrigerant to escape into the atmosphere.
We strictly adhere to a policy that promotes the recovery and limits the loss of refrigerant into the atmosphere.
When working on transport temperature control systems, a recovery process that prevents or minimizes refrigerant
loss to the atmosphere is required by law. In addition, service personnel must be aware of the appropriate European
Union, National, Federal, State, and/or Local regulations governing the use of refrigerants and certification of
technicians. For additional information on regulations and technician programs, contact your local THERMO KING
dealer.
S e r v i c e T o o l s - Use the proper service tools. Gauge manifold sets should include appropriate shutoff valves or
disconnects near the end of each service line.
R e c o v e r y E q u i p m e n t - Recovery equipment must be used. Proper recovering, storing and recycling of refrigerants is
an important part of all service work.
S e r v i c e P r o c e d u r e s - Recommended procedures must be used to minimize refrigerant loss.
C o m p o n e n t s m a y b e i s o l a t e d by closing service valves and performing system pump-downs.
C o m p o n e n t s u n a b l e t o b e i s o l a t e d for service must be repaired only after refrigerant is properly recovered.
R-134a/R-404A/R-452A
R-134aR-404AR452A
NOTICE
Equipment Damage!
Use only Polyolester-based refrigeration compressor oil in R-134a/R-404A/R-452A systems. See Thermo King
Parts Manual for part number.
NOTICE
System Contamination!
Do not mix Polyolester and standard synthetic compressor oils. Keep Polyolester compressor oil in tightly
sealed containers. If Polyolester oil becomes contaminated with moisture or standard oils, dispose of
properly–DO NOT USE.
NOTICE
System Contamination!
When servicing Thermo King R-134a, R-23, R-404A, R-452A or R-513A units, use only those service tools
certified for and dedicated to R-134a/R-23/R-404A/R-452A/R-513A refrigerant and Polyolester compressor oils.
Residual non-HFC refrigerants or oils will contaminate R-134a/R-23/R-404A/R-452A/R-513A systems.Please
check serial# plate for type and volume of Refrigerant charged. Please do not blend with other refrigerants
than the original charged refrigerant
TK 61377-18-MM-EN 3
Introduction
Contents
This manual is organized into the following chapters:
Chapter Purpose
Safety Precautions Provides detailed safety information. You should be familiar with the safety
precautions before working on any unit.
Model Systems (Systems Designations) Table This table lists the bills of material and kit options that make up your unit.
Use them for the following purposes:
1. To determine if you have the right manual for your unit: the bill of
material (B/M) number on your unit serial plate should match one of
the bill of material numbers listed in this section. If you cannot find
your unit in the matrix, call TK Service for more information.
2. To communicate with TK Service Department: If you need to call TK
Service, you must know your model number(s) in order for the service
representative to help you.
Unit Description Gives an overview description of your unit including standard and optional
features, illustrations, and general a/c theory.
Maintenance Chapters Provide detailed maintenance procedures required for your unit. (Electrical,
Refrigeration, Compressor, Clutch, Structural)
Blank Pages
This manual may contain blank pages at the end of chapters. This is normal. There is no information missing from the
manual.
Roadside/Curbside Terminology
Roadside/Curbside terminology: These terms can be confusing because of differences between North America and
Europe. Please note:
4 TK 61377-18-MM-EN
Introduction
Curbside: The side of the truck to the driver’s right when the driver is in his seat and facing forward.
Roadside: The side of the truck to the driver’s left when the driver is in his seat and facing forward.
TK 61377-18-MM-EN 5
Introduction
General Information
The maintenance information in this manual covers unit models:
Direct Smart Reefer III Microprocessor Control System Diagnostic Manual TK 61096
The information in this manual is provided to assist owners, operators and service people in the proper upkeep and maintenance
of Thermo King units.
6 TK 61377-18-MM-EN
Table of Contents
Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Danger, Warning, Caution, and Notice . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Auto Start/Stop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Battery Installation and Cable Routing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Refrigerant Hazards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Refrigerant Oil Hazards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Electrical Hazards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
High Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Low Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Microprocessor Service Precautions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Welding Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
First Aid. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Electrical System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Electric Standby Power Supply Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Optional Electric Heaters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Refrigeration System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Compressors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Belt Tension . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Solder Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Unit Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Condenser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Evaporator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Control Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
DSR Control System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Oil Separator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Refrigerant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Liquid Injection System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Evaporator Drain Line Heaters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Electric Standby Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Unit Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Standard Features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Optional Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Protection Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Control Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
TK 61377-18-MM-EN 7
Table of Contents
P.C. Boards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Electronic Control Module (ECM) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Refrigeration System Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Solenoids and Valves. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Hot Gas Solenoid (HGS) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Liquid Injection Solenoid (LIS) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Discharge Check Valve. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Condenser Inlet Solenoid (CIS) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Suction Pressure Regulator Valve (SPR) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
CPR Bypass Solenoid. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Compressor Pressure Regulator Valve (CPR) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Liquid Line Check Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
CPR Check Valve. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Liquid Line Solenoid . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Switches and Transducers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Unit Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Cool Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Null Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Purge Mode – Model 30 and Model 50 Units Only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Heat Mode – Model 30 and Model 50 Units Only. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Defrost Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Serial Number Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Unit Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Maintenance Inspection Schedule . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Electrical Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Electronic Control System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Defrost System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Defrost Termination Switch. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Defrost Termination Switch Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Liquid Injection System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Condenser Fan Motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Condenser Fan Motor Removal and Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Evaporator Fan Motors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Evaporator Fan Motor Removal and Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Drain Line Heaters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Drain Line Heater Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
8 TK 61377-18-MM-EN
Table of Contents
Fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Controller Fuses: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Control Box Fuses: Printed Circuit Boards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Harness Fuses: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Relay Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Relay Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
AC Components Model 20 and Model 50 Units Only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Electrical Contactors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Compressor Motor Contactor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Compressor Motor Contactor Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Electric Heat Contactor – HC (Model 20 Option Only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Electric Heat Contactor Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Compressor Motor Overload Relay – OL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Compressor Motor Overload Relay Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Transformer – T1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Transformer Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Transformer Replacement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Bridge Rectifier – BR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Capacitors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Capacitor Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Capacitor Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Start Relay – SR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Start Relay Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Start Relay Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Compressor Motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Testing 115/1/60 Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Testing 208-230/1/60 Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Testing 208-230/3/60 Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Compressor Motor Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Electric Standby Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Refrigeration Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Evacuating and Charging the Refrigeration System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Checking the Refrigerant Charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Testing the Refrigerant Charge with an Empty Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Testing the Refrigerant Charge with a Loaded Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Suction (Low Side) Bump Charging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Checking Compressor Oil Charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Refrigeration System Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Cleanup Procedure for Small Truck Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Tools Required. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Clean-up Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Putting the Unit Back Into Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Putting the Unit Back Into Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Refrigeration Service Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
TK 61377-18-MM-EN 9
Table of Contents
10 TK 61377-18-MM-EN
Table of Contents
Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Accumulator (Model 30 and 50 Only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Removal. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Liquid Line Check Valve (Model 30 and 50 Only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Liquid Line Check Valve Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Liquid Line Check Valve Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
Replacing Refrigerant Hoses (Speedy Clip System) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
Compressor Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Compressor Failures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Compressor Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Belt Tensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Engine Driven Compressor Belt and Pulleys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Electric Standby Compressor Belt . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Structural Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Micro-Channel Coil Cleaning Recommendations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Cleaning Intervals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Cleaning Methods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Unit Mounting Bolts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
TK 61377-18-MM-EN 11
Safety Precautions
Danger, Warning, Caution, and Notice
Thermo King® recommends that all service be performed by a Thermo King dealer and to be aware of several general
safety practices.
Safety advisories appear throughout this manual as required. Your personal safety and the proper operation of this unit
depend upon the strict observance of these precautions. The four types of advisories are defined as follows:
DANGER
Indicates an imminently hazardous situation which, if not avoided, will result in
death or serious injury!
WARNING
Indicates a potentially hazardous situation which, if not avoided, could result in
death or serious injury!
CAUTION
Indicates a potentially hazardous situation which, if not avoided, could result in
minor or moderate injury and unsafe practices!
NOTICE
Indicates a situation that could result in equipment or property-damage only
accidents!
Auto Start/Stop
CAUTION
Risk of Injury!
The unit can start and run automatically any time the unit is turned on. Turn the unit On/Off switch Off before
doing inspections or working on any part of the unit. Please note that only Qualified and Certified personnel
should attempt to service your Thermo King unit.
CAUTION
Risk of Injury!
The vehicle's engine may be equipped with Auto Start/Stop. The vehicle must be turned off before servicing
the unit.
12 TK 61377-18-MM-EN
Safety Precautions
WARNING
Hazard of Explosion!
Improperly installed battery cables could result in a fire, explosion, or injury. Battery cables must be installed,
routed, and secured properly to prevent them from rubbing, chaffing, or making contact with hot, sharp, or
rotating components.
WARNING
Fire Hazard!
Do not attach fuel lines to battery cables or electrical harnesses. This has the potential to cause a fire and
could cause serious injury or death.
WARNING
Personal Protective Equipment (PPE) Required!
A battery can be dangerous. A battery contains a flammable gas that can ignite or explode. A battery stores
enough electricity to burn you if it discharges quickly. A battery contains battery acid that can burn you.
Always wear goggles or safety glasses and personal protective equipment when working with a battery. If you
get battery acid on you, immediately flush it with water and get medical attention.
WARNING
Hazard of Explosion!
Always cover battery terminals to prevent them from making contact with metal components during battery
installation. Battery terminals grounding against metal could cause the battery to explode.
CAUTION
Hazardous Service Procedures!
Set all unit electrical controls to the OFF position before connecting battery cables to the battery to prevent
unit from starting unexpectedly and causing personal injury.
NOTICE
Equipment Damage!
Do not connect other manufacturer’s equipment or accessories to the unit or to the TK Batteries unless
approved by Thermo King. Failure to do so can result in severe damage to equipment and void the warranty.
Refrigerant Hazards
DANGER
Hazardous Pressures!
Always store refrigerant in proper containers, out of direct sunlight and away from intense heat. Heat
increases pressure inside storage containers, which can cause them to burst and could result in severe
personal injury.
DANGER
Combustible Hazard!
Do not use oxygen (O2 ) or compressed air for leak testing. Oxygen mixed with refrigerant is combustible.
WARNING
Hazardous Gases!
Do not use a Halide torch. When a flame comes in contact with refrigerant, toxic gases are produced. These
gases can cause suffocation, even death.
TK 61377-18-MM-EN 13
Safety Precautions
WARNING
Personal Protective Equipment (PPE) Required!
Refrigerant in a liquid state evaporates rapidly when exposed to the atmosphere, freezing anything it contacts.
Wear butyl lined gloves and other clothing and eye wear when handling refrigerant to help prevent frostbite.
When working with or around hazardous chemicals, ALWAYS refer to appropriate Material Data Safety Sheets
(MSDS) and OSHA/GHS (Global Harmonized System of Classification and Labelling of Chemicals) guidelines
for information on allowable personal exposure levels, proper respiratory protection, and handling
instructions.
NOTICE
Equipment Damage!
When being transferred, refrigerant must be in liquid state to avoid possible equipment damage.
NOTICE
Equipment Damage!
