Technical Information Proline Promag 55S: Electromagnetic Flowmeter

This document provides technical information about the Proline Promag 55S electromagnetic flowmeter. It describes the measuring principle, system design, inputs and outputs, power supply, mechanical construction, performance characteristics, installation requirements, operating environment, certifications, and ordering information. The flowmeter uses an electromagnetic measuring principle that is independent of pressure, density, temperature and viscosity. It has a large range of liners and can measure solids content up to 80% by weight, making it ideal for demanding applications with high solids content and abrasion.

Uploaded by

great
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
19 views

Technical Information Proline Promag 55S: Electromagnetic Flowmeter

This document provides technical information about the Proline Promag 55S electromagnetic flowmeter. It describes the measuring principle, system design, inputs and outputs, power supply, mechanical construction, performance characteristics, installation requirements, operating environment, certifications, and ordering information. The flowmeter uses an electromagnetic measuring principle that is independent of pressure, density, temperature and viscosity. It has a large range of liners and can measure solids content up to 80% by weight, making it ideal for demanding applications with high solids content and abrasion.

Uploaded by

great
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 48

TI00071D/06/EN/15.

21 Products Solutions Services


71524756

Technical Information
Proline Promag 55S
Electromagnetic flowmeter

The flowmeter with outstanding abrasion resistance and integrated solids


content diagnostics
Application Your benefits
• The bidirectional measuring principle is virtually independent • Superb signal stability due to unique signal processing
of pressure, density, temperature and viscosity • Maximum safety – industry-optimized measuring electrodes
• Ideal for the most demanding applications with high solids and linings
content and high abrasion • Energy-saving flow measurement – no pressure loss due to
cross-section constriction
Device properties
• Maintenance-free – no moving parts
• Intensified coil system
• Highest performance – with integrated solids measurement
• Large range of liners
for demanding fluids
• Solids content up to 80% by weight
• Highest safety – integrated electrode cleaning
• 4-line backlit display with touch control
• Automatic recovery of data for servicing
• Two switch outputs
• HART, PROFIBUS PA/DP, FOUNDATION Fieldbus
Proline Promag 55S

Table of contents

Function and system design . . . . . . . . . . . . . . . . . . . . . .3 Pressure tightness (lining) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23


Measuring principle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Limiting flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Measuring system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Pressure loss . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Vibrations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Measured variable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Mechanical construction . . . . . . . . . . . . . . . . . . . . . . . 27
Measuring ranges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Design, dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Operable flow range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Input signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Measuring tube
specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Material . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 Fitted electrodes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Output signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Process connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Signal on alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Surface roughness . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Low flow cut off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Galvanic isolation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Operability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Switching output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Local operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Language groups . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Remote operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Terminal assignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Supply voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Certificates and approvals . . . . . . . . . . . . . . . . . . . . . . 44
Power consumption . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 CE mark . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Power supply failure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 C-tick symbol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Electrical connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Ex approval . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Electrical connection, remote version . . . . . . . . . . . . . . . . . . . . . 8 Sanitary compatibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Potential equalization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Pressure equipment directive . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Cable entries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 FOUNDATION Fieldbus certification . . . . . . . . . . . . . . . . . . . . . 44
Remote version cable PROFIBUS DP/PA certification . . . . . . . . . . . . . . . . . . . . . . . . . 44
specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Other standards and guidelines . . . . . . . . . . . . . . . . . . . . . . . . . 44

Performance characteristics . . . . . . . . . . . . . . . . . . . . 13 Ordering information . . . . . . . . . . . . . . . . . . . . . . . . . . 45


Reference operating
conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Maximum measured error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Repeatability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45

Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Registered trademarks . . . . . . . . . . . . . . . . . . . . . . . . . 45
Mounting location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Orientation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Inlet and outlet runs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Adapters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Length of connecting cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Foundations, supports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Ambient temperature range . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Storage temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Degree of protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Shock and vibration resistance . . . . . . . . . . . . . . . . . . . . . . . . . 19
Electromagnetic compatibility (EMC) . . . . . . . . . . . . . . . . . . . . 19

Process . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Medium temperature range . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Conductivity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Pressure-temperature ratings . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Medium pressure range (nominal pressure) . . . . . . . . . . . . . . 23

2 Endress+Hauser
Proline Promag 55S

Function and system design


Measuring principle Faraday’s law of induction states that a voltage is induced in a conductor moving in a magnetic field.
In electromagnetic measuring, the flowing medium corresponds to the moving conductor. The induced
voltage is proportional to the flow velocity and is detected by two measuring electrodes and
transmitted to the amplifier. Flow volume is computed on the basis of the pipe’s diameter. The
constant magnetic field is generated by a switched direct current of alternating polarity.

Ue
I

V
B
I
L
A0003191

Ue = B · L · v
Q=A·v
Ue induced voltage
B magnetic induction (magnetic field)
L electrode gap
v flow velocity
Q volume flow
A pipe cross-section
I current strength

Measuring system The flow measuring system consists of the following components:
• Promag 55 transmitter
• Promag S sensor (DN 15 to 600 / ½ to 24")
Two versions are available:
• Compact version: Transmitter and sensor form a single mechanical unit.
• Remote version: Transmitter and sensor are installed separately.

Measurement of solids flow rates


In combination with a density meter, e.g. with "Gammapilot M" from Endress+Hauser, Promag 55S also
determines the throughput of solids in mass, volume or percentage rates.
The following order specifications are required for this: order option for software function "Solids
content flow" (F-CHIP) and order option for a current input.

rM

m 2
rC
rS

1 V

A0006118

Solids content flow measurement (m) with the aid of a density and flow measuring device. If the solid density (ρS ) and the density of
the carrier liquid (ρC ) are also known, they can be used to calculate the solids flow.
1 Flow measuring device (Promag 55S) → volume flow (V). The solid density (ρS ) and the density of the transport liquid (ρC )
must be entered in the transmitter.
2 Density measuring device (e.g. "Gammapilot M") → total fluid density (ρM ) (transport liquid and solids)

Endress+Hauser 3
Proline Promag 55S

Input
Measured variable • Flow rate (proportional to induced voltage)
• Conductivity (without temperature compensation)

Measuring ranges • Flow rate: Typical v = 0.01 to 10 m/s (0.03 to 33 ft/s) with the specified measuring accuracy
• Conductivity s = 5 to 2000 μS/cm
not for sensors without reference electrode (Promag S with brush electrodes)

Operable flow range Over 1000 : 1

Input signal Status input (auxiliary input)


U = 3 to 30 V DC, Ri = 5 kΩ, galvanically isolated
Configurable for: totalizer(s) reset, positive zero return, error-message reset

Status input (auxiliary input) with PROFIBUS DP


U = 3 to 30 V DC, Ri = 3 kΩ, galvanically isolated.
Switch level: ±3…±30 V DC, independent of polarity.
Configurable for: positive zero return, error message reset, zero point adjustment start

Current input
Active/passive selectable, galvanically isolated, full scale value adjustable, resolution: 3 μA,
temperature coefficient: typically 0.005% o.f.s./°C (0.003% o.f.s./°F)
• Active: 4 to 20 mA, Ri ≤ 150 Ω, Uout = 24 V DC, short-circuit proof
• Passive: 0/4 to 20 mA, Ri ≤ 150 Ω, Umax = 30 V DC

Output
Output signal Current output
Active/passive selectable, galvanically isolated, time constant selectable (0.01 to 100 s),
full scale value adjustable, temperature coefficient: typically 0.005% o.f.s./°C (0.003 % o.f.s./°F),
resolution: 0.5 μA
• Active: 0/4 to 20 mA, RL < 700 Ω (for HART: RL ≥ 250 Ω)
• Passive: 4 to 20 mA; supply voltage VS : 18 to 30 V DC; Ri ≥ 150 Ω

Pulse/frequency output
Active/passive selectable (Ex i version passive only), galvanically isolated
• Active: 24 V DC, 25 mA (max. 250 mA over 20 ms), RL > 100 Ω
• Passive: open collector, 30 V DC, 250 mA
• Frequency output: end frequency 2 to 10000 Hz (fmax = 12500 Hz), on/off ratio 1:1,
pulse width max. 10 s
• Pulse output: pulse value and pulse polarity selectable, pulse width configurable (0.05 to 2000 ms)

PROFIBUS DP interface
• Transmission technology (Physical Layer): RS485 according to ASME/TIA/EIA-485-A: 1998,
galvanically isolated
• Profile Version 3.0
• Data transmission rate: 9.6 kBaud to 12 MBaud
• Automatic identification of data transmission rate
• Function blocks: 2 × analog input, 3 × totalizer
• Output data: volume flow, calculated mass flow, totalizer 1 to 3
• Input data: positive zero return (ON/OFF), totalizer control, value for local display
• Cyclic data transmission compatible with previous model Promag 35S
• Bus address adjustable via miniature switches or local display (optional) at the measuring device
• Available output combination →  6

