Technical Information Proline Promag 55S: Electromagnetic Flowmeter
Technical Information Proline Promag 55S: Electromagnetic Flowmeter
Technical Information
Proline Promag 55S
Electromagnetic flowmeter
Table of contents
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Registered trademarks . . . . . . . . . . . . . . . . . . . . . . . . . 45
Mounting location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Orientation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Inlet and outlet runs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Adapters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Length of connecting cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Foundations, supports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Ambient temperature range . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Storage temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Degree of protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Shock and vibration resistance . . . . . . . . . . . . . . . . . . . . . . . . . 19
Electromagnetic compatibility (EMC) . . . . . . . . . . . . . . . . . . . . 19
Process . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Medium temperature range . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Conductivity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Pressure-temperature ratings . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Medium pressure range (nominal pressure) . . . . . . . . . . . . . . 23
2 Endress+Hauser
Proline Promag 55S
Ue
I
V
B
I
L
A0003191
Ue = B · L · v
Q=A·v
Ue induced voltage
B magnetic induction (magnetic field)
L electrode gap
v flow velocity
Q volume flow
A pipe cross-section
I current strength
Measuring system The flow measuring system consists of the following components:
• Promag 55 transmitter
• Promag S sensor (DN 15 to 600 / ½ to 24")
Two versions are available:
• Compact version: Transmitter and sensor form a single mechanical unit.
• Remote version: Transmitter and sensor are installed separately.
rM
m 2
rC
rS
1 V
A0006118
Solids content flow measurement (m) with the aid of a density and flow measuring device. If the solid density (ρS ) and the density of
the carrier liquid (ρC ) are also known, they can be used to calculate the solids flow.
1 Flow measuring device (Promag 55S) → volume flow (V). The solid density (ρS ) and the density of the transport liquid (ρC )
must be entered in the transmitter.
2 Density measuring device (e.g. "Gammapilot M") → total fluid density (ρM ) (transport liquid and solids)
Endress+Hauser 3
Proline Promag 55S
Input
Measured variable • Flow rate (proportional to induced voltage)
• Conductivity (without temperature compensation)
Measuring ranges • Flow rate: Typical v = 0.01 to 10 m/s (0.03 to 33 ft/s) with the specified measuring accuracy
• Conductivity s = 5 to 2000 μS/cm
not for sensors without reference electrode (Promag S with brush electrodes)
Current input
Active/passive selectable, galvanically isolated, full scale value adjustable, resolution: 3 μA,
temperature coefficient: typically 0.005% o.f.s./°C (0.003% o.f.s./°F)
• Active: 4 to 20 mA, Ri ≤ 150 Ω, Uout = 24 V DC, short-circuit proof
• Passive: 0/4 to 20 mA, Ri ≤ 150 Ω, Umax = 30 V DC
Output
Output signal Current output
Active/passive selectable, galvanically isolated, time constant selectable (0.01 to 100 s),
full scale value adjustable, temperature coefficient: typically 0.005% o.f.s./°C (0.003 % o.f.s./°F),
resolution: 0.5 μA
• Active: 0/4 to 20 mA, RL < 700 Ω (for HART: RL ≥ 250 Ω)
• Passive: 4 to 20 mA; supply voltage VS : 18 to 30 V DC; Ri ≥ 150 Ω
Pulse/frequency output
Active/passive selectable (Ex i version passive only), galvanically isolated
• Active: 24 V DC, 25 mA (max. 250 mA over 20 ms), RL > 100 Ω
• Passive: open collector, 30 V DC, 250 mA
• Frequency output: end frequency 2 to 10000 Hz (fmax = 12500 Hz), on/off ratio 1:1,
pulse width max. 10 s
• Pulse output: pulse value and pulse polarity selectable, pulse width configurable (0.05 to 2000 ms)
PROFIBUS DP interface
• Transmission technology (Physical Layer): RS485 according to ASME/TIA/EIA-485-A: 1998,
galvanically isolated
• Profile Version 3.0
• Data transmission rate: 9.6 kBaud to 12 MBaud
• Automatic identification of data transmission rate
• Function blocks: 2 × analog input, 3 × totalizer
• Output data: volume flow, calculated mass flow, totalizer 1 to 3
• Input data: positive zero return (ON/OFF), totalizer control, value for local display
• Cyclic data transmission compatible with previous model Promag 35S
• Bus address adjustable via miniature switches or local display (optional) at the measuring device
• Available output combination → 6
4 Endress+Hauser
Proline Promag 55S
PROFIBUS PA interface
• Transmission technology (Physical Layer): IEC 61158-2 (MBP), galvanically isolated
• Profile version 3.0
• Current consumption: 11 mA
• Permissible supply voltage: 9 to 32 V
• Bus connection with integrated reverse polarity protection
• Error current FDE (Fault Disconnection Electronic): 0 mA
• Function blocks: 2 × analog input, 3 × totalizer
• Output data: volume flow, calculated mass flow, totalizer 1 to 3
• Input data: positive zero return (ON/OFF), totalizer control, value for local display
• Cyclic data transmission compatible with previous model Promag 35S
• Bus address adjustable via miniature switches or local display (optional) at the measuring device
Pulse/frequency output
Failsafe mode selectable
Relay output
"de-energized" in the event of a fault or power supply failure
PROFIBUS DP/PA
Status and alarm messages in accordance with PROFIBUS Profile Version 3.0
Low flow cut off Switch points for low flow freely selectable.
