ABB Thermal Overload Relays
ABB Thermal Overload Relays
Tripping Class 20
New
ABB
Motor Protection — general Tripping classes of the thermal overload relays
It is very important to choose an adequate protective device for Standard tripping classes are 10 A, 10, 20, 30. The tripping
the safety of the motor during operation and for its durability. class indicates according to IEC 60947-4-1 the maximum
The efficiency of protection methods varies according to the ap- tripping time in seconds under specified conditions of test at
plication. The overview below will help you to choose. 7.2 times the setting current and specifics tripping and non trip-
There is no general rule and we are available to advise you for ping times for 1.5 and 7.2 times the setting current.
special applications and especially in the case of difficult start-
ing. An economic and effective protection are thermal overload Construction and function
relays with protection against: • General
> Overload Thermal O/L relays and their accessories meet UL, Nema, CSA
> Phase failure imbalance and most other important international standards (IEC), European
> Phase loss standards (EN) and the most important national standards. They
meet the certification and approval directives required through-
Description out the world.
• Available for starter construction with A Line contactors and Thermal overload relays are 3 pole. The motor current flows
separate panel mounting through their bimetals (1 per phase) which are indirectly heated.
• Designed for close couple mounting – separate base Under the effect of the heating, the bimetals bend, cause the
mounting available for all overload relays relay to trip and the position of the auxiliary contacts to change.
• Full automatic function, Manual reset, Test phase or Reset The relay setting range is graduated in amps. In compliance with
can also be adjusted to function as a stop button international and national standards, the setting current is the
• Remote trip and reset option available motor nominal current and not the tripping current (no tripping
• Screwdriver guide holes, all terminal screws are available at 1.05 x setting current, tripping at 1.2 x setting current). The
from the front tripping curves (cold or warm starting, 3 phases and 2 phases)
• Trip indication are shown in the main catalog.
• Ambient compensation -25 °C to +55 °C The relays are built to be self protecting in the event of an over-
(-13 °F to +131 °F) load until the short circuit protection device is activated.
Ordering Details Order code Setting range Max. fuse Packing Weight/
A…A gL/gG unit piece
Type A piece kg
TA25DU trip class 20 for contactors A9 … A40 and (T) AL9 … (T) AL30
TA25DU-1.8-20 1SAZ211401R1025 1.3 … 1.8 10 1 0.170
TA25DU-2.4-20 1SAZ211401R1028 1.7 … 2.4 16 1 0.170
TA25DU-3.1-20 1SAZ211401R1031 2.2 … 3.1 16 1 0.170
TA25DU-4.0-20 1SAZ211401R1033 2.8 … 4.0 20 1 0.170
TA25DU-5.0-20 1SAZ211401R1035 3.5 … 5.0 25 1 0.170
TA25DU-6.5-20 1SAZ211401R1038 4.5 … 6.5 25 1 0.170
TA25DU-8.5-20 1SAZ211401R1040 6.0 … 8.5 32 1 0.170
TA25DU-11-20 1SAZ211401R1043 7.5 … 11 40 1 0.170
TA25DU-14-20 1SAZ211401R1045 10 … 14 50 1 0.170
TA25DU
TA25DU-19-20 1SAZ211401R1047 13 … 19 63 1 0.170
TA25DU-25-20 1SAZ211401R1051 18 … 25 80 1 0.170
TA25DU-32-20 (1) 1SAZ211401R1053 24 … 32 (1) 100 1 0.190
(1)
with terminal block DX25: 1x16mm2
TA42DU trip class 20 for contactors A30, A40 and (T) AL30, (T) AL40
TA42DU-25-20 1SAZ311401R1001 18 … 25 100 1 0.370
TA42DU-32-20 1SAZ311401R1002 22 …32 125 1 0.370
TA42DU-42-20 1SAZ311401R1003 29 … 42 160 1 0.370
TA42DU
TA75DU trip class 20 for contactors A50 … A75 and AE50 … AE75
TA75DU-25-20 1SAZ321401R1001 18 … 25 100 1 0.370
TA75DU-32-20 1SAZ321401R1002 22 … 32 125 1 0.370
TA75DU-42-20 1SAZ321401R1003 29 … 42 160 1 0.370
TA75DU-52-20 1SAZ321401R1004 36 … 52 200 1 0.370
TA75DU-63-20 1SAZ321401R1005 45 … 63 200 1 0.370
TA75DU-80-20 1SAZ321401R1006 60 … 80 250 1 0.370
TA75DU
No Tripping at 1.05 Ie
Tripping at 1.2 Ie within 2 hours
TA80DU Time
Class 30 9 - 30 sec
Class 20 6 - 20 sec
Class 10 4 - 10 sec
Ie (adjusted current)
1.2 Ie 7.2 Ie
Thermal Overload Relays with Trip Class 20
Resistances and power losses per phase
Short-circuit protection
Setting range Short-circuit protection (fuses) UL UL Resistance Power loss
Type „2“ Type „1“ per phase per phase
co-ordination co-ordination
Fuse/600V 600V at upper
from … to gL/gG gL/gG K5 CB current setting
A A A A A A mOhm W
Type „1“ co-ordination according to IEC 60947-4-1: Under short-circuit conditions, the starter shall cause no danger to persons or
installation and may not be suitable for further service without repair and replacement of parts.