4 Endress+Hauser
Proline Promag 55S

PROFIBUS PA interface
• Transmission technology (Physical Layer): IEC 61158-2 (MBP), galvanically isolated
• Profile version 3.0
• Current consumption: 11 mA
• Permissible supply voltage: 9 to 32 V
• Bus connection with integrated reverse polarity protection
• Error current FDE (Fault Disconnection Electronic): 0 mA
• Function blocks: 2 × analog input, 3 × totalizer
• Output data: volume flow, calculated mass flow, totalizer 1 to 3
• Input data: positive zero return (ON/OFF), totalizer control, value for local display
• Cyclic data transmission compatible with previous model Promag 35S
• Bus address adjustable via miniature switches or local display (optional) at the measuring device

FOUNDATION Fieldbus interface


• FOUNDATION Fieldbus H1
• Transmission technology (Physical Layer): IEC 61158-2 (MBP), galvanically isolated
• ITK version 5.01
• Current consumption: 12 mA
• Inrush current: < 12 mA
• Error current FDE (Fault Disconnection Electronic): 0 mA
• Permissible supply voltage: 9 to 32 V
• Bus connection with integrated reverse polarity protection
• Function blocks:
– 5 × Analog Input (execution time: 18 ms each)
– 1 × PID (25 ms)
– 1 × Digital Output (18 ms)
– 1 × Signal Characterizer (20 ms)
– 1 × Input Selector (20 ms)
– 1 × Arithmetic (20 ms)
– 1 × Integrator (18 ms)
• Total VCRs: 48
• Total link objects in VFD: 40
• Output data: volume flow, calculated mass flow, temperature, totalizer 1 to 3
• Input data: positive zero return (ON/OFF), reset totalizer
• Link Master (LM) functionality is supported

Signal on alarm Current output


Failsafe mode selectable (e.g. according to NAMUR recommendation NE 43)

Pulse/frequency output
Failsafe mode selectable

Relay output
"de-energized" in the event of a fault or power supply failure

PROFIBUS DP/PA
Status and alarm messages in accordance with PROFIBUS Profile Version 3.0

Load See "output signal"

Low flow cut off Switch points for low flow freely selectable.

Galvanic isolation All circuits for inputs, outputs, and power supply are galvanically isolated from each other.

Switching output Relay output


Normally closed (NC or break) or normally open (NO or make) contacts available
(default: relay 1 = NO, relay 2 = NC),
max. 30 V / 0.5 A AC; 60 V / 0.1 A DC, galvanically isolated. Configurable for: error messages, empty
pipe detection (EPD), direction of flow, limit values.

Endress+Hauser 5
Proline Promag 55S

Power supply
Terminal assignment Terminal No.
Order code for
"Input / Output" 20 (+) / 21 (–) 22 (+) / 23 (–) 24 (+) / 25 (–) 26 (+) / 27 (–)

Fixed communication boards (fixed assignment)

Current output
A – – Frequency output
HART

Current output
B Relay output 2 Relay output 1 Frequency output
HART

PROFIBUS PA
H – – –

+5V (ext. PROFIBUS DP


J – –
termination)

FOUNDATION
K – – –
Fieldbus

Flexible communication boards

Current output
C Relay output 2 Relay output 1 Frequency output
HART
Current output
D Status input Relay output Frequency output
HART

Current output
L Status input Relay output 2 Relay output 1
HART

Current output
M Status input Frequency output 2 Frequency output 1
HART
PROFIBUS DP
P Current output Frequency output Status input

PROFIBUS DP
V Relay output 2 Relay output 1 Status input

Current output 1
2 Relay output Current output 2 Frequency output
HART
Current input Current output 1
3 Current output 2 Frequency output
HART

4 Current input Relay output Frequency output Current output


HART

5 Status input Current input Frequency output Current output


HART

Supply voltage 20 to 260 V AC, 45 to 65 Hz


20 to 64 V DC

Power consumption AC: < 45 VA at 260 V AC; < 32 VA at 110 V AC (incl. sensor)
DC: < 19 W (including sensor)
Switch-on current:
• Max. 2.5 A (< 200 ms) at 24 V DC
• Max. 2.5 A (< 5 ms) at 110 V AC
• Max. 5.5 A (< 5 ms) at 260 V AC

Power supply failure Lasting min. 1 power cycle:


• EEPROM or HistoROM/T-DAT saves measuring system data if power supply fails
• HistoROM/S-DAT: exchangeable data storage device which stores sensor characteristic data
(nominal diameter, serial number, calibration factor, zero point etc.)

6 Endress+Hauser
Proline Promag 55S

Electrical connection
A B

d
g
b

a
a
b d/(g)(d)

HART PROFIBUS PA*


FOUNDATION Fieldbus*
– 27 PA(–)/FF(–) 27
+ 26 PA(+)/FF(+) 26
– 25 d – 25 d
+ 24 + 24
f – 23 e f – 23 e
+ 22 + 22
– 21 – 21
+ 20 + 20

N (L-) 2 c N (L-) 2 c
L1 (L+)1 L1 (L+)1
b b

PROFIBUS DP* PROFIBUS DP**

A (RxD/TxD-N) 27 A (RxD/TxD-N) 27
B (RxD/TxD-P) 26 B (RxD/TxD-P) 26
– 25 d – 25 d
+ 24 + 24
f – 23 e f – 23 e
+ 22 + 22
– 21 – 21
+ 20 g + 20 g

N (L-) 2 c N (L-) 2 c
L1 (L+)1 L1 (L+)1
b b

A0015195

Connecting the transmitter, cable cross-section max. 2.5 mm 2 (14 AWG)


A View A (field housing)
B View B (wall-mount housing)
*) Fixed communication boards
**) Flexible communication boards
a Connection compartment cover
b Cable for power supply: 20 to 260 V AC / 20 to 64 V DC
- Terminal No. 1: L1 for AC, L+ for DC
- Terminal No. 2: N for AC, L– for DC
c Ground terminal for protective conductor
d Input/output cable: see Terminal assignment →  6
Fieldbus cable:
- Terminal No. 26: DP (B) / PA (+) / FF (+): with polarity protection
- Terminal No. 27: DP (A) / PA (–) / FF (–): with polarity protection
e Ground terminal for input/output cable / Fieldbus cable
f Service adapter for connecting service interface FXA193 (Fieldcheck, FieldCare)
g Electrode cable: see Terminal assignment →  6
Cable for external termination (only for PROFIBUS DP with permanent assignment communication board):
- Terminal No. 24: +5 V
- Terminal No. 25: DGND

Endress+Hauser 7
Proline Promag 55S

Electrical connection,
remote version c d

GND
S1
E1
E2
S2

E
S
6 5 7 8 4 37 36 42 41
a

c d
n.c. n.c. n.c.
b
5 7 4 37 42 41

E1

E
E2
GND
A0011722

Connecting the remote version


a Connection compartment, wall-mount housing
b Cover of connection housing, sensor
c Electrode cable
d Coil current cable
n.c. unconnected, insulated cable shields
Terminal no. and cable colors: 6/5 = brown; 7/8 = white; 4 = green; 36/37 = yellow

Potential equalization Standard case


Perfect measurement is only ensured when the medium and the sensor have the same electrical
potential. Most Promag sensors have a reference electrode installed as standard, which guarantees the
required potential equalization. This usually means that additional potential equalization measures
are unnecessary.
Promag S:
• Reference electrode is standard for electrode materials 1.4435/316L, Alloy C-22, tantalum,
titanium Gr. 2, Duplex 1.4462, tungsten carbide coating (for electrodes made of 1.4435)
• Reference electrode is optional for electrode material platinum
• Reference electrode not present in measuring tubes with a natural rubber lining in conjunction with
brush electrodes

! Note!
For installation in metal pipes, it is advisable to connect the ground terminal of the transmitter housing
to the piping. Also, observe company-internal grounding guidelines.

A0004375

Potential equalization by means of the transmitter's ground terminal

8 Endress+Hauser
Proline Promag 55S

! Note!
• For sensors without reference electrodes or without metal process connections, carry out potential
equalization as per the instructions for special cases described below. These special measures are
particularly important when standard grounding practice cannot be ensured or extremely strong
matching currents are expected.
• Sensors with brush electrodes do not have a reference electrode. For this reason, ground disks must
be installed if necessary to ensure sufficient potential equalization to the fluid. This applies in
particular to isolating lined pipes which are not grounded →  9.

Special cases

Metal, ungrounded piping


In order to prevent outside influences on measurement, it is necessary to use ground cables to connect
each sensor flange to its corresponding pipe flange and ground the flanges. Connect the transmitter or
sensor connection housing, as applicable, to ground potential by means of the ground terminal
provided for the purpose (see diagram).
The ground cable for flange-to-flange connections can be ordered separately as an accessory from
Endress+Hauser →  45.
• DN  300 (12"): The ground cable is in direct connection with the conductive flange coating and is
secured by the flange screws (A).
• DN  350 (14"): The ground cable connects directly to the metal transport bracket (B).

! Note!
Also, observe company-internal grounding guidelines.