Galvanic isolation All circuits for inputs, outputs, and power supply are galvanically isolated from each other.
Endress+Hauser 5
Proline Promag 55S
Power supply
Terminal assignment Terminal No.
Order code for
"Input / Output" 20 (+) / 21 (–) 22 (+) / 23 (–) 24 (+) / 25 (–) 26 (+) / 27 (–)
Current output
A – – Frequency output
HART
Current output
B Relay output 2 Relay output 1 Frequency output
HART
PROFIBUS PA
H – – –
FOUNDATION
K – – –
Fieldbus
Current output
C Relay output 2 Relay output 1 Frequency output
HART
Current output
D Status input Relay output Frequency output
HART
Current output
L Status input Relay output 2 Relay output 1
HART
Current output
M Status input Frequency output 2 Frequency output 1
HART
PROFIBUS DP
P Current output Frequency output Status input
PROFIBUS DP
V Relay output 2 Relay output 1 Status input
Current output 1
2 Relay output Current output 2 Frequency output
HART
Current input Current output 1
3 Current output 2 Frequency output
HART
Power consumption AC: < 45 VA at 260 V AC; < 32 VA at 110 V AC (incl. sensor)
DC: < 19 W (including sensor)
Switch-on current:
• Max. 2.5 A (< 200 ms) at 24 V DC
• Max. 2.5 A (< 5 ms) at 110 V AC
• Max. 5.5 A (< 5 ms) at 260 V AC
6 Endress+Hauser
Proline Promag 55S
Electrical connection
A B
d
g
b
a
a
b d/(g)(d)
N (L-) 2 c N (L-) 2 c
L1 (L+)1 L1 (L+)1
b b
A (RxD/TxD-N) 27 A (RxD/TxD-N) 27
B (RxD/TxD-P) 26 B (RxD/TxD-P) 26
– 25 d – 25 d
+ 24 + 24
f – 23 e f – 23 e
+ 22 + 22
– 21 – 21
+ 20 g + 20 g
N (L-) 2 c N (L-) 2 c
L1 (L+)1 L1 (L+)1
b b
A0015195
Endress+Hauser 7
Proline Promag 55S
Electrical connection,
remote version c d
GND
S1
E1
E2
S2
E
S
6 5 7 8 4 37 36 42 41
a
c d
n.c. n.c. n.c.
b
5 7 4 37 42 41
E1
E
E2
GND
A0011722
! Note!
For installation in metal pipes, it is advisable to connect the ground terminal of the transmitter housing
to the piping. Also, observe company-internal grounding guidelines.
A0004375
8 Endress+Hauser
Proline Promag 55S
! Note!
• For sensors without reference electrodes or without metal process connections, carry out potential
equalization as per the instructions for special cases described below. These special measures are
particularly important when standard grounding practice cannot be ensured or extremely strong
matching currents are expected.
• Sensors with brush electrodes do not have a reference electrode. For this reason, ground disks must
be installed if necessary to ensure sufficient potential equalization to the fluid. This applies in
particular to isolating lined pipes which are not grounded → 9.
Special cases
! Note!
Also, observe company-internal grounding guidelines.
A B
A0004376
Endress+Hauser 9
Proline Promag 55S
c a
A006117
! Note!
• Risk of damage by electrochemical corrosion. Note the electrochemical insulation rating, if the
ground disks and measuring electrodes are made of different materials.
• Also, observe company-internal grounding guidelines.
A0004377
Potential equalization/ground disks in the case of plastic pipes or isolating lined pipes
(ground cable: copper wire at least 6 mm 2 / 10 AWG)
10 Endress+Hauser
Proline Promag 55S
! Note!
For the remote version, both the sensor and the transmitter must be installed so that they are
potential-free.