Use the correct oil in Thermo King systems to avoid damaging equipment and nullifying its warranty.
NOTICE
Equipment Damage!
Do not mix refrigerant oils. Mixing incompatible oils will damage the system.
NOTICE
Equipment Damage!
Use dedicated refrigeration equipment to prevent contaminating refrigeration systems with the wrong type of
oil or refrigerant.
NOTICE
System Contamination!
Do not expose the refrigerant oil to the air any longer than necessary. Store refrigerant oil in an approved
sealed container to avoid moisture contamination. The oil will absorb moisture, which results in much longer
evacuation times and possible system contamination.
NOTICE
Material Damage!
Wipe up spills immediately. Refrigerant oil can damage paints and rubber materials.
14 TK 61377-18-MM-EN
Safety Precautions
Electrical Hazards
High Voltage
I m p o r t a n t : Do not move the vehicle if the power cable or the electric standby icon is illuminated.
DANGER
Hazardous Voltage!
Lethal amounts of voltage are present in some electrical circuits. Use extreme care when working on an
operating refrigeration unit. If there is a risk of energized electrical contact, arc, or flash, technicians MUST put
on all PPE in accordance with OSHA, NFPA 70E, or other local, state, or country-specific requirements for arc
flash protection PRIOR to servicing the unit. NEVER PERFORM ANY SWITCHING, DISCONNECTING, OR
VOLTAGE TESTING WITHOUT PROPER ELECTRICAL PPE AND ARC FLASHING CLOTHING. ELECTRICAL
METERS AND EQUIPMENT MUST BE PROPERLY RATED FOR INTENDED VOLTAGE.
WARNING
Hazardous Voltage!
Treat all wires and connections as if they were high voltage until a meter and wiring diagram indicate
otherwise. Only use tools with insulated handles. Never hold uninsulated metal tools near exposed, energized
conductors. If there is a risk of energized electrical contact, arc, or flash, technicians MUST put on all PPE in
accordance with OSHA, NFPA 70E, or other local, state, or country-specific requirements for arc flash
protection PRIOR to servicing the unit. NEVER PERFORM ANY SWITCHING, DISCONNECTING, OR VOLTAGE
TESTING WITHOUT PROPER ELECTRICAL PPE AND ARC FLASHING CLOTHING. ELECTRICAL METERS AND
EQUIPMENT MUST BE PROPERLY RATED FOR INTENDED VOLTAGE.
WARNING
Hazardous Voltage!
Never work alone on high voltage circuits in the refrigeration unit. Another person should be nearby to shut
off the unit and provide aid in the event of an accident. If there is a risk of energized electrical contact, arc, or
flash, technicians MUST put on all PPE in accordance with OSHA, NFPA 70E, or other local, state, or country-
specific requirements for arc flash protection PRIOR to servicing the unit. NEVER PERFORM ANY SWITCHING,
DISCONNECTING, OR VOLTAGE TESTING WITHOUT PROPER ELECTRICAL PPE AND ARC FLASHING
CLOTHING. ELECTRICAL METERS AND EQUIPMENT MUST BE PROPERLY RATED FOR INTENDED VOLTAGE.
WARNING
Personal Protective Equipment (PPE) Required!
In the event of an electrical accident, all required PPE should be near the work area in accordance with OSHA,
NFPE 70E, or other local, state, or country-specific requirements for a Category 2 risk.
WARNING
Risk of Injury!
Do not make rapid moves when working on high voltage circuits in refrigeration units. Do not grab for falling
tools because you might accidentally touch a high voltage source.
WARNING
Hazardous Voltage w/Capacitors!
Be careful when working with electrical circuits that contain capacitors. Some capacitors hold a significant
electrical charge that might cause burns or shocks if accidentally discharged. Capacitors must be discharged
before working on electrical circuits. If there is a risk of energized electrical contact, arc, or flash, technicians
MUST put on all PPE in accordance with OSHA, NFPA 70E, or other local, state, or country-specific
requirements for arc flash protection PRIOR to servicing the unit. NEVER PERFORM ANY SWITCHING,
DISCONNECTING, OR VOLTAGE TESTING WITHOUT PROPER ELECTRICAL PPE AND ARC FLASHING
CLOTHING. ELECTRICAL METERS AND EQUIPMENT MUST BE PROPERLY RATED FOR INTENDED VOLTAGE.
TK 61377-18-MM-EN 15
Safety Precautions
Low Voltage
WARNING
Live Electrical Components!
Control circuits used in refrigeration units are low voltage (12 to 48 Vdc). However, the large amount of
amperage available can cause severe burns if accidentally shorted to ground with metal objects, such as tools.
Do not wear jewelry, watches, or rings because they increase the risk of shorting out electrical circuits and
damaging equipment or causing severe burns. If there is a risk of energized electrical contact, arc, or flash,
technicians MUST put on all PPE in accordance with OSHA, NFPA 70E, or other local, state, or country-specific
requirements for arc flash protection PRIOR to servicing the unit. NEVER PERFORM ANY SWITCHING,
DISCONNECTING, OR VOLTAGE TESTING WITHOUT PROPER ELECTRICAL PPE AND ARC FLASHING
CLOTHING. ELECTRICAL METERS AND EQUIPMENT MUST BE PROPERLY RATED FOR INTENDED VOLTAGE.
Welding Precautions
Take precautions before electrically welding any portion of the unit or the vehicle to which it is attached. Verify that
welding currents are not allowed to flow through the unit’s electronic circuits.
Observe the following precautions when welding to avoid damaging electronic components.
• If the microprocessor has a power switch, turn it OFF before connecting or disconnecting the battery.
• Disconnect power to the unit.
• Disconnect all wire harnesses from the microprocessor. Disconnect the ECU and the battery charger if so equipped.
• If there are any electrical circuit breakers in the control box, switch them OFF.
• Close the control box.
• Components that could be damaged by welding sparks should be removed from the unit.
• Use normal welding procedures, but keep the ground return electrode as close to the area being welded as
practical. This will reduce the likelihood of stray welding currents passing through any electronic circuits.
First Aid
REFRIGERANT
• E y e s : For contact with liquid, immediately flush eyes with large amounts of water and get prompt medical
attention.
16 TK 61377-18-MM-EN
Safety Precautions
• S k i n : Flush area with large amounts of warm water. Do not apply heat. Remove contaminated clothing and shoes.
Wrap burns with dry, sterile, bulky dressing to protect from infection. Get prompt medical attention. Wash
contaminated clothing before reuse.
• I n h a l a t i o n : Move victim to fresh air and use Cardio Pulmonary Resuscitation (CPR) or mouth-to-mouth
resuscitation to restore breathing, if necessary. Stay with victim until emergency personnel arrive.
• F r o s t B i t e : In the event of frost bite , the objectives of First Aid are to protect the frozen area from further injury,
warm the affected area rapidly, and to maintain respiration.
REFRIGERANT OIL
• E y e s : Immediately flush with large amounts of water for at least 15 minutes. Get prompt medical attention.
• S k i n : Remove contaminated clothing. Wash thoroughly with soap and water. Get medical attention if irritation
persists.
• I n h a l a t i o n : Move victim to fresh air and use Cardio Pulmonary Resuscitation (CPR) or mouth-to-mouth
resuscitation to restore breathing, if necessary. Stay with victim until emergency personnel arrive.
• I n g e s t i o n : Do not induce vomiting. Immediately contact local poison control center or physician.
ENGINE COOLANT
• E y e s : Immediately flush with large amounts of water for at least 15 minutes. Get prompt medical attention.
• S k i n : Remove contaminated clothing. Wash thoroughly with soap and water. Get medical attention if irritation
persists.
• I n g e s t i o n : Do not induce vomiting. Immediately contact local poison control center or physician.
BATTERY ACID
• E y e s : Immediately flush with large amounts of water for at least 15 minutes. Get prompt medical attention. Wash
skin with soap and water.
• I N H A L A T I O N : Provide fresh air. Rinse mouth and nose with water. Seek immediate medical assistance.
• S K I N C O N T A C T : Immediately remove contaminated clothing. Wash skin with large volumes of water, for at least
15 minutes. Wash skin with soap and water. Do not apply fatty compounds. Seek immediate medical assistance.
• I N G E S T I O N : If the injured person is fully conscious: make the person drink extensive amounts of milk. Do not
induce vomiting. Take the injured person immediately to a hospital.
ELECTRICAL SHOCK
Take IMMEDIATE action after a person has received an electrical shock. Get quick medical assistance, if possible.
The source of the shock must be quickly stopped, by either shutting off the power or removing the victim. If the power
cannot be shut off, the wire should be cut with an non-conductive tool, such as a wood-handle axe or thickly insulated
cable cutters. Rescuers should wear insulated gloves and safety glasses, and avoid looking at wires being cut. The
ensuing flash can cause burns and blindness.
If the victim must be removed from a live circuit, pull the victim away with a non-conductive material. Use wood, rope,
a belt or coat to pull or push the victim away from the current. DO NOT TOUCH the victim. You will receive a shock from
current flowing through the victim’s body. After separating the victim from power source, immediately check for signs
of a pulse and respiration. If no pulse is present, start Cardio Pulmonary Resuscitation (CPR). If a pulse is present,
respiration might be restored by using mouth-to-mouth resuscitation. Call for emergency medical assistance.
ASPHYXIATION
Move victim to fresh air and use Cardio Pulmonary Resuscitation (CPR) or mouth-to-mouth resuscitation to restore
breathing, if necessary. Stay with victim until emergency personnel arrive.
TK 61377-18-MM-EN 17
Specifications
Electrical System
12 Vdc 24 Vdc
Fuses
Common Fuses
Fuse 5: Roadside (Engine) Compressor Clutch (CCL1), Liquid Injection Switch 20 amps 10 amps
(LIS), Liquid Injection Valve (LIV), EVAP1 Defrost Hot Gas Solenoid Valve (PS1),
Compressor Motor Contactor (CMC), Heat Pilot Solenoid (PS5)
Fuse 30: Condenser Fan Motor (CFM) (located in CF1 wire near terminal strip in 16 amps 10 amps
condenser section)
Fuse 8: (Spectrum Only) EVAP2 Liquid Solenoid Valve (PS2), EVAP1 Liquid 20 amps 10 amps
Solenoid Valve (PS3), EVAP2 Defrost Hot Gas Solenoid Valve (PS4), Drain Heaters
3 and 4 (HT3, HT4)
Fuse 20: Transformer AC Power Supply (located at compressor motor contactor in 4 amps 4 amps
condenser section)
Fuse 21: Battery Power Supply (located in 2 wire near battery) 50 amps (Single Temp) 60 amps (Multi-Temp)
Fuse 31: Condenser Fan Motor 2 (CFM2) (located in CF2 wire near terminal strip in 16 amps 10 amps
condenser section)
18 TK 61377-18-MM-EN
Specifications
Voltage 12 Vdc
Coil for Heat Pilot Solenoid (PS5) - Truck Engine Coolant Heat Option Only
Voltage 12 Vdc
Voltage 12 Vdc
Capacitors
TK 61377-18-MM-EN 19
Specifications
Transformer
Power 500 VA
Frequency 50/60 Hz
V-500/V-600
Refrigeration System
N o t e : Units from January 2016 are available with R-404A, R-452A or R-134A Refrigerants. All of which comply with F-
Gas legislation revision 2014 (Regulation (EC) No 517/2014)
Refrigerant GWP
R-404A 3922
R-452A 2140
R-134A 1430
20 TK 61377-18-MM-EN
Specifications
CAUTION
Service Procedure!