A B

A0004376

Potential equalization with equalizing currents in ungrounded, metal pipes


(ground cable: copper wire, at least 6 mm 2 /10 AWG)
A Installing ground cable at DN ≤ 300 (12")
B Installing ground cable at DN ≥ 350 (14")

Pre-installed ground cable for DN ≤ 300 (12") (order option)


Ground cables which are preinstalled on the sensor flange, are also available. These ground cables can
be mounted and connected electrically to the piping in different ways:
• Using a screw on the side of the pipe flange (a)
• Using the flange screws (b)
• Using a pipe clip installed around the pipe (c)

Endress+Hauser 9
Proline Promag 55S

c a

A006117

Possibilities for connecting and mounting pre-installed ground cables


(ground cable: copper wire at least 6 mm 2 /10 AWG)

Plastic pipes and isolating lined pipes


Normally, potential is matched using the reference electrodes in the measuring tube. However, in
exceptional cases it is possible that, due to the grounding plan of a system, matching currents flow over
the reference electrodes. This can lead to destruction of the sensor, e.g. through electro-chemical
decomposition of the electrodes. In such cases, e.g. for fiberglass or PVC pipings, it is therefore
essential that you use additional ground disks for potential equalization. This applies also to two-
phase or two-component flow, where the fluid is not well mixed or its constituents are not mixable.

! Note!
• Risk of damage by electrochemical corrosion. Note the electrochemical insulation rating, if the
ground disks and measuring electrodes are made of different materials.
• Also, observe company-internal grounding guidelines.

A0004377

Potential equalization/ground disks in the case of plastic pipes or isolating lined pipes
(ground cable: copper wire at least 6 mm 2 / 10 AWG)

Plastic pipes and isolating lined pipes


In such cases, install the measuring instrument without potential in the piping:
• When installing the measuring device, make sure that there is a terminal assignment between the
two piping runs (copper wire, at least 6 mm2 / 10 AWG).
• When using ground disks in plastic or isolating lined pipes, ensure that they are electrically
connected with each other (copper wire at least 6 mm2 / 10 AWG).
• Make sure that the mounting material used does not establish a conductive connection between the
pipe and the measuring device and that the mounting material withstands the torques applied when
the threaded fasteners are tightened during installation.
• Check the galvanic isolation using an insulation tester (protection against contact).
• Also comply with the regulations applicable to potential-free installation.

10 Endress+Hauser
Proline Promag 55S

! Note!
For the remote version, both the sensor and the transmitter must be installed so that they are
potential-free.

2 2
1

A0004378

Potential equalization and cathodic protection (connecting cable: copper wire at least 6 mm2 / 10 AWG)
1 Isolation transformer power supply
2 Electrically insulated

Cable entries Power-supply and electrode cables (inputs/outputs):


• Cable gland M20 × 1.5 (8 to 12 mm / 0.31 to 0.47")
• Cable entries for thread ½" NPT, G ½"
Fieldbus cable:
• Fieldbus connector for PROFIBUS PA, M12 × 1 / PG 13.5 plus adapter PG 13.5 / M20.5
• Fieldbus connector for FOUNDATION Fieldbus, 7/8-16 UNC × M20
Connecting cable for remote version:
• Cable gland M20 × 1.5 (8 to 12 mm / 0.31 to 0.47")
• Cable entries for thread ½" NPT, G ½"

Remote version cable Coil current cable


specifications • 2 × 0.75 mm² (18 AWG) PVC cable with common, braided copper shield (⌀ ~ 7 mm / 0.28")
• Conductor resistance: ≤37 Ω/km (≤0.011 Ω/ft)
• Capacitance: core/core, shield grounded: ≤120 pF/m (≤37 pF/ft)
• Operating temperature:
– Cable not permanently routed: –20 to +80 °C (–4 to +176 °F)
– Cable permanently routed: –40 to +80 °C (–40 to +176 °F)
• Cable cross-section: max. 2.5 mm² (14 AWG)
Electrode cable
• 3 × 0.38 mm² (20 AWG) PVC cable with common, braided copper shield (⌀ ~ 7 mm / 0.28") and
individually shielded cores
• With Empty Pipe Detection (EPD): 4 × 0.38 mm² (20 AWG) PVC cable with common, braided copper
shield (⌀ ~ 7 mm / 0.28") and individually shielded cores
• Conductor resistance: ≤ 50 Ω/km (≤ 0.015 Ω/ft)
• Capacitance: core/shield: ≤ 420 pF/m (≤ 128 pF/ft)
• Operating temperature:
– Cable not permanently routed: –20 to +80 °C (–4 to +176 °F)
– Cable permanently routed: –40 to +80 °C (–40 to +176 °F)
• Cable cross-section: max. 2.5 mm² (14 AWG)

Endress+Hauser 11
Proline Promag 55S

1
2
3
4
5
6
7
a b

A0003194

a Electrode cable
b Coil current cable
1 Core
2 Core insulation
3 Core shield
4 Core jacket
5 Core reinforcement
6 Cable shield
7 Outer jacket

As an option, Endress+Hauser can also deliver reinforced connecting cables with an additional,
reinforcing metal braid. We recommend such cables for the following cases:
• Directly buried cable
• Cables endangered by rodents
• Device operation which should comply with the IP 68 (NEMA 6P) standard of protection
Operation in zones of severe electrical interference
The measuring device complies with the general safety requirements in accordance with EN 61010-1,
the EMC requirements of IEC/EN 61326 and NAMUR recommendation NE 21.

! Note!
Grounding of the shield is by means of the ground terminals provided for the purpose inside the
connection housing. Keep the stripped and twisted lengths of cable shield to the terminals as short as
possible.

12 Endress+Hauser
Proline Promag 55S

Performance characteristics
Reference operating To DIN EN 29104 and VDI/VDE 2641:
conditions • Fluid temperature: +28 °C ± 2 K (+82 °F ± 2 K)
• Ambient temperature: +22 °C ± 2 K (+72 °F ± 2 K)
• Warm-up time: 30 minutes
Installation:
• Inlet run > 10 × DN
• Outlet run > 5 × DN
• Sensor and transmitter grounded.
• Sensor centered relative to the pipe.

Maximum measured error Pulse output:


• Standard: ±0.2% o.r. ± 2 mm/s (±0.2% o.r. ± 0.08 in/s)
• With brush electrodes (Option): ±0.5% o.r. ± 2 mm/s (±0.5% o.r. ± 0.08 in/s)
(o.r. = of reading)
Current output:
In addition typically ±5 μA

! Note!
Supply-voltage fluctuations have no effect within the specified range.

[%]
2.5
2.0
1.5
1.0
0.5
0
0 1 2 4 6 8 10 [m/s]
v
0 5 10 15 20 25 30 32 [ft]
A0004456

Max. measured error in % of reading

Conductivity
• Max. measuring error not specified
• Without temperature compensation (cell constant is a factory setting)

Repeatability Volume flow


• Standard: max. ±0.1% o.r. ± 0.5 mm/s (±0.1% o.r. ± 0.02 in/s)
• With brush electrodes (Option): max. ±0.2% o.r. ± 0.5 mm/s (±0.2% o.r. ± 0.02 in/s)
(o.r. = of reading)

Conductivity
• Max. ±5% o.r.
(o.r. = of reading)

Endress+Hauser 13
Proline Promag 55S

Installation

Mounting location The accumulation of air or gas bubbles in the measuring tube could result in an increase in measuring
errors. Avoid the following locations:
• At the highest point of a pipeline. Risk of air accumulating.
• Directly upstream from a free pipe outlet in a vertical pipeline.

h ³ 2 ´ DN

A0003202

Mounting location

Installation of pumps
Do not install the sensor on the intake side of a pump. This precaution is to avoid low pressure and the
consequent risk of damage to the lining of the measuring tube. Information on the lining's resistance
to partial vacuum →  23.
It might be necessary to install pulse dampers in systems incorporating reciprocating, diaphragm or
peristaltic pumps. Information on the measuring system's resistance to vibration and shock →  19.

A0003203

Installation of pumps

14 Endress+Hauser
Proline Promag 55S

Partially filled pipes


Partially filled pipes with gradients necessitate a drain-type configuration. The Empty Pipe Detection
function offers additional protection by detecting empty or partially filled pipes.

! Note!
Risk of solids accumulating. Do not install the sensor at the lowest point in the drain. It is advisable to
install a cleaning valve.

³ 2 ´ DN

³ 5 ´ DN

A0003204

Installation with partially filled pipes

Down pipes
Install a siphon or a vent valve downstream of the sensor in down pipes h ≥ 5 m (16.4 ft). This
precaution is to avoid low pressure and the consequent risk of damage to the lining of the measuring
tube. This measure also prevents the system losing prime, which could cause air inclusions.
Information on the lining's resistance to partial vacuum →  23.

2
h

A0008157

Installation measures for vertical pipes


1 Vent valve
2 Siphon
h Vertical height of the down pipe regarding the sensor

Endress+Hauser 15
Proline Promag 55S

Orientation An optimum orientation position helps avoid gas and air accumulations and deposits in the measuring
tube. Promag, nevertheless, supplies a range of functions and accessories for correct measuring of
problematic fluids:
• Electrode Cleaning Circuit (ECC) for applications with fluids producing build-up, e.g. electrically
conductive deposits → "Description of Device Functions" manual.
• Empty Pipe Detection (EPD) ensures the detection of partially filled measuring tubes, e.g. in the case
of degassing fluids.

Vertical orientation
A vertical orientation is ideal in the following cases:
• For self-emptying piping systems and when using empty pipe detection.
• For sludge containing sand or stones and where the solids cause sedimentation.

A0008158

Horizontal orientation
The measuring electrode plane should be horizontal. This prevents brief insulation of the two
electrodes by entrained air bubbles.

! Note!
Empty Pipe Detection functions correctly with the measuring device installed horizontally only when
the transmitter housing is facing upward (see diagram). Otherwise there is no guarantee that Empty
Pipe Detection will respond if the measuring tube is only partially filled or empty.