2 2
1
A0004378
Potential equalization and cathodic protection (connecting cable: copper wire at least 6 mm2 / 10 AWG)
1 Isolation transformer power supply
2 Electrically insulated
Endress+Hauser 11
Proline Promag 55S
1
2
3
4
5
6
7
a b
A0003194
a Electrode cable
b Coil current cable
1 Core
2 Core insulation
3 Core shield
4 Core jacket
5 Core reinforcement
6 Cable shield
7 Outer jacket
As an option, Endress+Hauser can also deliver reinforced connecting cables with an additional,
reinforcing metal braid. We recommend such cables for the following cases:
• Directly buried cable
• Cables endangered by rodents
• Device operation which should comply with the IP 68 (NEMA 6P) standard of protection
Operation in zones of severe electrical interference
The measuring device complies with the general safety requirements in accordance with EN 61010-1,
the EMC requirements of IEC/EN 61326 and NAMUR recommendation NE 21.
! Note!
Grounding of the shield is by means of the ground terminals provided for the purpose inside the
connection housing. Keep the stripped and twisted lengths of cable shield to the terminals as short as
possible.
12 Endress+Hauser
Proline Promag 55S
Performance characteristics
Reference operating To DIN EN 29104 and VDI/VDE 2641:
conditions • Fluid temperature: +28 °C ± 2 K (+82 °F ± 2 K)
• Ambient temperature: +22 °C ± 2 K (+72 °F ± 2 K)
• Warm-up time: 30 minutes
Installation:
• Inlet run > 10 × DN
• Outlet run > 5 × DN
• Sensor and transmitter grounded.
• Sensor centered relative to the pipe.
! Note!
Supply-voltage fluctuations have no effect within the specified range.
[%]
2.5
2.0
1.5
1.0
0.5
0
0 1 2 4 6 8 10 [m/s]
v
0 5 10 15 20 25 30 32 [ft]
A0004456
Conductivity
• Max. measuring error not specified
• Without temperature compensation (cell constant is a factory setting)
Conductivity
• Max. ±5% o.r.
(o.r. = of reading)
Endress+Hauser 13
Proline Promag 55S
Installation
Mounting location The accumulation of air or gas bubbles in the measuring tube could result in an increase in measuring
errors. Avoid the following locations:
• At the highest point of a pipeline. Risk of air accumulating.
• Directly upstream from a free pipe outlet in a vertical pipeline.
h ³ 2 ´ DN
A0003202
Mounting location
Installation of pumps
Do not install the sensor on the intake side of a pump. This precaution is to avoid low pressure and the
consequent risk of damage to the lining of the measuring tube. Information on the lining's resistance
to partial vacuum → 23.
It might be necessary to install pulse dampers in systems incorporating reciprocating, diaphragm or
peristaltic pumps. Information on the measuring system's resistance to vibration and shock → 19.
A0003203
Installation of pumps
14 Endress+Hauser
Proline Promag 55S
! Note!
Risk of solids accumulating. Do not install the sensor at the lowest point in the drain. It is advisable to
install a cleaning valve.
³ 2 ´ DN
³ 5 ´ DN
A0003204
Down pipes
Install a siphon or a vent valve downstream of the sensor in down pipes h ≥ 5 m (16.4 ft). This
precaution is to avoid low pressure and the consequent risk of damage to the lining of the measuring
tube. This measure also prevents the system losing prime, which could cause air inclusions.
Information on the lining's resistance to partial vacuum → 23.
2
h
A0008157
Endress+Hauser 15
Proline Promag 55S
Orientation An optimum orientation position helps avoid gas and air accumulations and deposits in the measuring
tube. Promag, nevertheless, supplies a range of functions and accessories for correct measuring of
problematic fluids:
• Electrode Cleaning Circuit (ECC) for applications with fluids producing build-up, e.g. electrically
conductive deposits → "Description of Device Functions" manual.
• Empty Pipe Detection (EPD) ensures the detection of partially filled measuring tubes, e.g. in the case
of degassing fluids.
Vertical orientation
A vertical orientation is ideal in the following cases:
• For self-emptying piping systems and when using empty pipe detection.
• For sludge containing sand or stones and where the solids cause sedimentation.
A0008158
Horizontal orientation
The measuring electrode plane should be horizontal. This prevents brief insulation of the two
electrodes by entrained air bubbles.
! Note!
Empty Pipe Detection functions correctly with the measuring device installed horizontally only when
the transmitter housing is facing upward (see diagram). Otherwise there is no guarantee that Empty
Pipe Detection will respond if the measuring tube is only partially filled or empty.
