Ps7 SMC en-US en-US
Ps7 SMC en-US en-US
Preface 2
Basics 3
SIMATIC
Installation of the
Management Console 4
Process Control System PCS 7
SIMATIC Management Console
Operator control 5
(V9.1)
Menus and dialog boxes 6
Operating Manual
02/2021
A5E50318373-AA
Legal information
Warning notice system
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent damage
to property. The notices referring to your personal safety are highlighted in the manual by a safety alert symbol, notices
referring only to property damage have no safety alert symbol. These notices shown below are graded according to
the degree of danger.
DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.
WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.
CAUTION
indicates that minor personal injury can result if proper precautions are not taken.
NOTICE
indicates that property damage can result if proper precautions are not taken.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will be
used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to property
damage.
Qualified Personnel
The product/system described in this documentation may be operated only by personnel qualified for the specific
task in accordance with the relevant documentation, in particular its warning notices and safety instructions.
Qualified personnel are those who, based on their training and experience, are capable of identifying risks and
avoiding potential hazards when working with these products/systems.
Proper use of Siemens products
Note the following:
WARNING
Siemens products may only be used for the applications described in the catalog and in the relevant technical
documentation. If products and components from other manufacturers are used, these must be recommended or
approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance
are required to ensure that the products operate safely and without any problems. The permissible ambient
conditions must be complied with. The information in the relevant documentation must be observed.
Trademarks
All names identified by ® are registered trademarks of Siemens AG. The remaining trademarks in this publication may
be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software described.
Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the information in this
publication is reviewed regularly and any necessary corrections are included in subsequent editions.
1 Security information.............................................................................................................................. 7
2 Preface ................................................................................................................................................... 9
3 Basics ................................................................................................................................................... 17
3.1 Functions of the Management Console .............................................................................. 17
3.2 Description of the functions ............................................................................................... 18
3.2.1 Functions for software administration ................................................................................ 18
3.2.2 Functions for determining inventory data ........................................................................... 19
4 Installation of the Management Console ............................................................................................ 23
4.1 Managing rights ................................................................................................................ 23
4.2 Installing the Management Console ................................................................................... 26
4.3 Installing SIMATIC Management Agent ............................................................................... 28
4.4 Installing the SIMATIC Management Agent over remote desktop connection ....................... 30
4.5 Communication using different subnets ............................................................................. 31
4.6 Licensing ........................................................................................................................... 33
4.7 Relocate the Management Console in the network ............................................................. 34
4.8 Removing the Management Console .................................................................................. 35
5 Operator control .................................................................................................................................. 37
5.1 Starting the Management Console ..................................................................................... 37
5.2 Layout of the user interface................................................................................................ 38
5.2.1 Title bar ............................................................................................................................. 40
5.2.2 Menu bar........................................................................................................................... 40
5.2.3 Toolbar .............................................................................................................................. 41
5.2.4 Project view ....................................................................................................................... 42
5.2.4.1 Network view .................................................................................................................... 42
5.2.4.2 Symbols in the network view.............................................................................................. 44
5.2.4.3 Plant view.......................................................................................................................... 46
5.2.4.4 Symbols in the plant view .................................................................................................. 47
5.2.5 Details areas in the network view ....................................................................................... 47
5.2.5.1 "Details area" overview in the network view........................................................................ 47
5.2.5.2 "Installed SIMATIC software" tab ......................................................................................... 48
5.2.5.3 "Inventory data" tab ........................................................................................................... 49
5.2.5.4 "License keys" tab............................................................................................................... 49
5.2.5.5 "Device status" tab ............................................................................................................. 50
5.2.6 Details area in the plant view ............................................................................................. 53
5.2.6.1 "Details area" overview in the plant view ............................................................................ 53
5.2.6.2 "Inventory data" tab ........................................................................................................... 53
5.2.7 Status bar .......................................................................................................................... 54
5.2.8 Messages and events ......................................................................................................... 55
3ODQWEXV
6ZLWFKHV
$XWRPDWLRQV\VWHP
)LHOGEXV
'LVWULEXWHG,2
ILHOGGHYLFHV
• PUD Manager
The "PUD Manager" is an innovative tool to access documentation, comes with PCS 7
software. Some of the highlights:
– Create your own Manual Collection.
– Customize the documentation set according to your needs.
– Efficient search engine to access your information.
To install the PUD Manager and integrate the documents, refer to Siemens Industry Support
(https://support.industry.siemens.com/cs/ww/en/view/109748882).
Note
Updating the software and the "SIMATIC Management Agent" service
The software update using the Management Console cannot be performed for some software
packages of PCS 7. The following software packages can only be distributed as new installations
with the SIMATIC Management Console:
• Process Historian
• Information Server
• OpenPCS 7
(Update of the "SIMATIC Management Agent" service is available only for the versions
ranging from 8.1 - 9.0.x).
• Web Option for OS
(Web Client or Web Diagnostic Client: Updating the "SIMATIC Management Agent" service is
available only for the versions ranging from 8.1 - 9.0.x).
• Safety Matrix
(To upgrade the Safety Matrix of the "SIMATIC Management Agent" service, user must
uninstall the existing Safety Matrix in the target station and install the latest version available
manually).
You can find additional information on this in the following sections:
• Section "Downward compatibility with the agents (Page 75)"
• Section "Update or repair SMAgent (Page 64)"
Version Changes
As of V9.1 • Microsoft software update
The Management Console remotely controls the deployment of Microsoft software updates from WSUS to
WUA on each target computer using the SIMATIC Management Agent.
• Windows Defender signature version and events
The Management Console displays all the events logged in by the Windows Defender in the Events window.
Critical events are displayed in the Alarms window as well. Also, inventory information of Virus protection
now covers the Signature version of Windows Defender.
• Downward compatibility with the Agents
The Management Console supports communication with agents of versions 9.0 and above. This avoids the
necessity to perform an update of all agents before an updated Management Console can be used with
already installed PCS 7 computers of an older version.
• Software integrity check for PCS 7
The Management Console verifies the integrity of the software to be installed as part of the remote software
deployment.
• Supported Operating system
The Management Console V9.1 supports the following operating systems:
Windows 10 Enterprise 2019 LTSC
Windows Server 2019 Standard edition 64 bit
Windows Server 2019 Data Center edition 64 bit (SIVaaS only)
• SIMATIC Hardware Compare
The Management Console can compare the versions of the installed hardware and the corresponding firm‐
ware with the latest versions available, and generate a detailed MS Excel report that displays the difference
in the versions.
As of V9.0 • Web server Settings
SP1 The Management Console can install or update software on a target computer on which web server is in
runtime.
• Plant Inventory online data
The inventory details determined from device data is displayed in a separate column as online data under
"Inventory" tab in the Plant view.
• Export inventory details
The inventory details of plant and network objects are exported automatically.
The folder location to save the exported inventory details can also be configured in the "Inventory Data Export"
tab in the "Settings" dialog.
• SIMATIC Software compare
The Management Console can now compare the versions of installed software with the latest version of
software. The Comparison of SIMATIC software excel sheet displays the difference in the version and the
product links to download the respective software.
• Project inventory data export in iBase format
The Inventory data exported for a project is generated in iBase format.
As of V9.0 • The online inventory details can be determined for field devices also.
Update 2
Version Changes
As of V9.0 • The inventory data for I/O modules now includes information about the slot position of the module in the
Update 1 rack.
As of V9.0 • Inventory data for ET200SP HA devices
The SIMATIC Management Console gathers additional inventory data for ET200SP HA devices that is available
through PROFINET. This includes device information that is not configured or visible in PCS 7 hardware
engineering (HW Config). Other devices connected to a PCS 7 system through PROFINET provide additional
hardware information which the SIMATIC Management Console is able to display as part of the plant hier‐
archy and inventory reports.
• Include manually entered inventory data for external components in inventory report.
• The inventory provides the build number of the installed Windows version. This is due to a change in MS
upgrade philosophy starting from Windows 10. Feature updates (former patches) will no longer be reflected
in versions but only shown as a difference in the build number.
• Additional to the tape the following data on the hard disk will be displayed:
– Manufacturer
– Name
– Form factor
– Capacity
– Driver version
– Driver date
• The details of the installed third-party software will be extended with:
– SQL server
– Installed version of Microsoft .NET Framework with version number
– Microsoft patches with Product name, Publisher, Title, KB and installation date.
– Installed security software with manufacturer, product, version (Symantec Endpoint Protection, McAfee
Agent, McAfee Endpoint Protection Suite, Trend Micro OfficeScan Corporate Edition V11.0).
• The inventory report has been extended to include the following information:
– Number of Process Objects used in the ES project. This information will be available as part of a new entry
"Project" under the ES in the Plant View.
• The SIMATIC Management Console can also be started without a license. In this case all the computers can
only be assigned to a single group called "Non-licensed computers". The only functions available in this group
are Determine Inventory Data, Export Inventory Data and Update SMAgent.
• In case SMAgent licenses on the SIMATIC Management Console are not sufficient to assign further computers
to user defined groups, computers can still be assigned to the "Non-licensed computers".
• Export maintenance data to an XML file using "Project inventory data export..." feature.
• System ID (SID) included in the inventory data.
• The availability of a target computer is not checked for database functions like "Project inventory data ex‐
port..." or "Apply Inventory Data Profile" in case data for the target computer is available in the database.
• The alarm message system is improved as follows:
– Dedicated message texts differentiate between online and offline determination of inventory data (plant
view).
Version Changes
As of V8.2 • Structure of the plant
– In a Windows domain, the best security level is possible through Kerberos authentication of the frames
between the Management Console and computers with installed SIMATIC Management Agent.
– The frames to establish a connection between the Management Console and managed computers with
installed SIMATIC Management Agent are protected by a Pre-Shared Key (PSK = shared network key).
• Conditions for installation and application of the Management Console
The installation and application of the Management Console is released when the following requirements are
met on the computers with installed SIMATIC Management Agent (Management Console and managed
computers):
– The operating system has been approved for this PCS 7 version. You can find additional information on this
in the Process Control System PCS 7; PCS 7 Readme documentation.
– PCS 7 Version at least PCS 7 V8.0 and higher with the latest released service pack
• Installation of software PCS 7 V8.0 and higher with the latest released service pack
The following software has been released for installation with the Management Console software:
PCS 7 V8.0 and higher with the latest released service pack.
The functionality of the Management Console cannot be used on computers that are operated with Windows
XP or Windows Server 2003.
• Rights management
The Management Console supports the addition of (domain) user groups in the local user groups.
• Setup packages
The content of the setup packages is apparent.
• You can find a list of all products and PCS 7 components that can be installed using the Management Console
in the Industry Online Support under entry ID 107796665: Internet link (http://
support.industry.siemens.com/cs/ww/en/view/107796665)
As of V8.1 • The operating states on the PC stations are determined and displayed for the following PCS 7 products before
the installation of software packages: Operator Station (PCS 7 OS); SIMATIC BATCH; SIMATIC Route Control
• Inventory data profiles allow the comparison of actual device configurations with the target device configu‐
rations
• Ongoing installation procedures are displayed in a list, if the installation procedures were started using the
Management Console.
• Installation report for PCS 7 plants with installed PCS 7 version as of the DVD PCS 7 V8.0 SP2.
Requirement: The installation procedures were started using this Management Console.
Note
SIMATIC Management Console and the other computers present in the network can be remotely
accessed only to initiate and authenticate the installation of Management Agents in the
respective computers. Any other remote operation of the SIMATIC Management Console is not
supported.
Note
Installing and updating the Process Control System; SIMATIC PCS 7 software package
• Note the following in the section "Preface; Table 2-1 Overview of the most important
changes (Page 13)".
• The SIMATIC Management Console cannot be used to install or update SIMATIC softwares
in the computer(s) in which it is currently installed. For instance, the Engineering station
software has to be manually installed and updated using the Engineering station
software setup in the SIMATIC Management Console computer.
• Microsoft software updates can be installed in all the SIMATIC Management Agent
computers using the SIMATIC Management Console.
For additional information refer Installing and updating software-Overview (Page 76).
NOTICE
License terms and security instructions
If the license terms and security instructions are accepted when the setup files are created, the
terms and instructions must also be provided to all other persons who are also authorized to
install setup packages.
Recommendation:
Copy the contents to a file and notify the authorized persons of the contents.
Example
The following steps are required for the installation of SIMATIC software when using the
Management Console.
Executing setup
• The Management Console installs the software packages on assigned computers.