A
1

2 2

A
3

A0003207

1 EPD electrode for empty pipe detection (not available for "measuring electrode only" option)
2 Measuring electrodes for signal detection
3 Reference electrode for potential equalization (not available for "measuring electrode only" option)

16 Endress+Hauser
Proline Promag 55S

Inlet and outlet runs If possible, install the sensor well clear of fittings such as valves, T-pieces, elbows etc.
Compliance with the following requirements for the inlet and outlet runs is necessary in order to
ensure measuring accuracy.
• Inlet run ≥ 5 × DN
• Outlet run ≥ 2 × DN

³ 5 x DN ³ 2 x DN

A0003210

Adapters Suitable adapters to DIN EN 545 (double-flange reducers) can be used to install the sensor in larger-
diameter pipes. The resultant increase in the rate of flow improves measuring accuracy with very slow-
moving fluids. The nomogram shown here can be used to calculate the pressure loss caused by cross-
section reduction.

! Note!
The nomogram applies to fluids of viscosity similar to water.
1. Calculate the ratio of the diameters d/D.
2. From the nomogram, read off the pressure loss as a function of fluid velocity (downstream from
the reduction) and the d/D ratio.

[mbar] 100

8 m/s

7 m/s

6 m/s

10
5 m/s

4 m/s
max. 8°
3 m/s
d D
2 m/s
1

1 m/s

d / D 0.5 0.6 0.7 0.8 0.9


A0003213

Pressure loss due to adapters (for pressure losses in US units, please contact Endress+Hauser)

Endress+Hauser 17
Proline Promag 55S

Length of connecting cable In order to ensure measuring accuracy, comply with the following instructions when installing the
remote version:
• Secure the cable run or route the cable in an armored conduit. Movement of the cable can falsify the
measuring signal, particularly if the fluid conductivity is low.
• Route the cable well clear of electrical machines and switching elements.
• Ensure potential equalization between sensor and transmitter, if necessary.
• The permissible cable length Lmax depends on the fluid conductivity (see Figure).
• The maximum connecting cable length is 10 m (32.8 ft) when empty pipe detection (EPD) is
switched on.

[µS/cm]

50

40

30
L max
20

10
5
0 [m]
0 10 20 30 40 50 L max
[ft]
0 50 100 150

A0006116

Permitted lengths for connecting cable in remote version, as a function of the conductivity of the fluid
Gray shaded area = permissible area
Lmax = Length of connecting cable

Foundations, supports If the nominal diameter is DN ≥ 350 (14"), mount the sensor on a foundation of adequate load-bearing
strength.

! Note!
Risk of damage.
Do not support the weight of the sensor on the metal casing: the casing would buckle and damage the
internal magnetic coils.

A0003209

Correct support for large nominal diameters (DN ≥ 350 / 14")

18 Endress+Hauser
Proline Promag 55S

Environment

Ambient temperature range Transmitter:


• Standard:
– Compact version: –20 to +50 °C (–4 to +122 °F)
– Remote version: –20 to +60 °C (–4 to +140 °F)
• Optional:
– Compact version: –40 to +50 °C (–40 to +122 °F)
– Remote version: –40 to +60 °C (–40 to +140 °F)

! Note!
At ambient temperatures below –20 °C (–4 °F), the readability of the display may be impaired.
Sensor:
• Flange material carbon steel: –10 to +60 °C (+14 to +140 °F)
• Flange material stainless steel: –40 to +60 °C (–40 to +140 °F)

! Note!
Do not exceed the min. and max. temperatures for the lining of the measuring tube
(→ "Medium temperature range").
Note the following points:
• Install the device at a shady location. Avoid direct sunlight, particularly in warm climatic regions.
• If both fluid and ambient temperatures are high, install the transmitter at a remote location from the
sensor (→ "Medium temperature range").

Storage temperature The storage temperature corresponds to the operating temperature range of the transmitter and
sensor.

Degree of protection • Standard: IP 67 (NEMA 4X) for transmitter and sensor


• Optional: IP 68 (NEMA 6P) for remote version of Promag S sensor
• For information regarding applications where the device is buried directly in the soil or is installed
in a flooded wastewater basin please contact your local Endress+Hauser Sales Center.

Shock and vibration Acceleration up to 2 g by analogy with IEC 600 68-2-6


resistance
(High temperature version: no data available)

Electromagnetic According to IEC/EN 61326 and NAMUR recommendation NE 21


compatibility (EMC)

Endress+Hauser 19
Proline Promag 55S

Process

Medium temperature range The permitted temperature depends on the lining of the measuring tube:
• 0 to +60 °C (+32 to +140 °F) for natural rubber (DN 65 to 600 / 2½ to 24")
• 0 to +80 °C (+32 to +176 °F) for hard rubber (DN 65 to 600 / 2½ to 24")
• –20 to +50 °C (–4 to +122 °F) for polyurethane (DN 25 to 600 / 1 to 24")
• –20 to +180 °C (–4 to +356 °F) for PFA (DN 25 to 200 / 1 to 8"), restrictions → see diagrams
• –40 to +130 °C (–40 to +266 °F) for PTFE (DN 15 to 600 / ½ to 24"), restrictions → see diagrams

TA [°F] [°C] HT
140 60

100 40
2
20

0 PFA
-20
1
PTFE
-40 -40
-40 -20 0 20 40 60 80 100 120 140 160 180 [°C]
TF
-40 0 100 200 300 360 [°F]
A0006119

Promag S compact versions (with PFA or PTFE lining)


TA Ambient temperature
TF Fluid temperature
HT High temperature version with insulation
1 Gray shaded area → temperature range from –10 to –40 °C (–14 to –40 °F) applies only to stainless steel flanges
2 HE + IP 68 to 130 °C (266 °F) only

TA [°F] [°C] HT
140 60

100 40
2
20

0 PFA
-20
1
PTFE
-40 -40
-40 -20 0 20 40 60 80 100 120 140 160 180 [°C]
TF
-40 0 100 200 300 360 [°F]
A0002671

Promag S remote versions (with PFA or PTFE lining)


TA Ambient temperature
TF Fluid temperature
HT High temperature version with insulation
1 Gray shaded area → temperature range from –10 to –40 °C (–14 to –40 °F) applies only to stainless steel flanges
2 HE + IP 68 to 130 °C (266 °F) only

20 Endress+Hauser
Proline Promag 55S

Conductivity Minimum conductivity:


• ≥ 5 μS/cm for all liquids (incl. demineralized water)

! Note!
In the remote version, the required minimum conductivity is also influenced by the length of the cable
→  18.

Pressure-temperature The following diagrams contain material load curves (reference curves) for various process connections
ratings relating to the fluid temperature. But the maximal permissible fluid temperature always depends on
the lining material of the sensor and/or the sealing material.

Process connection: flange according to EN 1092-1 (DIN 2501)


Process connection material: S235JRG2, S235JR+N, P250GH, P245GH, E250C, A105

[psi] [bar]
600 40
PN 40
500 35
30
400
25
PN 25
300 20

200 15
PN 16
10
100 PN 10
5
PN 6
0 0
-40 -20 0 20 40 60 80 100120140160180 [°C]

-40 0 100 200 300 360 [°F]

A0021188-EN

Process connection: flange according to EN 1092-1 (DIN 2501)


Process connection material: 1.4571, F316L

[psi] [bar]
600 40
PN 40
500 35
30
400
25
PN 25
300 20

200 15
PN 16
10
100 PN 10
5 PN 6
0 0
-60 -40 -20 0 20 40 60 80 100120140 160180 [°C]

-40 0 100 200 300 360 [°F]

A0021184-EN

Endress+Hauser 21
Proline Promag 55S

Process connection: flange according to ASME B16.5


Process connection material: A105

[psi] [bar]
900 60
800
700 50 Class 300
600 40
500
400 30
300 20
200 Class 150
10
100
0 0
-40 -20 0 20 40 60 80 100120140 160180 [°C]

-40 0 100 200 300 360 [°F]


A0021182-EN

Process connection: flange according to ASME B16.5


Process connection material: F316L

[psi] [bar]
900 60
800
700 50
600 40
500 Class 300
400 30
300 20
200
10 Class 150
100
0 0
-40 -20 0 20 40 60 80 100120140 160180 [°C]

-40 0 100 200 300 360 [°F]


A0021185-EN

Process connection: flange according to JIS B2220


Process connection material: A105, A350 LF2, F316L

[psi] [bar]
30
400

300 20K
20

200
10K
10
100

0 0
-40 -20 0 20 40 60 80 100120140 160180 [°C]

-40 0 100 200 300 360 [°F]


A0021183-EN

22 Endress+Hauser
Proline Promag 55S

Process connection: flange according to AS 2129 Table E or AS 4087 PN 16


Process connection material: A105, P235GH, P265GH, S235JRG2

[psi] [bar]

300 20

200 15
Table E
10
100
5
0 0
-40 -20 0 20 40 60 80 100120140 160 [°C]

-40 0 100 200 300 [°F]


A0021189-EN

Process connection: flange according to AS 2129 Table E or AS 4087 PN 16


Process connection material: A105, P265GH, S275JR

[psi] [bar]

300 20
PN 16
200 15
10
100
5
0 0
-40 -20 0 20 40 60 80 100120140 160 [°C]