A
1
2 2
A
3
A0003207
1 EPD electrode for empty pipe detection (not available for "measuring electrode only" option)
2 Measuring electrodes for signal detection
3 Reference electrode for potential equalization (not available for "measuring electrode only" option)
16 Endress+Hauser
Proline Promag 55S
Inlet and outlet runs If possible, install the sensor well clear of fittings such as valves, T-pieces, elbows etc.
Compliance with the following requirements for the inlet and outlet runs is necessary in order to
ensure measuring accuracy.
• Inlet run ≥ 5 × DN
• Outlet run ≥ 2 × DN
³ 5 x DN ³ 2 x DN
A0003210
Adapters Suitable adapters to DIN EN 545 (double-flange reducers) can be used to install the sensor in larger-
diameter pipes. The resultant increase in the rate of flow improves measuring accuracy with very slow-
moving fluids. The nomogram shown here can be used to calculate the pressure loss caused by cross-
section reduction.
! Note!
The nomogram applies to fluids of viscosity similar to water.
1. Calculate the ratio of the diameters d/D.
2. From the nomogram, read off the pressure loss as a function of fluid velocity (downstream from
the reduction) and the d/D ratio.
[mbar] 100
8 m/s
7 m/s
6 m/s
10
5 m/s
4 m/s
max. 8°
3 m/s
d D
2 m/s
1
1 m/s
Pressure loss due to adapters (for pressure losses in US units, please contact Endress+Hauser)
Endress+Hauser 17
Proline Promag 55S
Length of connecting cable In order to ensure measuring accuracy, comply with the following instructions when installing the
remote version:
• Secure the cable run or route the cable in an armored conduit. Movement of the cable can falsify the
measuring signal, particularly if the fluid conductivity is low.
• Route the cable well clear of electrical machines and switching elements.
• Ensure potential equalization between sensor and transmitter, if necessary.
• The permissible cable length Lmax depends on the fluid conductivity (see Figure).
• The maximum connecting cable length is 10 m (32.8 ft) when empty pipe detection (EPD) is
switched on.
[µS/cm]
50
40
30
L max
20
10
5
0 [m]
0 10 20 30 40 50 L max
[ft]
0 50 100 150
A0006116
Permitted lengths for connecting cable in remote version, as a function of the conductivity of the fluid
Gray shaded area = permissible area
Lmax = Length of connecting cable
Foundations, supports If the nominal diameter is DN ≥ 350 (14"), mount the sensor on a foundation of adequate load-bearing
strength.
! Note!
Risk of damage.
Do not support the weight of the sensor on the metal casing: the casing would buckle and damage the
internal magnetic coils.
A0003209
18 Endress+Hauser
Proline Promag 55S
Environment
! Note!
At ambient temperatures below –20 °C (–4 °F), the readability of the display may be impaired.
Sensor:
• Flange material carbon steel: –10 to +60 °C (+14 to +140 °F)
• Flange material stainless steel: –40 to +60 °C (–40 to +140 °F)
! Note!
Do not exceed the min. and max. temperatures for the lining of the measuring tube
(→ "Medium temperature range").
Note the following points:
• Install the device at a shady location. Avoid direct sunlight, particularly in warm climatic regions.
• If both fluid and ambient temperatures are high, install the transmitter at a remote location from the
sensor (→ "Medium temperature range").
Storage temperature The storage temperature corresponds to the operating temperature range of the transmitter and
sensor.
Endress+Hauser 19
Proline Promag 55S
Process
Medium temperature range The permitted temperature depends on the lining of the measuring tube:
• 0 to +60 °C (+32 to +140 °F) for natural rubber (DN 65 to 600 / 2½ to 24")
• 0 to +80 °C (+32 to +176 °F) for hard rubber (DN 65 to 600 / 2½ to 24")
• –20 to +50 °C (–4 to +122 °F) for polyurethane (DN 25 to 600 / 1 to 24")
• –20 to +180 °C (–4 to +356 °F) for PFA (DN 25 to 200 / 1 to 8"), restrictions → see diagrams
• –40 to +130 °C (–40 to +266 °F) for PTFE (DN 15 to 600 / ½ to 24"), restrictions → see diagrams
TA [°F] [°C] HT
140 60
100 40
2
20
0 PFA
-20
1
PTFE
-40 -40
-40 -20 0 20 40 60 80 100 120 140 160 180 [°C]
TF
-40 0 100 200 300 360 [°F]
A0006119
TA [°F] [°C] HT
140 60
100 40
2
20
0 PFA
-20
1
PTFE
-40 -40
-40 -20 0 20 40 60 80 100 120 140 160 180 [°C]
TF
-40 0 100 200 300 360 [°F]
A0002671
20 Endress+Hauser
Proline Promag 55S
! Note!
In the remote version, the required minimum conductivity is also influenced by the length of the cable
→ 18.
