Autonics CX Series - Data Sheet

This document summarizes the features and specifications of the CX Series LCD Display Counter/Timer. It has an LCD display for improved visibility and can be set for voltage or no-voltage input. The counter has a prescale value range of 0.00001 to 99999.9 and various input/output modes. The timer has a wide time setting range of 0.001 seconds to 99999.9 hours and 15 output modes. It is available in compact DIN sizes of W48xH48mm or W72xH72mm.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
16 views

Autonics CX Series - Data Sheet

This document summarizes the features and specifications of the CX Series LCD Display Counter/Timer. It has an LCD display for improved visibility and can be set for voltage or no-voltage input. The counter has a prescale value range of 0.00001 to 99999.9 and various input/output modes. The timer has a wide time setting range of 0.001 seconds to 99999.9 hours and 15 output modes. It is available in compact DIN sizes of W48xH48mm or W72xH72mm.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 26

CX Series

DIN W48×H48mm, W72×H72mm LCD Display Counter/Timer


Features SENSORS

● Improved visibility with LCD display


● Input method: v oltage input (PNP)/no-voltage input (NPN) selectable model (by parameter setting),
CONTROLLERS
Free voltage input model
● Setting range of one-shot output time: 0.01 sec to 99.99 sec by 0.01 sec unit
● Mounting space saving with compact design (back length: 64.5mm) MOTION DEVICES

[Counter]
● Setting range of prescale value: 0.00001 to 99999.9 SOFTWARE

● Various input/output mode (input: 11 types, output: 11 types)


● Start point (counting value reset) setting
● TOTAL counter display mode
: Displays the present value and the integrated value
simultaneously.

[Timer]
(J)
● Various output mode (15 types) Temperature
Controllers
● Wide time setting range: 0.001 sec to 99999.9 hour
● '0' time setting function
(K)
SSRs

Please read “Safety Considerations”


in the instruction manual before using. (L)
Power
Controllers

Manual (M)
For the detail information, please refer to user manual, and be sure to follow cautions written in the technical descriptions (catalog, website). Counters

Visit our website (www.autonics.com) to download manuals.


(N)
Timers

Ordering Information
(O)
Digital
Panel Meters

CX 6 S - 1P 4 F (P)
Indicators
Voltage input (PNP)/no-voltage input (NPN)
No mark
Signal input method selectable type
F Free voltage input (Q)
Converters
Power supply 2 24VAC 50/60Hz, 24-48VDC
4 100-240VAC 50/60Hz (R)
Digital
Output 1P 1-stage setting Display Units

2P 2-stage setting
(S)
Sensor
Size S DIN W48×H48mm Controllers
M DIN W72×H72mm
Display digit (T)
6 999999 (6-digit) Switching
Mode Power
Item Supplies
CX LCD Display counter/Timer
(U)
Recorders

(V)
HMIs

(W)
Panel PC

(X)
Field Network
Devices

M-41
CX Series

Specifications
Model CX6S-1P CX6S-2P CX6M-1P CX6M-2P
Display digits 6-digit
7-segment (1st, 2nd digits of counting value display: white, setting value display: green) LCD method,
Display method 11-segment (the other digits of counting value display: white) LCD method,
Operation display part: yellow LCD method
Character Counting value 4.1×10.1mm 6.2×15.2mm
size (W×H) Setting value 3.3×8.1mm 5×12.3mm
Power AC voltage 100-240VACᜠ 50/60Hz
supply AC/DC voltage 24VACᜠ 50/60Hz, 24-48VDCᜡ
Permissible voltage range 90 to 110% of rated voltage
AC volt- CX6 - Max. 6.4VA Max. 6.7VA Max. 7.1VA Max. 7.5VA
consumption

age CX6 - F Max. 4.2VA Max. 4.9VA Max. 4.7VA Max. 5.4VA
Power

AC: max. 5.5VA AC: max. 5.6VA AC: max. 6.2VA AC: max. 6.3VA
CX6 -
AC/DC DC: max. 3.5W DC: max. 3.6W DC: max. 4W DC: max. 4.1W
voltage AC: max. 3.6VA AC: max. 4.0VA AC: max. 3.9VA AC: max. 4.5VA
CX6 - F
DC: max. 2.5W DC: max. 2.8W DC: max. 2.9W DC: max. 3.3W
Max. INA/ CX6 - Selectable among 1cps/30cps/300cps/1kcps/5kcps
INB counting
speed CX6 - F 20cps
Counter

Counting range -99999 to 999999


Scale Decimal point up to fifth digit
Min. signal CX6 - RESET, TOTAL RESET signal: selectable among 1ms/20ms
width CX6 - F RESET signal: 25ms
999.999s, 9999.99s, 99999.9s, 999999s, 99m 59.99s, 999m 59.9s, 9999m 59s, 99999.9m, 999999m,
Time range
99h 59m 59s, 9999h 59m, 99999.9h
Operation mode Up, Down
Min. signal CX6 - INA, INHIBIT, RESET, TOTAL RESET signal: selectable among 1ms/20ms
Timer

width CX6 - F INA, INH, RESET signal: 25ms


Repeat error [CX6 - ]-In case of power ON start: max. ±0.01% ±0.05s
Set error In case of signal ON start: max. ±0.01% ±0.03s
Voltage error [CX6 - F]-In case of power ON start: max. ±0.01% ±0.08s
Temp. error In case of signal ON start: max. ±0.01% ±0.06s
Selectable among voltage input (PNP)/no-voltage input (NPN)
CX6 - [Voltage input (PNP)]-input impedance: 10.8kΩ, [H]: 5-30VDCᜡ, [L]: 0-2VDC
[No-voltage input (NPN)]-short-circuit impedance: max. 1kΩ, short-circuit residual voltage: max. 2VDC
Input method
[Free voltage input]-INA (START) , INB (INHIBIT) input
CX6 - F [H]: 24-240VDCᜡ/24-240VACᜠ 50/60Hz, [L]: 0-10VDC/VAC
[No-voltage input]-RESET input, short-circuit impedance: max. 1kΩ, short-circuit residual voltage: max. 2V
One-shot output time 0.01 to 99.99s setting
Type SPDT (1c): 1 SPST (1a): 2 SPDT (1c): 1 SPDT (1c): 2
Contact
Control Capacity Max. 250VACᜠ 3A, 30VDCᜡ 3A resistive load
output Solid Type NPN open collector: 1 NPN open collector: 2
-
state Capacity Max. 30VDCᜡ 100mA
External power supply※1 Max. 12VDCᜡ ±10%, 100mA
Memory retention Approx. 10 years (non-volatile memory)
Insulation resistance Over 100MΩ (at 500VDC megger)
Dielectric strength 3,000VAC 50/60Hz for 1 min
Noise AC voltage Square-wave noise by noise simulator (pulse width 1㎲) ±2kV
immunity AC/DC voltage Square-wave noise by noise simulator (pulse width 1㎲) ±500V
Mechanical 0.75mm amplitude at frequency 10 to 55Hz (for 1 min) in each X, Y, Z direction for 1 hour
Vibration
Malfunction 0.5mm amplitude at frequency 10 to 55Hz (for 1 min) in each X, Y, Z direction for 10 min
Mechanical 300m/s² (approx. 30G) in each X, Y, Z direction for 3 times
Shock
Malfunction 100m/s² (approx. 10G) in each X, Y, Z direction for 3 times
Relay life Mechanical Min. 5,000,000 operations
cycle Malfunction Min. 100,000 operations
Protection structure Front part: IP50 (IEC standard)
Environ- Ambient temp. -10 to 55℃, storage: -25 to 65℃
ment Ambient humi. 35 to 85%RH, storage: 35 to 85%RH
Approval
CX6 - Approx. 157g (approx. 112g) Approx. 162g (approx. 117g) Approx. 235g (approx. 170g) Approx. 240g (approx. 175g)
AC voltage
Weight※2

CX6 - F Approx. 155g (approx. 110g) Approx. 160g (approx. 115g) Approx. 233g (approx. 168g) Approx. 238g (approx. 173g)
AC/DC CX6 - Approx. 156g (approx. 111g) Approx. 161g (approx. 116g) Approx. 234g (approx. 169g) Approx. 239g (approx. 174g)
voltage CX6 - F Approx. 154g (approx. 109g) Approx. 159g (approx. 114g) Approx. 232g (approx. 167g) Approx. 237g (approx. 172g)
※1: This is for the voltage input (PNP)/no-voltage input (NPN) selectable model (CX6 - ).
※2: The weight includes packaging. The weight in parenthesis is for unit only.
※Environment resistance is rated at no freezing or condensation.