• The Management Console enables the simultaneous installation of SIMATIC software on
several computers.
Note
Process mode
Software must not be installed on operator control and monitoring stations that are in
process mode. We recommend that the following steps are performed for the stations in
question before installation:
• Exit process mode.
• Close the projects.
Additional information
• Section "Installing the Management Console (Page 26)"
• Section "Managing rights (Page 23)"
Note
Determine inventory data
The computers of the plant must be at least of the version PCS 7 V8.0.
Note the following in the section "Preface; Table 2-1 Overview of the most important changes
(Page 13)".
Objects
Inventory data can come from both objects in the plant (online data) and objects in project data
(offline data). Inventory data can be acquired for the following PCS 7 plant objects:
• Computer
• Network components (Ethernet switches)
• Automation system components
• Remote I/Os (including the I/O modules)
• Field devices
Inventory data
Inventory data can include the following information:
• Plant designation (depending on the designation system, e.g., HID / TAG)
• Geographical location (depending on the designation system, e.g., LID)
• Description (user-defined)
• Message (user-defined)
• Device name
• Device type
• Serial number
• Article number (e.g. Siemens: MLFB; order number)
• Hardware version
• Operating system version
• Firmware version
• Windows Defender Signature version
• Installed SIMATIC software
• License information (license keys for SIMATIC software)
• Third-party software installed with PCS 7 software media.
Additional information
• Section ""Inventory data" tab (Page 49)"
• Section "Determining inventory data in the network view (Page 97)"
Note
Changing Windows user management
• Computer has to be restarted if changes were made to the local Windows groups in the
Windows user management while operating the Management Console.
• Always make changes to the user groups for the target system computers as well. Changes
to the local Windows groups take effect once the program is restarted.
• The target system computer has to be restarted if changes were made on the target systems
in the "SIMATIC Management Users" group in Windows user management.
Note
SQL database can only be accessed by a Windows user logged in on the SIMATIC Management
Console computer. Also, the user must be a part of the SMMC Management Administrators and/
or SMMC Management Users group to be able to access the database.
Note
Determining inventory data in the plant view
Requirements on the engineering station and Maintenance Station:
• A member of the "SIMATIC Management Users" group must be logged onto the
engineering station.
This user must be a member of the "SIMATIC NET" group on the engineering station.
• If inventory data of switches is to be determined online, the following conditions must also
be fulfilled:
– The switches are configured on a Maintenance Station.
– The user logged onto the engineering station is a member of the "SIMATIC NET" group on
the Maintenance Station.
Note
Setting up permissions for users
Ensure that permissions are set up for the following users:
• Users of the Management Console
• The "SIMATIC Management Users" group on the target computer
Note
Recommendation for increased plant safety
The SMB signature is a function of the operating system. With SMB, communication can be
signed at the level of the package.
• To increase the security of your plant, "SMB-2 Signing" can be activated.
• Apply this setting according to the specifications of the operating system manufacturer.
Inadequate protection of the SIMATIC Management Console installation can have the result that
the SIMATIC Management Console installation and thus the managed documents could be
manipulated.
• Make sure that the user logged on to the local computer in Windows does not have
administrator rights.
• Make sure that only the administrator and no other users have write permission for the
directory in which SIMATIC Management Console is installed.
Additional information
For additional information on permissions and creating users in the online help of the operating
system, use keyword "Help and support".
Requirements
The following requirements must be met before using the Management Console:
• Operating system
The operating system installed on the computers has been released for SIMATIC PCS 7. For
additional information refer : "www.siemens.com/pcs7-documentation (http://
www.siemens.com/pcs7-documentation)".
• Permission
The user must have administrator rights to install the Management Console.
• Software
The software to be installed is available from one shared storage location (shared network
path, for example \\<Computer name>\<Shared name>). More information can be found on
the naming conventions and path information in the PCS 7 Readme - Online documentation.
Additional information
• Section "Starting the Management Console (Page 37)"
• Section "Managing rights (Page 23)"
• Section "Relocate the Management Console in the network (Page 34)"
• Section "Communication using different subnets (Page 31)"
Requirements
The following requirements must be met before using the Management Console:
• Operating system
The operating system installed on the computers has been released for SIMATIC PCS 7.
Additional information can be found on this in the PCS 7 documentation:
– Process Control System; SIMATIC PCS 7 in the PCS 7 Readme (online) on the Internet
• Permission
The user must have administrator rights to install the Management Console.
• Software
The software to be installed is available from one storage location (shared network path).
Note
Domain controller
The "SIMATIC Management Agent" service should not be installed on a domain controller.
You must install the "SIMATIC Management Agent" service on computers to be managed before
you can use the Management Console. You have the following installation options:
• Installation using the PCS 7 setup
Requirements: The operating system has been approved for this PCS 7 version of the setup.
• Installation from a data media.
The software package required for installation of the "SIMATIC Management Agent" is available
in the following directory- Additional_Products\SMA__Vx.x.
1. To install the "SIMATIC Management Agent" service, run the setup.exe file.
2. Follow the instructions in the subsequent dialogs.
Note
Starting the "SIMATIC Management Agent" service
• If the "SIMATIC Management Agent" service was not explicitly selected in the PCS 7 setup,
start the service on the respective computer for access.
• If the "SIMATIC Management Agent" service was explicitly selected in the PCS 7 setup or re-
installed separately, the service is activated on the respective computer.
• The status of the service does not change if the "SIMATIC Management Agent" service was
updated at a later time.
Note
Remote installation
Remote installation of the "SIMATIC Management Agent" service is only permitted if process
mode is disabled on the computers on which the service is to be installed.
The software for the installation of the "SIMATIC Management Agent" service is available from
one shared storage location (shared network path, for example, \\<Computer name>\<Shared
name>).
Procedure
The following steps can be carried out as an alternative to local installation of the "SIMATIC
Management Agent" service.
1. Set up release for the path at which the software for the installation of the "SIMATIC
Management Agent" service is to be run.
2. Open "mstsc" using the search box in the start menu.
The "remote desktop connection" is opened.
3. In the "Computer" input box, enter the computer name or the TCP/IP address of a target
computer on which the "SIMATIC Management Agent" is to be installed.
4. Click "Connect".
The remote desktop connection opens.
5. In the "User name" input box, enter the name of the administrator who has administrator
rights on the target computer.
6. Enter the password of the administrator in the "Password" input box.
7. Click "OK".
And start working remotely on the target computer in the network.
8. Open Windows Explorer.
9. In the command line, enter in UNC notation the share path on which the software package
is located (\\<Computer name>\<Share name>).
10.Navigate to the setup for the "SIMATIC Management Agent":
…\PCS7_Vxx\Additional_Products\SMA__Vx.x
For example:
\\<Computer name>\<Share name>\PCS7_Vxx\Additional_Products\SMA__Vx.x
11.Run setup.
The "SIMATIC Management Agent" software package is installed.
12.Close the remote desktop connection.
13.Repeat steps 4 to 13 for all other target computers.
Note
Network type: Domain or workgroup
The type of network in which the SIMATIC Management Consoles - computers and the
computers with installed SIMATIC Management Agent - are located must always be the same.
If the computers are located in different subnets, the communication settings of the local
Windows firewall and any existing external firewall are to be adjusted, if installed.
Configuration of the local Windows firewall
As standard, the local Windows firewall of a computer only enables the local subnet as
authorized area.
Change the "SIMATIC Management Agent" (SMAgent_32.exe) service for the computers in the
local firewall:
1. Open the settings of the Windows firewall.
2. Select the advanced settings.
3. Select "Inbound Rules" in the tree structure.
4. Select the "SIMATIC Management Agent" program and open the properties from the shortcut
menu.
5. Open the "Scope" tab.
6. In the "Remote IP Address" area, enable the setting "These IP addresses".
7. Enter the required subnet areas or fixed IP addresses.
Configuration of the external firewall
Make the following changes if both these statements apply:
• The computers are located in different subnets.
• The communication between the SIMATIC Management Console computer and the target
computer with installed SIMATIC Management Agent is protected by an external firewall.
When using an external firewall, add exceptions for the subnets in the settings of this firewall.
Add the following TCP and UDP ports:
• 7911
• 7912
If an external firewall or router which is used closes inactive connections then, ensure that
the update cycle time in SMMC is less than the timeout of the device to close inactive
connections.
Note
Automatic detection of computers is limited to the particular subnet in order to limit the
network load. Therefore, the computers that are not a part of the subnet must be manually
assigned to the SIMATIC Management Console by right-clicking on "Network" and choosing
the "Add computer" option.
Additional information
For additional information on the documentation Process Control System PCS 7; PCS 7 - PC
Configuration.
• Access to PC stations outside a subnet
• Using encrypted communication
4.6 Licensing
The SIMATIC Management Console is a product of PCS 7 that requires a license. SIMATIC
software checks the license for software use based on license keys. These license keys are the
technical representatives of the license.
Additional information
• Information on the number of used license keys is available in the section ""License keys" tab
(Page 49)".
• For additional information on licenses and license-dependent quantity structures of PCS 7 in
the documentation Process Control System PCS 7; Licenses and Quantity Structures.
• For additional information on the provision of license keys in the plant in the
documentation SIMATIC; Automation License Manager.
• Information on licensing models can be requested from Siemens contact person.
• When the SMA license key is not sufficient for all the assigned computers, a dialog is
displayed, where computers can be deselected to move from the network to the "Non-
licensed computers" folder.
• When SIMATIC Management Console license is not available or the trial license is no longer
valid, a dialog is displayed, where SIMATIC Management console can be opened with all the
assigned computers in the "Non-licensed computers" folder or cancel the opening process
from SIMATIC Management Console.
Note
Only one Management Console is permitted in the network
In a network, try to install only one Management Console. That way, computers that are to be
managed only report the information to a single Management Console computer.
Back up of the Management Console data can be saved in the database, and can be restored
whenever required.
Uninstall the following while executing the removal through the "Programs and Functions"
software management:
• SIMATIC Management Console
• SIMATIC Management Agent
Note
• Uninstalling the SIMATIC Management Agent is only possible through MS Windows
functions, which are available in the SEBU_SMA installation software(PCS 7 additional
products.)
• Uninstalling the software is necessary to convert the Management Console computer into a
managed computer.
• To convert the Management Console into a managed computer (Agent computer), the actual
Management Console is to be uninstalled using "Programs and features". Which will stop the
SIMATIC Management Agent services temporarily. The SIMATIC Management Agent services
are to be manually restarted through services.msc in the Agent computer, so that it can be
assigned to the new Management Console.
Logon
Authenticate with "user name" and "password" before working with the Management Console.
Enter the pre-shared key for the first application of the Management Console.
The pre-shared key should be changed at regular intervals. To do this, select the menu command
Options > Set pre-shared key... .
For additional information refer "Connecting (Page 68)".
Note
• The user must be a member of the local "SIMATIC Management Users" group.
• While logging in, always use the credentials assosciated with the environment in which the
Management Console is installed. In most cases, the environment would be "Domain". So,
the computer would be connected to the domain, and identification methods of domain will
be used to authenticate the account. In that case, use a Windows credential that is a member
of the domain to log into the application.
• If in case, the environment of the computer in which the Management Console is installed
has to be switched from Workgroup to Domain or vice-versa-
– Make sure to manually add all the users associated with the Management Console to the
"SIMATIC Management Users" and "SIMATIC Administrators" group for that particular
environment.
If not, the users won't be able to access the SIMATIC Management Console database and
therefore can't log in.
– Once done, restart the machine for the privileges to take effect.
To do so, drag a computer from the "Non-assigned computers" folder and drop it into the
"Network" folder in the network view.
Note
Representation of the computer with the Management Console in network view
• Management Console is active, only when the first computer is connected to the network.
• When at least one computer has been assigned to the Management Console, the computer
in which the Management Console is installed gets highlighted in bold.
If in case the authentication fails, and a connection could not be established with the
required computer, check-
• The correctness of the credentials entered.
• If the system clocks of the Management Console and the selected computer are
synchronized. Make sure that the time difference between the two systems are not more
than 4 minutes.
Additional information
• Section "Assigning computers (Page 58)"
• Section "Managing rights (Page 23)"
• Section "Language... (Page 135)"
Display
The plant objects are displayed in the project view on the left side of the Management Console
dialog box. The width of this area can be changed. Use the tabs to select how the plant objects
are displayed:
• Network view (Page 42): The network view shows the computers of the network in a tree
structure defined by the user.