Pressure-temperature The following diagrams contain material load curves (reference curves) for various process connections
ratings relating to the fluid temperature. But the maximal permissible fluid temperature always depends on
the lining material of the sensor and/or the sealing material.
[psi] [bar]
600 40
PN 40
500 35
30
400
25
PN 25
300 20
200 15
PN 16
10
100 PN 10
5
PN 6
0 0
-40 -20 0 20 40 60 80 100120140160180 [°C]
A0021188-EN
[psi] [bar]
600 40
PN 40
500 35
30
400
25
PN 25
300 20
200 15
PN 16
10
100 PN 10
5 PN 6
0 0
-60 -40 -20 0 20 40 60 80 100120140 160180 [°C]
A0021184-EN
Endress+Hauser 21
Proline Promag 55S
[psi] [bar]
900 60
800
700 50 Class 300
600 40
500
400 30
300 20
200 Class 150
10
100
0 0
-40 -20 0 20 40 60 80 100120140 160180 [°C]
[psi] [bar]
900 60
800
700 50
600 40
500 Class 300
400 30
300 20
200
10 Class 150
100
0 0
-40 -20 0 20 40 60 80 100120140 160180 [°C]
[psi] [bar]
30
400
300 20K
20
200
10K
10
100
0 0
-40 -20 0 20 40 60 80 100120140 160180 [°C]
22 Endress+Hauser
Proline Promag 55S
[psi] [bar]
300 20
200 15
Table E
10
100
5
0 0
-40 -20 0 20 40 60 80 100120140 160 [°C]
[psi] [bar]
300 20
PN 16
200 15
10
100
5
0 0
-40 -20 0 20 40 60 80 100120140 160 [°C]
Medium pressure range • EN 1092-1 (DIN 2501): PN 10 (DN 200 to 600 / 8 to 24"), PN 16 (DN 65 to 600 / 2½ to 24"),
(nominal pressure) PN 25 (DN 200 to 600 / 8 to 24"), PN 40 (DN 15 to 150 / ½ to 6")
• ASME B16.5: Class 150 (DN ½ to 24"), Class 300 (DN ½ to 6")
• JIS B2220: 10K (DN 50 to 600 / 2 to 24"), 20K (DN 15 to 600 / ½ to 24")
• AS 2129: Table E (DN 25 / 1", DN 50 / 2")
• AS 4087: PN 16 (DN 50 / 2")
Promag S Measuring tube Resistance of measuring tube lining to partial vacuum (SI units)
Nominal lining Limit values for abs. pressure [mbar] at various fluid temperatures
diameter
[mm] 25 °C 80 °C 100 °C 130 °C 150 °C 180 °C
15 PTFE 0 0 0 100 – –
25 PTFE / PFA 0/0 0/0 0/0 100/0 –/0 –/0
Endress+Hauser 23
Proline Promag 55S
Promag S Measuring tube Resistance of measuring tube lining to partial vacuum (US units)
Nominal lining Limit values for abs. pressure [psi] at various fluid temperatures
diameter
[inch] 77 °F 176 °F 212 °F 266 °F 302 °F 356 °F
½" PTFE 0 0 0 1.5 – –
1" PTFE / PFA 0/0 0/0 0/0 1.5/0 –/0 –/0
– PTFE / PFA 0/0 0/0 0/0 1.5/0 –/0 –/0
1½" PTFE / PFA 0/0 0/0 0/0 1.5/0 –/0 –/0
2" PTFE / PFA 0/0 0/0 0/0 1.5/0 –/0 –/0
– PTFE / PFA 0/0 * 0.6/0 1.9/0 –/0 –/0
3" PTFE / PFA 0/0 * 0.6/0 1.9/0 –/0 –/0
4" PTFE / PFA 0/0 * 2.0/0 2.5/0 –/0 –/0
– PTFE / PFA 2.0/0 * 3.5/0 5.6/0 –/0 –/0
6" PTFE / PFA 2.0/0 * 3.5/0 5.6/0 –/0 –/0
8" PTFE / PFA 2.9/0 * 4.2/0 5.9/0 –/0 –/0
10" PTFE 4.8 * 5.8 7.7 – –
12" PTFE 5.8 * 7.3 9.1 – –
14" PTFE 6.8 * 8.7 10.6 – –
16" PTFE 7.8 * 9.7 11.6 – –
18" PTFE
20" PTFE Partial vacuum is impermissible!
24" PTFE
* No value can be quoted.