M-42
LCD Display Counter/Timer

Connections
CX6S Series SENSORS

1. Voltage input (PNP), no-voltage input (NPN) selectable model


CONTROLLERS
CX6S-1P CX6S-2P2 CX6S-2P4
CONTACT OUT: CONTACT OUT1/OUT2: CONTACT OUT1/OUT2:
250VAC 3A, 30VDC 3A 250VAC 3A, 30VDC 3A 250VAC 3A, 30VDC 3A MOTION DEVICES

RESISTIVE LOAD RESISTIVE LOAD RESISTIVE LOAD


1 7 INA 1 OUT2 7 INA 1 7 INA SOFTWARE

2 OUT 8 INB/INH 2 8 INB/INH 2 8 INB/INH


OUT2
3 9 12VDC 100mA 3 OUT1 9 12VDC 100mA 3 9 12VDC 100mA

4 10 0VDC 4 10 0VDC 4 10 0VDC


OUT1
※1
5 11 RESET 5 11 RESET 5 11 RESET

6 12 TOTAL RESET 6 12 TOTAL RESET 6 12 TOTAL RESET


(J)
Temperature
SOURCE: SOURCE: SOURCE: Controllers

100-240VAC 50/60Hz 6.4VA 24VAC 50/60Hz 5.6VA 100-240VAC 50/60Hz 6.7VA


24VAC 50/60Hz 5.5VA 24-48VDC 3.6W (K)
SSRs
24-48VDC 3.5W

(L)
Power
Controllers

(M)
2. Free voltage input model Counters

CX6S-1P F CX6S-2P2F CX6S-2P4F


(N)
Timers
CONTACT OUT CONTACT OUT1/OUT2 CONTACT OUT1/OUT2
: 250VAC 3A, 30VDC 3A : 250VAC 3A, 30VDC 3A :2 50VAC 3A, 30VDC 3A
RESISTIVE LOAD RESISTIVE LOAD RESISTIVE LOAD (O)
Digital
SIGNAL INPUT SIGNAL INPUT SIGNAL INPUT Panel Meters
: 24-240VAC 50/60Hz, 24-240VDC : 24-240VAC 50/60Hz, 24-240VDC : 24-240VAC 50/60Hz, 24-240VDC
OUT2
1 7 1 7 1 7 (P)
Indicators
INA INA INA
2 8 2 8 2 8
INB/INH INB/INH OUT2 INB/INH
(Q)
3 9 3 9 3 9 Converters
OUT INPUT OUT1 INPUT INPUT
4 10 4 10 4 10
OUT1 (R)
※1 Digital
5 11 5 11 5 11 Display Units
RESET RESET RESET
6 12 6 12 6 12
0VDC 0VDC 0VDC (S)
Sensor
Controllers
SOURCE: 100-240VAC 50/60Hz 4.2VA SOURCE: 24VAC 50/60Hz 4.0VA SOURCE: 100-240VAC 50/60Hz 4.9VA
24VAC 50/60Hz 3.6VA 24-48VDC 2.8W (T)
Switching
24-48VDC 2.5W Mode Power
Supplies

(U)
Recorders

(V)
HMIs

(W)
Panel PC

(X)
Field Network
Devices

M-43
CX Series

Connections
CX6M Series
1. Voltage input (PNP), no-voltage input (NPN) selectable model
CX6M-1P CX6M-2P
CONTACT OUT: 250VAC 3A, 30VDC 3A CONTACT OUT1/OUT2: 2
 50VAC 3A, 30VDC 3A
RESISTIVE LOAD RESISTIVE LOAD

1 10 INA 1 10 INA

2 OUT 11 INB 2 OUT2 11 INB

3 12 12VDC 100mA 3 12 12VDC 100mA


0VDC 0VDC
4 13 4 13

5 14 RESET 5 OUT1 14 RESET

6 15 INHIBIT 6 15 INHIBIT
SOLID SOLID 16 TOTAL RESET
7 16 TOTAL RESET 7
STATE ※1 STATE OUT1
※1
8 OUT: 17 8 OUT: 17
30VDC 30VDC
9 100mA 18 9 100mA OUT2 18
SOURCE: 100-240VAC 50/60Hz 7.1VA SOURCE: 1
 00-240VAC 50/60Hz 7.5VA
24VAC 50/60Hz 6.2VA 24VAC 50/60Hz 6.3VA
24-48VDC 4W 24-48VDC 4.1W

2. Free voltage input model


CX6M-1P F CX6M-2P F
CONTACT OUT: 250VAC 3A, 30VDC 3A CONTACT OUT1/OUT2: 2  50VAC 3A, 30VDC 3A
RESISTIVE LOAD RESISTIVE LOAD
SIGNAL INPUT: 24-240VAC 50/60Hz, 24-240VDC SIGNAL INPUT: 24-240VAC 50/60Hz, 24-240VDC
1 10 1 10
INA INA
2 OUT 11 2 OUT2 11
INB/INH INB/INH
3 12 3 12
SIGNAL INPUT SIGNAL INPUT
4 13 4 13
5 14 5 OUT1 14
6 15 6 15
RESET RESET
7 SOLID 0VDC 16 SOLID 0VDC 16
7
※1 STATE STATE
※1
8 OUT: 17 8 OUT: OUT1 17
30VDC 30VDC
9 18 9
100mA 100mA OUT2 18
SOURCE: 100-240VAC 50/60Hz 4.7VA SOURCE: 1
 00-240VAC 50/60Hz 5.4VA
24VAC 50/60Hz 3.9VA 24VAC 50/60Hz 4.5VA
24-48VDC 2.9W 24-48VDC 3.3W

※1: AC voltage type: 100-240VAC 50/60Hz


AC/DC voltage type: 24VAC 50/60Hz, 24-48VDC

M-44
LCD Display Counter/Timer

Dimensions (unit: mm)


CX6S Series Panel cut-out SENSORS

CX6S Series
48 6 64.5 Min. 65 CONTROLLERS

45 +0.6
0
MOTION DEVICES

Min. 65
44.8
+0.6
45 0

SOFTWARE

CX6M Series
72 6 64.5
CX6M Series
Min. 91
(J)
Temperature
Controllers

68 +0.7
0
67.5

(K)

Min. 91
SSRs
68 +0.7
0

(L)
Power
Controllers

(M)
Counters

Bracket
CX6S Series CX6M Series (N)
Timers
±0.2
48.6 30.6
3.3

(O)
45 +0.2
0 20 Digital
5 Panel Meters
16 +0.3

4
0

(P)
46
-0.05
44.9 +0.2

Indicators
36

37.5

(Q)
40.5

Converters

15
55 (R)
21 Digital
12 Display Units

23.9
(S)
Sensor
Controllers

56
(T)
Switching
Mode Power
Supplies
Terminal cover (sold separately)
C
 X6S Series C
 X6M Series (U)
Recorders
(RSA-COVER, 48×48mm) (RMA-COVER, 72×72mm)
22 4 70 10 (V)
3 48.4 13 HMIs