Select the network view to perform the following with the Management Console:
– Determine the inventory data of computers
– Install software on target computers (remote installation)
• Plant view (Page 46): The plant view shows the objects of the PCS 7 projects in a tree
structure.
– Select the plant view to use the Management Console to determine the inventory data of
PCS 7 plants.
The right side of the dialog box contains the details area and "Messages" area.
• In the details area, select which information is to be displayed from the tabs. The information
displayed depends on the following conditions:
– The object selected in the project view
– The menu command (menu line, toolbar, shortcut menu)
Note
View when you reopen the Management Console
The Management Console always starts in the network view.
Sorting in tables
Additional information
Section ""Event display" dialog box (Page 56)"
Layout
Given below is an overview of the Management Console menus.
Menu Submenu
File • Back up data... (Page 127)
• Restore data... (Page 128)
• Exit (Page 128)
Edit • Create group (Page 129)
• Delete group (Page 129)
• Disable console assignment (Page 129)
• Update network view (Page 130)
View • Network view (Page 131)
• Plant view (Page 132)
• Event display... (Page 133)
• Running installations... (Page 133)
• SMAgent license display... (Page 134)
Menu Submenu
Options • Language... (Page 135)
• Set pre-shared key... (Page 135)
• Settings... (Page 136)
• Setup management... (Page 139)
• Project inventory data export... (Page 142)
• External components... (Page 142)
• Inventory data profile wizard... (Page 143)
• Create license report... (Page 144)
? (Help) • Available plug-ins... (Page 145) 1)
• Help (Page 145)
• Info... (Page 145)
1)
The plug-ins supplied with the Management Console cannot be installed or removed separately.
5.2.3 Toolbar
The toolbar is located below the menu bar. By clicking on a button, the menu command can be
invoked without having to open a menu.
Toolbar
Symbols
Meaning of the symbols:
Note
Following installation of the Management Console
The following objects are displayed in the network view following installation of the
Management Console:
• "Network" node
• "Non-licensed Computers" (computer which has no SMAgent license)
• "Non-assigned Computers" group (includes newly discovered computers in the same subnet
with installed and activated SIMATIC Management Agent service)
• Name of the computer with the local Management Console.
The following computers are displayed in the network view when the Management Console
opens:
• Computers with an activated SIMATIC Management Agent are detected automatically.
• Computers that have already been assigned to the Management Console. The computers are
shown regardless of their availability.
Object Meaning
Non-assigned computers 1)
The computer has been recognized by the Management Console.
Note:
To be able to use the functions of the Management Console, assign the
computer to the Management Console.
Non-licensed computers The following functions are used in this node:
• SMAgent Update
• Determine inventory data
• Export inventory data
Assigned computers 1)
The computer has been assigned to the Management Console.
Options:
• The computer communicates with the Management Console.
• The computer does not communicate with the Management Con‐
sole. Examples of such computers are:
– Computers which are switched off.
– Computers which have been excluded from the analysis for serv‐
icing purposes.
– Different pre-shared key between Management Console and
computers with installed SIMATIC Management Agent
Additional information is available in the section "How to change
the pre-shared key on a computer at a later time (Page 71)".
Groups with computers1) Every user of the Management Console can create groups and move
computers within the Management Console.
1)
See symbols in the network view
Information is displayed in the tabs in the details area when clicked on a SIMATIC PC station.
Note
For all other objects, no data is displayed (network nodes, groups, non-assigned or non-
accessible computers).
Additional information
• Section "Starting the Management Console (Page 37)"
• Section "Create group (Page 63)"
• Section "Network view (Page 131)"
Icon Meaning
Network folder
Computers located directly in the network folder are assigned to the local Management
Console.
Group
Computer
Not available The computer is assigned to the local Management Console but
is not available.
Action "running" Actions have been started for this computer. At least one action
has not yet been completed.
Action "successful" Actions started for this computer have been completed success‐
fully.
Action "running" - er‐ Actions have been started for this computer. At least one error
ror detected was detected during execution.
• Check the messages for computers with action errors.
Action "completed" - All actions are finished for this computer. At least one error was
error detected detected during execution.
• Check the messages for computers with
action errors.
Version mismatch The master Management Agent and the client Management
with compatibility Agent are of different versions, yet they are compatible. Man‐
agement Console will be able to communicate with the target
computer, but only for limited functionalities.
Version mismatch The computer is outdated, it must be updated to facilitate com‐
without compatibility munication between the computer and the Management Con‐
sole.
Refer "Updating the SMAgent" for more information.
Not ready for installa‐ The computer is not ready for installation.
tion For additional information refer "Computer is not ready for in‐
stallation (Page 123)"
Note
Following installation of the Management Console
The plant view only shows the "Plants" node.
Additional information
• Section "Starting the Management Console (Page 37)"
• Section "Plant view (Page 132)"
Icon Meaning
Attachment folder
Rack
SIMATIC station
SIMATIC H station
Network switch
External components
Note
Only the installation date of the software package is displayed and not the version details of the
software package.
The installation date of the software package is not modified due to the installation of an update
for the software package.
The column "Latest version" is displayed on the "Installed SIMATIC software" tab only when the
software versions are compared through "Compare SIMATIC software versions..." option. This
column lists the latest version of the installed software and the values in the "Latest version"
column is displayed only when there is a difference between the installed version and latest
version of the software.
If the software version is different from the version specified in the version definition file (XML),
then the installed software details are displayed in red. If the software version is same as the
version in the XML file, then the installed software details are displayed in black.
If SIMATIC software version comparison is applied for a network, group or a computer, the status
of the computer is displayed as "Comparison of SIMATIC software versions:<applied date and
time>" at the top of the tab.
If inventory details are determined for the network, the status is changed to "Inventory
determined: <date and time>"and the "Latest version" column is not displayed.
For more information on the SIMATIC software version comparison feature see, Comparing
SIMATIC software versions (Page 117).
Procedure
You can find additional information about this in the section "Determining inventory data in the
network view (Page 97)".
Procedure
For additional information refer "Inventory data in the network view (Page 97)".
Note
Detailed information on license keys
Detailed information on license keys can be obtained with the Automation License Manager.
The "Status" column only shows the following information for the respective license key:
• Installed
• Used
Details of the other columns can be found in the description for the Automation License
Manager.
Procedure
For additional information refer "Determining inventory data in the network view (Page 97)".
Requirements
• The computer is connected to the Management Console.
• The network view is opened, and a computer is selected.
Procedure
1. For additional information refer "Determining inventory data in the network view
(Page 97)".
Note
Update time
The information in the "Device status" tab is updated after the following events:
• After a computer in the network view is selected for the first time (change to another PC
or back)
• Automatically after expiration of the update time for devices (see paragraph "Setting the
update")
Setting the update
• The device status is automatically updated in the SIMATIC Management Console.
• Specify the cycle time for updating in the menu Options > Settings > "Update device
status" tab (Page 136).
Result
• Up-to-date information for available computers is shown in the details area.
• The latest status information is displayed for the selected computer in the "Device status" tab.
Status information
The status information contains computer-specific properties:
• Connection status
Shows the status of the connection to the Management Console:
– Connected
– Physically available
– Not available
• Action
Shows the status of the current action or the last action executed.
Examples:
– SIMATIC software installation running without errors since <date, time> ....
– SIMATIC software installation completed without errors <date, time> ....
• Agent Version
Shows the version of the "SIMATIC Management Agent" service installed on the computer.
• Role
Displays the configurations of the PC stations based on the installed software packages.
Examples:
– OS server
– OS client/engineering station
For additional information refer the Process Control System PCS 7; PCS 7 - PC Configuration
documentation.
• Operating mode (WinCC)
Displays the determined operating mode of WinCC for the computer. Options:
• Autostart (WinCC)
Displays the determined AutoStart configuration of WinCC and the activated project for the
computer. Options:
• AutoStart (BATCH)
Displays the determined AutoStart configuration of SIMATIC BATCH and the activated project
for the computer. Options:
• Redundancy status
Displays the determined redundancy status for the computer. Options:
In the plant view, the inventory data of the object selected in the tree structure is determined.
The determined plant inventory details of the selected component are displayed in this tab. On
the “Inventory Data” tab, selected object and its configured devices can be viewed in the tree
view. Also, the inventory details of other plant such as property of the device, value (offline), and
value (online) are displayed.
The inventory data determined from configuration data on the engineering machine is displayed
in the Value (offline) column and the inventory data determined from device is displayed in the
Value (online) column.
When the configuration data (offline) is determined it overwrites the existing plant inventory
details and the Management Console displays only the latest value (offline) details. When the
device data (online) is determined, both Value (offline) and Value (online) details are displayed.
Note
If connection to the Automation system device is not available, then the determined device data
(online) displays only offline values.
Procedure
You can find additional information about this in the section "Inventory data in the plant view
(Page 100)".
Layout
Given below is an overview of the elements in the status bar:
Alarm lists
Information about all the Management Console objects are displayed in lists.
Default setting:
New entries are added in the first row and scrolling is automatic.
The lists are available at the following locations:
• In the details area: "Alarm list (Page 55)"
This information is deleted when the following actions are performed:
– The Management Console is closed.
– The Console GUI language is switched.
Information for the following objects is only displayed in the "Messages" tab:
– Unavailable PC stations
• In the ""Event display" dialog box (Page 56)"
This information is saved and retained even when the Management Console is closed.
Configuring columns
• Sorting a column:
Left-click on the header of the relevant column to sort in ascending or descending order.
• Hiding and showing a column:
– Right-click on the relevant table header
– In the shortcut menu, select which columns are shown and hidden.
– To change the display, click on the corresponding menu entry.
Alarms
Alarm messages for all the objects of the Management Console are displayed. These messages
are deleted in the following cases:
• The Management Console is closed.
• The user interface language is switched (menu: "Options > Language...).
Export
The information displayed in the message list can be exported to a CSV file.
1. Select the shortcut menu command Export... in the message list.
2. In the "Save as" dialog window, enter the name of the export file and select the path where
the export file should be stored.
– "Save" button:
The information is exported.
– "Cancel" button:
The information is not exported.
The CSV file can be processed further (e.g. in Microsoft Excel).
Delete
Information displayed in the message list can be deleted.
Select the shortcut menu command Delete all in the message list.
Autoscroll
New messages are automatically displayed in the message list if the default setting for
"Autoscroll" in the Management Console is not changed.
To change this setting, select the shortcut menu command "Autoscroll" in the message list.
• Select the check box on the menu command which means Autoscroll is activated.
• Clear the check box on the menu command which means Autoscroll is deactivated.
Log
The following events are logged in the event display:
• Activation of the computer role "SIMATIC Management Console"
• Assign / cancel assignment of computers to the Management Console
• User logons to the Management Console
• All the events logged in by the Windows Defender.
• Feedback on installations
– Performed actions/functions
– Faulty actions/functions
• Activation of Demo mode
Note
Critical events logged in by the Windows defender are displayed in the "Alarms" window as well.
Export
The information shown in the event display can be exported to a CSV file.
1. Click "Export..." in the event display.
2. In the "Save as" dialog window, enter the name of the export file and select the path where
the export file should be stored.
– "Save" button:
The information is exported.
– "Cancel" button:
The information is not exported.
The CSV file can be processed further (e.g. in Microsoft Excel).
Delete
The information shown in the event display can only be deleted by users with administrative
rights.
• "Delete all" button:
All entries in the event display are deleted.
Requirements
• The user is logged on as the administrator of the Management Console (see section
"Managing rights (Page 23)").
• Group the computers to ensure that administration tasks in networks can be executed
efficiently. For additional information refer-
– Section "Create group (Page 63)"
– Section "Delete group (Page 129)"
Note
Rule for redundant computers
Always insert the computers of a redundant pair into the same group.
Note
Disable assignment
Removing assigned computers from the management:
Options:
• Shortcut menu item "Cancel assignment"
• Use the shortcut menu "Assign computer" to move the computer to the default group "Non-
assigned computer".
• The assignment of the computer to the Management Console can also be made by dragging
the computer to the default group "Non-assigned computer".
Computers that are not available in the network can be moved to the "Non-assigned computers"
group. After refreshing the network view, these computers are no longer present in the tree
structure.
Additional information
• Section "Update or repair SMAgent (Page 64)"
• Section "Disable console assignment (Page 129)"
• Section "Canceling the assignment of a computer (Page 62)"
Note
Rule for redundant computers
Always insert the computers of a redundant pair into the same group.