Fluorinated Refrigerant gases should not be ventilated to atmosphere. Take note of the refrigerant type (label
on outside of unit) and do not cross-contaminate.
Refer to the Vehicle Powered Truck Installation Standards and Procedures TK 61588 (Section 10 – System Evacuation
Procedures) and Section 12 – System Charging Procedures) for service information about evacuating and charging the
refrigeration system.
N o t e : *Final refrigerant charge will vary based on each unique installation
Table 1. R-134a Refrigeration System V-Series
Refrigerant Charge:
Low Pressure Cutout Switch (LPCO): Opens 5 to 11 in. Hg vacuum (-17 to -37 kPa)
Closes 4 to 7 psig (28 to 48 kPa)
High Pressure Cutout Switch (HPCO) Opens 2,068 ± 69 kPa (300 ± 10 psi)
Closes 1,379 ± 69 kPa (200 ± 10 psi)
CFPS (condenser fan pressure switch) Opens 896 ± 69 kPa (130 ± 10 psi)
Closes 1,241 ± 69 kPa (180 ± 10 psi)
CFSC (condenser fan speed control) switch Opens 1517 ± 48 kPa (220 ± 7 psi)
Closes 1,241 ± 48 kPa (180 ± 7 psi)
CSPS (condenser pressure control switch) Opens 1,724 + 138 kPa/-0 kPa (250 + 20 psi/-0 kPa)
Closes 1,379 ± 138 kPa (200 ± 20 psi)
Low Pressure Cutout Switch (LPCO): Opens 5 to 11 in. Hg vacuum (-17 to -37 kPa)
Closes 4 to 7 psig (28 to 48 kPa)
High Pressure Cutout Switch (HPCO) Opens 3,100 ± 69 kPa (450 ± 10 psi)
Closes 2,585 ± 69 kPa (375 ± 10 psi)
CFPS (condenser fan pressure switch) Opens 896 ± 69 kPa (130 ± 10 psi)
Closes 1,241 ± 69 kPa (180 ± 10 psi)
TK 61377-18-MM-EN 21
Specifications
CFSC (condenser fan speed control) switch Opens 2,068 + 138 kPa/-0 kPa (300 + 20 psi/-0 kPa)
Closes 1,379 ± 138 kPa (200 ± 20 psi)
CSPS (condenser pressure control switch) Opens 2,068 + 138 kPa/-0 kPa (300 + 20 psi/-0 kPa)
Closes 1,586 + 138 kPa/-0 kPa (230 + 20 psi/-0 kPa)
CPR (Compressor Pressure Regulator) Valve Setting - Model 30 and 50 Only 24 ± 2 psig (165 ± 14 kPa)
SPR (Electric Standby Suction Pressure Regulator) Valve Setting - Model 20 MAX Only 24 ± 2 psig (165 ± 14 kPa)
Compressors
NOTICE
Equipment Damage!
Use the correct oil in Thermo King systems to avoid damaging equipment and nullifying its warranty.
N o t e : Once the oil has been extracted from the compressor, note the oil level in order to be able to maintain the same
level in the replacement compressor. Polyol Ester (POE) or Polyvinyl Ether (PVE) compressor oil must be used in
conventional Thermo King units. Mineral oils or PAG oils must not be added to systems.
Standard Engine Driven Compressor: V-500/V-600 TK-16, 9.9 cu. in. (163 cc), Swash Plate, 6 Cylinder
Optional Engine Driven Compressor TK-312R, 11.4 cu. in. (187 cc), Reciprocating, 3 Cylinder
Electric Standby Compressor - Model 20 and 50 Only TK-13, 8 cu. in. (131 cc), Electric Motor Driven, Swash Plate, 6
Cylinder
System Oil Capacity - Swash Plate Model 10/20/30 6.1 oz (180 cc)
Compressors: Model 50 42.2 oz (1200 cc)
22 TK 61377-18-MM-EN
Specifications
Belt Tension
Belt Field Reset
Solder Applications
Refrigeration Components
For general refrigeration tubing connections: Joint Clearances: 0.003 to 0.005 in. (0.076 to 0.127 mm)
copper to copper or copper to brass
Use: Solder Type 15% Silver TK No. 203-364 Use: Flux Type TK
No. 203-365
For refrigeration tubing connections of dissimilar metals: Joint Clearances: 0.003 to 0.005 in. (0.076 to 0.127 mm)
copper to stainless steel or brass to stainless steel
Use: Solder Type 35% Silver TK No. 203-366 Use: Flux Type TK
No. 203-365
For hot water tubing connections: Joint Clearances: 0.003 to 0.005 in. (0.076 to 0.127 mm)
copper to copper or copper to brass
Use: Solder Type 95% Tin and 5% antimony TK No. 204-167 Use:
Flux Type TK No. 204-417
For hot water tubing connections of dissimilar metals: Joint Clearances: 0.003 to 0.005 in. (0.076 to 0.127 mm)
copper to stainless steel or brass to stainless steel
Use: Solder Type 35% Silver TK No. 203-366 Use: Flux Type TK
No. 203-365
NOTE: Some units may be equipped with compressor pressure regulator (CPR) valve and/or suction pressure regulator (SPR)
valve. To reduce the chance of overheating the CPR/SPR/DPR valve, 95-5 solder or equivalent may be used.
TK 61377-18-MM-EN 23
Unit Description
Introduction
The Thermo King Vehicle Powered Single Temperature and Multi-Temperature (Spectrum) truck refrigeration systems
are designed for transporting cold, frozen and deep frozen products on medium-sized trucks with one or more
compartments. There are four basic units:
• Model 10: Cool and defrost on truck engine driven compressor operation.
• Model 20: Cool and defrost on both truck engine driven compressor operation and electric standby compressor
operation.
• Model 30: Cool, heat, and defrost on truck engine driven compressor operation. Only available on MAX units.
• Model 50: Cool, heat, and defrost on both vehicle engine driven compressor operation and electric standby
compressor operation. Only available on MAX units.
The system consists of at least three separate assemblies: the condenser, the evaporator, and the compressor(s). The
condenser is installed on the front section or under the truck chassis, with the evaporator(s) (1 for Single–Temperature,
2 or 3 for Spectrum applications) on the roof. The road compressor is activated by the vehicle engine, using a belt. The
unit is connected to the compressor through refrigeration hoses and refrigeration tubes. On models with electric
standby operation, the second processor is activated using an electric motor.
Condenser
The condenser is mounted on the front of the truck box.
Evaporator
The evaporator is mounted on the ceiling inside the truck box. SPECTRUM units have two evaporators, one in each
compartment.
Compressor
The compressor is mounted to the trucks engine and driven by the engine by a belt-drive system. Model 20 and 50 units
also have an additional compressor driven by an electric motor in the condenser section for electric standby operation.
The evaporator, condenser and engine driven compressor are connected with refrigeration hoses that are assembled
during the installation process.
The engine driven compressor and the standby compressor are connected in parallel to the same refrigeration system
circuit. The compressors share refrigerant, but check valves isolate one compressor from the other during operation.
Control Circuits
The control circuits operate on 12 Vdc or 24 Vdc supplied by the vehicle batteries for engine operation. On standby
operation, the power is rectified from an AC transformer
Oil Separator
An oil separator is a standard feature. The oil separator separates compressor oil from refrigerant vapor and returns the
oil to the compressor through the suction line. The oil separator helps provide positive oil return at high compressor
speeds and low operating temperatures. This feature enhances compressor lubrication and extends compressor life.
24 TK 61377-18-MM-EN
Unit Description
Refrigerant
• V-Series units use R-134a refrigerant.
• V-Series MAX units use R-452A or R-404A refrigerant.
Unit Features
Standard Features
• In-Cab Controls with Digital LCD Thermometer
• Hot Gas Defrost
• Defrost Termination Switch
• Oil Separator
• Evaporator Drain Line Heaters (MAX Units Only, Optional on R-134a Units)
• Liquid Injection (MAX Units Only)
• Electric Standby Compressor (Model 20 and 50 Units Only)
• Hot Gas Heat (Model 30 and 50 units only)
Optional Features
• Door Switch Kit
• Discharge Muffler Kit
• Heat, Truck Engine Coolant (Only available for Model 10 and 20 Units)
• Heat, Truck Engine Coolant and Electric Standby Heater Strip (Only available for Model 20 Units)
• Snow Covers
• Electric Standby Plug (115Vac, 230Vac 1 phase, 230Vac 3 phase)
TK 61377-18-MM-EN 25
Unit Description
Protection Features
• Discharge (High) Pressure Transducer - The discharge pressure transducer is a pressure sensitive device. It is
located in the condenser section discharge line near the oil separator.
If the discharge pressure rises above a certain pressure, the ECM opens the circuit to the compressor clutch to
stop unit operation.
For units with R-134a, the ECM opens the compressor clutch circuit at 300 psig (2068 kPa) and shuts down the
unit. The ECM closes the compressor clutch circuit when the pressure drops to 200 psig (1379 kPa).
For units with R-404A or R-452A, the ECM opens the compressor clutch circuit at 450 psig (3103 kPa) and shuts
down the unit. The ECM closes the compressor clutch circuit when the pressure drops to 375 psig (2586 kPa).
• Low Pressure Cutout Switch - The Low Pressure Cutout Switch is a pressure sensitive switch located on the suction
line assembly in the evaporator. If the suction pressure falls below 5 to 11 in. Hg vacuum (-17 to -34 kPa), the switch
opens the LPCO/CH circuit. This signals the ECM to open the circuit to the compressor clutch to stop unit operation.
The ECM closes the compressor clutch circuit when the pressure rises to 4 to 7 psig (28 to 48 kPa).
Control Box
P.C. Boards
All Printed Circuit Boards within this unit, supplied by Thermo King can be easily identified by the Part Number
stamped on them.
26 TK 61377-18-MM-EN
Unit Description
TK 61377-18-MM-EN 27
Unit Description
L i q u i d I n j e c t i o n S w i t c h L I S ( M A X u n i t s ) - closes when the temperature of the refrigerant gas leaving the compressor
exceeds a determined temperature and activates the liquid injection valve (LIV) if the road clutch (CLU1) is also
activated. The LIV allows liquid refrigerant to flow from the liquid line to the metering orifice that is attached to the
suction line fitting on the compressor. As the refrigerant passes through the metering orifice, it expands and
evaporates, and cools the suction gas entering the compressor. This cooling effect is transferred to the discharge gas
leaving the compressor. When the discharge gas is cooled to a determined value, the LIS opens and refrigerant no
longer flows through the liquid injection system.
D e f r o s t T e r m i n a t i o n S w i t c h ( D K 1 , D K 2 ) - normally closed, DK1 or DK2 opens to stop the defrost operation in the
load compartment (DK1 for the main load compartment, DK2 for a remote load compartment, also used for condenser
defrost in reverse cycle units).