(W)
Panel PC
68.5
41
45

64

(X)
Field Network
Devices
18
22

13

M-45
CX Series

Unit Description
CX6S Series CX6M Series

1
1
7
2
8
3 7
9 2
4
10 5 8
11 6 9 3
4
10
12 13 14 5
11 6

12 13 14

1. Counting value display component (white)


RUN mode: Displays counting value for counter operation or time progress value for timer operation.
Function setting mode: Displays parameter.
2. Setting value display component (green)
RUN mode: Displays setting value.
Function setting mode: Displays parameter setting value.
3. Time unit indicator (h:m:s): Turns ON for time unit for timer.
4. Key lock indicator ( ): Turns ON for key lock setting.
5. Reset input indicator (RST): Turns ON for reset key input or reset signal input.
6. INH indicator (INH)
For the voltage input (PNP)/no-voltage input (NPN) selectable model (CX6 - ), it turns ON for INHIBIT signal input.
(In case of CX6S Series and timer mode, it turns ON for INB/INH signal input.)
For free voltage input model (CX6 - F), it turns ON for INB/INH signal input for timer.
7. Output indicator (OUT1, OUT2): Turns ON for the dedicated control output ON.
8. SV checking and changing indicator (SET, SET1, SET2) (green): Turns ON when checking and changing SV.
9. COUNTER indicator (COUNTER): Turns ON for counter operation.
10. TOTAL indicator※1 (TOTAL): In case of TOTAL counter display mode, it turns ON with the COUNTER indicator.
11. TIMER indicator (TIMER): Flashes (progressing time) or Turns ON (stopping time) for timer operation.
12. RESET key
RUN mode, Function setting mode: Press the RESET key to reset the counting value and turn OFF the output.
TOTAL counter display mode※1: Press the RESET key to reset the counting value of TOTAL counter.
13.  key
RUN mode: Hold the key over 3 sec to enter function setting mode.
Press the key to select SV2 (SET2)/SV1 (SET1)/TOTAL counter※1 display for counter operation.
Function setting mode: Hold the key over 3 sec to return RUN mode.
Press the key to save the SV and enter the next setting.
Function setting check mode: Hold the key over 1 sec to return RUN mode.
Changing SV mode: Press the key to save SV and return RUN mode.
14. , key
1)  key
RUN mode: Press the key to change SV and move SV (SET, SET1, SET2) digits.
Changing SV mode: Press the key to change digits.
2)  key
Changing SV mode: Increases SV.
Function setting mode: Changes the settings.

※1: This is for the voltage input (PNP)/no-voltage input (NPN) selectable model (CX6 - ).

M-46
LCD Display Counter/Timer

Input Connections
No-voltage input (NPN) SENSORS

● Solid-state input (standard sensor: NPN output type sensor) ● Contact input
CONTROLLERS
Sensor Counter/Timer Sensor Counter/Timer Counter/Timer
Brown Brown
+12V +12V +12V
MOTION DEVICES
5.4kΩ 5.4kΩ 5.4kΩ
Black ※1 Inner circuit Black ※1 Inner circuit ※2 Inner circuit
of input part of input part of input part
SOFTWARE

Blue Blue
0V 0V 0V
(NPN output) (NPN open collector output)
※1: CP1, CP2 (INHIBIT), SET input part
※2: Set counting speed as 1 or 30cps.

(J)
Temperature

Voltage input (PNP)


Controllers

● Solid-state input (standard sensor: PNP output type sensor) ● Contact input (K)
SSRs

Sensor Counter/Timer Sensor Counter/Timer Counter/Timer


Brown Brown ※2 (L)
+12V +12V +12V Power
Controllers

Black ※1 Inner circuit Black※1 Inner circuit Inner circuit (M)


of input part of input part of input part Counters

10.8kΩ 10.8kΩ 10.8kΩ


Blue Blue (N)
0V 0V 0V Timers

(PNP output) (PNP open collector output)


(O)
Digital
※1: CP1, CP2 (INHIBIT), SET input part Panel Meters
※2: Set counting speed as 1 or 30cps.
(P)
Indicators

(Q)

Output Connections Converters

Contact output Solid-state output (R)


Digital
Display Units

Counter/Timer ※1
Counter/Timer
(S)
Sensor
Load (+) Power
Controllers

(Power of load) for load (T)


Load (-) (DC) Switching
Mode Power
Supplies

※Select the load which capacity is not over contact ※For solid state output, select load power and load not to be over
(U)
capacity. (max. 30VDC, 100mA), swithching capacity. Recorders
※Do not supply reverse polarity voltage.
※1: F
 or using inductive load (relay, etc.), connect surge absorber
(V)
(diode, varistor etc.) at the both ends of load. HMIs

(W)
Panel PC

(X)
Field Network
Devices

M-47
CX Series

Operations and Functions (counter/timer)


Function setting
mode
Changing
(RUN mode) 3 sec SV mode
3 sec
(CX6 - )

TOTAL SET1 SET2 1 sec Function setting


RUN mode 1 sec check mode
counter value value

RESET
RESET PV RESET
(CX6 - F)
(RUN mode)
Reset TOTAL
counter
[Counter] 12:30:25
OUT1
Display PV
OUT2

SET2
1:25:47
TIMER
Display SET2

12:34:56
OUT1
Display PV
OUT2
5:43:50 Display SET1
[Timer]
SET1
TIMER

Counter mode
● Changing
 SV mode
When input signal is ON during changing SV, it operates counting and output control.
It is available to set SV as '0' and the dedicated output for SV '0' occurs.
There are output mode which cannot set SV as '0'. (the setting value display component flashes three times when SV is set as '0')

RUN mode

Press the key to enter changing SV mode in RUN mode.


When entering changing SV mode, the counting value display component displays the
current value and the setting value display component displays SV.

SET2
value
After setting SV at each parameter, press the key to save SV and it moves
next parameter setting or returns to RUN mode.

SET1
value (CX6 - F)

TOTAL Reset TOTAL


RESET
(CX6 - ) counter counter

M-48
LCD Display Counter/Timer
● Function setting mode
※1: In case of free voltage input model (CX6 - F), these parameters do not appear due to fixed setting.
※2: This parameter is for the voltage input(PNP)/no-voltage input(NPN) selectable model (CX6 - ). SENSORS
※ : When changing the setting of shaded parameters, all output turn OFF.

RUN mode
CONTROLLERS
3 sec -Hold the key over 3 sec in RUN mode and it enters
3 sec
function setting mode.
-Hold the key over 3 sec in function setting mode
Counter/Timer [C-T] MOTION DEVICES
Function setting mode

and it returns to RUN mode.

Input mode [InM]


SOFTWARE

Output mode [OUtM]

Max. counting speed※1 [CPS]

OUT2 output time [OUT2]


OUT output time
[OUtT] OUT1 output time [OUT1]
(J)
Temperature
Controllers
Decimal point [DP]

(K)
Min. reset time※1 [RESET] SSRs

Input logic※1 [SIG] (L)


Power
Controllers
Prescale decimal point [SClDP]
(M)
Counters
Prescale value [SCL]

TOTAL counter※2 [TOTAL] (N)


Timers

Start Point value [START]


(O)
Digital
Panel Meters
Memory protection [DATA]

(P)
Key lock [LOCK] Indicators

(Q)
Converters

● Function setting check mode (only for free voltage input model (CX6 - F))
-When checking the saved parameters, press the , key to check next item. (R)
Digital
-At function setting check mode, the counting value display component displays the parameters and the setting value display Display Units

component displays the SV of the parameters.


(S)
● Checking SV of TOTAL counter Sensor
Controllers
-At TOTAL counter operation, the counting value display component displays the current value and the setting value display component
displays TOTAL counter counting value. (T)
Switching
※When TOTAL counter counting value is over 999999, it counts from 0 again. Mode Power
Supplies

● Switching display of the setting value display component


(only for voltage input (PNP)/no-voltage input (NPN) selectable model (CX6 - ) (U)
Recorders
-In case of 2-stage setting model(CX6 -2P ), whenever pressing the key, each SET2, SET1, TOTAL COUNTER value
displays consecutively.
(V)
HMIs
● Display HOLD output mode for counter
-It displays the over value of prescale value. (W)
-When SV is n multiplied by prescale value and the display value after HOLD output mode and Panel PC

SV are different, the prescale value is not the 1/n time of SV.
(X)
● RESET Field Network
Devices
-In RUN mode, function setting mode, press the RESET key to reset the current value and the output turns OFF.
-At TOTAL counter display mode, press the RESET key to reset TOTAL counter counting value and the current counting value.