Procedure
1. Select a folder in the network view (network or group).
2. Select the "Add computer..." command in the shortcut menu.
The "Add computer" dialog opens.
3. Enter the name of the computer. Click "OK".
To add multiple computers, separate the computer names with semicolons.
Result
The computers are displayed in the selected folder. The icon in front of the computer name
indicates the status.
For additional information refer "Symbols in the network view (Page 44)".
When your SMAgent license count is not enough for the inserted target pc, then the target pc
is added to "Non-licensed computers" node.
Additional information
• Section "Canceling the assignment of a computer (Page 62)"
• Section "Disable console assignment (Page 129)"
Note
Canceling the assignment of a computer
When the assignment of a computer to a Management Console is removed, the associated pre-
shared key is removed.
Result
The computers are moved to the "Non-assigned computers" group and receive the status "Non-
assigned". For additional information refer "Symbols in the network view (Page 44)".
Procedure
1. Open the Management Console in the network view...
2. Select a single computer, a group, or root "network".
3. Select the menu command "Reset status" from the shortcut menu.
Additional information
• Section "Update network view (Page 130)"
Administration of groups
Group the computers to ensure that administration tasks in networks can be executed
efficiently.
• Each computer can be assigned to any group depending on the number of licenses available.
• A computer may either be in no group at all or in a maximum of one group.
The following functions can be executed:
• Create group
• Rename group
• Delete group (Page 129)
A Tree structure with the existing groups in the Management Console network view displays:
• "Network" group
• "Non-assigned computers" group
• "Non-licensed computers" group
• Groups created by an administrator
Requirements
• The user is logged on as the administrator of the Management Console (see section
"Managing rights (Page 23)").
• Preparation for use of the Management Console is complete.
For additional information refer "Installing the Management Console (Page 26)".
Create group
Once the Management Console has been started, computers on which the "SIMATIC
Management Agent" is activated attempt to establish communication with the Management
Console. If no plant-specific groups have as yet been created, create plant-specific groups and
assign the computers to the plant-specific groups.
Recommendation:
Working with the Management Console in larger plants becomes more manageable when plant-
specific groups are created(for example, dividing up computers into groups of servers and
assigned clients; distribution according to plant areas).
1. Select the network folder in the network view.
2. Select the menu command Create group in the shortcut menu.
3. Enter a name for the plant-specific group.
Additional information
• Section "Network view (Page 42)"
• Section ""Edit" menu (Page 129)"
• Section "Adding computers (Page 60)"
• Section "Assigning computers (Page 58)"
NOTICE
Computers with SIMATIC BATCH prior to PCS 7 Version 8.1 SP1
The SIMATIC Management Agent cannot be updated via the Management Console.
Install the SIMATIC Management Agent on the local computer via the setup from the following
folder of the SIMATIC PCS 7 DVD 2 or PCS 7 media:
Additional_Products > SMA__Vx.x.
Note
Updating the "SIMATIC Management Agent" service is prohibited for target computers on which
one of the following software packages is installed:
• Process Historian
• Information Server
• Web option for OS
– Web Server
– Web Client or Web Diagnostic Client
Updating the "SIMATIC Management Agent" service is possible as of installed version 8.1.
The "SIMATIC Management Agent" service can be updated on a target computer on which web
server is in runtime by enabling the "Web server Settings". For additional information, please
refer to the section Downward compatibility with the agents (Page 75).
The "SIMATIC Management Agent" service cannot be updated (from an older version to current
version) on a target computer with SIMATIC Management Console installed on it.
Basic procedure
The following actions are required for updating the "SIMATIC Management Agent" service:
• Update the "SIMATIC Management Agent" service on the target computer using the
Management Console.
• Deactivate the process mode on the target computer by SIMATIC Management Agent when
it is necessary for the update. This is because reboots are executed for updates older than
V8.2.
• Close any open project on the target computer by SIMATIC Management Agent, when it's
necessary for the update. This is because reboots are executed for updates older than V8.2.
• Update SMAgent.
Note
• Reboot the target computer by the Management console, if necessary.
• Activate the process mode by SIMATIC Management Agent when Autostart is configured.
If the comparison shows a difference in the versions, the respective target computer in the
network (not the Management Console computer) is marked with the following symbol in the
network tree view:
That means, the version of the "SIMATIC Management Agent" is different to the version on the
Management Console computer and it is not compatible. Only the "Update SMAgent" function
is available for the computers marked with this symbol. All functions are available after updating
the service.
The Management Console can manage and communicate with the SIMATIC Management
Agents of certain old versions. In that case the following symbol is displayed:
For more information refer Downward compatibility with the agents (Page 75)
Requirements
• The "SIMATIC Management Agent" setup is available on a shared storage path (File server or
local folder).
• A share has been set up for the user for this storage path.
• The storage path is entered in the "SIMATIC Management Agent" tab. Storage path: "SIMATIC
PCS 7 DVD 2 or PCS 7 media: Additional_Products > SMA__Vx.x. " or a copy from the SMAgent
Setup.
• The user is a member of the Windows user group "SIMATIC Management Administrators".
Note
Requirement for shared update of SIMATIC Management Agents (group or multiple
computers).
When computers are selected for shared update of SIMATIC Management Agents, the same
version of the SIMATIC Management Agent must be installed on these computers.
Example:
The shared update of SIMATIC Management Agents of version 8.0 SP2 and version 8.1 SP1 is not
possible when the computers are in the same group. An error message will be displayed.
Procedure
1. Select an object in the network view.
– Network
– Group
– Computer
– Non-licensed computers
2. Select Update SMAgent... from the shortcut menu.
– The "SIMATIC Management Agent Setup" dialog opens.
– The "SIMATIC Management Agent" setup is selected or can be selected if a SIMATIC
Management Agent Setup has not been entered in the "Settings" option.
3. Select the setup. Click "Next". The "Install SIMATIC software (2/4) - Computer status" dialog
for the selected setup is displayed.
4. Make the necessary settings. For additional information refer "Dialog "Install SIMATIC
software (2/4) - Computer status" (Page 87)".
5. Click "Next".
The "Install SIMATIC software (3/4) - Configure start behavior" dialog opens.
6. Make the necessary settings.
For additional information refer "Dialog "Install SIMATIC software (3/4) - Configure start
behavior" (Page 88)".
7. Click "Next".
The "Install SIMATIC software (4/4) - Requirements for the installation of the SIMATIC
software" dialog opens.
8. On the "Install SIMATIC software (4/4) - Requirements for the Installation of the SIMATIC
software" dialog, you can select the below option to continue with the update:
"I have read the readme file for the products to be installed. I confirm that I have read and
understood the installation and security information".
9. Select both the check boxes:
"I have made sure that no setups are active or have been started by other processes on the
target computers".
"I agree that process mode is ended on the target systems".
10.Click "OK".
The actions required to update SIMATIC Management Agent are performed.
Result
The service is updated on all computers that were selected for installation.
Once the update is complete, the status symbol for the computers in the network view is also
updated.
Additional information
• Installing SIMATIC software (Page 81)
• Communication using different subnets (Page 31)
5.4.1 Connecting
As of V8.2, the frames to establish a connection between the Management Console and
managed computers with installed and activated service "SIMATIC Management Agent" are
protected by a Pre-Shared Key.
Pre-shared key
• The pre-shared key is an application-specific, shared network key that was agreed to
beforehand.
The protection only involves the connection frames required for the application of the
Management Console. The pre-shared key has no effect on the connection frames from other
applications.
• Enter the pre-shared key for the first application of the Management Console.
The Management Console automatically assigns the pre-shared key to a computer when it is
initially assigned to the Management Console.
Note
Canceling the assignment of a computer
When the assignment of a computer to a Management Console is removed, the pre-shared key
is removed on this computer.
Note
Make sure that the PSKs (Pre-shared keys) are invalidated in the whole plant (e.g. by setting a
new PSK using "SIMATIC Management Agent Configurator"), when a SIMATIC Management
Console computer is decommissioned.
Network in which the computer is located The following applies to the connection:
Management Console Plant computers with
SIMATIC Management
Agent
Domain Domain Connection possible
Workgroup Workgroup
Domain Workgroup No connection possible.
Workgroup Domain
Firewall
PC stations can be located in different subnets in a network. The subnets can, for example, be
connected by routers and protected by a firewall. The firewall rules must be adapted to allow
access to the other network in each case. For additional information refer the
documentation Process Control System PCS 7; PCS 7 - PC Configuration.
Additional information
• Section "Starting the Management Console (Page 37)"
• Section "SIMATIC Management Agent Configurator (Page 70)"
Actions Meaning
Reset pre-shared key Deletes the pre-shared key on the local computer that was
assigned by a SIMATIC Management Console or a user.
New pre-shared key... Opens the dialog box "Set pre-shared key..." .
For more information refer "Set pre-shared key... (Page 135)".
The action only has an effect on the local computer.
Note
The Management Console can only establish communication links to computers for which the
same pre-shared key is configured.
It might be necessary to change the pre-shared key for a computer in a plant at a later time (for
example, after restoring a configuration by using a backup).
Requirements
• Administrative rights are required to change the pre-shared key.
• Execute the action on the local computer.
3. Enter the pre-shared key defined in the Management Console into the input boxes.
For more information refer "SIMATIC Management Agent Configurator (Page 70)".
4. If it matches the pre-shared key, the current Management Console is shown in the dialog
window.
5. Click "OK".
6. Click "Close".
Note
• The user is prompted with an option to either allow or deny integrity check before starting an
installlation/update.
• Simultaneous integrity checks for different computers are allowed only when software
packages or SIMATIC Management Agent updates are being installed.
• When a granular installation is in progress, installation of a software on a different computer
will be permitted only after the previously initiated integrity check concludes.
Procedure
By default, Software integrity check will be enabled. To disable/re-enable Software integrity
check -
1. Select Options > Settings option.
2. Open the ‘Software Administration’ Tab. Enable or disable the option - "Software integrity
check enabled" based on the requirement.
If the "Software integrity check is disabled, a comment must be added in the "Comment on
selection" window.
3. Click "Finish"
Note
• The results of an integrity check can either be found under the SIMATIC Management
Console alarms or event displays.
• Integrity check fails when an existing file/folder is deleted or altered in the PCS 7 Bundle.
• Integrity check doesn't fail if a new file/folder is added to the PCS 7 Bundle.
Note
The following computers are changed by the steps to be executed:
• Computers with installed SIMATIC Management Console
• Computers in the plant with installed SIMATIC Management Agent
Prerequisites
• Installed software on the computer with installed SIMATIC Management Console
– SIMATIC Management Console as of V8.1
• Required software packages
– SIMATIC Management Console V9.0; SIMATIC Management Agent V9.0
Basic procedure
The SIMATIC Management Console is updated in four steps:
1. Store the installation files.
2. Back up the configuration and setting data of the SIMATIC Management Console.
3. Update the computer with installed SIMATIC Management Console.
4. Restore the configuration and setting data of the SIMATIC Management Console.
Note
• The software packages to be installed must be available on a shared path.
• Ensure that the selected path names do not exceed 85 characters when you set the paths for
the software.
• Select a path with a unique name for each software package. For example:
– \\<Computer>\<Path>\<SMMC_Version_and_Date> (example path for the SIMATIC
Management Console Vxx software package)
– \\<Computer>\<Path>\<SMA_Version_and_Date> (example path for the SIMATIC
Management Agent Vxx software package)
• Ensure to unzip only the Web Package. Enable the option "Extract the product without being
installed".
Result
The update of the SIMATIC Management Console is complete.
Prerequisites
The downward compatible SIMATIC Management Agents must be re-assigned to the SIMATIC
Management Console application in order to establish communication.
Requirements
• The software to be installed is available from one shared storage location (shared network
path, for example \\<Computer name>\<Shared name>).
• A share has been set up for the user for this storage path of the software.
• The user is a member of the Windows user group "SIMATIC Management Administrators".
Note
Installation
Updating software using the Management Console is not permitted for some software and
package installations of PCS 7.
The following software and package installations of PCS 7 can only be distributed as new
installations with the SIMATIC Management Console:
• Process Historian
• Information Server
• OpenPCS 7 (update of the "SIMATIC Management Agent" service possible as of installed
version 8.1).
• Web Option for OS
(Web Client or Web Diagnostic Client: Updating the "SIMATIC Management Agent" service is
possible as of installed version 8.1).
This software needs to be manually installed for a software update.
Note
Adding computers to process mode using autostart
Make sure that starting a computer with a modified installation is not going to cause plant faults.
