0% found this document useful (0 votes)
345 views

Sensus WPD Brochure

The document summarizes the main characteristics of the WP-Dynamic Turbine Water Meter for measuring cold water flow rates up to 50°C and PN 16 pressure. It has a hermetically sealed register, patented hydrodynamically balanced rotor, and symmetrical calibration adjustment. Key specifications include nominal diameters from 40-400mm, maximum flow rates, minimum flow rates, accuracy curves, head loss curves, dimensions, weights, materials, dials, pulse values, and available designs.

Uploaded by

Noel
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
345 views

Sensus WPD Brochure

The document summarizes the main characteristics of the WP-Dynamic Turbine Water Meter for measuring cold water flow rates up to 50°C and PN 16 pressure. It has a hermetically sealed register, patented hydrodynamically balanced rotor, and symmetrical calibration adjustment. Key specifications include nominal diameters from 40-400mm, maximum flow rates, minimum flow rates, accuracy curves, head loss curves, dimensions, weights, materials, dials, pulse values, and available designs.

Uploaded by

Noel
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

WP-Dynamic Turbine Water Meter

for cold water up to 50 ºC / PN 16


DN 40 … DN 400

Main characteristics Application

Hermetically sealed register (IP 68)


Measurement of high, relatively constant flow rates, e.g. behind pumps
Patented hydrodynamically balanced rotor
(≤DN 300)
Patented symmetrical calibration adjustment Available options
(≤DN 300)
Register may be rotated through 360°
Up to 3 pulsers (1 x OD, 2 x RD) may be fitted without breaking the approval
High overload capability seal
Pattern approved removable measuring element 1/4” connection port for pressure sensors
Powder coating affords max. corrosion protection May be equipped with 3 different electronic registers
Not affected by external magnetic fields

HYBRID ELECTRONIC ENCODER

Cold water meters pressure rate PN 40 please see special leaflet

www.sensus.com
Pattern Approval Sign Installation

Nominal Diameter DN 40 ...


D95 DN 300 horizontal
Pipe vertical
Marking:
6.132.36 Metrological class B inclined
30 °C Meter head upwards
sideways
Nominal Diameter DN 400
D80
Installation Requirements
Marking:
Unrestricted straight pipe in front of the meter 3 x DN (DN400 5 x DN)
6.132.01 Metrological class B
30 °C No abrupt restrictions directly behind the meter

Performance Table

Performance data WP-Dynamic 50 ºC


Nominal Diameter DN 40 50 65 80 100 125 150 200 250 300 400

Size of meter (acc. to EEC) Qn 10 15 25 40 60 100 150 250 400 600 1000
Qmax maximum peak flow
once in life time 24 h Qmax m3/h 60 90 120 200 300 350 600 1200 1600 2000 3000
or 5 min. 1,2 x Qmax (±2%)
Qn continuous flow (±2%) m3/h 40 50 70 120 230 250 450 800 1250 1400 2000
Qt transitional flow (±2%) m3/h 0.8 0.7 0.8 0.8 1.8 2.0 4.0 6.0 11.0 15.0 50
Qmin minimum flow (±5%) m3/h 0.30 0.30 0.40 0.50 0.80 1.00 1.8 4.0 6.0 12.0 25
starting flow m3/h 0.15 0.15 0.20 0.25 0.25 0.5 1.0 1.5 3.0 8.0 15

Performance data according to EEC-specification 30 ºC class B



Nominal Diameter DN 40 50 65 80 100 125 150 200 250 300 400
Size of meter (acc. to EEC) Qn 10 15 25 40 60 100 150 250 400 600 1000
Qmax maximum peak flow
short time m3/h 30 30 50 80 120 200 300 500 800 1200 2000
Qn continuous flow m /h 3
15 15 25 40 60 100 150 250 400 600 1000
Qt transitional flow m3/h 3.0 3.0 5.0 8.0 12.0 20.0 30 50 80 120 200
Qmin minimum flow m3/h 0.45 0.45 0.75 1.20 1.80 3.00 4.5 7.5 12.0 18.0 30

LB1100INT Page 2
Typical Accuracy Curve Typical Head Loss Curve

5%

+
2%
%
error

2%
-
5%

Qmin Qt Qn m3/h
Qmax
flow ratem3/h

Qmax = maximum peak flow


Qn = continuous flow
Qt = transitional flow ±2%
Qmin = minimum flow ±5%

Dimensions and Weights

Nominal Diameter DN 40 50 65 80 80 100 125 150 200 250 300 400


Size of meter (acc. to EEC) Qn 10 15 25 40 40 60 100 150 250 400 600 1000
Dimensions overall length L *) mm 220 200 200 200 225 250 250 300 350 450 500 500
height H mm 120 120 120 150 150 150 160 177 206 231 256 380
h mm 69 73 85 95 95 105 118 135 162 194 226 295
g mm 200 200 200 270 270 270 280 356 441 466 491 785
Weights meter kg 7.4 7.7 10.0 13.6 14.0 18.0 20.5 35.5 50.5 72.3 99.3 187
measuring element kg 1.4 1.4 1.4 3.0 3.0 3.0 3.0 5.5 7.5 7.5 7.5 25
body kg 6.0 6.3 8.6 10.6 11.0 15.0 17.5 30.0 43.0 63.8 91.8 162

*) Other overall lengths on request

Dimension Picture Materials

Body PN16 cast iron


Measuring element plastic
Rotor plastic
We also use brass
the following materials stainless steel

WP-Dynamic for cold water


LB1100INT Page 3
Dials

DN 40 … DN 125 DN 150 …DN 300 DN 400

Diameter Nominal Smallest reading Max. reading


DN m3 m3
50 ... 125 0.0005 1 000 000
150 ... 300 0.005 10 000 000
400 0.05 100 000 000

Pulse Values

Pulser pulse value


DN 40 … DN 125 DN 150 ... DN 300 DN 400

RD 01 0.1 and 1 m3 1 and 10 m3


10 and
alternatively alternatively
100 m3
0.01 and 1 m3 0.1 and 10 m3

OD 01 0.001 m3 0.01 m3 0.1 m3

OD 03 0.01 m3 0.1 m3 1 m3

Available Designs
Diameter Nominal DN 40 50 65 80 80 100
Overall length *) mm 220 200 200 200 225 250
Order no. PN16 828593 828595 828597 828599 828601 828603

Diameter Nominal DN 125 150 200 250 300 400


Overall length *) mm 250 300 350 450 500 500
Order no. PN16 828605 828607 828717 828719 828743 829195
Other overall lengths on request

Order Example
type
diameter nominal
working temperature
pressure rate
overall length
WP-Dynamic, DN 50, 50/16, L= 200 mm, 1/0.1 m3 pulse values
drilled according to EN 1092 PN 16 flange drilling
828595 order no.

Certified according to ISO 9001


Quality Management System ÖQS Reg.no. 3496/0

UK & Ireland Enquiries


Sensus Metering Systems 11 The Quadrangle, Abbey Park, Romsey, Hampshire SO51 9DL UK
T: +44 (0) 1794 526100 F: +44 (0) 1794 526101 Email: [email protected] www.sensus.com

International Enquiries
Sensus GmbH Hannover Meineckestraße 10, D-30880 Laatzen Germany
T: +49 (0) 5102 74-0 F: +49 (0) 5102 74-3341 Email: [email protected] www.sensus.com

09001 Subject to changes without prior notice. LB1100INT Page 4