-40 0 100 200 300 [°F]


A0023077-EN

Medium pressure range • EN 1092-1 (DIN 2501): PN 10 (DN 200 to 600 / 8 to 24"), PN 16 (DN 65 to 600 / 2½ to 24"),
(nominal pressure) PN 25 (DN 200 to 600 / 8 to 24"), PN 40 (DN 15 to 150 / ½ to 6")
• ASME B16.5: Class 150 (DN ½ to 24"), Class 300 (DN ½ to 6")
• JIS B2220: 10K (DN 50 to 600 / 2 to 24"), 20K (DN 15 to 600 / ½ to 24")
• AS 2129: Table E (DN 25 / 1", DN 50 / 2")
• AS 4087: PN 16 (DN 50 / 2")

Pressure tightness (lining) Pressure tightness in SI units [mbar]


Promag S Measuring tube Resistance of measuring tube lining to partial vacuum (SI units)
Nominal lining Limit values for abs. pressure [mbar] at various fluid temperatures
diameter
[mm] 25 °C 50 °C 80 °C 100 °C 130 °C 150 °C 180 °C
25 to 600 Polyurethane 0 0 - - - - -
65 to 600 Natural rubber 0 0 - - - - -
65 to 600 Hard rubber 0 0 0 - - - -

Promag S Measuring tube Resistance of measuring tube lining to partial vacuum (SI units)
Nominal lining Limit values for abs. pressure [mbar] at various fluid temperatures
diameter
[mm] 25 °C 80 °C 100 °C 130 °C 150 °C 180 °C
15 PTFE 0 0 0 100 – –
25 PTFE / PFA 0/0 0/0 0/0 100/0 –/0 –/0

Endress+Hauser 23
Proline Promag 55S

32 PTFE / PFA 0/0 0/0 0/0 100/0 –/0 –/0


40 PTFE / PFA 0/0 0/0 0/0 100/0 –/0 –/0
50 PTFE / PFA 0/0 0/0 0/0 100/0 –/0 –/0
65 PTFE / PFA 0/0 * 40/0 130/0 –/0 –/0
80 PTFE / PFA 0/0 * 40/0 130/0 –/0 –/0
100 PTFE / PFA 0/0 * 135/0 170/0 –/0 –/0
125 PTFE / PFA 135/0 * 240/0 385/0 –/0 –/0
150 PTFE / PFA 135/0 * 240/0 385/0 –/0 –/0
200 PTFE / PFA 200/0 * 290/0 410/0 –/0 –/0
250 PTFE 330 * 400 530 – –
300 PTFE 400 * 500 630 – –
350 PTFE 470 * 600 730 – –
400 PTFE 540 * 670 800 – –
450 PTFE
500 PTFE Partial vacuum is impermissible!
600 PTFE
* No value can be quoted.

Pressure tightness in US units [psi = pounds/inch2]


Promag S Measuring tube Resistance of measuring tube lining to partial vacuum (US units)
Nominal lining Limit values for abs. pressure [psi] at various fluid temperatures
diameter
[inch] 77 °F 122 °F 176 °F 212 °F 266 °F 302 °F 356 °F
1 to 24" Polyurethane 0 0 - - - - -
3 to 24" Natural rubber 0 0 - - - - -
3 to 24" Hard rubber 0 0 0 - - - -

Promag S Measuring tube Resistance of measuring tube lining to partial vacuum (US units)
Nominal lining Limit values for abs. pressure [psi] at various fluid temperatures
diameter
[inch] 77 °F 176 °F 212 °F 266 °F 302 °F 356 °F
½" PTFE 0 0 0 1.5 – –
1" PTFE / PFA 0/0 0/0 0/0 1.5/0 –/0 –/0
– PTFE / PFA 0/0 0/0 0/0 1.5/0 –/0 –/0
1½" PTFE / PFA 0/0 0/0 0/0 1.5/0 –/0 –/0
2" PTFE / PFA 0/0 0/0 0/0 1.5/0 –/0 –/0
– PTFE / PFA 0/0 * 0.6/0 1.9/0 –/0 –/0
3" PTFE / PFA 0/0 * 0.6/0 1.9/0 –/0 –/0
4" PTFE / PFA 0/0 * 2.0/0 2.5/0 –/0 –/0
– PTFE / PFA 2.0/0 * 3.5/0 5.6/0 –/0 –/0
6" PTFE / PFA 2.0/0 * 3.5/0 5.6/0 –/0 –/0
8" PTFE / PFA 2.9/0 * 4.2/0 5.9/0 –/0 –/0
10" PTFE 4.8 * 5.8 7.7 – –
12" PTFE 5.8 * 7.3 9.1 – –
14" PTFE 6.8 * 8.7 10.6 – –
16" PTFE 7.8 * 9.7 11.6 – –
18" PTFE
20" PTFE Partial vacuum is impermissible!
24" PTFE
* No value can be quoted.

24 Endress+Hauser
Proline Promag 55S

Limiting flow The diameter of the pipe and the flow rate determine the nominal diameter of the sensor. The
optimum flow velocity is between 2 and 3 m/s (6 to 10 ft/s). The flow velocity (v), moreover, has to be
matched to the physical properties of the fluid:
• v < 2 m/s (6 ft/s): for abrasive fluids where solids do not cause sedimentation (e.g. lime milk)
• v > 2 m/s (6 ft/s): for fluids producing build-up (e.g. wastewater sludge)
• v > 2 m/s (6 ft/s): for abrasive sludge with a high sand or stone content and where the solids easily
cause sedimentation (e.g. ore slurry)

! Note!
Flow velocity can be increased, if necessary, by reducing the nominal diameter of the sensor through
the use of adapters →  17.

Flow rate characteristic values - Promag S (SI units)

Nominal Recommended flow rate Factory settings


diameter

[mm] min./max. full scale value Full scale value Pulse value Low flow cut off
(v ≈ 0.3 or 10 m/s) (v ≈ 2.5 m/s) (≈ 2 pulse/s) (v ≈ 0.04 m/s)

15 4 to 100 dm3/min 25 dm3/min 0.20 dm3 0.5 dm3/min

25 9 to 300 dm3/min 75 dm3/min 0.50 dm3 1 dm3/min

32 15 to 500 dm3/min 125 dm3/min 1.00 dm3 2 dm3/min

40 25 to 700 dm3/min 200 dm3/min 1.50 dm3 3 dm3/min

50 35 to 1100 dm3/min 300 dm3/min 2.50 dm3 5 dm3/min

65 60 to 2000 dm3/min 500 dm3/min 5.00 dm3 8 dm3/min

80 90 to 3000 dm3/min 750 dm3/min 5.00 dm3 12 dm3/min

100 145 to 4700 dm3/min 1200 dm3/min 10.00 dm3 20 dm3/min

125 220 to 7500 dm3/min 1850 dm3/min 15.00 dm3 30 dm3/min

150 20 to 600 m3/h 150 m3/h 0.025 m3 2.5 m3/h

200 35 tof 1100 m3/h 300 m3/h 0.05 m3 5.0 m3/h

250 55 to 1700 m3/h 500 m3/h 0.05 m3 7.5 m3/h

300 80 to 2400 m3/h 750 m3/h 0.10 m3 10 m3/h

350 110 to 3300 m3/h 1000 m3/h 0.10 m3 15 m3/h

400 140 to 4200 m3/h 1200 m3/h 0.15 m3 20 m3/h

450 180 to 5400 m3/h 1500 m3/h 0.25 m3 25 m3/h

500 220 to 6600 m3/h 2000 m3/h 0.25 m3 30 m3/h

600 310 to 9600 m3/h 2500 m3/h 0.30 m3 40 m3/h

Endress+Hauser 25
Proline Promag 55S

Flow rate characteristic values - Promag S (US units)

Nominal Recommended flow rate Factory settings


diameter

[inch] min./max. full scale value Full scale value Pulse value Low flow cut off
(v ≈ 1.0 or 33 ft/s) (v ≈ 8.2 ft/s) (≈ 2 pulse/s) (v ≈ 0.1 ft/s)

½" 1.0 to 27 gal/min 6 gal/min 0.05 gal 0.10 gal/min

1" 2.5 to 80 gal/min 18 gal/min 0.20 gal 0.25 gal/min

1¼" 4 to 130 gal/min 30 gal/min 0.20 gal 0.50 gal/min

1½" 7 to 190 gal/min 50 gal/min 0.50 gal 0.75 gal/min

2" 10 to 300 gal/min 75 gal/min 0.50 gal 1.25 gal/min

2½" 16 to 500 gal/min 130 gal/min 1 gal 2.0 gal/min

3" 24 to 800 gal/min 200 gal/min 2 gal 2.5 gal/min

4" 40 to 1250 gal/min 300 gal/min 2 gal 4.0 gal/min

5" 60 to 1950 gal/min 450 gal/min 5 gal 7.0 gal/min

6" 90 to 2650 gal/min 600 gal/min 5 gal 12 gal/min

8" 155 to 4850 gal/min 1200 gal/min 10 gal 15 gal/min

10" 250 to 7500 gal/min 1500 gal/min 15 gal 30 gal/min

12" 350 to 10600 gal/min 2400 gal/min 25 gal 45 gal/min

14" 500 to 15000 gal/min 3600 gal/min 30 gal 60 gal/min

16" 600 to 19000 gal/min 4800 gal/min 50 gal 60 gal/min

18" 800 to 24000 gal/min 6000 gal/min 50 gal 90 gal/min

20" 1000 to 30000 gal/min 7500 gal/min 75 gal 120 gal/min

24" 1400 to 44 000 gal/min 10500 gal/min 100 gal 180 gal/min

Pressure loss • No pressure loss if the sensor is installed in a pipe of the same nominal diameter.
• Pressure losses for configurations incorporating adapters according to DIN EN 545 →  17.