This is particularly important when installing software on computers in redundant systems.
Take particular care with computers for process mode with the following software:
• PCS 7 OS
• SIMATIC BATCH
• SIMATIC Route Control
Note
Dependency of the interface language
In the case of an installation using the Management Console, the following applies to a software
installation or update:
The installation depends on the language that was set on the Management Console:
• When a setup package is created
• When software is updated
If this language is not available, the software will be installed by the Management Console in
English and needs to be switched after installation.
Set the interface language of the Management Console accordingly before updating
software or creating a setup package.
Note
Transferring and updating license keys
This function requires the Automation License Manager.
Note
Installation of software packages without user input
Only SIMATIC products made available by PCS 7 can be installed without user input.
Note
Disclaimer of liability
Siemens accepts no liability for any damage which may occur as a result of the use of the
Management Console for the installation of software which has not been approved.
NOTICE
Operating target computers during software installation
To avoid undefined states, the following actions are prohibited during the software
installation:
• Operation of target computers.
• Switching the operating mode.
Note
Updating software
Need not create setup packages for updating software using a PCS 7 DVD as of PCS 7 V8.0 SP2.
The setups must be known to the Management Console.
For additional information refer:
• Section "Preface; Table 2-1 Overview of the most important changes (Page 13)"
• Section "Setup management... (Page 139)"
• Section "Updating SIMATIC software (Page 84)"
Multiple setups cannot be selected while updating the software.
Setup packages
Save the following with a plant-specific name in a setup package:
• Combinations of setups which can be installed without configuration-specific setup dialogs.
• Settings for a SIMATIC setup program with configuration-specific setup dialogs
– Example: Settings in the PCS 7 setup to install multiple software packages using a setup
package. To create a setup package, start the setup of PCS 7 on the Management Console.
Setup runs in configuration mode. The selected installation parameters are stored in a
setup package file.
– When making the selection, note that specific settings are required for certain software
packages. For additional information refer:"Settings... (Page 136)".
Names of plant-specific setup packages can be found under the "Setup packages" tab in the
"Setup management" dialog.
Select only one setup package for installation. New interactive entries need not be created in the
setup dialogs of the software packages contained in the setup package.
Requirement
The setup packages have been entered in the Setup management in the "Setups" tab.
5. Click "Next".
If a SIMATIC setup which requires configuration-specific setup dialogs for software
installation is selected, these dialogs open and the settings are saved in the setup package.
6. Click "Next".
The summary for the setup package is displayed.
Supplementary information can be added in the "Comment on setup" input box.
This information is displayed when the setup package is selected.
7. Click "Finish".
The setup package is adopted in the list in the "Setup packages" tab.
Additional information
Section "Setup management... (Page 139)"
Requirements
• The computers on which the software is to be installed are assigned to the Management
Console.
• All the necessary permissions have been set up. For additional information refer "Managing
rights (Page 23)".
– The user is a member of the Windows user group "SIMATIC Management Administrators".
– The software to be installed is available from one shared storage location (shared network
path, for example \\<Computer name>\<Shared name>).
– A share has been set up for the user for this storage path of the software.
• Setups and software packages are entered in the Management Console.
For additional information refer "Setup management... (Page 139)".
• Observe the information in the section "Settings... (Page 136)".
• Computers of a redundant pair must be assigned to the same group.
Note
Installing a redundant server pair
If the partner computer is not recognized as fully available, the Management Console rejects the
installation of software packages in process mode. In process mode, the servers of a redundant
server pair can only be installed one after the other for availability reasons (mutual exclusion of
readiness for installation).
Try to identify the servers that belong to a redundant server pair in the detailed information
about the computer (see section "Dialog "Install SIMATIC software (2/4) - Computer status"
(Page 87)".
Note
Number of simultaneous remote installations
With the SIMATIC Management Console, software packages can be installed on multiple
computers at the same time. The number of computers on which an installation can be carried
out at the same time depends on the following factors:
• Performance/speed of the network
• Performance of the file server (Storage location of the PCS 7 media)
Do not carry out a remote installation on more than 20 to 30 computers at the same time in order
to avoid an overload. This is provided that no other actions (for example, inventorying) are
running on the SIMATIC Management Console computer.
Note
Computers with hard disk encryption/activated BIOS password
Some software packages require a restart of the computer during or after installation of the
software.
If passwords must be entered for computers after a restart (BIOS, hard disk encryption, etc.), the
remote installation cannot be completed without "local" operator input when you use the
SIMATIC Management Console.
Recommendation
1. To install the same software packages on multiple computers, create installation-specific
groups (OS Client, for example).
2. Assign the computers to an installation-specific group.
3. Apply the setup package to the group.
For additional information refer "Assigning computers (Page 58)".
Procedure
NOTICE
Possible restart due to installation
Please note that installing software may initiate a restart of the target computer.
1. In the network view, select the object on which software or a software package should be
installed.
Possible selection:
– A computer
– A group
2. Select the shortcut menu command Install SIMATIC software....
The "Install SIMATIC software (1/4) - Select software" dialog window is displayed.
For additional information refer "Dialog "Install SIMATIC software (1/4) - Select software"
(Page 87)".
3. Select the setups/setup packages. Click "Next".
The "Install SIMATIC software (2/4) - Computer status" dialog for the selected setup/setup
package is displayed.
4. Make the necessary settings.
For additional information refer "Dialog "Install SIMATIC software (2/4) - Computer status"
(Page 87)".
5. Click "Next".
The "Install SIMATIC software (3/4) - Configure start-up behavior" dialog opens.
6. Make the necessary settings.
For additional information refer "Dialog "Install SIMATIC software (3/4) - Configure start
behavior" (Page 88)".
7. Click "Next".
The "Install SIMATIC software (4/4) - Requirements for the installation of the SIMATIC
software" dialog opens.
8. Make the necessary settings.
For additional information refer "Dialog "Install SIMATIC software (4/4) - Requirements for the
installation of the SIMATIC software" (Page 90)".
9. Click "OK".
The actions required for the installation of the selected software are performed.
Note
• On the "Setup package" tab, you can only select one setup package to install.
• Multiple setup packages cannot be installed on the same computer simultaneously and if the
setup package is selected, then all the products configured for the setup gets installed on the
computer.
Show progress
The number of plant components and component availability may mean the process can take
some time.
The symbol "Action running" is displayed for the status of a group during an action. Detailed
information is displayed within the group at the computer symbol.
Information on the symbols is available in the section "Symbols in the network view (Page 44)".
If error messages come up in the Management Console, refer the following section:
"Determining the cause (Page 119)".
Note
No check for incomplete installations
After installing software, it might be necessary to restart the computer. This restart is used to
apply settings in the operating system.
• If the computer is not restarted before carrying out an additional installation, inconsistent
operating states may occur. When using the Management Console to install or update
software, pending requests to restart are executed automatically.
• To skip restarting of the computer after installing or updating software, make sure that there
are no pending requests for a restart.
Note
Software installation timed-out notification
The time-out notification occurs in the "Alarms" window, when the software installation to the
assigned computer from the Management console takes more than 12 hours. The installation
status of the assigned computer can be monitored even after the time-out notification occurs.
Requirements
• Software is to be updated from the PCS 7 media.
• The computers on which the software is to be installed are assigned to the Management
Console.
• All the necessary permissions have been set up. For additional information refer "Managing
rights (Page 23)".
– The user is a member of the Windows user group "SIMATIC Management Administrators".
– The software to be installed is available from one shared storage location (shared network
path, for example \\<Computer name>\<Shared name>).
– A share has been set up for the user for this storage path of the software.
• Setups are entered in the Management Console.
For additional information refer "Setup management... (Page 139)".
• Observe the information in the section "Settings... (Page 136)".
Note
Updating a redundant server pair
In process mode, the servers of a redundant server pair can only be updated one after the other
for availability reasons (mutual exclusion of readiness for installation).
Identify the servers that belong to a redundant server pair in the detailed information about the
computer (see section "Dialog "Install SIMATIC software (2/4) - Computer status" (Page 87)".
Note
Number of simultaneous remote accesses
Using PCS 7 Setup, installed software can be simultaneously updated on multiple computers
with the SIMATIC Management Console. The number of computers on which a simultaneous
update can be carried out depends on the following factors:
• Performance/speed of the network
• Performance of the file server (storage location of the PCS 7 media)
Do not carry out a remote update on more than 20 to 30 computers at the same time in order
to avoid an overload. This is provided that no other actions (for example, inventorying) are
running on the SIMATIC Management Console computer.
Note
Computers with hard disk encryption/activated BIOS password
Some software packages require a restart of the computer during or after installation of the
software.
If passwords must be entered for computers after a restart (BIOS, hard disk encryption, etc.), the
remote installation cannot be completed without "local" operator input when you use the
SIMATIC Management Console.
Procedure
NOTICE
Possible restart due to installation
Please note that installing software may initiate a restart of the target computer.
Note
• Multiple setups cannot be selected while updating the software.
• Select only the setup.exe files from the PCS 7 setup.
1. In the network view, select the object on which software should be updated from the PCS 7
setup.
Possible selection:
– A computer
– A group
2. Select the shortcut menu command Update SIMATIC software....
The "Install SIMATIC software (1/4) - Select software" dialog window is displayed.
For additional information refer "Dialog "Install SIMATIC software (1/4) - Select software"
(Page 87)".
3. Select the setup. Click "Next".
The "Install SIMATIC software (2/4) - Computer status" dialog for the selected setup is
displayed.
4. Make the necessary settings.
For additional information refer "Dialog "Install SIMATIC software (2/4) - Computer status"
(Page 87)".
5. Click "Next".
The "Install SIMATIC software (3/4) - Configure start-up behavior" dialog opens.
6. Make the necessary settings.
For additional information refer "Dialog "Install SIMATIC software (3/4) - Configure start
behavior" (Page 88)".
7. Click "Next".
The "Install SIMATIC software (4/4) - Requirements for the installation of the SIMATIC
software" dialog opens.
8. Make the necessary settings.
For additional information refer "Dialog "Install SIMATIC software (4/4) - Requirements for the
installation of the SIMATIC software" (Page 90)".
9. Click "OK".
The actions required for the installation of the selected software are performed.
Note
Progress display
The number of plant components and component availability may mean the process can take
some time.
The symbol "Action running" is displayed for the status of a group during an action. Detailed
information is displayed within the group at the computer symbol.
Information on the symbols is available in the section "Symbols in the network view (Page 44)".
If error messages come up in the Management Console, refer to the information in the section
"Determining the cause (Page 119)".
Note
Setups that are not integrated in PCS 7 Setup
These software packages (WinCC Update, for example) can only be installed using the
Management Console, if the following requirements are met:
• No input is required in the Setup dialogs during the execution of the setup.
• A setup package has been created for this product.
Status unknown
Note
Update software on redundant computers
The simultaneous updating of a pair of servers in process mode is blocked in the Management
Console.
Recommendation:
1. First update the computer which is not the current master.
2. After this update and completing any necessary measures and any adjustment procedures
that may be necessary, switch the master over.
3. After this, update the partner computer of the updated computers.
Information on the automatic launch of process mode for the computers selected for installation
is displayed.
5.5.8.4 Dialog "Install SIMATIC software (4/4) - Requirements for the installation of the
SIMATIC software"
Requirements
• Note the following in the section "Preface; Table 2-1 Overview of the most important changes
(Page 13)".
• The installed software packages were installed with PCS 7 Setup as of PCS 7 V8.0 SP2.
Software installations of separate products support the installation report only with the
following information:
– Installation started message.
– Installation completed message.
• The installation procedures in the report period were started using this Management
Console software package.
Procedure
1. Select one of the following objects in the network view:
– Network
– Group
– Computer
2. In the shortcut menu, select the command Create installation report...
Note
• Microsoft (MS) software updates might take several hours for a computer that is being
updated every month regularly under normal conditions.
• The SIMATIC Management console remotely deploys the Microsoft software updates from
WSUS (Windows Server Update Services) to WUA (Windows Update Agent) on each target
computer using the SMA (SIMATIC Management Agent).
Note
Microsoft software updates cannot be deployed on the target computers in which one of the
following software packages are installed:
• Process Historian
• Information Server
Deployment
The SIMATIC Management Console pops-up a confirmation box in the target computers, for the
operator to confirm the deployment of Microsoft software updates in the respective computers.
The operator can either choose to confirm or postpone.