24 Endress+Hauser
Proline Promag 55S
Limiting flow The diameter of the pipe and the flow rate determine the nominal diameter of the sensor. The
optimum flow velocity is between 2 and 3 m/s (6 to 10 ft/s). The flow velocity (v), moreover, has to be
matched to the physical properties of the fluid:
• v < 2 m/s (6 ft/s): for abrasive fluids where solids do not cause sedimentation (e.g. lime milk)
• v > 2 m/s (6 ft/s): for fluids producing build-up (e.g. wastewater sludge)
• v > 2 m/s (6 ft/s): for abrasive sludge with a high sand or stone content and where the solids easily
cause sedimentation (e.g. ore slurry)
! Note!
Flow velocity can be increased, if necessary, by reducing the nominal diameter of the sensor through
the use of adapters → 17.
[mm] min./max. full scale value Full scale value Pulse value Low flow cut off
(v ≈ 0.3 or 10 m/s) (v ≈ 2.5 m/s) (≈ 2 pulse/s) (v ≈ 0.04 m/s)
Endress+Hauser 25
Proline Promag 55S
[inch] min./max. full scale value Full scale value Pulse value Low flow cut off
(v ≈ 1.0 or 33 ft/s) (v ≈ 8.2 ft/s) (≈ 2 pulse/s) (v ≈ 0.1 ft/s)
24" 1400 to 44 000 gal/min 10500 gal/min 100 gal 180 gal/min
Pressure loss • No pressure loss if the sensor is installed in a pipe of the same nominal diameter.
• Pressure losses for configurations incorporating adapters according to DIN EN 545 → 17.
Vibrations Secure and fix both the piping and the sensor if the vibrations are severe.
! Note!
It is advisable to install sensor and transmitter separately if vibration is excessively severe. Information
on the permitted resistance to vibration and shock → 19.
A0003208
26 Endress+Hauser
Proline Promag 55S
Mechanical construction
Design, dimensions Transmitter wall-mount housing (non hazardous area and II3G / zone 2)
D
Esc
- + E
B
C
F G
A E
H J K J
N
S S
M
R
L
O
P Q P
A0001150
A B C D E F G H J K
L M N O P Q R S T 1)
A B C D E F G H J K
8.46 9.84 3.56 6.27 5.31 3.54 1.77 > 1.97 3.18 2.08
L M N O P Q R S T 1)
Endress+Hauser 27
Proline Promag 55S
There is a separate mounting kit for the wall-mounted housing. It can be ordered from Endress+Hauser
as an accessory. The following installation variants are possible:
• Panel-mounted installation
• Pipe mounting
+0.5 (+0.019)
–0.5 (–0.019)
210 (8.27)
+0.5 (+0.019)
–0.5 (–0.019)
245 (9.65)
~110 (~4.33)
A0001131
Pipe mounting
Ø 20…70
(Ø 0.79…2.75)
~155 (~ 6.1)
A0001132
28 Endress+Hauser
Proline Promag 55S
A B
C
D
F
E
G
J
H L
A0012462
DN A B C D E F G H J L
The fitting length (L) is always the same, regardless of the pressure rating.
1) Only DN 25 and DN 50 are available for flanges according to AS.
All dimensions in [mm]
Endress+Hauser 29
Proline Promag 55S
DN A B C D E F G H J L
ASME
The fitting length (L) is always the same, regardless of the pressure rating.
All dimensions in [inch]
D1
(4.33)
110
E1
A0005570
Measurement D1, E1 = Measurement D, E of the standard remote version plus 110 mm (4.33")
30 Endress+Hauser
Proline Promag 55S
A B
C
F
E
G
J
H L
A0003220
DN A B C D E F G H J L
EN (DIN)
450 129 163 143 102 785.5 452.5 333.0 666 292 650
The fitting length (L) is always the same, regardless of the pressure rating.
All dimensions in [mm]
DN A B C D E F G H J L
ASME
18" 5.08 6.42 5.63 4.02 30.9 17.8 13.1 26.2 11.5 25.6
The fitting length (L) is always the same, regardless of the pressure rating.
All dimensions in [inch]
Endress+Hauser 31
Proline Promag 55S
A B
A* C
D
-Esc+ E
F
E
G
H
K L
A0005423
DN A A* B C D E F G H K L
1)
EN (DIN) / JIS / AS
15 341 257 84 94 120 200
The fitting length (L) is always the same, regardless of the pressure rating.
1)
Only DN 25 and DN 50 are available for flanges according to AS.
All dimensions in [mm]
32 Endress+Hauser
Proline Promag 55S
DN A A* B C D E F G H K L
ASME
The fitting length (L) is always the same, regardless of the pressure rating.
