vph24 v2.0
vph24 v2.0
Overexcitation protection
ANSI 24, IEC V/HZ
VERSION INFORMATION
2 Overexcitation protection
www.protecta.hu
CONTENTS
CONTENTS
3 Overexcitation protection
www.protecta.hu
USED SYMBOLS
USED SYMBOLS
Additional information
4 Overexcitation protection
www.protecta.hu
OVEREXCITATION
PROTECTION FUNCTION
The problem to be solved is as follows. The flux is the integrated value of the voltage:
𝛷(𝑡) = 𝛷 + 𝑢(𝑡) 𝑑𝑡
In steady state, this integral can be high if the area under the sinusoidal voltage-time function is
large. Mathematically this means that in steady state the flux, as the integral of the sinusoidal
voltage function, can be expressed as
𝑈
𝛷(𝑡) = 𝑘 𝑐𝑜𝑠 𝜔 𝑡
𝑓
The peak value of the flux increases if the magnitude of the voltage increases, and/or the flux can
be high if the duration of a period increases; this means that the frequency of the voltage
decreases. That is, the flux is proportional to the peak value (or to the RMS value) of the voltage
and inversely proportional to the frequency.
Note: the overexcitation protection function is intended to be applied near the generator, where
the voltage is expected to be pure sinusoidal, without any distortion. Therefore, a continuous
integration of the voltage and a simple peak detection algorithm can be applied.
The effect of high flux values is the symmetrical saturation of the iron core of the generator or that
of the unit transformer. During saturation, the magnetizing current is high and distorted; high
current peaks can be detected. The odd harmonic components of the current are of high
magnitude and the RMS value of the current also increases. The high peak values of the currents
generate high dynamic forces, the high RMS value causes overheating. During saturation, the
flux leaves the iron core and high eddy currents are generated in the metallic part of the generator
or transformer in which normally no current flows, and which is not designed to withstand
overheating.
The frequency can deviate from the rated network frequency during start-up of the generator or
at an unwanted disconnection of the load. In this case the generator is not connected to the
network and the frequency is not kept at a “constant” value. If the generator is excited in this state
and the frequency is below the rated value, then the flux may increase above the tolerated value.
Similar problems may occur in distributed generating stations in case of island operation.
5 Overexcitation protection
www.protecta.hu
OVEREXCITATION
PROTECTION FUNCTION
The supervised quantity is the calculated U/f value as a percentage of the nominal values (index
N):
𝑈 𝑈
𝑓 𝑈
𝐺= 100[%] = 100[%]
𝑈 𝑓
𝑓 𝑓
The over-dimensioning of generators in this respect is usually about 5%, that of the transformer
about 10%, but for unit transformers this factor can be even higher.
By function pickup, the protection generates a start signal and a delayed alarm signal aimed to
inform the controller to decrease the excitation. If the time delay (determined by the parameter
values of the selected characteristics) expires, the function generates a trip command to decrease
or to switch off the excitation and the generator.
6 Overexcitation protection
www.protecta.hu
OVEREXCITATION
PROTECTION FUNCTION
Operating time
𝑡(𝐺) = 𝑡 when 𝐺 >𝐺
t(G)
tOP
G
GS
where
tOP (seconds) theoretical operating time if G> GS, fix, according to the parameter
setting “Definite Time Delay”.
Reset time
7 Overexcitation protection
www.protecta.hu
OVEREXCITATION
PROTECTION FUNCTION
Thermal counter
Once the actual U/f value initiates a function start, a thermal counter also starts. At counter value
100%, the function initiates a trip command.
Reset time
If the calculated flux is below the drop-off flux value (when 𝐺 < 0.95 ∗ 𝐺 ), then the calculated
flux value decreases linearly to zero. The time to reach zero is defined by the parameter “Cooling
Time”.
10
Minutes
0.1
100 105 110 115 120 125 130 135 140
Volts/Hertz in %
8 Overexcitation protection
www.protecta.hu
OVEREXCITATION
PROTECTION FUNCTION
where
TMS = 1… 60, time multiplier setting,
U/f flux value calculated at the measured voltage and frequency,
UN/fN flux at rated voltage and rated frequency,
Uset/fset flux setting value.
100
Max Time Delay
0.1
100 110 120 130 140 150 160
Volts/Hertz in %
If the function starts, the maximum tripping time is limited by the parameter “Max Time Delay”.
This time delay is valid if the flux is above the preset value of “Start U/f LowSet”.
This inverse type characteristic is also combined with a minimum time delay, the value of which
is set by user parameter “Min Time Delay”. This time delay is valid if the flux is above the setting
value of “Start U/f HighSet”.
9 Overexcitation protection
www.protecta.hu
OVEREXCITATION
PROTECTION FUNCTION
Reset time
If the calculated flux is below the drop-off flux value (when 𝐺 < 0.95 ∗ 𝐺 ), then the calculated
flux value decreases linearly to zero. The time to reach zero is defined by the parameter “Cooling
Time”.