M-49
CX Series

Parameter Setting (Counter)


( key: moves parameters, key: changes parameter setting value)
Parameter Parameter setting value
Counter/Timer ※COUNT: Counter
COUNT TIME
[C-T] TIME: Timer
UP UP-1 UP-2 UP-3 DN DN-1
Input mode
[InM] UD-C※1 UD-B※1 UD-A DN-3 DN-2
Input mode is UP, UP-1, UP-2, UP-3 or DN, DN-1, DN-2, DN-3,
F N [ R K P Q A

Output mode Input mode is UD-A, UD-B※1, UD-C※1


[OUtM] F N [ R K P Q A S T D

※If max. counting speed is 5kcps, and output mode is D, max. counting speed is automatically changed as 30cps,
factory default.
※Max. counting speed is when duty ratio of INA or INB input signal is 1:1.
Max. counting
30 300 1K 5K 1 It is applied for INA, or INB input as same.
speed※2
※When output mode is D, set max. counting speed one among 1cps, 30cps, 300cps, or
[CPS]
1kcps.
OUT 2 ※Set one-shot output time of OUT 2.

output time 3 ※Setting range: 00.01 to 99.99 sec
[OUT2] ※When output mode is F, N, S, T, D, this parameter does not appear. (fixed as HOLD)
※Set one-shot output time of OUT 1.
OUT 1
※ ※Setting range: 00.01 to 99.99 sec, Hold
output time 3
※When number of tens digit is flashing, press the key once and HOLD appears.
[OUT1]
※When output mode is S, T, D, this parameter does not appear. (fixed as HOLD)
OUT
※ ※Setting range: 00.01 to 99.99 sec
output time 3
※When output mode is F, N, S, T, D, this parameter does not appear. (fixed as HOLD)
[OUtT]
※4 ------ -----.- ----.-- ---.--- --.---- -.-----
Decimal point
[DP]
※Decimal point is applied to PV and SV.
※2
Min. reset time 1 20, unit: ms
[RESET] ※Set min. width of external reset signal input.
※2
Input logic
NPN: No-voltage input, PNP: Voltage input
[SIG]
Prescale -.----- -----.- ----.-- ---.--- --.----
decimal point※4
[SClDP] ※Decimal point of prescale should not set smaller than decimal point [DP].
Prescale value ※Setting range: 0.00001 to 99999.9
[SCL] ※Setting range of prescale is linked with prescale decimal point [SClDP] setting.
※1
TOTAL counter
ㅐㅜON OFF
[TOTAL]
※Setting range of start point value is linked with decimal point [DP] setting. (0.00000 to 999999)
Start point value
※When input mode is DN, DN-1, DN-2, this parameter does not appear.
[START] ※1
※When total count function is ON, this parameter does not appear.
Memory protection ※CLR: Resets the counting value when power OFF.
CLR REC
[DATA] REC: Maintains the counting value when power OFF. (memory protection)
※lOFF: Unlock keys, key lock indicator turns OFF
Key lock lOFF LOc1 LOc1: Locks RESET key, key lock indicator turns ON
[LOCK] LOc3 LOc2 LOc2: Locks , keys, key lock indicator turns ON
LOc3: Locks RESET , , keys, key lock indicator turns ON
※1: For voltage input (PNP), no-voltage input (NPN) model (CX6 - ).
※2: For free voltage input model(CX6 - F), these parameters do not appear due to fixed setting.
※3: For 1-stage setting model (CX6 -1P ), OUT1 does not appear.
The OUT2 output time is displayed as OUtT.
※4: Decimal point and prescale decimal point
-Decimal point: Set the decimal point for display value regardless of prescale value.
-Prescale decimal point: Set the decimal point for prescale value of counting value regardless of display value.

M-50
LCD Display Counter/Timer

Input Operation Mode (Counter)


Input mode Counting chart Operation SENSORS

H No counting
INA
L
CONTROLLERS

H ※When INA is counting input, INB is no


INB
UP L 7 counting input.
No counting
[UP] 6 When INB is counting input, INA is no MOTION DEVICES
5
4 counting input.
Count 3
2
1
SOFTWARE
0

H
INA
L
H ※When INA input signal is rising ( ),
INB
UP-1 L it counts.
[UP-1] No counting 5 ※INA: Counting input
4
3 ※INB: No counting input
Count 2 (J)
1 Temperature
0 Controllers

H
INA L (K)
SSRs

H ※When INA input signal is falling ( ),


UP-2 INB L it counts. (L)
Power
[UP-2] No counting 4 ※INA: Counting input Controllers
3 ※INB: No counting input
2
Count 1 (M)
Counters
0

H
INA (N)
L Timers

H ※When INA or INB input signal is rising


INB
UP-3 L ( ), it counts. (O)
Digital
[UP-3] 6 ※INA: Counting input Panel Meters
5 ※INB: Counting input
Count 3
2
1 (P)
Indicators
0

H No counting
INA L (Q)
Converters

H ※When INA is counting input, INB is no


INB L (R)
Down No counting counting input. Digital
Display Units
[DN] n When INB is counting input, INA is no
n-1
n-2 counting input.
Count n-3
n-4 (S)
n-5 Sensor
n-6 Controllers
n-7
0
(T)
Switching
H Mode Power
INA L Supplies

H ※When INA input signal is rising ( ), (U)


INB L Recorders
Down-1 it counts.
[DN-1] n No counting ※INA: Counting input
n-1
n-2 ※INB: No counting input (V)
Count n-3 HMIs
n-4
n-5
0
(W)
Panel PC
H
INA L
(X)
Field Network
H ※When INA input signal is falling ( ), Devices
INB L
Down-2 it counts.
[DN-2] n No counting ※INA: Counting input
n-1
n-2 ※INB: No counting input
Count n-3
n-4
n-5
0

M-51
CX Series

Input Operation Mode (Counter)


Input mode Counting chart Operation
H
INA
L
H ※When INA or INB input signal is rising
INB ( ) , it counts.
Down-3 L
[DN-3] n ※INA: Counting input
n-1
n-2 ※INB: Counting input
Count n-3
n-5
n-6
0
H
INA
L
※INA: Counting input
Up/ H INB: Counting command input
INB
Down-A L ※When INB is "L", counting command is up.
[UD-A] 4 4 When INB is "H", counting command is
3 3 3
Count 2 2 2 down.
1 1
0

H
INA
L ※INA: Up counting input
Up/ H INB: Down counting input
INB
Down-B L 4 4 ※When INA and INB input signals are rising
[UD-B] 3 3 3 ( ) at the same time, it maintains previ-
Count 2 2 2
1 ous value.
0

H
INA
L
Up/ ※When connecting encoder output A, B
H
INB phase with counter input, INA, INB, set
Down-C L 3 3 input mode [InM] as phase different input
[UD-C] 2 2 2 [UD-C] for counter operation.
Count 1 1
0
※A: over min. signal width, B: over than 1/2 of min. signal width. If the signal is smaller than these width, it may cause counting error (±1).
INA H
(INB) L ON OFF ON OFF
T.on T.off
T

※T.on, T.off: Min. signal width

※The meaning of "H", "L" ※Min. signal width by counting speed


Input method Voltage input No-voltage input [CX6 - ] [CX6 - F]
Character (PNP) (NPN) Counting Min. signal Counting Min. signal
H 5-30VDC Short speed width speed width
L 0-2VDC Open 1cps 500ms 20cps 25ms
30cps 16.7ms
300cps 1.67ms
1kcps 0.5ms
5kcps 0.1ms

M-52
LCD Display Counter/Timer

Output Operation Mode (Counter) One-shot output (0.01 to 99.99 sec)


Retained output
One-shot output Retained output

SENSORS
Output Input mode
Operation
mode Up, Up-1, 2, 3 Down, Down-1, 2, 3 Up/Down A, B, C
RESET CONTROLLERS
999999
SET 2 ※After count-up, counting display val-
F SET 1 ue increases or decreases until reset
MOTION DEVICES
[F] 0 signal is applied and retained output
OUT1 is maintained.
OUT2
(OUT) SOFTWARE

RESET
999999
SET 2
※After count- up, counting display
N SET 1
value and retained output are main-
[N] 0
tained until reset signal is applied.
OUT1
OUT2
(OUT)

RESET ※When count-up, counting display (J)


999999 value will be reset and count simulta- Temperature
Controllers
SET 2 neously.
C SET 1 ※OUT1 retained output will be off after
[C] 0 OUT2 one- shot time. (K)
SSRs
OUT1 ※The one-shot output time of OUT1
OUT2 one-shot output time is operated
(OUT) regardless of OUT2 output. (L)
Power
RESET ※After count-up, counting value Controllers

999999 display is reset after one-shot output


SET 2 time of OUT2 and it counts simulta- (M)
R SET 1 neously. Counters

[R] 0 ※OUT1 retained output will be off after


OUT1 OUT2 one-shot time.
(N)
OUT2 ※OUT1 one-shot output time is oper- Timers
(OUT) ated regardless of OUT2 output.
RESET ※After count-up, counting display (O)
999999 value increases or decreases until Digital
Panel Meters
SET 2
RESET input is applied.
K SET 1
※OUT1 retained output is off after
[K] 0
OUT2 one-shot time. (P)
Indicators
OUT1
※OUT1 one-shot output time is oper-
OUT2 ated regardless of OUT2 output.
(OUT)
(Q)
※After count-up, counting display val- Converters
ue is maintained while OUT2 output
RESET is on. (R)
999999 Counting value is internally reset and Digital
Display Units
SET 2 counts simultaneously.
P SET 1 ※When OUT2 output is off, displays
(S)
[P] 0 counting value while OUT2 is ON, Sensor
OUT1 and it increases or decreases. Controllers