D o o r S w i t c h e s ( D S W 1 , D S W 2 ) - used to stop unit operation except in defrost mode, when the load compartment
doors are opened.
O v e r l o a d S w i t c h ( O L ) - used to protect the motor from an electrical overload. When this normally open switch closes,
the unit shuts down.
T h e r m a l p r o t e c t i o n s w i t c h ( H T T 1 , H T T 2 ) - opens when engine temperature exceeds a determined value. This
information is used by the microprocessor to energise the tEP alarm.
P o w e r s u p p l y t h e r m a l p r o t e c t i o n s w i t c h ( T H M R 1 / 2 ) - Alarm tP4 appears when the power supply temperature
exceeds the preset value.
Unit Operation
Standard Model 10 and 20 units (without heat options) operate in Cool mode or Null mode, as required, to maintain the
load compartment temperature at the setpoint temperature.
Model 30 and 50 units, and 10 and 20 units with heat options (coolant or electric heat), operate in Cool, Null, or Heat as
required, to maintain the load compartment temperature at the setpoint temperature.
Defrost cycles occur manually or automatically, as required.
If power is shut off, the unit comes back in Null mode when the unit is restarted. There is a momentary delay at auto
start-up for circuit protection.
N o t e : The compressor will “bump start” five times while coming out of Null or when the unit is first started. In a “bump
start” the compressor is turned on for about one second and then goes off for about four seconds.
Figure 1. Thermostat Algorithm
Options:
• Coolant Heat - This option provides auxiliary heating by circulating hot engine coolant through the evaporator.
• Electric Heat - Provides auxiliary heat through resistive heat strips in the evaporator when connected to electric
standby.
28 TK 61377-18-MM-EN
Unit Description
Operation
The vehicle engine must be running and the unit must be turned on. On units with Electric Standby, connect the
external power cord and the unit switches to Electric mode operation. Unit operation can be tailored, as required, using
programmable settings as shown in the Direct Smart Reefer III Microprocessor Control System Diagnostic Manual TK
61096.
Cool Mode
When cooling is required (when there is a requirement to lower the evaporator return air temperature in the load
compartment), the controller energizes the compressor clutch (and compressor motor contactor in model 20/50 units)
and evaporator fans. The controller monitors the discharge pressure through the discharge pressure transducer (DPT).
The condenser fan is energized if necessary and turn on and off as determined by the controller.
The unit operates in Cool mode until the setpoint temperature is reached. The unit then enters Null mode. When the
temperature rises to a pre-determined number of degrees (programmable setting), the unit restarts in Cool mode.
Cool Mode Model 10
Notes:
• The following shows the Model 10 MAX unit. The standard Model 10 is similar but does not have the liquid
injection system (liquid injection solenoid (LIS), connecting lines, and liquid injection switch).
High pressure refrigerant vapor leaves the compressor and flows through the oil separator where oil is separated and
returned to the splice fitting in the suction line. The refrigerant flows through the condenser where the refrigerant
releases heat and condenses into high pressure liquid. The liquid refrigerant flows through the drier, liquid indicator,
and the expansion valve into the evaporator. There, liquid refrigerant absorbs heat as it evaporates into low pressure
vapor. The refrigerant returns to the compressor through the suction line.
If the compressor discharge temperature rises enough to close the liquid injection switch, the liquid injection valve
opens and liquid refrigerant flows through the liquid injection line, liquid injection orifice and splice fitting in the suction
line to cool the compressor. When the compressor discharge temperature falls enough to open the liquid injection
switch, liquid injection valve closes to stop liquid injection.
• Hot Gas Solenoid (HGS) – Closed/De-energized
• Liquid Injection Solenoid (LIS) – Closed/De-energized, but will open (energize) when the liquid injection switch is
closed to control the engine driven compressor temperature.
TK 61377-18-MM-EN 29
Unit Description
1. Low Pressure Cutout switch (LPCO) 9. Drier 17. Defrost Line (Hose #6)
2. Pressure Transducer 10. Service Valve 18. Suction Line (hose #12)
3. Oil Return Line 11. Liquid Indicator 19. Liquid Line (Hose #6)
4. Oil Separator 12. Liquid Injection Valve (LIS) 20. PS1 (Defrost Valve)
5. Injection Line 13. Discharge Line (hose #8) 21. Evaporator Coil
6. Condenser Coil 14. Suction Line (Hose # 16) 22. Expansion Valve
Legend
30 TK 61377-18-MM-EN
Unit Description
TK 61377-18-MM-EN 31
Unit Description
1. Low Pressure Cutout switch (LPCO) 10. Service Valve 19. Liquid Line (Hose #6)
3. Oil Return Line 12. Liquid Injection Valve (LIS) 21. Evaporator Coil
4. Oil Separator 13. Discharge Line (hose #8) 22. Expansion Valve
5. Injection Line 14. Suction Line (Hose # 16) 23. Discharge check valve
6. Condenser Coil 15. Liquid Injection Switch 24. Oil Balance Line
7 Service Valve 16. Truck Engine Compressor 25. Standby Compressor (CMC)
Legend
32 TK 61377-18-MM-EN
Unit Description
High pressure refrigerant vapor leaves the electric standby compressor and flows through the discharge check valve
and the oil separator where oil is separated and returned to a suction line. The refrigerant flows through the condenser
where the refrigerant releases heat and condenses into high pressure liquid. The liquid refrigerant flows through the
drier, liquid indicator, and the expansion valve into the evaporator. There, liquid refrigerant absorbs heat as it
evaporates into low pressure vapor. The refrigerant returns to the compressor through the suction pressure regulator.
• Discharge Check Valve – Closed to engine driven compressor, open to electric standby compressor
• Hot Gas Solenoid (HGS) – Closed/De-energized
• Liquid Injection Solenoid (LIS) – Closed/De-energized
TK 61377-18-MM-EN 33
Unit Description
1. Low Pressure Cutout switch (LPCO) 10. Service Valve 19. Liquid Line (Hose #6)
3. Oil Return Line 12. Liquid Injection Valve (LIS) 21. Evaporator Coil
4. Oil Separator 13. Discharge Line (hose #8) 22. Expansion Valve
5. Injection Line 14. Suction Line (Hose # 16) 23. Discharge check valve
6. Condenser Coil 15. Liquid Injection Switch 24. Oil Balance Line
7 Service Valve 16. Truck Engine Compressor 25. Standby Compressor (CMC)
8. Receiver 17. Defrost Line (Hose #6) 26. Suction Pressure Regulator
Legend
34 TK 61377-18-MM-EN
Unit Description
TK 61377-18-MM-EN 35
Unit Description
1. Low Pressure Cutout switch (LPCO) 10. Service Valve 19. Liquid Line (Hose #6)
2. Pressure Transducer 11. Liquid Indicator 20. PS1 (Hot Gas Solenoid Valve)
3. Oil Return Line 12. Liquid Injection Valve (LIS) 21. Evaporator Coil
4. Oil Separator 13. Discharge Line (hose #8) 22. Expansion Valve
5. Injection Line 14. Suction Line (Hose # 16) 23. Service Port
6. Condenser Coil 15. Liquid Injection Switch 24. Suction Pressure Regulator
7 Service Valve 16. Truck Engine Compressor 25. Accumulator (Suction Receiver)
8. Receiver 17. Defrost Line (Hose #6) 26. PS5 (Condenser Solenoid Valve)
Legend
36 TK 61377-18-MM-EN
Unit Description
1. Low Pressure Cutout switch (LPCO) 10. Service Valve 19. Liquid Line (Hose #6)
2. Pressure Transducer 11. Liquid Indicator 20. PS1 (Hot Gas Solenoid Valve)
3. Oil Return Line 12. Liquid Injection Valve (LIS) 21. Evaporator Coil
4. Oil Separator 13. Discharge Line (hose #8) 22. Expansion Valve
5. Injection Line 14. Suction Line (Hose # 16) 23. Service Port
7 Service Valve 16. Truck Engine Compressor 25. Accumulator (Suction Receiver)
8. Receiver 17. Defrost Line (Hose #6) 26. PS5 (Condenser Solenoid Valve)
9. Drier 18. Suction Line (hose #10) 27. By-Pass Solenoid Valve
Legend
TK 61377-18-MM-EN 37
Unit Description
38 TK 61377-18-MM-EN
Unit Description
1. Low Pressure Cutout switch (LPCO) 11. Liquid Indicator 21. Evaporator Coil
2. Pressure Transducer 12. Liquid Injection Valve (LIS) 22. Expansion Valve
3. Oil Return Line 13. Discharge Line (hose #8) 23. Oil Balance Line
4. Oil Separator 14. Suction Line (Hose # 16) 24. Suction Pressure Regulator
5. Injection Line 15. Liquid Injection Switch 25. Accumulator (Suction Receiver)
6. Condenser Coil 16. Truck Engine Compressor 26. PS5 (Condenser Solenoid Valve)
7 Service Valve 17. Defrost Line (Hose #6) 27. Standby Compressor (CMC)
8. Receiver 18. Suction Line (hose #12) 28. Discharge Check Valve
10. Service Valve 20. PS1 (Hot Gas Solenoid Valve) 30. Heat Exchanger
Legend
TK 61377-18-MM-EN 39
Unit Description
1. Low Pressure Cutout switch (LPCO) 12. Liquid Injection Valve (LIS) 23. Service Port
2. Pressure Transducer 13. Discharge Line (hose #10) 24. Pressure Switch
3. Oil Return Line 14. Suction Line (Hose # 16) 25. Accumulator (Suction Receiver)
4. Oil Separator 15. Liquid Injection Switch 26. PS5 (Condenser Solenoid Valve)
5. Injection Line 16. Truck Engine Compressor 27. By-Pass Solenoid Valve
6. Condenser Coil 17. Defrost Line (Hose #6) 28. PS2/PS3 (Solenoid Valve)
7 Service Valve 18. Suction Line (hose #12) 29. Check Valve
8. Receiver 19. Liquid Line (Hose #6) 30. Oil Balance Line
10. Relief Valve 21. Evaporator Coil 32. Discharge Check Valve
Legend
40 TK 61377-18-MM-EN
Unit Description
1. Low Pressure Cutout switch (LPCO) 11. Liquid Indicator 21. Evaporator Coil
2. Pressure Transducer 12. Liquid Injection Valve (LIS) 22. Expansion Valve
3. Oil Return Line 13. Discharge Line (hose #8) 23. Oil Balance Line
4. Oil Separator 14. Suction Line (Hose # 16) 24. Suction Pressure Regulator
TK 61377-18-MM-EN 41
Unit Description
6. Condenser Coil 16. Truck Engine Compressor 26. PS5 (Condenser Solenoid Valve)
7 Service Valve 17. Defrost Line (Hose #6) 27. Standby Compressor (CMC)
8. Receiver 18. Suction Line (hose #12) 28. Discharge Check Valve
Legend
42 TK 61377-18-MM-EN
Unit Description
Null Mode
The unit operates in Null mode when the setpoint temperature is reached and cooling (or heating) is not required. All
outputs are de-energized. If the temperature rises a pre-determined number of degrees (programmable setting), the
unit restarts in Cool mode. If the temperature falls a pre-determined number of degrees, and a heat option is present,
the unit restarts in Heat mode.