Note
• Selecting the "Postpone" button closes the window which re-appears after the configured
time interval. In case the message window is not confirmed or postponed within the
configured time-out, a confirmation is assumed automatically.
• For information on the WSUS, please refer Process Control System PCS 7; Compendium Part
F – Industrial Security.
Error handling
• The Management Console monitors the duration of the following phases during the
deployment of the Microsoft software updates with a defined time limit:
• Messages related to the progress and status of the installation process are displayed in the
message window, and are logged as events.
For more information on Microsoft updates, please refer Microsoft Support (https://
support.microsoft.com/)
Windows Update
Windows Update ("Settings > Update & Security") may display updates that have already been
installed via the SIMATIC Management Console under "Available updates" in the target
computer. Since, the updates are deployed via the SIMATIC Management Console and the
scanning is done by Microsoft, there might be a small delay in the status update at Microsoft's
end. To be sure about the installation status, check the "Alarms" window of the SIMATIC
Management Console.
To get a detailed overview of the updates, please export the Microsoft software updates
installation report. If the status does not get updated in the respective target computer, click on
"Install now" or "Check for updates" in the "Windows Update" dialog box, to initiate a scan.
Information displayed
Basic procedure
1. Select view
2. Select object
3. Determine inventory data
For more information refer-
– "Determining inventory data in the network view (Page 97)"
– "Determining inventory data in the plant view (Page 102)"
Note
Delayed display on the Management Console
Actions on the SIMATIC Management Console that are executed in addition to the action
"Determine inventory data" can cause a delayed display on the Management Console.
Requirements
The computers for which the information is to be determined must be assigned to the
Management Console.
Procedure
1. Select the object for which you want to determine inventory data:
– Network
– Group
– Computer
For example, Inventory data of the hard disk in the computer
The following inventory data of the hard disk in the computer from the "Installed hardware"
can be determined:
– Size
– Driver date
– Driver name
– Driver version
– Manufacturer
– Serial number
– Type
2. Select the Determine inventory data... command in the shortcut menu for the object.
The "Determine inventory data" dialog window opens.
3. The following options are already selected by default. If only some of the information should
be determined (e.g. only the license keys), the other check boxes can be cleared.
Options Meaning
"Determine computer information" check box Obtains the device-specific data. 1)
"Determine license keys" check box Obtains the installed license keys.1)
"Determine SIMATIC software" check box Obtains the installed SIMATIC software.1)
1)
The object data is obtained from the PCS 7 plant online.
4. Observe the following notes:
Click "OK".
The inventory data is determined.
Note
Show progress
The duration of the process depends on the number and availability of the plant components.
NOTICE
Inventory data is not determined
Please note that inventory data is not determined when the Management Console is ended
during determination of inventory data.
Result
After the inventory data was successfully determined, it is shown in the detail view in the
"Inventory data" tab.
Detailed information is displayed within the group at the computer symbol.
For more information refer "Symbols in the network view (Page 44)".
Additional information
• Section "Exporting inventory data in the network view (Page 98)"
• Section "Determining the cause (Page 119)"
• Section ""Details area" overview in the network view (Page 47)"
• Section ""Determine inventory data" not executed (Page 124)"
Exported data
The following data is exported depending on the selected basic object:
Basic object in the network view
The following data is displayed:
• Computer
• Hardware data
• Licenses
• Installed SIMATIC software
• Installed third-party software (To access the following information, select Inventory
data>Installed software>Installed third-party software).
– SQL Server
– Installed version of Microsoft .NET Framework with version number
– Microsoft patches with Product name, Publisher, Title, KB and installation date.
– Installed security software with manufacturer, product, version (Windows Defender,
McAfee Agent, McAfee Application Control).
Requirement
• The inventory data for the basic object has been determined.
• For more information refer "Determining inventory data in the network view (Page 97)".
Procedure
The information shown in the details area can be exported to a file.
1. Select the basic object and choose one of the following actions:
– Select the Export inventory data... command in the shortcut menu
– In the toolbar, click the "Export inventory data" button.
– Click the "..." button:
The "Export inventory data" dialog window opens.
- Select the folder in which the file is to be saved.
- Change the file name if required.
- Select the cover page.
2. Click "OK".
The information is exported.
The file name of the export inventory data file is displayed in the format: <default folder
path>_<file name>_<time stamp>.
Note
• The location path for the export inventory data can be specified on the "Inventory Export" tab.
For more information see, "Settings...". This setting is applicable only for automatically
generated export inventory data files.
Additional information
Section "Saving information in files (Page 124)"
Section "Identifying errors (Page 119)"
Requirement
• The engineering station is set (menu "Options > Settings"; tab "Specify Engineering Station").
For more information refer "Settings... (Page 136)".
• The projects to be selected must be known on the engineering station in SIMATIC Manager.
• Ensure that no changes are made to the engineering station while the projects are being
determined.
Procedure
The "Add plant" dialog box contains the following steps for preparing for determining inventory
data:
1. Specify engineering station (Page 101)
2. Select projects (Page 101)
Requirement
• The engineering station is set (menu "Options > Settings"; tab "Specify Engineering Station").
For more information refer "Settings... (Page 136)".
• The projects to be selected must be known on the engineering station in SIMATIC Manager.
• Ensure that no changes are made to the engineering station while the projects are being
determined.
Procedure
1. Open plant view in the Management Console.
2. Select the Add plant... command in the shortcut menu.
The dialog window "Add plant (1/2) - Specify Engineering Station" opens.
Note
• If no Engineering Station has been entered, the following alert box appears: "Please first
define an Engineering Station under "Options".
For more information refer "Settings... (Page 136)".
• When a previous inventory is in the network view only the computers with an installed
engineering station can be selected.
3. In the drop-down list, select the engineering station from which PCS 7 plant multiprojects/
projects are to be added.
4. Click "Next".
The "Dialog box "Add plant (2/2) - Select projects" (Page 101)" dialog box opens.
Requirements
• Select the engineering station on which the projects are available.
• In SIMATIC Manager make sure to get access to the selected projects.
Procedure
1. In the list, select the multiproject/project.
Note
List of multiprojects/projects
Users of the Management Console can determine the inventory data without entering a
password since the Management Console only has read access to projects. For more
information refer "Managing rights (Page 23)".
The following projects of the selected engineering station can be found in the list:
• PCS 7 multiprojects/projects displayed in the SIMATIC Manager
• Blocked / password-protected PCS 7 multiprojects/projects
Result
The Management Console is ready to determine the inventory data for the selected project.
Note
Delayed display on the Management Console
If actions are performed in addition to the "Determine inventory data" action in the SIMATIC
Management Console, it is possible that the additional actions will delay the display on the
Management Console.
Requirements
• The computers for which the information is to be determined must be assigned to the
Management Console.
• To obtain PCS 7 project-specific inventory data via plant view:
– The Management Console is able to access the engineering station data.
For more information refer "Managing rights (Page 23)".
– The engineering station has been specified.
For more information refer "Settings... (Page 136)".
– The PCS 7 project assigned to the plant has been selected.
For more information refer ""Add plant" overview (Page 100)".
Note
Inventory data of switches
If inventory data from switches is determined offline, only the following information about the
switch is available:
• Switch name
• IP address
If inventory data of switches is to be determined online, the following conditions must also be
fulfilled:
• A PCS 7 Maintenance Station (ASSET Management) is configured in your PCS 7 project.
• The switches are configured on this Maintenance Station.
• The user logged on to the engineering station is a member of the following groups:
– On the engineering station: Member of the local group "Administrators" (the member
does not have to be logged in as an administrator)
– On the maintenance station: Member of the group "SIMATIC NET"
• On the Maintenance Station, where the switches are configured in the SIMATIC Net-
configuration of Siemens communication settings, the option "Remote basis and remote
OPC-communication (UA and COM)" should be manually activated. It is recommended to
deactivate this option after the online determination.
If these conditions are not met, the inventory data of switches is determined offline.
Note
Inventory data of field devices
Requirements:
• SIMATIC PDM (as of V8.0) is installed on the engineering station.
Note the section "Preface; Table 2-1 Overview of the most important changes (Page 13)".
• The field devices are configured using SIMATIC PDM in the PCS 7 project.
• The Management Console is able to access the SIMATIC PDM data.
The Management Console only determines the data of field devices that is relevant for the
inventorying.
• In a system where field devices are configured, to get the complete online inventory data
install PDM and inventory data must first be determined with PDM.
• The inventory data for redundant field devices is also determined with PDM.
• The inventory data of the field devices is always determined from the project.
• The online display does not determine data from field devices that are in process mode, so
that a load is not placed on communication with the automation system and/or with the
field devices.
• If inventory data from field devices is determined, only the following information about the
field device is available:
– Plant designation (HID/TAG)
– Description (if available)
– Device type
– Firmware version
– Hardware version
– Article number / name
– Message (if available)
Note
Inventory data of CP device types
The following inventory data of a PCS 7 project on an engineering station can be determined for
CP device types:
• IP and MAC address for CP16x3
• IP and MAC address for CP443-1
Note
Interface module shown multiple times
If the "Configuration via PDM" option is activated in the "General" tab for an interface module in
HW Config, this interface module is shown multiple times in the plant view:
• "Configuration via PDM" option not activated (default)
– The interface module is shown with lower-level field devices on the automation system.
• "Configuration via PDM" option activated
– The interface module is shown with lower-level field devices on the automation system.
– For field devices, the interface module is shown with lower-level field devices.
Note
Inventory data of Process objects
The following inventory data of a PCS 7 project on an engineering station can be determined:
• Process Object count
• System ID (when available)
Procedure
1. Select the object for which you want to determine inventory data.
– Multiproject
– Project
Select the object for which you want to determine station data:
– Automation System
2. Select the Determine inventory data/Determine station data command in the shortcut
menu for the object.
The "Determine inventory data" dialog window opens.
3. Read the information displayed on the "Determine inventory data (1/2) – Condition for
determining inventory data" dialog window and select "I have made sure that no changes will
be made to PCS 7 projects" to continue with determining inventory data.
4. Select one of the options in "Determine inventory data (2/2) – Specify the data source" dialog
window:
Options Meaning
"Determine inventory data from configuration da‐ The data is determined based on the PCS 7 project
ta (offline)" check box (default setting) available on the engineering station.
"Determine inventory data from device data (on‐ The data is obtained from the PCS 7 plant includ‐
line/PDM)" check box ing the field devices.
Note the following:
NOTICE
Functions of the engineering station are disabled
While inventory data is being determined, the SIMATIC Management Console disables the
functions on the engineering station that are required for processing the PCS 7 project.
Make sure that the PCS 7 project does not need to be processed. Actions in SIMATIC
manager, HW Config and NetPro are disabled.
5. Click "Finish".
6. If "Determine inventory data from configuration data (offline)" as the data source has been
chosen, the below dialog box is displayed. Select "Yes" to continue.
Note
While determining inventory data from configuration data (offline), it overwrites the existing
online inventory plant data. Select "Determine inventory data from device data (online/
PDM)" to view the updated online plant data.
The inventory data is determined.
NOTICE
Inventory data is not determined
Please note that inventory data is not determined when the Management Console is ended
during determination of inventory data.
Note
Progress display
The duration of the process depends on the number and availability of the plant components.
The progress of actions is indicated:
• The symbol "Action running" is displayed for the status of a computer during an action.
• The symbol "Action running" is displayed for a group while actions are running for a
computer.
Communication errors are only displayed directly on the computer.
Note
Module properties in the plant view
For modules, the configured properties can be found in the "Inventory data" tab. Therefore, it is
possible that the displayed properties may differ for the same modules.
Result
After the inventory data was successfully determined, it is shown in the detail view.
Detailed information is displayed within the group at the computer symbol.
Information on the symbols is available in the section "Symbols in the plant view (Page 47)".
Note
Data obtained
Data already obtained is discarded.
Additional information
• Section "Exporting inventory data in the plant view (Page 107)"
• Section "Determining the cause (Page 119)"
• Section "Determine inventory data" not executed (Page 124)"
• Section "External components" (Page 142)
Exported data
The following data is exported depending on the selected basic object:
• The determined inventory data for the selected base object is exported.
• Links to the Internet are provided for additional information about Siemens products.
• Export inventory data to an XML file using "Project inventory data export..." feature.
Requirement
• The inventory data for the basic object has been determined.
• For additional information refer "Determining inventory data in the plant view (Page 102)".
Procedure
Export the information shown in the details area to a file.
1. Select the basic object and choose one of the following actions:
– Select the Export inventory data command in the shortcut menu
– In the toolbar, click the "Export inventory data" button.