OUT2 ※OUT1 retained output is off after


(T)
(OUT) OUT2 one-shot time. Switching
Mode Power
※OUT1 one-shot output time is oper- Supplies
ated regardless of OUT2 output.
RESET ※After count-up, counting display (U)
Recorders
999999 value increases or decreases during
SET 2
OUT2 one-shot time.
Q SET 1
※OUT1 retained output is off after (V)
[Q] 0
OUT2 one-shot time. HMIs
OUT1
※OUT1 one-shot output time is oper-
OUT2
(OUT)
ated regardless of OUT2 output. (W)
Panel PC
RESET
999999 ※After count-up, counting display
SET 2 value and OUT1 retained output (X)
Field Network
A SET 1 are maintained until RESET input is Devices
[A] 0 applied.
OUT1 ※OUT1 one-shot output time is oper-
OUT2 ated regardless of OUT2 output.
(OUT)
※OUT1 is available to set as ‘0’ regardless of output mode. The output for '0' setting executes.
※In case of C, R, P, Q output mode for OUT2, setting ‘0’ is not available.

M-53
CX Series

Output Operation Mode (Counter) Retained output Coincidence output

Output Input mode


Operation
mode Up/Down A, B, C
RESET
999999 ※OUT1 keeps ON status in following con-
SET2 dition
S SET1
: Counting display value ≥ SET1
0
[S] -99999
※OUT2 keeps ON status in following con-
dition
OUT1
: Counting display value ≥ SET2
OUT2
(OUT)

RESET
※OUT1 output is off
999999
SET2 : Counting display value ≥ SET1
(when SET1 is 0, OUT1 output maintains
T SET1
0 ON state.)
[T] -99999 ※OUT2 keeps ON status in following con-
OUT1 dition
OUT2 : Counting display value ≥ SET2
(OUT)

RESET ※When counting display value is equal to


999999 setting value (SET1, SET2) only, OUT1
SET2 or OUT2 output keeps ON status.
D SET1
0
※When setting 1kcps for counting speed,
[D] solid state contact output should be used.
-99999
(when using contact output, it is difficult
OUT1
OUT2
to execute normal output operation due
(OUT) to contact reaction time.)

※OUT1 is available to set as ‘0’ regardless of output mode. The output for '0' setting executes.
※In case of C, R, P, Q output mode for OUT2, setting ‘0’ is not available.

Output Operation for Other Conditions


When Start Point is larger or equal than setting value
(UP, UP-1, UP-2, UP-3, UD-A, UD-B, UD-C mode)
When setting SET2>Start Point>SET1
-UP, UP-1, UP-2, UP-3 mode: Output of OUT1 does not execute. When PV is same as SET2, output of OUT2 turns ON.
-UD-A, UD-B※1, UD-C※1 mode: When PV counts down and is same as SET1, output of OUT1 turns ON.
When setting SET2>Start Point=SET1
-In case of UP, UP-1, UP-2, UP-3, UD-A, UD-B※1, UD-C※1 mode, output of OUT1 turns ON when RESET ON to OFF.
※1: This is for the voltage input(PNP)/no-voltage input(NPN) selectable model (CX6 - ).

 hen SET1 is larger or equal than SET2 at down mode


W
When SET2>SET1
-Output of OUT1 does not execute.

When SET2=SET1
-Output of OUT1 turns ON for RESET OFF.

M-54
LCD Display Counter/Timer

Prescale Function (Counter)


This function is to set and display calculated unit for actual length, liquid, position, etc. It is called “prescale value” for measured length, liquid, SENSORS
or position, etc per 1 pulse. For example, when moving L, the desired length to be measured, and P, the number of pulses per 1 revolution of
a rotary encoder, occurs, prescale value is L/P.
CONTROLLERS
E.g.) Positioning control by counter and encoder

Pulley
MOTION DEVICES
Cutter

[Diameter (D) of pulley connected with encoder= 22mm, SOFTWARE


the number of pulses by 1 rotation of encoder=1,000]
Rotary encoder

× Diameter (D) of pulley


●Prescale value =
The number of pulses by 1 rotation
Motor of encoder

(J)
3.1416 × 22
= Temperature
Controllers
1000
Motor conlrol system
Counter = 0.069mm/pulse (K)
SSRs

(L)
Power
Set decimal point[DP] as [-----.-], prescale decimal point [SClDP] as [---.---], prescale value [SCL] as [0.069] at function setting mode. Controllers

It is available to control conveyer position by 0.1mm unit.


(M)
Counters

(N)
Timers

Start Point Function (Counter) (O)


Digital
In case of counter operation, set the start value for counting at Start point [START]. Panel Meters
● It is not available for DN, DN-1, DN-2, DN-3 input mode.
● When pressing the RESET key, PV is reset as the start point value.
(P)
● In case of C, R, P, Q output mode, it counts up and PV starts from the start point value. Indicators

(Q)
Converters

(R)
Digital
Display Units

(S)
Sensor
Controllers

(T)
Switching
Mode Power
Supplies

(U)
Recorders

(V)
HMIs

(W)
Panel PC

(X)
Field Network
Devices

M-55
CX Series

Timer mode
● Changing
 SV mode
When input signal is ON during changing SV, it operates counting and output control.
It is available to set SV as '0' and the dedicated output for SV '0' occurs.
There are output mode which cannot set SV as '0'. (the setting value display component flashes three times when SV is set as '0')

RUN mode

Press the key to enter changing SV mode in RUN mode.


When entering changing SV mode, the counting value display component
displays the current value and the setting value display component displays SV.

12:30:25
OUT1
Display PV
OUT2
1:25:47 Display SET2
SET2 TIMER

After setting SV at each parameter, press the key to save SV and it


moves next parameter setting or returns to RUN mode.
12:34:56
OUT1
Display PV
OUT2
SET1 5:43:50 Display SET1
TIMER

● Function setting mode


※1: In case of free voltage input model (CX6 - F), these parameters do not appear due to fixed setting.
※2: This parameter is for the voltage input(PNP)/no-voltage input(NPN) selectable model (CX6 - ).
※ : When changing the setting of shaded parameters, all output turn OFF.

RUN mode -Hold the key over 3 sec in RUN


3 sec mode and it enters function setting mode.
3 sec
-Hold the key over 3 sec in function
setting mode and it returns to RUN mode.
Counter/Timer [C-T]
Function setting mode

(In case of OND, OND.I, OND.2, OND.3,


UP/DOWN mode [U-D]
FLK.1, FLK.2, INT, INT.1, INT.2,
OFD, INTG, TOTAL※1, ONT.D)
Output mode [OUtM]
(In case of FLK, NFD, NFD.I)
Output ON time range
[OnRNG]
Time range [tRNG]
Output OFF time range
[OFfRNG]
(2-stage
output mode)
OUT2 output time [OUT2] (1-stage
output mode)
OUT1 output time [OUT1] OUT output time [OUtT]

Input logic※1 [SIG]

Input signal time※1 [IN-T] Memory protection※2 [DATA]

Key lock [LOCK]

M-56
LCD Display Counter/Timer
● Switching display of the setting value display component
Select the display value at the setting value display component.
Depends on output mode, there are manual display switching and auto display switching. SENSORS
-Manual display switching
1) In case of 2-stage setting model (CX6 -2P ) and OND, ONd1, ONd2, ONd3 output mode, it is available.
2) In run mode, whenever pressing the key, the setting value display component displays SET1, SET2 SV in turn. CONTROLLERS
In case of 1-stage setting model (CX6 -1P ), it is not available.
-Auto display switching
1) When output mode is FLK, NFD, NFd1for 1-stage or 2-stage setting model (CX6 -1/2P ) and INt2 mode for 2-stage setting MOTION DEVICES
model (CX6 -2P ), the setting value display component automatically displays the set times depends on the operation status.

● RESET SOFTWARE
-In RUN mode, function setting mode, press the RESET key to reset the current value and the output is also reset.