In addition, the evaporator fans might operate during Null mode if evaporator fan constant blow feature is enabled. See
the Direct Smart Reefer III Microprocessor Control System Diagnostic Manual TK 61096.
TK 61377-18-MM-EN 43
Unit Description
44 TK 61377-18-MM-EN
Unit Description
Defrost Mode
Defrost can be initiated any time the evaporator coil temperature is below 36 F (2.2 C), causing the defrost termination
switch to close. Defrost is initiated automatically by the defrost timer, or manually using the In-Cab Control Box.
Defrost will continue until the evaporator coil temperature rises to 48 F (8.9 C) causing the defrost termination switch to
open or the defrost termination timer has expired (whichever occurs first), ending the defrost cycle. Defrost cycle can be
also terminated by pressing the On/Off Key to turn the unit off, and then pressing it again to turn the unit back on.
The drain hose heaters are also energized during defrost (if so equipped).
TK 61377-18-MM-EN 45
Unit Description
46 TK 61377-18-MM-EN
Unit Description
Unit Components
Figure 11. V-500/V-600 MAX 10/20/30/50 Condenser
9 Compressor Pressure Regulator Valve (CPR) 19 Liquid Line Check Valve (30/50 units)
10 Condenser Fans
TK 61377-18-MM-EN 47
Unit Description
10 Suction pressure regulator valve (SPR) (Evaporator 1) 20 Liquid Line Check Valve (30/50 units)
48 TK 61377-18-MM-EN
Unit Description
TK 61377-18-MM-EN 49
Unit Description
50 TK 61377-18-MM-EN
Unit Description
TK 61377-18-MM-EN 51
Maintenance Inspection Schedule
N o t e : Please refer to your V-Series Operator Manual TK 61651-1-OP for Operator Weekly Checks
N o t e : Please refer to the latest EDAC labour Standards Guide on EMEA infocentral for Service Inspection Schedules for
your unit.
52 TK 61377-18-MM-EN
Electrical Maintenance
Electronic Control System
Refer to the Direct Smart Reefer III Microprocessor Control System Diagnostic Manual TK 61096 for complete service
information about Electronic Control System and the related components.
Defrost System
Defrost is initiated automatically by the programmable defrost timer, or manually by means of the In-Cab Control Box.
If demand defrost is enabled, a demand defrost cycle occurs, based on the Defrost Initiation Timer (DIT) and the Defrost
Termination Switch being closed. The evaporator coil temperature must be below 36 F (2.2 C) to allow defrost.
When defrost is required, the microprocessor output energizes the hot gas solenoid to supply hot refrigerant to the
evaporator coil and de-energizes the evaporator fans. The Defrost Initiation Timer (DIT) has counted-down its required
time-setting, and the Defrost Termination Switch is closed.
The unit remains in Defrost mode until the Defrost Termination Switch setpoint is reached (that is, when the evaporator
coil temperature rises to 48.0 F (8.9 C), or until the Defrost Termination Timer (DTT) count is completed). If the
evaporator coil temperature does not rise above 48.0 F (8.9 C) within the defrost duration time limit, the microprocessor
terminates the defrost operation.
The startup of the evaporator fans is delayed for several seconds after Defrost mode ends to prevent water from the
melting ice from being sprayed on the load.
Defrost initiation and termination settings are accessed through the Guarded Access Menu. Refer to the for instructions
on the use of Guarded Access Menu features.
The Defrost Initiation Timer offers programming choices of 0 to 480 minutes, in increments of 30 minutes. The factory
setting is 240 minutes. This parameter allows maintenance personnel to set the Defrost Initiation Timer. When it times-
out, it switches the unit from Cool mode to Defrost mode. The timer counts all the time that the unit is in Cool mode.
The count resets when Defrost mode starts. If the timer is set at 0 (zero), this is a test position. Defrost mode starts in 15
seconds.
The Defrost Termination Timer offers programming choices of 5 to 50 minutes, in increments of 5 minutes. The factory
setting is 30 minutes. This parameter allows maintenance personnel to set the Defrost Termination Timer, which begins
counting from the initiation of a Defrost mode. When the timer times-out, the unit is switched from Defrost mode to
Null mode. The timer resets at the end of a Defrost mode, or after the Defrost Termination Timer has timed-out. If the
timer is set at 0 (zero), this is a test position. Defrost mode stops in 15 seconds.
Installation
1. Place the switch in position and install the mounting hardware.
2. Connect the wires to the switch.
3. Connect the evaporator fan motor wires if needed and install the evaporator cover.
TK 61377-18-MM-EN 53
Electrical Maintenance
WARNING
Risk of Injury!
Take precautions to verify the unit will not accidentally start while servicing the system. Always turn off the
unit On/Off Switch when inspecting or servicing any components.
The condenser fan motors are maintenance free. If erratic or intermittent operation is observed, the current draw of the
motor should be measured while proper voltage is applied. The current draw for a condenser fan motor is
approximately 10.0 to 10.8 amps at 13 volts.
If the condenser fan motor does not run at all, check the fuses in the condenser fan motor circuit and the output to the
condenser fan when it should be energized.
Installation
1. Connect the fan motor power plug.
2. Place the fan motor in . Install and tighten the fan motor mounting screws (4).
3. Install the fan shroud and condenser cover.
4. Start the unit and verify correct fan motor operation.
WARNING
Risk of Injury!
Take precautions to verify the unit will not accidentally start while servicing the system. Always turn off the
unit On/Off Switch when inspecting or servicing any components.
The evaporator fan motors are maintenance free. If erratic or intermittent operation is observed, the current draw of the
motor should be measured while proper voltage is applied. The current draw for a evaporator motor is approximately
5.7 to 6.2amps at 13 volts.
If any of the evaporator fan motors do not run at all, check the fuses in the evaporator fan motor circuits and the outputs
to the evaporator fans when they should be energized.
54 TK 61377-18-MM-EN
Electrical Maintenance
Installation
1. Attach the fan motor to the evaporator or evaporator cover and tighten the fan motor mounting screws (4).
2. Connect the fan motor power plug(s).
3. Ensure the wires do not contact the fan blades inside the evaporator.
4. Install the evaporator cover.
5. Start the unit and verify correct fan motor operation.
Installation
1. Insert the heater wires into the drain hose drain hose as far as they will go. Note the following:
• Heater wires must extended into drain pan and be inserted into each drain hose as far as they will go.
• NEVER CUT HEATER RESISTANCE WIRES!
• DO NOT install more than one heater wire into each drain tube.
• DO NOT use band wraps to hold heater wires.
• DO NOT cover or wrap heater wires.
• DO NOT pinch the end of the heater wires tight.
TK 61377-18-MM-EN 55
Electrical Maintenance
Fuses
N o t e : Please refer to “Specifications Chapter of this manual ,” p. 18 for more information pertaining to your particular
unit.
Controller Fuses:
These fuses are located on the controller.
N o t e : Platform II ECM shown here as an example.
Figure 18. Controller Fuses
56 TK 61377-18-MM-EN
Electrical Maintenance
1. Fuse F20 - 5 amps (Model 20 and Model 50 only) 3. Fuse 26 - 15 amps (Electric Heat Option only)
2. Fuse F30 - 20 amps 4. Fuse F16 - 5 amps (Model 20 and Model 50 only)
Harness Fuses:
These fuses are located in wiring harnesses outside of the control box.
TK 61377-18-MM-EN 57
Electrical Maintenance
Relays
One or more relays are used in these units.
• Battery Power Relay (all units) Single Pole Single Throw (SPST)
• Electric Standby Power Relay (Model 20 and Model 50 units only) Single Pole Single Throw (SPST)
• Battery Relay (Model 20 and Model 50 units only) Single Pole Double Throw (SPDT)
Figure 21. Single Pole Single Throw (SPST) Relay
58 TK 61377-18-MM-EN
Electrical Maintenance
Relay Testing
A relay is energized when 12 Vdc or 24 Vdc power is applied to the relay coil across pins 85 and 86. When energized the
normally open (NO) contacts close and the normally closed (NC) contacts open.
1. Remove covers as needed to access the relays.
2. To check the battery power relay, turn the truck ignition switch on. To check the electric standby power relay and the
battery disconnect relay, connect the unit to an appropriate electric standby power supply.
3. Remove the relay from its socket and check for 12 Vdc or 24 Vdc between pins 85 and 86 in the relay socket. If
voltage is not present, check the circuits that supply power and ground to the relay coil.
4. Check the resistance between pins 85 and 86 on the relay. It should be approximately 90 ohms. If not, replace the
relay.
5. On a SPDT relay, check the NC contacts by checking for continuity between pins 30 and 87A. If the continuity is not
acceptable, replace the relay.
6. Use jumper wires and a 12 Vdc power supply to attached to pins 85 and 86 to energize the relay.
7. Check the NO contacts by checking for continuity between pins 30 and 87. If the continuity is not acceptable, replace
the relay.
Relay Replacement
1. Turn the truck ignition switch off and disconnect the electric standby power supply if applicable.
2. Remove covers as needed to access the relays.
3. Remove the relay from its socket.
4. Insert the new relay into the relay socket.
5. Reinstall any covers that were removed.
TK 61377-18-MM-EN 59
Electrical Maintenance
60 TK 61377-18-MM-EN
Electrical Maintenance
TK 61377-18-MM-EN 61
Electrical Maintenance
4. Electric Motor Start Capacitor (115/1/60 and 208-230/1/60 9. Electronic Control Module
units only)
Electrical Contactors
Test the contact points by checking the voltage drop across each set of points when the contactor is energized and the
system is operating. If the voltage drop across a set of points is more than 0.25 Vac, replace the contactor.
Test the contactor coil as follows:
1. Check the voltage to the coil. It should be at approximately 12 Vdc. If not, check for an open circuit.
62 TK 61377-18-MM-EN
Electrical Maintenance
2. Check the voltage after the coil. It should be 0 volts. If not, check for an open or high resistance in the circuit to
ground. If the voltage is 0 but the contactor does not pull-in, the coil is probably open. Check the resistance to verify.
It should be approximately 48 ohms.
Installation
1. Place the compressor motor contactor in position and install the mounting hardware.
2. Connect the wires to the compressor motor contactor. Make sure to connect the wires to the same terminals from
which they were removed.
3. Reinstall the cover.
TK 61377-18-MM-EN 63
Electrical Maintenance
2. Use a small screwdriver to set the opening amperage. See the Specifications chapter for the correct overload relay
setting.
3. Use a small screwdriver to remove the tab marked with an “H” to access the switch used to set the overload relay to
reset automatically.
Figure 26. Set Amperage and Remove Tab
4. Move the slide switch down until it clicks into place at the bottom of the slot (from which the tab marked “H” was
removed). This sets the overload relay to reset automatically.
64 TK 61377-18-MM-EN
Electrical Maintenance
The new overload relay is now set up correctly. Note which wires go to which terminals when removing the old
overload relay so the wires are connected correctly when the new overload relay is installed.
Removal
1. Turn the unit off and disconnect the electric standby power supply.
2. Remove the condenser cover.
3. Disconnect the wires from the compressor motor overload relay. Note which wires are attached to which terminals
so they can be reattached correctly.
4. Remove the compressor motor overload relay mounting hardware and remove the compressor motor overload
relay.