Vibrations Secure and fix both the piping and the sensor if the vibrations are severe.

! Note!
It is advisable to install sensor and transmitter separately if vibration is excessively severe. Information
on the permitted resistance to vibration and shock →  19.

A0003208

Measures to prevent vibration of the measuring device (L > 10 m / 33 ft)

26 Endress+Hauser
Proline Promag 55S

Mechanical construction
Design, dimensions Transmitter wall-mount housing (non hazardous area and II3G / zone 2)

D
Esc
- + E

B
C
F G
A E

H J K J

N
S S

M
R

L
O
P Q P

A0001150

Dimensions (SI units)

A B C D E F G H J K

215 250 90.5 159.5 135 90 45 > 50 81 53

L M N O P Q R S T 1)

95 53 102 81.5 11.5 192 8 × M5 20 2 × ⌀ 6.5


1)
Securing screw for wall mounting: M6 (screw head max. 10.5 mm)
All dimensions in [mm]

Dimensions (US units)

A B C D E F G H J K

8.46 9.84 3.56 6.27 5.31 3.54 1.77 > 1.97 3.18 2.08

L M N O P Q R S T 1)

3.74 2.08 4.01 3.20 0.45 7.55 8 × M5 0.79 2 × ⌀ 0.26


1)
Securing screw for wall mounting: M6 (screw head max. 0.41")
All dimensions in [inch]

Endress+Hauser 27
Proline Promag 55S

There is a separate mounting kit for the wall-mounted housing. It can be ordered from Endress+Hauser
as an accessory. The following installation variants are possible:
• Panel-mounted installation
• Pipe mounting

Installation in control panel

+0.5 (+0.019)
–0.5 (–0.019)
210 (8.27)

+0.5 (+0.019)
–0.5 (–0.019)
245 (9.65)

~110 (~4.33)

A0001131

Pipe mounting

Ø 20…70
(Ø 0.79…2.75)

~155 (~ 6.1)

A0001132

28 Endress+Hauser
Proline Promag 55S

Sensor, remote version DN ≤ 300 (12")

A B
C

D
F
E
G
J
H L

A0012462

Dimensions (SI units)

DN A B C D E F G H J L

EN (DIN) / JIS / AS1)

15 286 202 84 120 94 200

25 286 202 84 120 94 200


32 286 202 84 120 94 200

40 286 202 84 120 94 200

50 286 202 84 120 94 200

65 336 227 109 180 94 200

80 129 163 143 102 336 227 109 180 94 200

100 336 227 109 180 94 250

125 417 267 150 260 140 250

150 417 267 150 260 140 300

200 472 292 180 324 156 350

250 522 317 205 400 166 450

300 572 342 230 460 166 500

The fitting length (L) is always the same, regardless of the pressure rating.
1) Only DN 25 and DN 50 are available for flanges according to AS.
All dimensions in [mm]

Endress+Hauser 29
Proline Promag 55S

Dimensions (US units)

DN A B C D E F G H J L

ASME

½" 11.3 7.95 3.31 4.72 3.70 7.87

1" 11.3 7.95 3.31 4.72 3.70 7.87

1½" 11.3 7.95 3.31 4.72 3.70 7.87

2" 11.3 7.95 3.31 4.72 3.70 7.87

3" 13.2 8.94 4.29 7.09 3.70 7.87


5.08 6.42 5.63 4.02
4" 13.2 8.94 4.29 7.09 3.70 9.84

6" 16.4 10.5 5.91 10.2 5.51 11.8

8" 18.6 11.5 7.08 12.8 6.14 13.8


10" 20.6 12.5 8.07 15.8 6.54 17.7

12" 22.5 13.5 9.06 18.1 6.54 19.7

The fitting length (L) is always the same, regardless of the pressure rating.
All dimensions in [inch]

High temperature version DN ≤ 300 (12")

D1
(4.33)
110

E1

A0005570

Measurement D1, E1 = Measurement D, E of the standard remote version plus 110 mm (4.33")

30 Endress+Hauser
Proline Promag 55S

Sensor, remote version DN ≥ 300 (12")

A B
C

F
E
G
J
H L

A0003220

Dimensions (SI units)

DN A B C D E F G H J L

EN (DIN)

350 683.5 401.5 282.0 564 288 550


400 735.5 427.5 308.0 616 288 600

450 129 163 143 102 785.5 452.5 333.0 666 292 650

500 836.5 478.0 358.5 717 292 650


600 940.5 530.0 410.5 821 402 780

The fitting length (L) is always the same, regardless of the pressure rating.
All dimensions in [mm]

Dimensions (US units)

DN A B C D E F G H J L

ASME

14" 26.9 15.8 11.1 22.2 11.3 21.7

16" 29.0 16.8 12.1 24.3 11.3 23.6

18" 5.08 6.42 5.63 4.02 30.9 17.8 13.1 26.2 11.5 25.6

20" 32.9 18.8 14.1 28.2 11.5 25.6


24" 37.0 20.9 16.2 32.3 15.8 30.7

The fitting length (L) is always the same, regardless of the pressure rating.
All dimensions in [inch]

Endress+Hauser 31
Proline Promag 55S

Compact version DN ≤ 300 (12")

A B
A* C

D
-Esc+ E

F
E
G
H
K L

A0005423

Dimensions (SI units)

DN A A* B C D E F G H K L
1)
EN (DIN) / JIS / AS
15 341 257 84 94 120 200

25 341 257 84 94 120 200

32 341 257 84 94 120 200

40 341 257 84 94 120 200

50 341 257 84 94 120 200

65 391 282 109 94 180 200


80 227 207 187 168 160 391 282 109 94 180 200

100 391 282 109 94 180 250

125 472 322 150 140 260 250

150 472 322 150 140 260 300

200 527 347 180 156 324 350

250 577 372 205 166 400 450

300 627 397 230 166 460 500

The fitting length (L) is always the same, regardless of the pressure rating.
1)
Only DN 25 and DN 50 are available for flanges according to AS.
All dimensions in [mm]

32 Endress+Hauser
Proline Promag 55S

Dimensions (US units)

DN A A* B C D E F G H K L

ASME

½" 13.4 10.1 3.31 3.70 4.72 7.87

1" 13.4 10.1 3.31 3.70 4.72 7.87

1½" 13.4 10.1 3.31 3.70 4.72 7.87

2" 13.4 10.1 3.31 3.70 4.72 7.87

3" 15.4 11.1 4.29 3.70 7.09 7.87


8.94 8.15 7.36 6.61 6.30
4" 15.4 11.1 4.29 3.70 7.09 9.84

6" 18.6 12.7 5.91 5.51 10.2 11.8

8" 20.8 13.7 7.09 6.14 12.8 13.8


10" 22.7 14.7 8.07 6.54 15.8 17.7

12" 24.7 15.6 9.06 6.54 18.1 19.7

The fitting length (L) is always the same, regardless of the pressure rating.
All dimensions in [inch]

High temperature version DN ≤ 300 (12")

D1
(4.33)
110

E1

A0005529

Measurement D1, E1 = Measurement D, E of the standard compact version plus 110 mm (4.33")

Endress+Hauser 33
Proline Promag 55S

Compact version DN ≥ 300 (12")

A B
A* C

D
-Esc+ E

F
E
G
H
J L

A0005424

Dimensions (SI units)

DN A A* B C D E F G H J L

EN (DIN)

350 738.5 456.5 282.0 564 288 550


400 790.5 482.5 308.0 616 288 600

450 227 207 187 168 160 840.5 507.5 333.0 666 292 650

500 891.5 533.0 358.5 717 292 650


600 995.5 585.0 410.5 821 402 780

The fitting length (L) is always the same, regardless of the pressure rating.
All dimensions in [mm]

Dimensions (US units)

DN A A* B C D E F G H J L

ASME

14" 29.1 18.0 11.1 22.2 11.3 21.7

16" 31.1 19.0 12.1 24.3 11.3 23.6

18" 8.94 8.15 7.36 6.61 6.30 33.1 20.0 13.1 26.2 11.5 25.6

20" 35.1 21.0 14.1 28.2 11.5 25.6


24" 39.2 23.0 16.2 32.3 15.8 30.7

The fitting length (L) is always the same, regardless of the pressure rating.
All dimensions in [inch]

34 Endress+Hauser
Proline Promag 55S

Ground disk for flange connections

DN £ 300 (12") DN ³ 350 (14")


ÆE
ÆE

D
D
ÆB A
ÆB Æ ÆC
A ÆC
Æ

t t

A0003221

Dimensions (SI units)

DN1) A B C D E t

EN (DIN) / JIS / AS 4) PTFE, PFA, PU, HR, NRa5) NRb5)