● Display type of the setting value display component by output mode


-In case of 2-stage setting model (CX6 -2P ) and OND, ONd1, ONd2, ONd3, INt2 output mode, there are SET1 and SET2 setting.
It displays the each SV and the SET1, SET2 indicator turns ON when displaying or setting the each SV.
-In case of 1-stage setting model (CX6 -1P ) , SET is available and there is one setting value.
-In case of 1-stage setting model (CX6 -1P ), INt2 output mode is not available.
-FLK output mode has tOFF, tON setting values. In case of 2-stage setting model (CX6 -2P ) and 1-stage setting model
(CX6 -1P ), each SET2, SET display is available. (J)
Temperature
(tOFF, tON setting value is for OUT2 output. It displays SET2 or SET.) Controllers
-The other output modes display SET2 or SET and have one setting value.
(only for 1-stage setting model (CX6 -1P ))
(K)
SSRs
● Zero blanking display
PV is displayed with zero blanking for the highest unit. (L)
E.g.)When time range is 99m59.99s and PV is 00m04.05s, zero blanking is applied to minute which is the highest unit. Power
At the below digits of decimal point, it is not applied. Controllers

It displays as “0:04.05”.
(M)
Counters

(N)
Timers

(O)
Digital
Panel Meters

(P)
Indicators

(Q)
Converters

(R)
Digital
Display Units

(S)
Sensor
Controllers

(T)
Switching
Mode Power
Supplies

(U)
Recorders

(V)
HMIs

(W)
Panel PC

(X)
Field Network
Devices

M-57
CX Series

Parameter Setting (Timer) ( key: moves parameters, key: changes parameter setting value)
Parameter Parameter setting value
Counter/Timer ※COUNT: Counter
COUNT TIME
[C-T] TIME: Timer
UP DN
Up/Down mode
※UP: Time progresses from '0' to the setting time.
[U-D]
DN: Time progresses from the setting time to '0'.
Output mode OND ONd1 ONd2 ONd3 FLK FLk1 FLk2 INT
[OUtM] ONtD TOTAL ※1
INTG NFd1 NFD OFD INt2※2 INt1
Time range
[tRNG]※3 999.999 9999.99 99999.9 999999 99:59.99 999:59.9
output ON TIME range
TIMER s TIMER s TIMER s TIMER s TIMER m:s TIMER m:s

[OnRNG]※4,
output OFF TIME range 99999.9 9999:59 99:59:59 999999 99999.9 9999:59
TIMER h TIMER h:m TIMER h:m:s TIMER m TIMER m TIMER m:s

[OFfRNG]※4
※Set one-shot output time of OUT 2.
OUT 2 output time※5 ※Setting range: 00.01 to 99.99 sec, Hold
[OUT2] ※When number of tens digit is flashing, press the key once and HOLD appears.
※5 ※Set one-shot output time of OUT 1.
OUT 1 output time ※Setting range: 00.01 to 99.99 sec, Hold
[OUT1] ※When number of tens digit is flashing, press the key once and HOLD appears.

OUT output time ※5


※Setting range: 00.01 to 99.99 sec, Hold
[OUtT] ※When number of tens digit is flashing, press the key once and HOLD appears.
Input logic※6
NPN: No-voltage input, PNP: Voltage input
[SIG]
Input signal time※6 1 20, unit: ms
[IN-T] ※Set min. width of INA, INHIBIT, RESET, TOTAL RESET signal
CLR REC
Memory protection
※CLR: Resets the counting value when power OFF.
[DATA]
REC: Maintains the counting value when power OFF. (memory protection)
※lOFF: Unlock keys, key lock indicator turns OFF
Key lock lOFF LOc1 LOc1: Locks RESET key, key lock indicator turns ON
[LOCK] LOc3 LOc2 LOc2: Locks , keys, key lock indicator turns ON
LOc3: Locks RESET , , keys, key lock indicator turns ON
※1: This is for the voltage input (PNP)/no-voltage input (NPN) selectable model (CX6 - ).
※2: INt2 mode is available only for 2-stage setting model(CX6 -2P ).
※3: When output mode is OND, ONd1, ONd2, ONd3, FLk1, FLk2, INT, INt1, INt2, OFD, INTG, TOTAL, ONtD, set time range [tRNG].
※4: When output mode is FLK, NFD, NFD.1, set output ON TIME range [OnRNG] and output OFF TIME range [OFfRNG].
※5: In case of 1-stage setting model (CX6 -1P ), OUT1 output time does not appear.
OUT2 output time is displayed as OUtT.
※6: In case of free voltage input model (CX6 - F), this parameter does not appear due to fixed setting.

M-58
LCD Display Counter/Timer
One-shot output (0.01 to 99.99 sec)
One-shot output Retained output
Output Operation Mode (Timer) Retained output

Output SENSORS
Time chart
mode Operation
Signal On Delay (Power RESET)
CONTROLLERS
POWER 1)Time starts when INA signal turns ON.
2)When INA signal turns OFF,
INA(START) time resets.
INH(INHIBIT) 3)When INA signal is ON MOTION DEVICES

RESET
:P ower ON Time Start is operated.
RESET OFF Time Start is operated.
Setting time 2
OND 4)Control output operates as retained SOFTWARE
[OND] UP
Setting time 1 (Hold) or one-shot output.
0
Display
Setting time 2 INA
T1
Down
Setting time 1 OUT1
0 T2
OUT2
OUT1 (OUT) T1: Setting time 1
OUT2 T2: Setting time 2

Signal On Delay 1 (Power RESET) 1)Time starts when INA signal turns ON. (J)
Temperature
2)When INA signal is ON Controllers
POWER :P
 ower ON Time Start is operated.
INA(START) RESET OFF Time Start is operated. (K)
3)Control output operates as retained SSRs
INH(INHIBIT)
(Hold) or one-shot output.
RESET 4)Only first INA input signal is valid in (L)
OND.1 Setting time 2 case INA input signal is repeatedly Power
Controllers
[ONd1] UP Setting time 1
applied.
Display 0 INA (M)
Setting time 2 T1 Counters
Down Setting time 1
OUT1
T2
0
(N)
OUT2 Timers
OUT1 (OUT) T1: Setting time 1
OUT2 T2: Setting time 2
(O)
Power On Delay 2 (Power Hold) 1)Power ON Time Start Digital
Panel Meters
(there is no INA function)
POWER 2)RESET ON: Time RESET
INA(START) RESET ON→OFF: Time Start (P)
Indicators
INH(INHIBIT) 3)Control output operates as retained
(Hold) or one-shot output.
RESET
4)It memorizes display value at the (Q)
Setting time 2 moment of power OFF. Converters

OND.2 Setting time 1 HOLD


UP
[ONd2] (R)
0
Display Digital
Setting time 2 POWER Display Units
T1
Down Setting time 1
0 OUT1 (S)
T2 Sensor
Controllers
OUT2
OUT1 (OUT) T1: Setting time 1 (T)

OUT2 T2: Setting time 2 Switching


Mode Power
t a t-a Supplies
Power On Delay 3 (Power Hold/RESET) 1)Power ON Time Start
(there is no INA function) (U)
POWER 2)RESET ON: Time RESET Recorders

INA(START) RESET ON→OFF: Time Start


INH(INHIBIT) 3)Control output operates as retained (V)
RESET (Hold) or one-shot output. HMIs

Setting time 2
4)If time reached setting time at the
OND.3 UP moment of power ON, it is automati-
Setting time 1
[ONd3] cally reset.
(W)
Panel PC
0
Display HOLD
Setting time 2
Down Setting time 1 POWER (X)
0 Field Network
OUT2 Devices
(OUT)
OUT1
OUT2

※Power RESET: There is no memory protection. (resets the display value when power is off)
※Power Hold: There is memory protection.
(memorizes the display value at the moment of power off, indicates the memorized display value when power is resupplied.)