Installation
1. Place the compressor motor overload relay in position and install the mounting hardware.
2. Connect the wires to the compressor motor overload relay. Make sure to connect the wires to the same terminals
from which they were removed.
3. Reinstall the condenser cover.
Transformer – T1
The transformer converts 230 Vac to 12 Vac to provide power to the . The converts the 12 Vac to 12 Vdc to supply power
to the 12 Vdc control circuits.
Transformer Testing
Test the transformer as follows:
1. Disconnect the 6-pin connector in the wire harnesses to the transformer.
2. Connect the electric standby power receptacle to an appropriate AC power supply.
3. Check for AC voltage between the wires in the 6-pin connector.
4. the continuity of the L1 wire to the CMC, the continuity of the standby power harness, and the power supply.
5. Disconnect the AC power supply.
TK 61377-18-MM-EN 65
Electrical Maintenance
Transformer Replacement
Removal
1. Turn the unit off and disconnect the electric standby power supply.
2. Remove the cover.
3. Disconnect the wire harnesses connected to the transformer.
4. Remove the transformer mounting hardware and remove the transformer.
Installation
1. Place the transformer in position and install the mounting hardware.
2. Connect the wire harnesses to the transformer.
3. Reinstall the cover.
Bridge Rectifier – BR
The bridge rectifier converts the 11.7 Vac power from the transformer to 11.7 Vdc to supply power to the 12 Vdc control
circuits. The bridge rectifier is located on a heat sink below the left side of the condenser coil when viewed from the
front of the condenser.
Test the bridge rectifier as follows:
1. Connect the electric standby power receptacle to an appropriate AC power supply.
2. Check for AC voltage between the X1 and X4 wires at the rectifier.
3. Approximately 12 Vac should be present between X1 and X4. If not, check the continuity of the X1 and X4 wires to
the transformer, the transformer, and the AC circuits back to the power supply.
4. Check the rectifier output voltage (DC) between the 2R wire and the CH wire at the rectifier. If this voltage is less than
approximately 12 Vdc the rectifier bridge is defective.
Capacitors
Several capacitors are used in Model 20 and Model 50 units.
• Smoothing Capacitor (all voltages)
• Electric Motor Run Capacitor
• Electric Motor Start Capacitor
WARNING
Hazardous Voltage w/Capacitors!
Be careful when working with electrical circuits that contain capacitors. Some capacitors hold a significant
electrical charge that might cause burns or shocks if accidentally discharged. Capacitors must be discharged
before working on electrical circuits. If there is a risk of energized electrical contact, arc, or flash, technicians
MUST put on all PPE in accordance with OSHA, NFPA 70E, or other local, state, or country-specific
requirements for arc flash protection PRIOR to servicing the unit. NEVER PERFORM ANY SWITCHING,
DISCONNECTING, OR VOLTAGE TESTING WITHOUT PROPER ELECTRICAL PPE AND ARC FLASHING
CLOTHING. ELECTRICAL METERS AND EQUIPMENT MUST BE PROPERLY RATED FOR INTENDED VOLTAGE.
T o s a f e l y d i s c h a r g e a c a p a c i t o r : Turn the unit off and disconnect the electric standby power supply. Connect a 20,000
ohm, 5-watt resistor across the capacitor terminals for five seconds. Use a multimeter to confirm the capacitor is fully
discharged.
Capacitor Testing
1. Turn the unit off and disconnect the electric standby power supply.
66 TK 61377-18-MM-EN
Electrical Maintenance
Capacitor Replacement
Removal
1. Turn the unit off and disconnect the electric standby power supply.
2. Remove covers as needed to access the capacitor.
3. Discharge the capacitor as described above.
4. Disconnect the wires from the capacitor.
5. Remove the capacitor mounting hardware and remove the capacitor.
Installation
1. Place the capacitor in position and install the mounting hardware.
2. Connect the wires to the capacitor.
3. Reinstall any covers that were removed.
Start Relay – SR
The start relay is a normally closed (NC) single pole single throw (SPST) relay. It is used to open the circuit between the
start capacitor (SC) and the C1 circuit when the compressor motor gets up to speed after the compressor motor
contactor (CMC) is energized to supply AC power to the compressor motor.
TK 61377-18-MM-EN 67
Electrical Maintenance
4. Disconnect the wires from the start relay. Note which wires are attached to which terminals so they can be
reattached correctly.
5. Remove the start relay mounting hardware and remove the start relay.
Installation
1. Place the start relay in position and install the mounting hardware.
2. Connect the wires to the start relay. Make sure to connect the wires to the same terminals from which they were
removed.
3. Reinstall any covers that were removed.
Compressor Motor
Testing 115/1/60 Units
1. Connect the electric standby power receptacle to an appropriate AC power supply.
2. Set the thermostat so the unit will run in Cool.
3. Start the unit and run it in Cool on electric standby.
4. Check for AC voltage between the T1A and T2A wires at the compressor motor contactor.
5. Approximately 115 Vac should be present. If not, check the compressor motor contactor, the continuity of the
standby power harness, and the power supply. If the compressor motor contactor is not being energized (pulling
down) see “Electric Standby Circuits” below.
6. Check for AC voltage between the T1A and T2A wires at the compressor motor overload relay.
7. Approximately 115 Vac should be present. If not, check the continuity of the T1A and T2A wires.
8. Check for AC voltage between the T1-01 and T2-01 wires at the compressor motor overload relay.
9. Approximately 115 Vac should be present. If not, check the continuity of the PO wire on the compressor motor
overload relay and the compressor motor overload relay.
10. Turn the unit off, disconnect AC power supply, and check the connections in the junction box on the compressor
motor for to verify they are clean and tight.
11. Check the continuity of the T1-01 and T2-01 wires from the compressor motor overload relay to the compressor
motor. If both wires have good continuity, check the start relay, the start capacitor, the run capacitors and the
associated circuits. If those components are good, the compressor motor is most likely faulty.
68 TK 61377-18-MM-EN
Electrical Maintenance
TK 61377-18-MM-EN 69
Electrical Maintenance
2R circuits to the bridge rectifier (BR) and the X1 and X4 circuits from the bridge rectifier (BR) to the transformer
have good continuity, the bridge rectifier (BR) is defective. If the rectifier output voltage is acceptable go to step 4.
4. Check fuse F16 on the X1 wire at the smoothing capacitor (C1).
5. Check the rectifier output voltage (DC) on the X1 wire (pin B8 at Connector 1 on PCB1 in the ECM). If voltage is not
present, check the continuity of the X1 wire from the smoothing capacitor (C1). If the rectifier output voltage is
acceptable, go to step 6.
6. Check the voltage on 2R wire at the electric standby power relay (ESR). If voltage is not present, check the continuity
of the 2R wire from the smoothing capacitor (C1). If the voltage on the 2R wire at the electric standby power relay
(ESR) is acceptable, go to step 7.
7. Check the voltage on the 2RB and 2RB1 wires at the electric standby power relay (ESR). If voltage is not present,
check the continuity of the 2RB wire. If the voltage on both the 2RB and 2RB1 wires is acceptable, go to step 8.
8. Check the voltage on the 2RB1 wire at the battery disconnect relay (BDR). If voltage is not present, check the
continuity of the 2RB1 wire from the electric standby power relay (ESR). If the voltage on the 2RB1 wire at the
battery disconnect relay (BDR) is acceptable, go to step 9.
9. Check for continuity to ground on the CH1 wire at the battery disconnect relay (BDR). If continuity to ground on the
CH1 wire at the battery disconnect relay (BDR) is not present, check the continuity of the CH1 wire from the battery
disconnect relay (BDR) to the chassis ground. If there is good continuity to ground on the CH1 wire at the battery
disconnect relay (BDR), go to step 10.
10. Check for continuity to ground on the SWS wire at the electric standby power relay (ESR). If continuity to ground is
not present, check the continuity of the SWS wire from the battery disconnect relay (BDR). If the SWS wire has good
continuity, go to step 11. If there is good continuity to ground on the SWS wire at the electric standby power relay
(ESR), go to step 12.
11. Check for continuity to ground on the CH4 wire at the battery disconnect relay (BDR). If the CH4 wire has good
continuity to ground, the battery disconnect relay (BDR) is probably defective. If continuity to ground on the CH4
wire at the battery disconnect relay (BDR) is not present, check the continuity of the CH4 wire from the battery
disconnect relay (BDR) to the chassis ground.
12. Check the voltage on the 2RA wire at the electric standby power relay (ESR). If voltage is not present, the electric
standby power relay (ESR) is probably defective. If the voltage on the 2RA wire at the electric standby power relay
(ESR) is acceptable, go to step 13.
13. Check the voltage on the PC1 wire at Pin 2 in the PSC1 Connector on PCB1 in the ECM. If voltage is not present,
check the continuity of the PC1 circuit to the terminal board (TB) and the 2RA circuit to the electric standby power
relay (ESR). If the voltage on the PC1 wire is acceptable, go to step 14.
14. Check the voltage on the CMC wire at the compressor contactor (CMC). If voltage is not present, check the continuity
of the CMC circuit to Pin 10 in Connector 2 on PCB1 in the ECM and Fuse 5 on the ECM. If the CMC wire has good
continuity and Fuse 5 is good, the ECM may be defective. If the voltage on the CMC wire is acceptable, go to step 15.
15. Check for continuity to ground on the CHE wire at the compressor motor contactor (CMC). If there is good continuity
to ground on the CHE wire at the compressor motor contactor (CMC), the compressor motor contactor is probably
defective. If continuity to ground on the CHE wire at the compressor contactor (CMC) is not present, go to step 16.
16. Check the continuity of the CHE wire from the compressor motor contactor (CMC) to the chassis ground.
70 TK 61377-18-MM-EN
Refrigeration Maintenance
Evacuating and Charging the Refrigeration System
Refer to the Vehicle Powered Truck Installation Standards and Procedures TK 61588 (Section 10 – System Evacuation
Procedures) and Section 12 – System Charging Procedures) for service information about evacuating and charging the
refrigeration system
TK 61377-18-MM-EN 71
Refrigeration Maintenance
through the liquid line sight glass. Bubbles in the refrigerant indicate the unit is low on refrigerant. Refer to the
“Suction (Low Side) Bump Charging” procedure listed below to top-off the system.
N o t e : If no bubbles are present, there is sufficient refrigerant in the unit for that load at that particular box
temperature. This test does not determine if the unit contains a full charge of refrigerant.
72 TK 61377-18-MM-EN
Refrigeration Maintenance
Tools Required
• Motor-driven TK 214 “Flushing Compressor”
• Suction Line Filter (P/N 2040498 with Filter P/N 662292)
• Pipes (In Place of Oil Separator, Check Valve, Oil Separator and Standby Compressor)
Clean-up Procedure
1. Make sure all hose routing is correct.
2. Make sure that the oil trap is correctly installed.
3. Recover the contaminated refrigerant from the system.
4. Remove the lines from the compressors (engine driven and standby).
5. Flush each compressor using the flushing compressor and an HFC refrigerant. (Always recover the refrigerant
before disconnecting the flushing compressor.)