15 16 – 43 61.5 73
25 26 – 62 77.5 87.5

32 35 – 80 87.5 94.5

40 41 – 82 101 103
50 52 – 101 115.5 108

65 68 53 121 131.5 118

80 80 66 131 154.5 135


6.5
100 104 91.5 156 186.5 153

125 130 117 187 206.5 160

150 158 143.5 217 256 184 2


200 206 192 267 288 205

250 260 245 328 359 240


2)
300 312 294.5 375 413 273
3)
300 310 – 375 404 268

350 2) 343 323.5 433 479 365


2)
400 393 371 480 542 395
2)
450 439 420 538 583 417 9.0

500 2) 493 469 592 650 460


2)
600 593 566 693 766 522
1)
Ground disks at DN 15 to 250 can be used for all flange standards/nominal pressures available as standard.
2) PN 10/16, Cl 150
3)
PN 25, JIS 10K/20K
4)
Only DN 25 and DN 50 are available for flanges according to AS.
5) Abbreviations (lining): PU = Polyurethane, HR = Hard rubber, NR = Natural rubber thin, NR = Natural rubber
a b
thick
All dimensions in [mm]

Endress+Hauser 35
Proline Promag 55S

Dimensions (US units)

DN1) A B C D E t

ASME PTFE, PFA, PU, HR, NRa 2) NRb 2)

½" 0.63 – 1.69 2.42 2.87

1" 1.02 – 2.44 3.05 3.44

1½" 1.61 – 3.23 3.98 4.06

2" 2.05 – 3.98 4.55 4.25

3" 3.15 2.60 5.16 6.08 5.31


0.26
4" 4.09 3.60 6.14 7.34 6.02

6" 6.22 5.65 8.54 10.08 7.24

8" 8.11 7.56 10.5 11.3 8.07 0.08


10" 10.2 9.65 12.9 14.1 9.45

12" 12.3 11.6 14.8 16.3 10.8

14" 13.5 12.7 17.1 18.9 14.4

16" 15.45 14.6 18.9 21.3 15.6

18" 17.3 16.5 21.2 23.0 16.4 0.35

20" 19.4 18.5 23.3 25.6 18.1

24" 23.4 22.3 27.3 30.1 20.6


1) Grounddisks can be used for all pressure ratings.
2)
Abbreviations (lining): PU = Polyurethane, HR = Hard rubber, NRa = Natural rubber thin, NRb = Natural rubber
thick
All dimensions in [inch]

36 Endress+Hauser
Proline Promag 55S

Weight Weight in [kg]

Nominal Weight in kilograms [kg]


diameter

Compact version Remote version (without cable)

Sensor Transmitter

[mm] EN (DIN) / AS* JIS EN (DIN) / AS* JIS (Wall-mount housing)

15 6.5 6.5 4.5 4.5 6.0

25 7.3 7.3 5.3 5.3 6.0

PN 40

PN 40
32 8.0 7.3 6.0 5.3 6.0

40 9.4 8.3 7.4 6.3 6.0

50 10.6 9.3 8.6 7.3 6.0

65 12.0 11.1 10.0 9.1 6.0

80 14.0 12.5 12.0 10.5 6.0


PN 16

PN 16
100 16.0 14.7 14.0 12.7 6.0
125 21.5 21.0 19.5 19.0 6.0

10K
10K

10K
150 25.5 24.5 23.5 22.5 6.0

200 45 41.9 43 39.9 6.0

250 65 69.4 63 67.4 6.0


300 70 72.3 68 70.3 6.0

350 115 79 113 77 6.0


PN 10

PN 10

400 135 100 133 98 6.0

450 175 128 173 126 6.0

500 175 142 173 140 6.0

600 235 188 233 186 6.0

Transmitter (compact version): 3.4 kg


High-temperature version: +1.5 kg
* Only DN 25 and 50 are available for flanges according to AS

Endress+Hauser 37
Proline Promag 55S

Weight in [lbs]
Nominal Weight in pounds [lbs]
diameter
Compact version Remote version (without cable)
Sensor Transmitter
[inch] ASME ASME (Wall-mount housing)
½" 14 10 13
1" 16 12 13
1 ½" 21 16 13
2" 23 19 13
3" 31 26 13
4" 35 31 13
6" 56 52 13
Class 150

Class 150
8" 99 95 13
10" 165 161 13
12" 243 238 13
14" 386 381 13
16" 452 448 13
18" 562 558 13
20" 628 624 13
24" 893 889 13
Transmitter (compact version): 7.5 lbs
High-temperature version: +3.3 lbs

38 Endress+Hauser
Proline Promag 55S

Measuring tube
specifications
Measuring tube specifications - Promag S (SI units)

Nominal Pressure rating Inside diameter of measuring tube


diameter

EN AS AS ASME JIS with with


(DIN) 2129 4087 PFA PTFE PU HR NRa NRb
[mm] [inch] [bar] [lbs] [mm] [mm] [mm] [mm] [mm] [mm]

15 ½" PN 40 – – Cl 150 20K – 15 – – – –

25 1" PN 40 Table E – Cl 150 20K 23 26 24 – – –

32 – PN 40 – – – 20K 32 35 32 – – –

40 1½" PN 40 – – Cl 150 20K 36 41 38 – – –

50 2" PN 40 Table E PN 16 Cl 150 10K 48 52 50 50 – –

65 – PN 16 – – – 10K 63 67 66 66 63 52

80 3" PN 16 Table E PN 16 Cl 150 10K 75 80 79 79 76 65

100 4" PN 16 Table E PN 16 Cl 150 10K 101 104 102 102 101 91

125 – PN 16 – – – 10K 126 129 127 127 127 116

150 6" PN 16 Table E PN 16 Cl 150 10K 154 156 156 156 155 142

200 8" PN 10 Table E PN 16 Cl 150 10K 201 202 204 204 204 190

250 10" PN 10 Table E PN 16 Cl 150 10K – 256 258 258 258 244

300 12" PN 10 Table E PN 16 Cl 150 10K – 306 309 309 309 292

350 14" PN 10 Table E PN 16 Cl 150 10K – 337 342 342 341 322

400 16" PN 10 Table E PN 16 Cl 150 10K – 387 392 392 391 369

450 18" PN 10 Table E PN 16 Cl 150 10K – 432 437 437 440 417

500 20" PN 10 Table E PN 16 Cl 150 10K – 487 492 492 491 466

600 24" PN 10 Table E PN 16 Cl 150 10K – 593 594 594 593 562


Abbreviations (lining): PU = Polyurethane, HR = Hard rubber, NRa = Natural rubber thin, NRb = Natural rubber
thick

Endress+Hauser 39
Proline Promag 55S

Measuring tube specifications - Promag S (US units)

Nominal Pressure rating Inside diameter of measuring tube


diameter

EN AS AS ASME JIS with with


(DIN) 2129 4087 PFA PTFE PU HR NRa NRb
[inch] [mm] [bar] [lbs] [inch] [inch] [inch] [inch] [inch] [inch]

½" 15 PN 40 – – Cl 150 20K – 0.59 – – – –

1" 25 PN 40 Table – Cl 150 20K 0.91 1.02 0.94 – – –


E

– 32 PN 40 – – – 20K 1.26 1.34 1.26 – – –

1½" 40 PN 40 – – Cl 150 20K 1.42 1.61 1.50 – – –

2" 50 PN 40 Table PN 16 Cl 150 10K 1.89 2.05 1.97 1.97 – –


E

– 65 PN 16 – – – 10K 2.48 2.64 2.60 2.60 2.48 2.05

3" 80 PN 16 – – Cl 150 10K 2.95 3.15 3.11 3.11 2.99 2.56

4" 100 PN 16 – – Cl 150 10K 3.98 4.09 4.02 4.02 3.98 3.58

– 125 PN 16 – – – 10K 4.96 5.08 5.00 5.00 5.00 4.57

6" 150 PN 16 – – Cl 150 10K 6.06 6.14 6.14 6.14 6.10 5.59

8" 200 PN 10 – – Cl 150 10K 7.91 7.92 8.03 8.03 8.03 7.48

10" 250 PN 10 – – Cl 150 10K – 10.08 10.16 10.16 10.16 9.61

12" 300 PN 10 – – Cl 150 10K – 12.05 12.17 12.17 12.17 11.50

14" 350 PN 10 – – Cl 150 10K – 13.27 13.46 13.46 13.43 12.68

16" 400 PN 10 – – Cl 150 10K – 15.24 15.43 15.43 15.39 14.53

18" 450 PN 10 – – Cl 150 10K – 17.01 17.20 17.20 17.32 16.42

20" 500 PN 10 – – Cl 150 10K – 19.17 19.37 19.37 19.33 18.35

24" 600 PN 10 – – Cl 150 10K – 23.35 23.39 23.39 23.35 22.13

 Abbreviations (lining): PU = Polyurethane, HR = Hard rubber, NR = Natural rubber thin, NR = Natural rubber
a b
thick

40 Endress+Hauser
Proline Promag 55S

Inside diameter of measuring tube Thickness of lining material


Nominal diameter
with natural rubber NRb1) natural rubber NRb1)

[inch] [mm] [inch] [mm] [inch] [mm]