M-59
CX Series
One-shot output (0.01 to 99.99 sec)
One-shot output Retained output
Output Operation Mode (Timer) Retained output

Output
Time chart
mode Operation
Flicker (Power RESET)
1)Time starts when INA signal turns ON.
2)When INA signal is ON
:P ower ON Time Start is operated.
POWER RESET OFF Time Start is operat-
INA(START)
ed.
3)Control output operates as retained
INH(INHIBIT)
output, output turns off for the
RESET T.off time and turns off for the T.off
T.off time and turns on for the T.on time
Setting time
repeatedly.
FLK T.on
Setting time Ta+Tb = T.off
[FLK] UP
4)The T.on time and T.off time must be
0
Display set individually.
T.off
Setting time 5)In case of using the contact output,
Down T.on min. setting time must be set over
Setting time 100ms.
0
T.off T.on Ta Tb T.on T.off T.on T.off T.on T.off POWER

OUT2(OUT) INA
T.off T.on T.off

OUT2
(OUT)

Flicker 1 (Power Reset) 1)Time starts when INA signal turns ON.
2)When INA signal is ON
Retained (Hold) output :P ower ON Time Start is operated.
RESET OFF Time Start is operat-
POWER ed.
INA(START) 3)Control output operates as retained
INH(INHIBIT)
(Hold) output.
4)In case of using the contact output,
RESET min. setting time must be set over
Setting time 100ms.
Up
POWER
0
Display INA
Setting time T T T
Down
OUT2
0 (OUT) T: Setting time
FLK.1 OUT2(OUT)
[FLk1]
One-shot output 1)Time starts when INA signal turns ON.
2)When INA signal is ON
POWER :P ower ON Time Start is operated.
INA(START)
RESET OFF Time Start is operat-
ed.
INH(INHIBIT) 3)Control output operates as one-shot
RESET output.
Setting time 4)In case of using the contact output,
Up min. setting time must be set over
0 100ms.
Display
Setting time POWER
Down INA
0 T T T
t t t
OUT2
OUT2(OUT) (OUT) T: Setting time

※Power RESET: There is no memory protection. (resets the display value when power is off)
※Power Hold: There is memory protection.
(memorizes the display value at the moment of power off, indicates the memorized display value when power is resupplied.)

M-60
LCD Display Counter/Timer
One-shot output (0.01 to 99.99 sec)
One-shot output Retained output
Output Operation Mode (Timer) Retained output

Output
Time chart SENSORS
mode Operation
Flicker 2 (Power Hold)
1)Time starts when INA signal turns ON CONTROLLERS
and the display value at the moment
Retained (Hold) output when power is off is memorized.
2)When INA signal is ON
MOTION DEVICES
POWER :P ower ON Time Start is operated.
RESET OFF Time Start is operated.
INA(START) 3)Control output operates as retained
INH(INHIBIT) (Hold) output. SOFTWARE
4)Control output will be reversed when
RESET it reaches to setting time.
Setting time (at the initial start, OUT2 control
Up output is OFF).
0 5)In case of using the contact output,
Display min. setting time must be set over
Setting time
100ms.
Down
0 POWER
INA
FLK.2 OUT2(OUT) T T-c c T
(J)
Temperature
[FLk2] OUT2 Controllers

(OUT) Hold T: Setting time


(K)
One-shot output 1)Time starts when INA signal turns ON SSRs
and the display value at the moment
POWER when power is off is memorized.
2)When INA signal is ON (L)
INA(START) :P ower ON Time Start is operated. Power
Controllers
INH(INHIBIT) RESET OFF Time Start is operated.
3)Control output operates as one-shot
RESET
output. (M)
Counters
Setting time 4)In case of using the contact output,
Up min. setting time must be set over
0 100ms.
Display (N)
Setting time Timers
POWER
Down
0 INA
T T-c c T (O)
t t t a t-a t OUT2 Digital
(OUT) Panel Meters
OUT2(OUT) Hold T: Setting time
Interval (Power RESET) 1)Control output turns ON and time
starts when INA signal turns ON. (P)
Indicators
POWER 2)When INA signal is OFF, time is reset.
3)When INA signal is ON
INA(START)
:P ower ON Time Start is operated. (Q)
INH(INHIBIT) RESET OFF Time Start is operated. Converters

RESET 4)When it reaches setting time,


INT it is auto reset.
Setting time 5)Control output is ON when the time is (R)
[INT] Digital
Up progressing. Display Units
0
Display POWER
(S)
Setting time INA Sensor
Down T T Controllers
0 OUT2
(OUT) (T)
OUT2(OUT) T: Setting time Switching
Mode Power
Interval 1 (Power RESET) 1)Control output turns ON and time Supplies
starts when INA signal turns ON.
2)When INA signal is ON (U)
POWER
:P ower ON Time Start is operated. Recorders

INA(START) RESET OFF Time Start is operated.


3)When it reaches setting time,
INH(INHIBIT) it is auto reset. (V)
HMIs
RESET 4)Control output is ON when the time is
INT.1 progressing.
[INt1] Setting time 5)Time is ignored while time is pro- (W)
Up gressing. Panel PC
0
Display POWER
Setting time (X)
Down INA Field Network
T Devices
0 OUT2
(OUT)
OUT2(OUT) T: Setting time

※Power RESET: There is no memory protection. (resets the display value when power is off)
※Power Hold: There is memory protection.
(memorizes the display value at the moment of power off, indicates the memorized display value when power is resupplied.)

M-61
CX Series
One-shot output (0.01 to 99.99 sec)
One-shot output Retained output
Output Operation Mode (Timer) Retained output

Output
Time chart
mode Operation
Interval 2 (Power RESET)
1)Time starts when INA signal is ON,
and resets when INA signal is OFF.
2)INA signal is ON, OUT1 output is ON
POWER during T1 (HOLD) or t1.
INA(START)
3)When it reaches setting time 1, dis-
play value resets and OUT2 output
INH(INHIBIT) is ON during T2 (HOLD) or t2 output
RESET time.
※Output turns OFF when reaching
Setting time 1
INT.2 the setting time even if one-shot is
Setting time 2
[INt2] Up
longer than setting time.
0
Display INA
T1
Setting time 2
Down OUT1 T1: Setting time 1
Setting time 1 T2
t1 T2: Setting time 2
0 OUT2 t1: One-shot1
t2 t1: One-shot2
OUT1
(1-stage SET model has no INt2 mode)
OUT2

Signal Off Delay (Power RESET) 1)If INA is ON, control output remains
ON. (except when power is off and
POWER
reset is on)
2)When INA signal is OFF, time pro-
INA(START) cesses.
INH(INHIBIT) When it reaches setting time, indica-
RESET
tion value and control output are auto
OFD reset automatically.
Setting time
[OFD] Up POWER
0
Display INA
Setting time T
Down
0 OUT2
(OUT) T: Setting time
OUT2(OUT)

On-Off Delay (Power RESET) 1)When INA input is ON, output is ON


and time is progressing, then output
POWER is OFF after On_Delay time.
2)When INA input is OFF, output is ON
INA(START) and time is progressing, then output
INH(INHIBIT) is OFF after Off_Delay time.
RESET
3)If INA input is OFF within On_Delay
time, step 2 starts.
On_Delay 4)If INA input is ON within Off_Delay
NFD
[NFD] Off_Delay time, step 1 starts.
Up
0 INA
Display T1 T2
On_Delay
OUT2
Down Off_Delay (OUT) T1: On_Delay
0 T2: Off_Delay

OUT2(OUT)

※Power RESET: There is no memory protection. (resets the display value when power is off)
※Power Hold: There is memory protection.
(memorizes the display value at the moment of power off, indicates the memorized display value when power is resupplied.)