TK 61377-18-MM-EN 73
Refrigeration Maintenance
4. Discharge Line
5. Flushing Compressor
6. Suction Line
8. Recovered Oil
6. Remove any check valves (or check valve seats) from system to ensure flow in all directions.
7. Remove the oil separator and install a connecting pipe.
8. Remove the internal parts from the expansion valve.
9. Open any suction pressure regulator valves to their highest setting.
10. Install a temporary suction line filter (P/N 2040498 and P/N 662292) in the suction line.
11. Install a connecting pipe in place of the standby compressor.
12. Connect the flushing compressor system to the engine driven compressor discharge and suction lines (see
illustration).
13. Evacuate the system and check for leaks. Continue to evacuate to remove moisture and air.
14. Install HFC refrigerant and run the flushing compressor to flush the system. Energize (open) the defrost solenoid
during 30% to 40% of the clean-up. Solid contaminants will collect in the suction line filter. Oil from the system and
from the flushing compressor will drain out of the suction line filter. (Add compressor oil as required.) Refrigerant
oil in the flushing compressor will absorb acids from the system.
15. Test the recovered compressor oil for acid contamination.
16. Continue flushing until the compressor oil is clean.
74 TK 61377-18-MM-EN
Refrigeration Maintenance
TK 61377-18-MM-EN 75
Refrigeration Service Operations
N o t e : It is generally good practice to replace the filter drier whenever the high side is opened or when the low side is
opened for an extended period of time.
WARNING
Risk of Injury!
Disconnect the power supply before servicing the unit to prevent personal injury.
76 TK 61377-18-MM-EN
Refrigeration Service Operations
7. Condenser Coil
TK 61377-18-MM-EN 77
Refrigeration Service Operations
6. Hot Gas Solenoid (HGS) 17. Low Pressure Cut Out Switch (LPCO)
78 TK 61377-18-MM-EN
Refrigeration Service Operations
11. Sightglass
TK 61377-18-MM-EN 79
Refrigeration Service Operations
Figure 31. Condenser Components Model MAX 50 Spectrum with Bypass Valve
80 TK 61377-18-MM-EN
Refrigeration Service Operations
3. Evaporator Coil
TK 61377-18-MM-EN 81
Refrigeration Service Operations
82 TK 61377-18-MM-EN
Refrigeration Service Operations
5. Keep the compressor ports and the suction and discharge lines for the compressor covered to prevent
contamination of system components.
6. Remove the compressor mounting screws and remove the compressor.
Installation
N o t e : Any compressor installed in this system must contain 4 oz. (118 ml) of POE 120 compressor oil. Always check to
make sure that the compressor contains the proper amount and type of oil. Follow the system cleanup
procedures to remove old oil from the system.
1. Place the compressor in position and install the mounting screws and the belt.
2. Adjust the belt tension to the vehicle manufacturer specifications.
3. Connect clutch and liquid injection switch wires, and the refrigeration hoses. Pour the correct amount of oil for the
unit (see Specifications chapter) into the suction hose before installation.
4. Pressurize the system and test for leaks.
5. Evacuate the system and recharge.
Installation
N o t e : Any compressor installed in this system must contain 4 oz. (118 ml) of POE 120 compressor oil. Always check to
make sure that the compressor contains the proper amount and type of oil. Follow the system cleanup
procedures to remove old oil from the system.
1. Place the compressor in position and install the mounting bolts and the belt.
2. Adjust the belt to the proper tension (see Specifications).
3. Connect the discharge and suction tubes.
4. Connect the compressor clutch wires.
5. Reinstall the transformer (if removed).
6. Pressurize the system and test for leaks.
7. Reinstall the condenser cover.
8. Evacuate the system and recharge.
Condenser Coil
Removal
1. Recover the refrigerant charge.
2. Remove the condenser cover and fan shroud.
3. Remove the bridge rectifier.
4. Unsolder the inlet and liquid lines.
TK 61377-18-MM-EN 83
Refrigeration Service Operations
Installation
1. Clean the tubes for soldering.
2. Place the coil in the unit and rivet the coil in place using 12 TK specified rivets (see the appropriate Parts Manual).
3. Solder the inlet and liquid line connections.
4. Pressurize the system and test for leaks.
5. Evacuate the system.
6. Reinstall the bridge rectifier.
7. Reinstall the fan shroud and condenser cover.
8. Recharge the unit with the proper refrigerant.
Drier
Removal
1. Recover the refrigerant charge.
2. Remove the condenser cover.
3. Disconnect the ORS nuts at the end of the drier and sight glass.
4. Loosen the mounting hardware and remove the drier and sight glass.
5. Separate the drier and sight glass.
Installation
1. Coat the new O-rings with refrigerant oil (same type that is used in the system) and place the new O-rings in the
ORS fittings on the ends of the drier.
2. Install the sight glass on the outlet end of the drier.
3. Install the new drier and tighten the mounting band.
4. Install and tighten the ORS nuts. Hold the drier with a back-up wrench on the hex behind the ORS fitting.
5. Pressurize the system and test for leaks.
6. Evacuate the system.
7. Reinstall the condenser cover.
8. Recharge the unit with the proper refrigerant.
Installation
1. Install and tighten the transducer and reconnect the wires.
2. Pressurize the system and test for leaks.
3. Install the condenser .
84 TK 61377-18-MM-EN
Refrigeration Service Operations
Removal
1. Recover the refrigerant charge.
2. Remove covers as necessary to access the solenoid valve.
3. Remove the coil and disassemble the valve if unsoldering the valve.
TK 61377-18-MM-EN 85
Refrigeration Service Operations
4. Unsolder or disconnect the refrigeration lines from the valve, and remove the valve from the unit. Note the direction
of the flow arrow on the valve.
NOTICE
Equipment Damage!
Use a heat sink to prevent damaging the valve when soldering.
Installation
1. Clean the tubes for soldering if necessary.
2. Remove the coil and disassemble the valve if soldering.
3. Place the valve in position with the flow arrow pointing in the direction noted when removed.
4. Solder or connect the inlet and outlet connections. After the valve cools, assemble the valve and install the coil.
NOTICE
Equipment Damage!
Use a heat sink to prevent damaging the valve when soldering.
Oil Separator
The oil separator must be replaced if a compressor has failed and is being replaced. Also check the oil return line to
make sure it is not plugged by blowing air through it when replacing the oil separator.
Removal
1. Recover the refrigerant charge.
2. Remove the condenser cover / grille.
3. Disconnect the ORS nuts at the ends of the oil separator.
4. Loosen the mounting hardware and remove the oil separator.
Installation
1. Coat the new O-rings with refrigerant oil (same type that is used in the system) and place the new O-rings in the
ORS fittings on the ends of the oil separator.
2. Install and tighten the inlet and outlet ORS nuts. Hold the oil separator with a backup wrench on the hex behind the
ORS fitting.
3. Pressurize the system and check for leaks.
4. Evacuate the system.
5. Reinstall the condenser cover / grille.
6. Recharge the unit with the proper refrigerant.
Splice Fitting
The splice fitting is used on all units except the Model 20 units with R-134a. It is mounted in the suction line near the
engine driven compressor and has two 1/4 SAE flare access fittings. The liquid injection metering orifice and the liquid
injection line from the liquid injection solenoid are attached to one of the access fittings on MAX units. The oil return
line from the oil separator is attached to the other access fitting on Model 10 and Model 30 units.
I m p o r t a n t : Make sure that a liquid injection metering orifice is installed on the fitting to which the liquid injection line is
attached, and that a metering orifice is not installed on the fitting to which the oil return line is attached.
86 TK 61377-18-MM-EN
Refrigeration Service Operations
Installation
1. Coat the new O-rings with refrigerant oil (same type that is used in the system) and place the new O-rings in
position.
2. Place the check valve in position.
3. Connect the discharge line from engine driven compressor to the check valve assembly.
4. Connect the oil separator to the check valve assembly.
5. Connect the check valve assembly to the standby compressor outlet.
6. Pressurize the system and test for leaks.
7. Reinstall the condenser cover.
TK 61377-18-MM-EN 87
Refrigeration Service Operations
Checking Superheat
1. Examine and/or clean the evaporator and condenser coils.
2. Attach an accurate compound gauge to the suction access port nearest to where the equalizer line is connected to
the suction line. See the drawing below, which shows a typical evaporator.
3. Attach an accurate thermometer sensor to the suction line beside the suction access port. Secure it and insulate it
well.
Figure 34. Checking Superheat
1. Equalizer Line
88 TK 61377-18-MM-EN
Refrigeration Service Operations
9. The superheat should be between 6 °F (-3 °C) and 12 °F (-7 °C) at 0 °F (-18 °C) box temperature.
Calculate superheat according to the sample below for R-134a.
2 2 ° F ( - 6 ° C ) = Suction Line Temperature
1 2 p s i g ( 8 3 k P a ) = Suction Line Pressure
Convert equalizer line pressure to temperature using a pressure/temperature chart. F o r R - 1 3 4 a 1 2 p s i g ( 8 3 k P a ) =
10 °F (-12 °C)
Superheat = 22 °F - 10 °F = 12 °F
Superheat = -6 °C - (-12 °C) = 6 °C
TK 61377-18-MM-EN 89
Refrigeration Service Operations
Installation
1. Install and tighten the switch and reconnect the wires.
2. Pressurize the refrigeration system and test for leaks.
3. If no leaks are found, evacuate the system.
4. Connect the evaporator fan motor wires and install the evaporator cover.
5. Recharge the unit with the proper refrigerant.
90 TK 61377-18-MM-EN
Refrigeration Service Operations
5. Start the unit and run it in Defrost on the electric standby compressor until the pressure on the additional compound
gauge attached to the suction service port stabilizes at a pressure above 45 psig (310 kPa).
6. Remove the gauge manifold set, the additional compound gauge, and the jumper wire when finished with the test.
Installation
1. Clean the tubes for soldering.
2. Place the valve in position and solder the connections.
3. Pressurize the refrigeration system and test for leaks.
4. If no leaks are found, evacuate the system.
5. Recharge the unit with the proper refrigerant.
Installation
1. Clean the tubes for soldering.
2. Place the accumulator in position and solder the connections.
3. Install the mounting hardware.
4. Pressurize the system and test for leaks.
5. Evacuate and recharge the system.
TK 61377-18-MM-EN 91
Refrigeration Service Operations
Installation
1. Place the check valve assembly in position and install the nut that fastens it to the accumulator module frame.
2. Coat the new O-rings with refrigerant oil (same type that is used in the system) and place the new O-rings in the
ORS fittings for the ends of the check valve assembly.
3. Install and tighten the inlet and outlet ORS nuts. Hold the tubes with a backup wrench on the hex behind the ORS
fitting.
4. Pressurize the system and test for leaks.
5. Reinstall the accumulator module cover and the evaporator cover.
6. Evacuate and recharge the system.
92 TK 61377-18-MM-EN
Compressor Maintenance
Compressor Failures
Whenever a compressor fails check the compressor speed to verify it is within our guidelines. If the compressor speed
exceeds guidelines, a larger pulley needs to be install on the compressor. See Service Bulletin SB644 and the Vehicle
Powered Truck Installation Standards and Procedures Section 5 – Compressor Selection and Installation Standards for
detailed information.