– Click the "..." button:
The "Export inventory data" dialog window opens.
- Select the folder in which the file is to be saved.
- Change the file name if required.
2. Click "OK".
The information is exported.
The file name of the export inventory data file is displayed in the format: <default folder
path>_<file name>_<time stamp>.
Note
Location path for the export inventory data can be specified in the "Inventory Export" tab. For
more information see, "Settings...". This setting is applicable only for automatically generated
export inventory data files.
The file name of the exported inventory data determined from configuration data and device
data are displayed in the format: <configuration data>_<Projectname>_<date and time> and
<Online device data>_<projectname>_<date and time>.
Additional information
Section "Saving information in files (Page 124)"
Section "Identifying errors (Page 119)"
View Object
Network view Computer or network
Plant view PCS 7 project of the associated engineering station
• Known data is the basis for the inventory data profile (e.g., article number of a device)
5.6.5.2 Dialog "Inventory data profile wizard (1/3) - Select view and action"
The Management Console allows you to compare ACTUAL device configurations with saved
device configurations.
Note
Selected view
• If the current inventory data has been determined in the network view, an inventory data
profile cannot be created for data of the plant view.
• To create an inventory data profile based on known data (without determined inventory
data), the view with the required inventory data is to be found.
5.6.5.3 Dialog "Inventory data profile wizard (2/3) - Create/change inventory data profile"
This dialog is in the inventory data profile wizard.
Note
Naming conventions
The following special characters are allowed in the name: Space, underscore, dash, period.
• If "Load inventory data profile" option is chosen, an existing inventory data profile must be
selected in the dropdown list.
• If "Import inventory data profile from XML file" option is chosen, an inventory data profile file
must be selected at its storage location using the "..." button.
File type: XML file
An inventory profile file can be recognised by its name:
InventoryDataProfile_SIMATICSoftware_<... Version>.xml
After the inventory data profile file has been selected, the name of the imported filter is
displayed: SIMATICSoftware_<... Version> (e.g. SIMATICSoftware_<...> V8.2)
Note
Inventory data profile file in the PCS 7 media
You can find a file for pre-defined, version-specific filters:
• Additional Products/SMMC
Copy this file to the PC and make it available as a filter using the "Import inventory data profile"
option.
Parameter set
1. Adapt the parameter set in the table. The following actions are possible:
– Create parameter set
– Change parameter set
– Delete parameter set
Execute the following actions:
Use the examples in the table below for orientation.
Table 5-6 Example 1: Simple parameter set - Determine "Installed SIMATIC software"
Table 5-7 Example 2: Simple parameter set - Determine "Installed SIMATIC BATCH software"
Table 5-8 Example 3: Extended parameter set: Determine "Installed SIMATIC BATCH software prior to version 8.2"
Table 5-9 Example 4: Extended parameter set: Determine automation systems in which certain modules are combined, e.g.
"CPU 410-5H" and "CP 443-1 Advanced".
Note
Drop-down list "AND / OR" (logic operation)
If a logic function is selected in the "AND / OR" column in the drop-down list, parameter set (1)
is expanded by 5 parameters (2). The two lines of the parameter set can be linked with the
selected logical function.
Note
Parameters and categories
The possible parameters depend on both the view in which the inventory data was determined
on the Management Console, as well as the categories included in the available inventory data:
• Inventory data (from the network view or from the plant view)
• Installed SIMATIC software
• Installed third-party software
– Installed version of Microsoft .NET Framework with version number (Select Inventory
data > Installed software > Installed third-party software).
– Microsoft patches with Product name, Publisher, KB, installation date, and title.
– Installed security software with manufacturer, product, version (Symantec Endpoint
Protection, McAfee Agent, McAfee Endpoint Protection Suite, Trend Micro OfficeScan
Corporate Edition V11.0).
• Licenses
• From plant inventory data (configuration information)
Note
Value for inventory data profile based on known data
Make sure to find the exact value to filter the inventory data. Alternatively, select the PCS 7
installation packages to filter the inventory data.
Example:
If the installed software is determined, insert the "Release version" in the "Value" field.
The "Versions" drop-down list offers values that have not been filtered for the product (SIMATIC
BATCH). The contained values represent the technical versions of the installed software
products.
Recommendation:
Determine the inventory data before you create specific inventory data profiles to determine the
required data more easily.
Finish settings
Click "Next".
The "Inventory data profile wizard (3/3) - Save inventory data profile" dialog window opens.
5.6.5.4 Dialog box "Inventory data profile wizard (3/3) - Save inventory data profile"
This dialog is in the inventory data profile wizard.
Requirements
• The function "Determine inventory data" has been successfully completed for the view-
specific object. The inventory data has been determined in the required view (network view
or plant view). For additional information refer:
– Section "Determining inventory data in the network view (Page 97)"
– Section "Determining inventory data in the plant view (Page 102)"
• The required inventory data profile has been created in the Management Console.
For additional information refer ""Inventory data profile wizard" overview (Page 109)".
Procedure
1. Select the desired object in the tree structure.
– Network view: Network, group, computer
– Plant view: Multiproject, subproject
2. Select the "Apply inventory data profile" command in the shortcut menu.
The "Apply inventory data profile" dialog box opens.
3. Select the desired inventory data profile from the "Inventory data profile" drop-down list.
4. Click "..." to select the folder in which the export file is to be saved.
For additional information refer "Saving information in files (Page 124)".
5. Click "Apply".
The inventory data is filtered and the results are saved in the export file.
Note
Message
If no matches are found for the created inventory data profile, you receive a message.
Additional information
Refer Comparing SIMATIC hardware versions (Page 118)
Requirements
• An inventory data profile was exported as XML file.
For additional information refer "Dialog box "Inventory data profile wizard (3/3) - Save
inventory data profile" (Page 115)".
• Access to the XML file is possible in the Management Console.
Requirements
• The function Software Compare is enabled only for licensed computers.
• The version reference file is provided in the PCS 7 website.
Procedure
To compare software versions of installed software to the latest version of software:
1. Open the Network view in the Management Console.
2. Select a network, computer or a group of assigned computers which are to be compared.
3. In the context menu, select the command "Compare SIMATIC software versions...".
4. On the "Compare SIMATIC software version" window, click the "..." button to select the
version definition file.
Note
• The version reference file which consists of the standard versions of the software is
provided with the PCS 7 bundle in .XML format. This XML file must be selected for
software compare.
• The version reference file for the latest PCS 7 software can be downloaded from the PCS
7 website. This XML file must be selected for software compare."
5. Select the cover page for the software compare file from the drop-down list.
6. Click the "..." to select the storage path for the software version compare export excel sheet.
Note
The name of software version compare export excel sheet is saved in the format:
ComparedVersion_<date and time>.xlsx file.
Note
After the software version compare is successfully completed, status of the software compare
can be viewed in the "Alarms" tab.
The updated and outdated software can be viewed in the " Installed SIMATIC software" tab. Also,
the software details of the Ignored Profiles can be viewed on the "Installed SIMATIC software"
tab.
For additional information see "Inventory data" tab (Page 53)
Requirements
• SIMATIC Management console V9.1, latest update.
• A plant is added and project inventory data is determined.
Question Procedure
Have you installed a new Management Console? Activate the "SIMATIC Management Agent" service is on the computer
(see chapter "Installing SIMATIC Management Agent (Page 28)").
Question Procedure
Are sufficient license keys available for the "SIMATIC Check the number of assigned target computers and available license
Management Agent" service on the computer with the keys on the computer of the Management Console.
Management Console? Perform one of the following actions so that the Management Console
can be operated:
• Install additional license keys for the "SIMATIC Management
Agent" service on the computer with the Management Console.
• Remove target computers from the assignment to the Manage‐
ment Console.
Question Procedure
Has the computer with the Management Console been Check whether the computer is assigned to another Management
replaced? Console.
Has the computer been moved from workgroup to do‐ Restart Management Console computer.
main or are there any changes in the domain?
Is there a network connection to the computers? Open "cmd" using the search box in the start menu.
In the DOS window, enter the ping <IP address>
Is the computer prepared for access via the Manage‐ Check whether the "SIMATIC Management Agent" service is installed
ment Console? and activated/started.
Question Procedure
Is the valid pre-shared key entered on the target com‐ Check the pre-shared key.
puter?
Is the IP address or Windows hostname changed in the If the IP address or hostname of a target computer which was already
SIMATIC Management Agent target computer? assigned to Management Console is changed, then to reconnect with
the Management Console:
1. Disable assignment of the target computer.
2. Reboot the Management Console.
3. Assign the target computer again.
Question Procedure
Has the computer been assigned to the Management Check the Management Console to see which icon is displayed for
Console? target computers.
Is the computer prepared for access via the Manage‐ Check whether the "SIMATIC Management Agent" service is installed
ment Console? and activated/started.
Is the Management Agent on the target computer up Check the Management Console to see which icon is displayed for
to date? target computers.
Is the current user authorized to carry out the action? Check the permissions in the user management of the domain or lo‐
cally on the computers.
Was the Management Console restored from a backup? If the Management Console was restored from a backup on a newly
installed or a different computer, software packages in the backup
must be created again.
Question Procedure
Is another setup process (Example: A Security soft‐ Check if another setup process (Example: A Security software) is run‐
ware) running on the target computer? ning on the target computer.
• If no other setup process is running, reboot the target computer.
• If another setup process (Example: A Security software) is running,
wait until it is completed and then reboot the target computer.
Does the user on the target computer have permission Check the following on the target computer:
to access the target system? • Is the user account set up?
• Is the user account active?
• Have the administrative permissions been entered?
Does the user have administrative rights on the target Increase the level of the user's permissions.
system?
Question Procedure
Does the user have permission to access the share lo‐ Allow access to the target system.
cation on which the software is stored?
Are the installation requirements on the target system Ensure that the installation requirements are met.
met?
Question Procedure
Unable to create setup packages Possible Cause:
• Low bandwidth (less than 256 Kbit/s) of the connection to
the storage of the setup files. Check the strength of the
connection.
Question Procedure
Is the setup file available in the storage location? Check the software storage location (network path and name of the
setup file).
Question Procedure
Are the necessary software packages available? Check the software storage location (network path and name of the
setup file).
Question Procedure
Are processes run‐ Check the redundancy status.
ning on the instal‐ Pay attention to possible effects on process mode (e.g. if redundancy switchover is required).
lation computer Note: Redundancy status prevents software update
that may prevent
In process mode, the servers of a redundant server pair can only be installed one after the other for
installation of the
availability reasons (mutual exclusion of readiness for installation).
software packages?
• When a server pair is in process mode, simultaneous update of both computers using the Manage‐
ment Console is blocked in the Management Console.
• The redundant partner is not available.
• The software cannot be installed on the current master because the redundancy switchover is not
possible.
If PCS 7 software packages are being updated prior to version 8.1 on computers on which SIMATIC BATCH
or SIMATIC Route Control is installed:
Check whether process mode is activated.
Note: Process mode prevents additional actions
To update these software packages while using the SIMATIC Management Console, you must ensure that
process mode of all software packages is ended for these PC stations.
Setup cannot be Check whether the setup is suitable for installation with the Management Console.
installed? The software update using the Management Console cannot be performed for some software packages
of PCS 7.
The following software packages can only be distributed as new installations with the SIMATIC Manage‐
ment Console:
• Process Historian
• Information Server
• OpenPCS 7 (update of the "SIMATIC Management Agent" service possible as of installed version 8.1).
• Web Option for OS
(Web Client or Web Diagnostic Client: Updating the "SIMATIC Management Agent" service is possible
as of installed version 8.1).
These software packages need to be manually installed for a software update.
Is the installation Make sure that the server is not in the "fault" state.
computer a server?
Have you checked • Is the computer prepared?
the following cau‐ – Management Console cannot be operated (Page 120)
ses?
– Setup program is not found (Page 122)
– Setup package is not running (Page 122)
• Is the computer available?
– Computer is not recognized by the Management Console (Page 120)
Question Procedure
Is the current user entered in the "SIMATIC Manage‐ Check the permissions in the user management of the domain or lo‐
ment Users" user group on the Management Console cally on the computers.
computer and the target computer?
Is the inoperable function the setup management? Check that all installations are complete. For additional information
refer "Running installations... (Page 133)".