All dimensions in [inch]
D1
(4.33)
110
E1
A0005529
Measurement D1, E1 = Measurement D, E of the standard compact version plus 110 mm (4.33")
Endress+Hauser 33
Proline Promag 55S
A B
A* C
D
-Esc+ E
F
E
G
H
J L
A0005424
DN A A* B C D E F G H J L
EN (DIN)
450 227 207 187 168 160 840.5 507.5 333.0 666 292 650
The fitting length (L) is always the same, regardless of the pressure rating.
All dimensions in [mm]
DN A A* B C D E F G H J L
ASME
18" 8.94 8.15 7.36 6.61 6.30 33.1 20.0 13.1 26.2 11.5 25.6
The fitting length (L) is always the same, regardless of the pressure rating.
All dimensions in [inch]
34 Endress+Hauser
Proline Promag 55S
D
D
ÆB A
ÆB Æ ÆC
A ÆC
Æ
t t
A0003221
DN1) A B C D E t
15 16 – 43 61.5 73
25 26 – 62 77.5 87.5
32 35 – 80 87.5 94.5
40 41 – 82 101 103
50 52 – 101 115.5 108
Endress+Hauser 35
Proline Promag 55S
DN1) A B C D E t
36 Endress+Hauser
Proline Promag 55S
Sensor Transmitter
PN 40
PN 40
32 8.0 7.3 6.0 5.3 6.0
PN 16
100 16.0 14.7 14.0 12.7 6.0
125 21.5 21.0 19.5 19.0 6.0
10K
10K
10K
150 25.5 24.5 23.5 22.5 6.0
PN 10
Endress+Hauser 37
Proline Promag 55S
Weight in [lbs]
Nominal Weight in pounds [lbs]
diameter
Compact version Remote version (without cable)
Sensor Transmitter
[inch] ASME ASME (Wall-mount housing)
½" 14 10 13
1" 16 12 13
1 ½" 21 16 13
2" 23 19 13
3" 31 26 13
4" 35 31 13
6" 56 52 13
Class 150
Class 150
8" 99 95 13
10" 165 161 13
12" 243 238 13
14" 386 381 13
16" 452 448 13
18" 562 558 13
20" 628 624 13
24" 893 889 13
Transmitter (compact version): 7.5 lbs
High-temperature version: +3.3 lbs
38 Endress+Hauser
Proline Promag 55S
Measuring tube
specifications
Measuring tube specifications - Promag S (SI units)
32 – PN 40 – – – 20K 32 35 32 – – –
65 – PN 16 – – – 10K 63 67 66 66 63 52
100 4" PN 16 Table E PN 16 Cl 150 10K 101 104 102 102 101 91
150 6" PN 16 Table E PN 16 Cl 150 10K 154 156 156 156 155 142
200 8" PN 10 Table E PN 16 Cl 150 10K 201 202 204 204 204 190
250 10" PN 10 Table E PN 16 Cl 150 10K – 256 258 258 258 244
300 12" PN 10 Table E PN 16 Cl 150 10K – 306 309 309 309 292
350 14" PN 10 Table E PN 16 Cl 150 10K – 337 342 342 341 322
400 16" PN 10 Table E PN 16 Cl 150 10K – 387 392 392 391 369
450 18" PN 10 Table E PN 16 Cl 150 10K – 432 437 437 440 417
500 20" PN 10 Table E PN 16 Cl 150 10K – 487 492 492 491 466
600 24" PN 10 Table E PN 16 Cl 150 10K – 593 594 594 593 562
Abbreviations (lining): PU = Polyurethane, HR = Hard rubber, NRa = Natural rubber thin, NRb = Natural rubber
thick
Endress+Hauser 39
Proline Promag 55S
4" 100 PN 16 – – Cl 150 10K 3.98 4.09 4.02 4.02 3.98 3.58
6" 150 PN 16 – – Cl 150 10K 6.06 6.14 6.14 6.14 6.10 5.59
8" 200 PN 10 – – Cl 150 10K 7.91 7.92 8.03 8.03 8.03 7.48
Abbreviations (lining): PU = Polyurethane, HR = Hard rubber, NR = Natural rubber thin, NR = Natural rubber
a b
thick
40 Endress+Hauser
Proline Promag 55S
PN 16/150 lbs
4" 100 3.58 91 0.39 10
5" 125 4.57 116 0.39 10
Endress+Hauser 41
Proline Promag 55S
Electrodes:
• 1.4435 (316L), platinum, Alloy C-22, tantalum, titanium Gr. 2, tungsten carbide coating (for
electrodes made from 1.4435)
• 1.4310 (302) (for brush electrodes), Duplex 1.4462, Alloy X750 (for brush electrodes)
Seals: according to DIN EN 1514-1 form IBC
42 Endress+Hauser
Proline Promag 55S
Operability
Local operation Display elements
• Liquid-crystal display: illuminated, four lines with 16 characters per line
• Custom configurations for presenting different measured values and status variables
• 3 totalizers
• At ambient temperatures below –20 °C (–4 °F), the readability of the display may be impaired.