2½" 65 2.05 52 0.39 10

3" 80 2.56 65 0.39 10

PN 16/150 lbs
4" 100 3.58 91 0.39 10
5" 125 4.57 116 0.39 10

6" 150 5.59 142 0.47 12

8" 200 6.30 190 0.47 12

10" 250 9.61 244 0.47 12

12" 300 11.50 292 0.51 13

14" 350 12.68 322 0.55 14


PN 10
16" 400 14.53 369 0.63 16

18" 450 16.42 417 0.55 14

20" 500 18.35 466 0.67 17

24" 600 22.13 562 0.79 20

10" 250 9.57 243 0.47 12

12" 300 11.46 291 0.47 12

14" 350 12.60 320 0.51 13


150 lbs

16" 400 14.49 368 0.55 14

18" 450 16.42 417 0.55 14

20" 500 18.31 465 0.63 16


24" 600 22.17 563 0.63 16

NRb = Natural rubber thick

Material Transmitter housing:


• Compact and remote version: Powder-coated die-cast aluminum
Sensor housing:
• DN 15 to 300 (½ to 12"): Powder-coated die-cast aluminum
• DN 350 to 600 (14 to 24"): Painted steel
Measuring tube:
• DN < 350 (14"): Stainless steel 1.4301 (304) or 1.4306 (304L). For flanges of carbon steel with
Al/Zn protective coating.
• DN > 300 (12"): Stainless steel 1.4301 (304). For flanges of carbon steel with protective paint finish.
Flange:
• EN 1092-1 (DIN 2501): S235JRG2, S2345JR+N, P245GH, P250GH, E250C, A105, 1.4571, F316L
(DN < 350 (14"): with Al/Zn protective coating; DN > 300 (12") with protective paint finish)
• ASME B16.5: A105; F316L
(DN < 350 (14") with Al/Zn protective coating; DN > 300 (12") with protective paint finish)
• JIS B2220: A105, A350 LF2, F316L
(DN < 350 (14") with Al/Zn protective coating; DN > 300 (12") with protective paint finish)
• AS 2129: A105, P235GH, P265GH, S235JRG2, with Al/Zn protective coating
• AS 4087: A105, P265GH, S275JR, with Al/Zn protective coating
Ground disks: 1.4435 (316L) or Alloy C-22

Endress+Hauser 41
Proline Promag 55S

Electrodes:
• 1.4435 (316L), platinum, Alloy C-22, tantalum, titanium Gr. 2, tungsten carbide coating (for
electrodes made from 1.4435)
• 1.4310 (302) (for brush electrodes), Duplex 1.4462, Alloy X750 (for brush electrodes)
Seals: according to DIN EN 1514-1 form IBC

Fitted electrodes Comes as standard:


• 2 measuring electrodes for signal detection
• 1 EPD electrode for empty pipe detection
• 1 Reference electrode for potential equalization
Optionally available for measuring electrodes made of platinum:
• 1 EPD electrode for empty pipe detection
• 1 Reference electrode for potential equalization
For measuring tube with natural rubber lining in combination with brush electrodes:
• 2 brush electrodes for signal detection

Process connections Flange connection:


• EN 1092-1 (DIN 2501)
– DN < 300 (12"): Form A
– DN > 300 (12"): Form B
– DN 65 (2½") PN 16 and DN 600 (24") PN 16 exclusively according to EN 1092-1
• ASME B16.5
• JIS B2220
• AS 2129
• AS 4087

Surface roughness • Lining with PFA: ≤ 0.4 μm (16 μin)


• Electrodes: 0.3 to 0.5 μm (12 to 20 μin)
All data relate to wetted parts.

42 Endress+Hauser
Proline Promag 55S

Operability
Local operation Display elements
• Liquid-crystal display: illuminated, four lines with 16 characters per line
• Custom configurations for presenting different measured values and status variables
• 3 totalizers
• At ambient temperatures below –20 °C (–4 °F), the readability of the display may be impaired.

Operating elements
• Onsite operation with three optical sensor keys (//)
• Application-specific Quick Setup menus for straightforward commissioning

Language groups Language groups available for operation in different countries:


• Western Europe and America (WEA):
English, German, Spanish, Italian, French, Dutch, Portuguese
• Eastern Europe/Scandinavia (EES):
English, Russian, Polish, Norwegian, Finnish, Swedish, Czech
• South and East Asia (SEA):
English, Japanese, Indonesian
• China (CN):
English, Chinese

! Note!
You can change the language group via the operating program "FieldCare".

Remote operation Remote operation via HART, PROFIBUS DP/PA, FOUNDATION Fieldbus

Endress+Hauser 43
Proline Promag 55S

Certificates and approvals


CE mark The measuring system described in these Operating Instructions therefore complies with the legal
requirements of the EU Directives. Endress+Hauser confirms this by affixing the CE mark to it and by
issuing the CE declaration of conformity.

C-tick symbol The measuring system meets the EMC requirements of the "Australian Communications and Media
Authority (ACMA)".

Ex approval Information on the currently available Ex-rated versions (ATEX, FM, CSA etc.) is available on request
from your Endress+Hauser sales outlet. All information relevant to explosion protection is available in
separate documents that you can order as necessary.

Sanitary compatibility No applicable approvals or certification

Pressure equipment directive The measuring devices can be ordered with or without PED (Pressure Equipment Directive). If a device
with PED is required, this must be ordered explicitly. For devices with nominal diameters less than or
equal to DN 25 (1"), this is neither possible nor necessary.
• With the identification PED/G1/III on the sensor nameplate, Endress+Hauser confirms conformity
with the "Basic safety requirements" of Appendix I of the Pressure Equipment Directive 2014/68/EU.
• Devices with this identification (with PED) are suitable for the following types of fluid:
– Fluids of Group 1 and 2 with a steam pressure of greater or less than 0.5 bar (7.3 psi)
– Unstable gases
• Devices without this identification (without PED) are designed and manufactured according to good
engineering practice. They correspond to the requirements of Art.4, Section 3 of the Pressure
Equipment Directive 2014/68/EU. Their application is illustrated in Diagrams 6 to 9 in Appendix II
of the Pressure Equipment Directive 2014/68/EU.

FOUNDATION Fieldbus The flow device has successfully passed all the test procedures carried out and is certified and
certification registered by the Fieldbus Foundation. The device thus meets all the requirements of the following
specifications:
• Certified to FOUNDATION Fieldbus Specification
• The device meets all the specifications of the FOUNDATION Fieldbus H1
• Interoperability Test Kit (ITK), revision status 5.1 (device certification number: on request)
• The device can also be operated with certified devices of other manufacturers
• Physical Layer Conformance Test of the Fieldbus Foundation

PROFIBUS DP/PA The flowmeter has successfully passed all the test procedures carried out and is certified and registered
certification by the PNO (PROFIBUS User Organization). The device thus meets all the requirements of the following
specifications:
• Certified in accordance with PROFIBUS Profile Version 3.0 (device certification number: available on
request)
• The measuring device can also be operated with certified devices of other manufacturers
(interoperability)

Other standards and • EN 60529


guidelines Degrees of protection by housing (IP code)
• EN 61010-1
Protection Measures for Electrical Equipment for Measurement, Control,Regulation and Laboratory
Procedures
• IEC/EN 61326
"Emission in accordance with requirements for class A".
Electromagnetic compatibility (EMC requirements).
• ANSI/ISA-S82.01
Safety Standard for Electrical and Electronic Test, Measuring, Controlling and related Equipment -
General Requirements. Pollution degree 2, Installation Category II.
• CAN/CSA-C22.2 (No. 1010.1-92)
Safety requirements for Electrical Equipment for Measurement and Control and Laboratory Use.
Pollution degree 2, Installation Category I.

44 Endress+Hauser
Proline Promag 55S

• NAMUR NE 21
Electromagnetic compatibility (EMC) of industrial process and laboratory control equipment.
• NAMUR NE 43
Standardization of the signal level for the breakdown information of digital transmitters with analog
output signal.
• NAMUR NE 53
Software of field devices and signal-processing devices with digital electronics.

Ordering information
! Note!
Endress+Hauser reserves the right to change or modify product, specifications, and ordering
information at any time without notice. Please consult Endress+Hauser or your local representative for
the most recent information.

Accessories
Various accessories are available for the transmitter and the sensor. These can be ordered separately
from Endress+Hauser.

! Note!
For detailed information on specific order codes, please contact the Endress+Hauser service
organization.

Documentation
• Flow Measurement (FA005D)
• Technical Information
– Promag 55H (TI00096D)
• Operating Instructions/Description of Device Functions
– Promag 55 HART (BA00119D/BA00120D)
– Promag 55 PROFIBUS DP/PA (BA00124D/BA00125D)
– Promag 55 FOUNDATION Fieldbus (BA00126D/BA00127D)
• Supplementary documentation on Ex-ratings: ATEX, FM, CSA

Registered trademarks
HART®
Registered trademark of HART Communication Foundation, Austin, USA
PROFIBUS ®
Registered trademark of the PROFIBUS User Organisation, Karlsruhe, Germany
FOUNDATIONTM Fieldbus
Registered trademark of the Fieldbus Foundation, Austin, USA
HistoROM™, S-DAT®, T-DAT®, F-CHIP ®, FieldCare®, Fieldcheck®, Applicator®
Registered or registration-pending trademarks of the Endress+Hauser Group

Endress+Hauser 45
Proline Promag 55S

46 Endress+Hauser
Proline Promag 55S

Endress+Hauser 47
www.addresses.endress.com