Question Procedure
Are user-specific names used in the project Check the user-specific names in the project.
with characters that are not permitted? For additional information refer "Requirement for the "Determine inventory
data" function (Page 96)"
Should the inventory data of switches be de‐ Check whether the conditions for determining online data have been met:
termined online? • A user is logged on to the engineering station.
• The user logged on to the engineering station is a member of the local
Windows group "SIMATIC NET".
Should the inventory data of field devices be The online display does not include the determination of field devices that are
determined online? in process mode. This means that a load is not placed on communication to the
automation system or to the field devices.
Should the inventory data of field devices be Check whether the conditions for determining data of field devices have been
determined offline? met:
• SIMATIC PDM (as of V8.0) is installed on the engineering station.
• The field devices are configured using SIMATIC PDM in the PCS 7 project.
• The Management Console is able to access the SIMATIC PDM data.
Information
Note
Visualization of the files
• To read PDF files, a PDF reader that is compatible with PDF 1.7 (ISO32000-1:2008 PDF) is
required.
• We recommend Microsoft EXCEL for editing the XLSX and CSV files.
Note
Pre-shared key
The pre-shared key valid at the time of the backup is not saved. To restore communication to the
connected computers, the currently valid pre-shared key must be known.
Note
Alarms
Alarms recorded by the SIMATIC Management Console cannot be backed up.
Procedure
1. Select the menu command File > Back up data.
The "Back up / recover SIMATIC Management database" dialog opens.
2. Select the path and file name for the backup file.
3. Click "OK".
Note
Restoring data from a Management Console with assigned computers
• First use the "Disable console assignment (Page 129)" menu command before restoring the
data.
• The valid pre-shared key is not included in the backup.
To restore communication to the connected computers, the currently valid pre-shared key
must be entered.
Procedure
1. Select the menu command File > Restore data.
The "Back up / recover SIMATIC Management database" dialog opens.
2. Select the path and file name of the back up file.
3. Click "OK".
Note
Consider the following factors while restoring a back up file in the SIMATIC Management Console
computer:
• Data present in the SIMATIC Management Console are overridden with data in the back up
file.
• The overridden data cannot be retrieved unless a back up of the data is taken before restoring
the back up file.
6.1.3 Exit
Exits the Management Console dialog box.
Version 1:
1. Select the network object in the network view.
2. Select the menu command Create group in the shortcut menu.
Version 2:
1. Select the network object in the network view.
2. Select the menu command Edit > Create group.
Result
A folder for a group with the name "New group" is created in the network view.
Recommendation: Rename the new group.
Procedure
1. Select the group in the network view.
2. Select the menu command Edit > Delete group.
The computers in the previously selected group are moved to the "Non-assigned computers"
folder.
Note
The menu command "Delete group" cannot be used for the "Unassigned computers" group.
The console assignment of the Management Console to all computers in the network must be
canceled if the Management Console is to be switched to another computer.
Note
All data of the Management Console is deleted.
Requirements
• The user is logged on as the administrator of the Management Console (see section
"Managing rights (Page 23)").
• The Management Console is started.
Procedure
1. Select the menu command Edit > Disable console assignment.
A note on canceling the console assignment is displayed.
2. Click "OK".
The console assignment is canceled.
Result
Management Console can be started on another computer.
Additional information
Section "Adding computers (Page 60)"
Note
This menu command can only be used on the objects of the network view.
Reset status
The "Reset status" function resets the status displayed by the SIMATIC Management Console.
Application example:
An already completed action is displayed with "Action is running". This means that additional
actions are blocked on this computer.
Note
Following installation of the Management Console
The plant view only shows the "Plants" node.
Object Determine inventory Export inventory data Remove <Object> Reset status
data
Multiproject X X X -
Subproject of a Multi‐ X X - -
project
Single project X X X -
Engineering station - - X X
Additional information
• Section "Starting the Management Console (Page 37)"
Table is empty?
If there is no entry in the table, all remote installations that were started with the Management
Console are terminated when the menu is opened. For more information refer "Event display
(Page 56)".
6.4.1 Language...
Procedure
1. Pay attention to the information in the dialog box.
– To hide the entires from people around, select the check box "Hide characters when
typing" (default setting: selected).
– Enter the new pre-shared key.
– Enter the new pre-shared key also in the "Confirm new pre-shared key" input box.
2. Click "OK".
6.4.3 Settings...
The Options > Settings command is used to specify settings for work with the Management
Console.
Function Selection
Preparing the Manage‐ 1. In the "Add ES" drop-down list, select the computer name of one or more
ment Console for evaluat‐ engineering stations.
ing engineering station
2. Click on the "Add" button.
project data.
The computers are added to the list "Available ES".
3. Click "OK"
Note:
Then select the PCS 7 project – or projects – from the plant view.
The license name and the process object count can also be found when
the project is selected (Only when we determine the inventory data for
the added plant).
Note
The functions of the Management Console can only be used on the computers in the network
on which the same version of the "SIMATIC Management Agent" service is installed.
If the check box is selected, the Management Console ends the active runtime of the web server
and closes the projects on the target computer and then, the Management Console installs or
updates the software on target computers.
Note
If auto-start is enabled on the target computers and in the Management Console, then after the
installation of software the projects start automatically.
If the check box on the "Web server" tab is not selected and the runtime of the web server is
active, the Management Console does not allow the installation of the software and a is
displayed in the "Status" column as displayed in the below dialog.
Note
When inventory data export path is not specified in the "Inventory Data Export" tab, by default
the automatically generated inventory data export files are saved in the Libraries>Documents
folder.
Additional information
For more information refer
• Section "Setup management... (Page 139)"
• Section "Installing SIMATIC software (Page 81)"
• Section "Setup packages (Page 79)"
"Setups" tab
The storage location of a software package must be entered in the "Setups" list if it is to be
installed with the Management Console.
Note
Providing the software
• Possible storage location for supplied software:
– Directories and drives
– On the local computers or on the network
• The software to be installed is available from one shared storage location (shared network
path, for example \\<Computer name>\<Shared name>).
• The user of the Management Console must have access to the local drives, external drives or
folders. For more information refer "Managing rights (Page 23)".
• Software distributed between more than one media (for example, 2 DVDs) must be copied
to the same storage location. This ensures that the media does not need to be changed
during software installation.
• Only members of the "SIMATIC Management Administrator" user group can install or update
SIMATIC Management Software.
• User must be a member of "SIMATIC Management User" group to create packages.
Name Path
Plant-specific setup name Location of the software for SIMATIC product (\\<Compute name>
\<Share name>\<Name of setup file>)
Note
Setups that are not integrated in PCS 7 Setup
These software packages (WinCC Update, for example) can only be installed using the
Management Console, if the following requirements are met:
• No input is required in the Setup dialogs during the execution of the setup.
• A setup package has been created for the products.
Note
Make sure that only the administrator and no other users have write permission for the directory
in which the setup files and setup packages for SIMATIC Management Console is located.
Create plant-specific setups for computers in the "Setup packages" tab. For installation on
individual computers or groups of computers, select only the required setup packages.
Managing setup
1. Select the menu command Options > Setup management ... .
The "Setup management" dialog opens.
2. Select the "Setups" tab.
The "Setups" list appears in the "Setup management" dialog.
The following actions are possible:
Note
Select only one setup to create a setup package. The SIMATIC Management Console does not
allow selection of multiple setups.
Note
Confirming license terms and safety instructions
Individuals who confirm the licensing conditions and safety instructions when creating setup
packages must pay attention to the following:
Ensure that all persons authorized to install the setup packages accept these conditions.
Recommendation:
If necessary, copy the contents into a file and provide the authorized persons with these
contents.
Additional information
Section "Setup packages (Page 79)"
Section "Project inventory data export" (Page 142)
Introduction
This section briefs how the project inventory data export feature can be used for SIMATIC
Management console. The SIMATIC Management Console can generate data of objects in the
generic iBase format. iBase is a hierarchical representation of hardware and software data for
projects. In the iBase format the data is classified into operator systems, automation systems,
network systems and field components. The classification, reference ID and key number for each
object can be viewed in the iBase format. This feature helps to export project data in an XML file.
Prerequisites
The following operations must be performed before exporting the inventory data. Please refer
to the following sections:
1. "Add plant" overview (Page 100)
2. Dialog window "Add plant (1/2)- Specify Engineering Station" (Page 101)
3. Dialog box "Add plant (2/2) – Select projects" (Page 101)
4. Determining inventory data in the plant view (Page 102)
Note
• Project data can be exported for only one project at a time.
Procedure
1. In the "SIMATIC Management Console" window, select "Options>Project inventory data
export". The "Select project" window appears.
2. In the "Select project" window, select the project to export data in XML format. The "Export
inventory data" window appears.
3. In the "Export inventory data" window, select the cover page for the project from the "Please
select the cover page" drop down list. Select the storage location for the XML file from the
"Please select the storage location" file browser and click "OK".
4. An example of the iBase data in the XML file structure is shown below:
Procedure
1. Select the Options > External components... menu command.
The "External components" dialog box opens.
2. In the "Please chose the file to import" area, click the [...] button to import the file.
3. Click 'OK'.
The CSV file is imported. The properties of Manual Components.csv file are:
• The timestamp of the imported file is displayed in the "Imported on:" and "Modified on:" fields.
• The user-defined import file must be in CSV format.
• The first line must contain names of the header (seperated with ";").
• The lines containing devices with their special information (seperated with ";").
• The "External components" tab contains the same content in all languages. Translation is not
needed here.
Example for customer components CSV file is as follows:
Name of device; Tech location; Serial Number; Version; Description
HP Printer 460; Test area 5; 100-55-768;V6.1; Printer for Logging
Test Switch; Test area 6; 54XC-FDE;V6.2; Switch for special test
Note
Check the "Delete External Components" option to delete the imported file, else, the newly
imported file will replace the existing one.
Requirements
• Inventory data have been determined in the Management Console.
• The currently determined inventory data contains the corresponding categories.
Note
Examples of missing categories in the inventory data
• The current inventory data only contains the installed license keys:
An inventory data profile for determining "Installed SIMATIC software" cannot be created.
• Inventory data profiles are always view-specific (network view or plant view).
If the current inventory data has only been determined in the network view, inventory data
profiles cannot be created for the plant view.
• If needed, determine the inventory data in the network or plant view before creating a new
inventory data profile.
Actions Dialog
Select origin of inventory data and action Section "Dialog "Inventory data profile wizard (1/3) - Select
view and action" (Page 110)"
Specify parameter sets Section "Dialog "Inventory data profile wizard (2/3) - Create/
change inventory data profile" (Page 111)"
Select version categories and save/export Section "Dialog box "Inventory data profile wizard (3/3) -
the inventory data profile Save inventory data profile" (Page 115)"
Requirement
The engineering station has been specified.
For more information refer "Settings... (Page 136)".
Procedure
1. Select the Options > Create license report... menu command.
The "Create license report - use of license keys" dialog box opens.
2. Select a cover page from the drop-down list box for the license report.
3. Select a storage location for the license report.
4. Click "OK".
Result
The result is stored in an XLSX file.
Requirements
The user of the Management Console is a member of the "SIMATIC Management User" Windows
group.
Procedure
1. Select the menu command ? > Available plug-ins ... .
A list with the following columns is displayed in the dialog box:
Column Meaning
Plug-in name Name of the Management Console component
Company Component manufacturer
Version Version number of the component
Description Area of application in the Management Console
6.5.2 Help
This menu command is used to open the "SIMATIC Management Console" help files in the PUD
application.
6.5.3 Info...
Legal information is displayed.
I R
Installation
Remote, 17
Management Console, 26
Operator input, 37
Preparing, 139
Service, 37
Software, 81, 84
Remote access, 37
Symbols, 46
Remote desktop connection, 17, 30
Installing
Requirement
Management Console, 27
Administrator, 27, 28
Remote installation, 30
Network copy of the PCS 7 DVD, 27, 28
Service on remote computers, 28
Operating system, 27, 28
Update, 27
S
Service
Starting/deactivating, 29
Setup, 136
Preparing, 139
Setup packages
Preparing, 79
SIMATIC BATCH, 137
Updating SIMATIC Management Agent, 64
SIMATIC hardware
Compare, 119
SIMATIC Management Users
Permissions, 24
Windows group, 24
SIMATIC software
Compare, 117
Installing, 81
Update, 84
Sorting, 39
Starting
Service, 29
Status, 44, 47
Computer, 45
Group, 44
Symbols, 41
Toolbar, 41
U
Update, 27
V
Virtual Network Connection, 17
Virus pattern, 99
VNC, 17