Compressor Test
1. Rotate the compressor shaft by hand. It should rotate smoothly without catching or binding. If not, replace the
compressor.
Figure 37. Rotate Compressor Shaft
2. Spin the pulley with the clutch de-energized. The pulley should spin freely with no wobbling or roughness. If not, it
should be replaced.
3. Check the clutch air gap. It should be 0.016-0.03 inches (0.4-0.8 mm). The clutch might not engage if the air gap is
excessive. See Setting Clutch Air Gap later in this chapter for details.
4. Check the clutch coil resistance. See the Specifications chapter for the coil resistance.
5. Check for voltage between the CLU (or CLU1 depending on your unit) wire at the compressor clutch and the
compressor body when the unit is in Cool and the compressor should be running. A minimum of 11.5 Vdc should be
present. If not, check the CLU circuit back to the ECM and fuse F5. Also check that there is good continuity between
the compressor body and the chassis ground (CH).
N o t e : The engine driven compressor must be equipped with a ground strap when installed. Refer to Ground Strap
Installation in Section 5 – Compressor Selection and Installation Standards of the Vehicle Powered Truck
Installation Standards and Procedures TK 56430 for detailed information about the ground strap.
6. Check the compressor discharge pressure. A good compressor should be able to raise the discharge pressure to 200
psig (1379 kPa) for R-134a, or 350 psig (2413 kPa) for R-404A/R-452A, with the condenser covered.
I m p o r t a n t : This test must be performed with a full system charge. Confirm the system is fully charged before
proceeding.
a. Install a gauge manifold set on the compressor being tested.
b. Set thermostat on the lowest setting.
c. Start and run the unit in Cool with the compressor being tested.
d. Cover the condenser to raise the discharge pressure.
e. A good compressor should be able to raise the discharge pressure to the following:
• R-134a: 200 psig (1379 kPa)
• R-404A/R-452A: 350 psig (2413 kPa)
TK 61377-18-MM-EN 93
Compressor Maintenance
I m p o r t a n t : This test should only be run for a short time. Shut the system down immediately once the target
pressure is reached.
Belt Tensions
Engine Driven Compressor Belt and Pulleys
Correct pulley alignment and proper belt tension are very important factors in compressor installation. The compressor
clutch must be perfectly aligned with the engine pulley and any auxiliary idler or belt adjustment pulley components.
Check the pulley and belt alignment by referring to “Belt Alignment” in Section 5 of the Vehicle Powered Truck
Installation Standards and Procedures- TK 61588. Double check by making sure the belt goes from pulley to pulley in
perfect alignment with no indication of a sideward bend.
Adjust the belt tension to vehicle manufacturer specifications. Check the belt tension again after 36 to 48 hours of initial
operation of the unit because the belt may stretch slightly during the first hours of use. Remember, good alignment and
proper belt tension ensure long belt life
94 TK 61377-18-MM-EN
Structural Maintenance
Micro-Channel Coil Cleaning Recommendations
Cleaning Intervals
• The coils should be cleaned a Minimum of once a year.
• It is recommended that any time the unit is in for service or maintenance that the coils be inspected and cleaned if
needed.
• The coil should be cleaned if there are visible accumulations that obstruct the view of the fins or tubes of the coil.
• The coils should be cleaned if there is debris imbedded in the tubes and fins.
The area and conditions in which the unit operates will dictate the cleaning intervals and method(s) needed.
Cleaning Methods
N o t e : Listed in order of recommended method.
• Take a cloth or towel and wipe the air side of the coil going with the fins, across the tubes. See (Figure 39, p. 97) for
results. The coil will clean in a manner similar to the way lint cleans from the lint trap of a household clothes dryer.
• Use a soft bristled brush (DO NOT USE A WIRE BRUSH) and brush the coil going with the fins, across the tubes. The
coil will clean in a manner similar to the way lint cleans from the lint trap of a household clothes dryer.
• A vacuum with a soft attachment can be used to suck the debris off the face as well as in the fins and tubes from the
air side of the coil.
• Compressed air can be used and will work best when blown thru the coil from the non-air side when possible.
Blowing thru from the airside may imbed debris in the coil that was only on the surface. It is recommended to start
with one of the first three options before using compressed air if the non-air side is not accessible. The angle at
which the air should be directed at the coil should not be less than 75 degrees (Figure 40, p. 97).
• Power water sprayer may be used in pressures under 600 psi. Water will work best when blown thru the coil from
the non-air side when possible. Spraying thru from the airside may imbed debris in the coil that was only on the
surface. It is recommended to start with one of the first three options before using water if the non-air side is not
accessible. The angle at which the water should be directed at the coil should not be less than 75 degrees (Figure
40, p. 97).
TK 61377-18-MM-EN 95
Structural Maintenance
Notes:
1. Chemicals to aid in cleaning WILL VOID WARRANTY and are NOT RECOMMENDED.
2. In some instances, it may take a combination of two methods to result in a clean coil. Such as, first wiping
the coil to clean the surface and then using a vacuum, water or compressed air to clean down in the fins. This
will depend on the type of debris that needs to be cleaned from the coil.
3. Do not allow the coil to come into contact with any hard vacuum nozzle, air nozzle, or any other tool. This will
damage the tubes of the coil.
4. The use of cleaning agents or detergents is strongly discouraged due to the possibility of degradation of the
construction. If using a power washer, the nozzle pressure should not exceed 600 psi (41 bar). For the best
results, spray the coil perpendicular to the face of the coil. The spray nozzle should be kept between 1 inch
and 3 inches (25 to 75 millimetres) from the coil surface.
5. If necessary to use a chemical cleaner or detergent use a cleaner that does not contain any hydrofluoric acids
and is between 7 and 8 on the pH scale. Ensure dilution instructions provided by the detergent supplier are
followed. In case of doubt about the compatibility of the detergent with the type of materials listed above,
always ask the supplier for a written confirmation of the compatibility. Should a chemical cleaner be
required, it is MANDATORY that all components are thoroughly rinsed with water even if the instructions of
the cleaner specify that it is a “no rinse” cleaner.
NOTICE
Equipment Damage!
Failure to comply with above mentioned guidelines will lead to a shortened life of the equipment to an
indeterminable degree.
6. The repeated transportation of meat and fish waste can cause extensive corrosion to the evaporator coils
and evaporator section tubing over time due to ammonia formation and can reduce the lifespan of the coils.
Appropriate additional measures should be taken to protect the coils against the aggressive corrosion that
can result from transportation of such products.
Figure 38. Coil Before Cleaning
96 TK 61377-18-MM-EN
Structural Maintenance
Figure 39. Coil after Wiping Right Hand Side with Cloth
TK 61377-18-MM-EN 97
Structural Maintenance
98 TK 61377-18-MM-EN
Structural Maintenance
TK 61377-18-MM-EN 99
Over-the-Road Mechanical Diagnosis
CONDITION POSSIBLE CAUSE REMEDY
Unit turned On—In-Cab Control Box Vehicle ignition switch is not on Turn the vehicle ignition switch on
display does not come on
Vehicle Ignition Switch Fuse F14 blown Check for short circuits and replace fuse
In-Cab Control Box harness disconnected Check In-Cab Control Box harness and repair or
or faulty replace
Unit turned On—In-Cab Control Box Battery Power Supply Fuse F21 blown Check for short circuits and replace fuse
display comes on but unit does not
operate Battery Power Relay (BPR) faulty Check BPR
100 TK 61377-18-MM-EN
Electric Standby Mechanical Diagnosis
CONDITION POSSIBLE CAUSE REMEDY
Unit turned On—In-Cab Control Box Unit not connected to Standby power or Connect power cord. Verify that the Electric Standby
display does not come on Standby power is turned off. power is turned on and is the correct voltage.
Transformer AC Power Supply Fuse F20 Check for short circuits and replace fuse
blown
Controller Standby Power Supply Fuse Check for short circuits and replace fuse
F16 blown
In-Cab Control Box harness disconnected Check In-Cab Control Box harness and repair or
or faulty replace
Unit turned On—In-Cab Control Box No standby power to compressor motor Provide power to unit; check power at:
display comes on but compressor 1. Motor contactor hot side
motor does not run 2. Motor contactor load side (contactor closed)
3. Overload relay
4. Motor terminals
Open or faulty overload relay Determine cause and reset or replace overload relay
Compressor motor hums but does not Locked rotor (overload relay will open Remove interference or replace motor
run after a period of time)
Low line voltage or no voltage on one leg Check power source for correct voltage, phase, and
frequency. Bring voltage up to within 10% of motor
rating
Compressor motor runs but Electric standby compressor belt loose Check belt tension
compressor does not
Compressor clutch faulty Check compressor clutch
TK 61377-18-MM-EN 101
Refrigeration Diagnosis
CONDITION POSSIBLE CAUSE REMEDY
Unit short cycles Shortage of refrigerant (low pressure Repair leak and recharge
cutout)
Cycling on high discharge pressure Check condenser air flow and fan
Defrost timer set too low for application. Adjust timer to higher interval
Unit operates long or continuously Shortage of refrigerant Repair leak and recharge
Too many door openings Keep doors closed, install plastic curtains
Box temperature too high Thermostat setpoint too high Reset thermostat
Head pressure too low Refrigerant shortage Repair leak and recharge
102 TK 61377-18-MM-EN
Refrigeration Diagnosis
Frosted or sweating suction line Expansion valve set too low, admitting Adjust expansion valve
excess refrigerant
Condenser coil is cool when unit is in Refrigerant undercharge Repair leak and recharge
cool operation
Compressor inefficient Replace compressor
Unit in vacuum, frost on expansion Ice plugging expansion valve orifice Apply hot wet cloth to expansion valve. Moisture
valve only indicated by increase in suction pressure. Replace
drier
TK 61377-18-MM-EN 103
Refrigeration Diagnosis Chart
Unit Not Heating (Model 30/50)
SYMPTOM
High suction pressure
No suction pressure
POSSIBLE CAUSES
• • • • Overcharge of refrigerant
• • • • • • • Shortage of refrigerant
• • • • • • • • No refrigerant
• • • • Restricted dehydrator
104 TK 61377-18-MM-EN
Unit Not Heating (Model 30/50)
Refrigeration Diagnosis Chart
SYMPTOM
High suction pressure
No suction pressure
POSSIBLE CAUSES
TK 61377-18-MM-EN 105
Diagram Index
The following table lists the diagrams that are relevant to this unit.
The diagrams are available on EMEA Info Central.
2E28292 V-500/V-600 MAX Single Temperature and V-500 DSPECTRUM DSR-III unit Wiring Diagram
2E28293 V-500/V-600 MAX Single Temperature and V-500 SPECTRUM DSR-III unit Schematic Diagram
106 TK 61377-18-MM-EN
Notes
TK 61377-18-MM-EN 107
Thermo King – by Trane Technologies (NYSE: TT), a global climate innovator – is a worldwide leader in sustainable
transport temperature control solutions. Thermo King has been providing transport temperature control solutions
for a variety of applications, including trailers, truck bodies, buses, air, shipboard containers and railway cars since
1938. For more information, visit www.thermoking.com or www.tranetechnologies.com.
Thermo King has a policy of continuous product and product data improvements and reserves the right to change design and specifications
without notice. We are committed to using environmentally conscious print practices.