Operating elements
• Onsite operation with three optical sensor keys (//)
• Application-specific Quick Setup menus for straightforward commissioning
! Note!
You can change the language group via the operating program "FieldCare".
Remote operation Remote operation via HART, PROFIBUS DP/PA, FOUNDATION Fieldbus
Endress+Hauser 43
Proline Promag 55S
C-tick symbol The measuring system meets the EMC requirements of the "Australian Communications and Media
Authority (ACMA)".
Ex approval Information on the currently available Ex-rated versions (ATEX, FM, CSA etc.) is available on request
from your Endress+Hauser sales outlet. All information relevant to explosion protection is available in
separate documents that you can order as necessary.
Pressure equipment directive The measuring devices can be ordered with or without PED (Pressure Equipment Directive). If a device
with PED is required, this must be ordered explicitly. For devices with nominal diameters less than or
equal to DN 25 (1"), this is neither possible nor necessary.
• With the identification PED/G1/III on the sensor nameplate, Endress+Hauser confirms conformity
with the "Basic safety requirements" of Appendix I of the Pressure Equipment Directive 2014/68/EU.
• Devices with this identification (with PED) are suitable for the following types of fluid:
– Fluids of Group 1 and 2 with a steam pressure of greater or less than 0.5 bar (7.3 psi)
– Unstable gases
• Devices without this identification (without PED) are designed and manufactured according to good
engineering practice. They correspond to the requirements of Art.4, Section 3 of the Pressure
Equipment Directive 2014/68/EU. Their application is illustrated in Diagrams 6 to 9 in Appendix II
of the Pressure Equipment Directive 2014/68/EU.
FOUNDATION Fieldbus The flow device has successfully passed all the test procedures carried out and is certified and
certification registered by the Fieldbus Foundation. The device thus meets all the requirements of the following
specifications:
• Certified to FOUNDATION Fieldbus Specification
• The device meets all the specifications of the FOUNDATION Fieldbus H1
• Interoperability Test Kit (ITK), revision status 5.1 (device certification number: on request)
• The device can also be operated with certified devices of other manufacturers
• Physical Layer Conformance Test of the Fieldbus Foundation
PROFIBUS DP/PA The flowmeter has successfully passed all the test procedures carried out and is certified and registered
certification by the PNO (PROFIBUS User Organization). The device thus meets all the requirements of the following
specifications:
• Certified in accordance with PROFIBUS Profile Version 3.0 (device certification number: available on
request)
• The measuring device can also be operated with certified devices of other manufacturers
(interoperability)
44 Endress+Hauser
Proline Promag 55S
• NAMUR NE 21
Electromagnetic compatibility (EMC) of industrial process and laboratory control equipment.
• NAMUR NE 43
Standardization of the signal level for the breakdown information of digital transmitters with analog
output signal.
• NAMUR NE 53
Software of field devices and signal-processing devices with digital electronics.
Ordering information
! Note!
Endress+Hauser reserves the right to change or modify product, specifications, and ordering
information at any time without notice. Please consult Endress+Hauser or your local representative for
the most recent information.
Accessories
Various accessories are available for the transmitter and the sensor. These can be ordered separately
from Endress+Hauser.
! Note!
For detailed information on specific order codes, please contact the Endress+Hauser service
organization.
Documentation
• Flow Measurement (FA005D)
• Technical Information
– Promag 55H (TI00096D)
• Operating Instructions/Description of Device Functions
– Promag 55 HART (BA00119D/BA00120D)
– Promag 55 PROFIBUS DP/PA (BA00124D/BA00125D)
– Promag 55 FOUNDATION Fieldbus (BA00126D/BA00127D)
• Supplementary documentation on Ex-ratings: ATEX, FM, CSA
Registered trademarks
HART®
Registered trademark of HART Communication Foundation, Austin, USA
PROFIBUS ®
Registered trademark of the PROFIBUS User Organisation, Karlsruhe, Germany
FOUNDATIONTM Fieldbus
Registered trademark of the Fieldbus Foundation, Austin, USA
HistoROM™, S-DAT®, T-DAT®, F-CHIP ®, FieldCare®, Fieldcheck®, Applicator®
Registered or registration-pending trademarks of the Endress+Hauser Group
Endress+Hauser 45
Proline Promag 55S
46 Endress+Hauser
Proline Promag 55S
Endress+Hauser 47