Type „2“ co-ordination according to IEC 60947-4-1: Under short-circuit conditions, the contactor or starter shall cause no danger
to persons or installation and shall be suitable for further use. The risk of contact welding is recognized, in which case the manu-
facturer shall indicate the measures to be taken as regards the maintenance of the equipment
Standard technical data, operating data and dimensions see TA...Relay Main Catalog
Thermal Overload Relays with Trip Class 20
Technical data
Short-circuit ratings
Voltage Type Setting range 5 kA 10 kA 18 kA
480 V A…A Fuse K5 CB Fuse K5 CB Fuse K5 CB
on request
TA25DU-25-20 18 … 25 70 - 70 70 -
TA25DU-32-20 24 … 32 100 - 100 100 -
TA42DU TA42DU-25-20 18 … 25 80 80 80 150 -
TA42DU-32-20 22 …32 100 80 100 150 -
TA42DU-42-20 29 … 42 150 80 150 200 -
TA75DU TA75DU-25-20 18 … 25 80 80 80 150 -
TA75DU-32-20 22 … 32 100 80 100 150 -
TA75DU-42-20 29 … 42 150 80 150 200 -
TA75DU-52-20 36 … 52 175 125 175 250 -
TA75DU-63-20 45 … 63 200 125 200 250 -
TA75DU-80-20 60 … 80 250 125 250 250 -
TA80DU TA80DU-42-20 29 … 42 150 80 150 150 -
TA80DU-52-20 36 … 52 175 125 175 175 -
TA80DU-63-20 45 … 63 200 125 200 250 -
TA80DU-80-20 60 … 80 250 150 250 250 -
TA25DU-25-20 18 … 25 70 - 70 70 -
TA25DU-32-20 24 … 32 100 - 100 100 -
TA42DU TA42DU-25-20 18 … 25 80 80 80 150 -
TA42DU-32-20 22 …32 100 80 100 150 -
TA42DU-42-20 29 … 42 150 80 150 200 -
TA75DU TA75DU-25-20 18 … 25 80 80 80 150 -
TA75DU-32-20 22 … 32 100 80 100 150 -
TA75DU-42-20 29 … 42 150 80 150 150 -
TA75DU-52-20 36 … 52 175 125 175 175 -
TA75DU-63-20 45 … 63 200 125 200 250 -
TA75DU-80-20 60 … 80 250 125 250 250 -
TA80DU TA80DU-42-20 29 … 42 150 80 150 150 -
TA80DU-52-20 36 … 52 175 125 175 175 -
TA80DU-63-20 45 … 63 200 125 200 250 -
TA80DU-80-20 60 … 80 250 150 250 250 -
Thermal Overload Relays with Trip Class 20
Table for tripping time
Tripping times of thermal overload relays as a function of a multiple of the setting current from cold state
(tolerance +/- 20% of the tripping time).
(12/05 • 1 • GVD)
6.0 … 8.5 46.1 27 20 15 11.7 10
7.5 … 11 42.3 25 17.8 14.1 10.9 10.5
10 … 14 39.4 25 16.8 13 9.9 8.5
13 … 19 38.1 21 13.6 10 7.4 6.2
18 … 25 44.4 25 16.1 11 9 8
24 … 32 44.4 27 17.7 13 9.8 8.5
ABB
ABB STOTZ-KONTAKT GmbH ABB Global Contact Directory
P. O. Box 10 16 80
D-69006 Heidelberg The ABB Contact Directory (http://www.abb.com/contacts/)
Telephone: ++49 62 21 / 701-0 helps you find local contacts for ABB products in your country.
Telefax: ++49 62 21 / 701-729
Please select the relevant product group from the dropdown
http://www.abb.de/stotz-kontakt
menu to the right or from the page.