M-62
LCD Display Counter/Timer
One-shot output (0.01 to 99.99 sec)
One-shot output Retained output
Output Operation Mode (Timer) Retained output

Output
Time chart SENSORS
mode Operation
On-Off Delay1 (Power RESET)
1)When INA input turns ON, time CONTROLLERS

POWER progresses and output turns ON after


On_Delay time.
INA(START) 2)When INA input turns OFF, time pro- MOTION DEVICES
gresses and output turns OFF after
INH(INHIBIT)
Off_Delay time.
RESET 3)If INA input turns OFF within
SOFTWARE
NFD.1 On_Delay On_Delay time, output will turn ON
[NFd1] and step 2 operate.
Off_Delay
Up 4)If INA input turns ON within
0 Off_Delay time, output will turn OFF
Display
On_Delay and step 1 operate.
Down
Off_Delay INA
T1 T2
0
OUT2
OUT2(OUT) (OUT) T1: On_Delay (J)
T2: Off_Delay Temperature
Controllers
Integration Time (Power RESET) 1)Time is progressing while INA input
is ON.
POWER 2)Time progress stops while INA input (K)
SSRs
INA(START) is OFF.
3)When it reaches the setting time,
INH(INHIBIT) (L)
output is ON. Power
RESET Controllers
INTG Setting time
[INTG]
Up (M)
0 Counters
Display
Setting time
Down (N)
0 Timers

OUT2(OUT)
When memory protection setting is OFF 1)Time starts when INA input is ON. (O)
Digital
2)When RESET signal is ON, the Panel Meters
POWER
display value is reset.
INA(START)
3)Time progress stops when INHIBIT (P)
INH(INHIBIT) signal is ON. Indicators
RESET 4)The progressed time is reset when
Max. power OFF.
time range (Q)
Up Converters
0
Display Max.
(R)
Down time range Digital
Display Units
TOTAL 0
[TOTAL] When memory protection setting is ON 1)Time starts when INA input is ON.
(S)
2)When RESET signal is ON, the Sensor
POWER
display value is reset. Controllers
INA(START)
3)Time progress stops when INHIBIT
(T)
INH(INHIBIT) signal is ON. Switching
Mode Power
RESET 4)The progressed time at the moment Supplies
Max. of power OFF is memorized.
Up time range
(U)
0 Recorders
Display
Max.
Down time range
(V)
0 HMIs

※Power RESET: There is no memory protection. (resets the display value when power is off)
※Power Hold: There is memory protection. (W)
(memorizes the display value at the moment of power off, indicates the memorized display value when power is resupplied.) Panel PC

※When memory protection setting is OFF, it does not memorize the display value when power turns OFF.
(the display value is reset when power turns OFF) (X)
※When memory protection setting is ON, it memorizes the display value when power turns OFF. Field Network
Devices
When re-suppling the power, it displays the memorized value.

M-63
CX Series
One-shot output (0.01 to 99.99 sec)
One-shot output Retained output
Output Operation Mode (Timer) Retained output

Output
Time chart Operation
mode
When memory protection setting is OFF ※ON time indicate mode of INA signal.
1)Time reset start operates when INA
POWER
signal turns ON.
INA(START)
2)Time progress stops while INA signal is
INH(INHIBIT) OFF.
RESET 3)When INA signal is OFF, if INA input
OUT2(OUT) time is greater than the setting time,
Setting time the display value flashes and the opera-
Up
tion stops until RESET signal ON.※1
0
Display 4)When time progress stops and power
Setting time turns OFF, the progressed time is reset.
Down
On Time 0
Display When memory protection setting is ON ※ON time indicate mode of INA signal.
[ONtD] 1)Time reset start operates when INA
POWER signal turns ON.
INA(START) 2)Time progress stops while INA signal is
INH(INHIBIT) OFF.
RESET 3)When time progress stops and power
OUT2(OUT) turns OFF, the progressed time at the
Setting time
moment of power OFF is memorized.

Up
0
Display
Setting time
Down

0
※1: For free voltage input model (CX6 - F).
※Power RESET: There is no memory protection. (resets the display value when power is off)
※Power Hold: There is memory protection.
(memorizes the display value at the moment of power off, indicates the memorized display value when power is resupplied.)
※When memory protection setting is OFF, it does not memorize the display value when power turns OFF.
(the display value is reset when power turns OFF)
※When memory protection setting is ON, it memorizes the display value when power turns OFF.
When re-suppling the power, it displays the memorized value.

M-64
LCD Display Counter/Timer
One-shot output (0.01 to 99.99 sec)
Timer '0' Time Setting Retained output
A
 vailable output operation mode to set '0' time setting SENSORS
OND, ONd1, ONd2, ONd3, NFD, NFd1 One-shot output Retained output
Operation according to output mode (at 0 time setting) CONTROLLERS

1) OND (Signal ON Delay) mode [OND]


● Set '0' for setting time1 . ● Set '0' for setting time2 . MOTION DEVICES
Up mode Down mode
INA (START) INA (START)
Setting time 2 Setting time 1 SOFTWARE

0 0

OUT 1 OUT 1

OUT 2 OUT 2

2) OND.1 (Signal ON Delay 1) mode [ONd1]


● Set '0' for setting time1 . ● Set '0' for setting time2 . (J)
Up mode Down mode Temperature
Controllers
INA (START) INA (START)
RESET RESET (K)
SSRs
Setting time 2 Setting time 1

(L)
0 0 Power
Controllers
OUT 1 OUT 1

OUT 2 OUT 2 (M)


Counters

3) OND.2 (Power ON Delay 2) mode [ONd2]


● Set '0' for setting time1 . ● Set '0' for setting time2 . (N)
Timers
Up mode Down mode Up mode
POWER POWER (O)
Digital
RESET RESET Panel Meters
Setting time 2 Setting time 1
(P)
Indicators
0 0
OUT 1 OUT 1
(Q)
OUT 2 OUT 2 Converters

4) OND.3 (Power ON Delay 3) mode [ONd3] (R)


Digital
● Set '0' for setting time1 . ● Set '0' for setting time2 . Display Units
Up mode Down mode Up mode
(S)
POWER POWER Sensor
Controllers
RESET RESET
Setting time 2 Setting time 1 (T)
Switching
Mode Power
Supplies
0 0

OUT1 OUT1 (U)


Recorders

OUT2 OUT2

5) NFD (ON-OFF Delay) mode [NFD] (V)


HMIs

● Set '0' for Off_Delay setting time. ● Set '0' for On_Delay setting time.
(W)
INA (START) INA (START) Panel PC

RESET RESET
On_Delay UP Off_Delay (X)
UP Field Network
Devices
DISPLAY 0 DISPLAY 0
DOWN On_Delay DOWN Off_Delay
0 0
OUT 2 OUT 2
(OUT) (OUT)

M-65
CX Series
6) NFD.1 (ON-OFF Delay1) mode [NFd1]
Set ‘0’ for Off_Delay setting time. Set ‘0’ for On_Delay setting time.
INA (START) INA (START)
RESET RESET

On_Delay Off_Delay
Up
Up 0 0
Display Display
On_Delay Off_Delay
Down Down
0 0
OUT2 OUT2
(OUT) (OUT)

When SET1 is greater than SET2


In case of OND[OND], OND.1[ONd1], OND.2[ONd2] , or OND.3[ONd3] output mode,
●U P mode: When timer setting value 1 (SET1) is greater than setting value 2 (SET2), OUT1 output does not turn ON.
●D OWN mode: When timer setting value 1 (SET1) is greater than setting value 2 (SET2), OUT1 output does not turn ON.
When timer setting value 1 (SET1) and setting value 2 (SET2) are same, OUT1 output turns ON when applied the start signal.

Factory Default
Factory default
- Parameter
CX6 - CX6 - F
InM UD-C UD-A
OUtM F F
CPS 30 -
OUT2 (OUtT※1) HOLD (fixed) HOLD (fixed)
OUT1※1 0)10 0)10
DP ------ ------
Counter RESET 20ms -
SIG NPN -
SClDP -.-----, -.-----,
SCL !00000 !00000
TOTAL※2 OFF -
START 000000 000000
DATA CLR CLR
U-D UP UP
OUtM OND OND
OUT2 (OUtT※1) HOLD HOLD
Timer OUT1※1 0)10 0)10
tRNG 99(999s 99(999s
SIG※2 NPN -
IN-T 20ms -
LOCK lOFF lOFF
SET1 1000 1000
SET2 5000 5000
※1: For 1-stage setting model (CX6 -1P ), OUT1 does not appear.
The output time of OUT2 is displayed as OUtT.
※2: This is for the voltage input (PNP)/no-voltage input (NPN) selectable model (CX6 - ).

Cautions during Use


● Follow instructions in ‘Cautions during Use’. Otherwise, it may cause unexpected accidents.
● In case of 24-48VDC, 24VAC model, power supply should be insulated and limited voltage/current or Class 2, SELV power supply device.
● Use the product, 0.1 sec after supplying power.
● When supplying or turning off the power, use a switch or etc. to avoid chattering.
● Install a power switch or circuit breaker in the easily accessible place for supplying or disconnecting the power.
● Keep away from high voltage lines or power lines to prevent inductive noise.
In case installing power line and input signal line closely, use line filter or varistor at power line and shielded wire at input signal line.
Do not use near the equipment which generates strong magnetic force or high frequency noise.
●T  his unit may be used in the following environments.
①Indoors (in the environment condition rated in ‘Specifications’)
②Altitude max. 2,000m
③Pollution degree 2
④Installation category II

M-66