10 Overexcitation protection
www.protecta.hu
OVEREXCITATION
PROTECTION FUNCTION
VPH24
Status
signals
Flux calculation
This module integrates the voltage to obtain the flux time-function and determines the
magnitude of the flux.
Characteristics
This module calculates the required time delay based on the magnitude of the flux and the
parameter settings.
Decision logic
The decision logic module combines the status signals to generate the trip command of the
function.
11 Overexcitation protection
www.protecta.hu
OVEREXCITATION
PROTECTION FUNCTION
ULL FluxMagn
Flux
calculation
12 Overexcitation protection
www.protecta.hu
OVEREXCITATION
PROTECTION FUNCTION
The inputs are the magnitude of the flux (FluxMagn) and parameters.
The outputs are the internal status signals of the function. These indicate the started state and
the generated trip command if the time delay determined by the characteristics expired.
FluxMagn
Enumerated parameter
Integer parameters
13 Overexcitation protection
www.protecta.hu
OVEREXCITATION
PROTECTION FUNCTION
Float parameters
14 Overexcitation protection
www.protecta.hu
OVEREXCITATION
PROTECTION FUNCTION
VPH24_St_GrI_
VPH24_GenSt_GrI
AND _
VPH24_Al_GrI_
VPH24_Alarm_GrI
AND _
VPH24_Tr_GrI_
VPH24_GenTr_GrI
AND _
VPH24_Blk_GrO_
NOT
Table 1-4 The binary input signals of the overexcitation protection function
BINARY STATUS SIGNAL EXPLANATION
Output status of a graphic equation defined by the user to
VPH24_Block_GrO_
disable the overexcitation protection function.
Output status of a graphic equation defined by the user to reset
VPH24_Reset_GrO_
the thermal counter
The binary output status signals of the overexcitation protection function are listed in Error!
Reference source not found..
Table 1-5 The binary output status signals of the overexcitation protection function
BINARY OUTPUT SIGNALS SIGNAL TITLE EXPLANATION
VPH24_GenSt_GrI_ General Start General starting of the function
VPH24_Alarm_GrI_ Alarm Alarm generated 10sec after General Start
VPH24_GenTr_GrI_ General Trip General trip command of the function
15 Overexcitation protection
www.protecta.hu
OVEREXCITATION
FUNCTION OVERVIEW
The graphic appearance of the function block of the overexcitation protection function is shown
on Figure 2-1. The block shows all binary input and output status signals which are applicable in
the graphic equation editor.
Figure 2-1 The graphic appearance of the function block of the overexcitation protection
function
2.1 Settings
2.1.1 Parameters
16 Overexcitation protection
www.protecta.hu
OVEREXCITATION
FUNCTION OVERVIEW
17 Overexcitation protection
www.protecta.hu
OVEREXCITATION
FUNCTION OVERVIEW
2.1.2 Characteristics
The function offers three different characteristics to satisfy the different user requirements.
t(G)
tOP
G
GS
10
Minutes
0.1
100 105 110 115 120 125 130 135 140
Volts/Hertz in %
18 Overexcitation protection
www.protecta.hu
OVEREXCITATION
FUNCTION OVERVIEW
100
Max Time Delay
10
Minutes
0.1
100 110 120 130 140 150 160
Volts/Hertz in %
Table 2-2 The measured analogue value of the overexcitation protection function
MEASURED VALUE DIMENSION EXPLANATION
Actual heat of the protected object.
Actual Heat % 100% corresponds to the inverse time
characteristic trip value.
Remark: Following a successful thermal trip operation, the counter starts a linear count-down
from 100% to zero. Duration of the count-down corresponds to the cooling time parameter.
19 Overexcitation protection
www.protecta.hu
OVEREXCITATION
FUNCTION OVERVIEW
Table 2-3 The binary input signals of the overexcitation protection function
BINARY STATUS SIGNAL EXPLANATION
Output status of a graphic equation defined by the user to
VPH24_Block_GrO_
disable the overexcitation protection function.
Output status of a graphic equation defined by the user to reset
VPH24_Reset_GrO_
the thermal counter
Table 2-4 The binary output status signals of the overexcitation protection function
BINARY OUTPUT SIGNALS SIGNAL TITLE EXPLANATION
VPH24_GenSt_GrI_ General Start General starting of the function
VPH24_Alarm_GrI_ Alarm Alarm generated 10sec after General Start
VPH24_GenTr_GrI_ General Trip General trip command of the function
2.2.6 Events
The following events are generated in the event list, as well as sent to SCADA according to the
configuration.
20 Overexcitation protection
www.protecta.hu
OVEREXCITATION
FUNCTION OVERVIEW
21 Overexcitation protection
www.protecta.hu