MODULE-3 Single Phase Transformers NOTES
MODULE-3 Single Phase Transformers NOTES
Surat Pyari
MODULE – 3
Prepared
Transformer
Where:
VP – is the Primary Voltage
This means in this example, that if there are 3 volts on the primary winding there will be 1
volt on the secondary winding, 3 volts-to-1 volt. Then we can see that if the ratio between the
number of turns changes the resulting voltages must also change by the same ratio, and this is
true.
Transformers are all about “ratios”. The ratio of the primary to the secondary, the ratio of the
input to the output, and the turns ratio of any given transformer will be the same as its
voltage ratio. In other words for a transformer: “turns ratio = voltage ratio”. The actual
number of turns of wire on any winding is generally not important, just the turns ratio and
this relationship is given as:
A Transformers Turns Ratio
The laminations of the core type transformer are of U-I shape as shown in the figure.
The core of the shell type transformer is made up either U-T shape or E-I shape (see the
figure).
https://www.youtube.com/watch?v=H2hYUu8lPY0
As the magnetic lines of flux flow around the core, it passes through the secondary winding,
inducing voltage across it. The Faraday’s Law is used to determine the voltage induced
across the secondary coil and it is given by:
N. dɸ/dt
where,
‘N’ is the number of coil turns
The frequency is the same in primary and secondary windings.
Thus, we can say that the voltage induced is the same in both the windings as the same
magnetic flux links both the coils together. Also, the total voltage induced is directly
proportional to the number of turns in the coil.
Where
KȠ is a proportionality constant which depends upon the volume and quality of the material
of the core used in the transformer,
f is the supply frequency,
Bmax is the maximum or peak value of the flux density.
The iron or core losses can be minimized by using silicon steel material for the construction
of the core of the transformer.
Where,
Ke – coefficient of eddy current. Its value depends upon the nature of magnetic material like
volume and resistivity of core material, the thickness of laminations
These losses varied according to the load and known hence it is also known as variable
losses. Copper losses vary as the square of the load current.
Transformer Efficiency:
The Efficiency of the transformer is defined as the ratio of useful output power to the input power.
The input and output power are measured in the same unit. Its unit is either in Watts (W) or
KW. Transformer efficiency is denoted by Ƞ.
Where,
V2 – Secondary terminal voltage
I2 – Full load secondary current
Cosϕ2 – power factor of the load
Pi – Iron losses = hysteresis losses + eddy current losses
Pc – Full load copper losses = I22Res
Consider, the x is the fraction of the full load. The efficiency of the transformer regarding x is
expressed as
The efficiency of the transformer along with the load and the power factor is expressed by the given
relation:
The value of the terminal voltage V2 is approximately constant. Thus, for a given power factor the
Transformer efficiency depends upon the load current I2. In equation (1), the numerator is constant
and the transformer efficiency will be maximum if the denominator with respect to the variable I2 is
equated to zero.
Thus, the transformer will give the maximum efficiency when their copper loss is equal to the iron
loss.
From equation (2) the value of output current I2 at which the transformer efficiency will be maximum
is given as
If x is the fraction of full load KVA at which the efficiency of the transformer is maximum then,
Copper losses = x2Pc (where Pc is the full load copper losses)
Iron losses = Pi
For maximum efficiency
x2 Pc = Pi
Therefore
Thus, output KVA corresponding to maximum efficiency
Putting the value of x from the above equation (3) in equation (4) we will get,
The above equation (5) is the maximum efficiency condition of the transformer.