Autonics CX Series - Data Sheet
Autonics CX Series - Data Sheet
[Counter]
● Setting range of prescale value: 0.00001 to 99999.9 SOFTWARE
[Timer]
(J)
● Various output mode (15 types) Temperature
Controllers
● Wide time setting range: 0.001 sec to 99999.9 hour
● '0' time setting function
(K)
SSRs
Manual (M)
For the detail information, please refer to user manual, and be sure to follow cautions written in the technical descriptions (catalog, website). Counters
Ordering Information
(O)
Digital
Panel Meters
CX 6 S - 1P 4 F (P)
Indicators
Voltage input (PNP)/no-voltage input (NPN)
No mark
Signal input method selectable type
F Free voltage input (Q)
Converters
Power supply 2 24VAC 50/60Hz, 24-48VDC
4 100-240VAC 50/60Hz (R)
Digital
Output 1P 1-stage setting Display Units
2P 2-stage setting
(S)
Sensor
Size S DIN W48×H48mm Controllers
M DIN W72×H72mm
Display digit (T)
6 999999 (6-digit) Switching
Mode Power
Item Supplies
CX LCD Display counter/Timer
(U)
Recorders
(V)
HMIs
(W)
Panel PC
(X)
Field Network
Devices
M-41
CX Series
Specifications
Model CX6S-1P CX6S-2P CX6M-1P CX6M-2P
Display digits 6-digit
7-segment (1st, 2nd digits of counting value display: white, setting value display: green) LCD method,
Display method 11-segment (the other digits of counting value display: white) LCD method,
Operation display part: yellow LCD method
Character Counting value 4.1×10.1mm 6.2×15.2mm
size (W×H) Setting value 3.3×8.1mm 5×12.3mm
Power AC voltage 100-240VACᜠ 50/60Hz
supply AC/DC voltage 24VACᜠ 50/60Hz, 24-48VDCᜡ
Permissible voltage range 90 to 110% of rated voltage
AC volt- CX6 - Max. 6.4VA Max. 6.7VA Max. 7.1VA Max. 7.5VA
consumption
age CX6 - F Max. 4.2VA Max. 4.9VA Max. 4.7VA Max. 5.4VA
Power
AC: max. 5.5VA AC: max. 5.6VA AC: max. 6.2VA AC: max. 6.3VA
CX6 -
AC/DC DC: max. 3.5W DC: max. 3.6W DC: max. 4W DC: max. 4.1W
voltage AC: max. 3.6VA AC: max. 4.0VA AC: max. 3.9VA AC: max. 4.5VA
CX6 - F
DC: max. 2.5W DC: max. 2.8W DC: max. 2.9W DC: max. 3.3W
Max. INA/ CX6 - Selectable among 1cps/30cps/300cps/1kcps/5kcps
INB counting
speed CX6 - F 20cps
Counter
CX6 - F Approx. 155g (approx. 110g) Approx. 160g (approx. 115g) Approx. 233g (approx. 168g) Approx. 238g (approx. 173g)
AC/DC CX6 - Approx. 156g (approx. 111g) Approx. 161g (approx. 116g) Approx. 234g (approx. 169g) Approx. 239g (approx. 174g)
voltage CX6 - F Approx. 154g (approx. 109g) Approx. 159g (approx. 114g) Approx. 232g (approx. 167g) Approx. 237g (approx. 172g)
※1: This is for the voltage input (PNP)/no-voltage input (NPN) selectable model (CX6 - ).
※2: The weight includes packaging. The weight in parenthesis is for unit only.
※Environment resistance is rated at no freezing or condensation.
M-42
LCD Display Counter/Timer
Connections
CX6S Series SENSORS
(L)
Power
Controllers
(M)
2. Free voltage input model Counters
(U)
Recorders
(V)
HMIs
(W)
Panel PC
(X)
Field Network
Devices
M-43
CX Series
Connections
CX6M Series
1. Voltage input (PNP), no-voltage input (NPN) selectable model
CX6M-1P CX6M-2P
CONTACT OUT: 250VAC 3A, 30VDC 3A CONTACT OUT1/OUT2: 2
50VAC 3A, 30VDC 3A
RESISTIVE LOAD RESISTIVE LOAD
1 10 INA 1 10 INA
6 15 INHIBIT 6 15 INHIBIT
SOLID SOLID 16 TOTAL RESET
7 16 TOTAL RESET 7
STATE ※1 STATE OUT1
※1
8 OUT: 17 8 OUT: 17
30VDC 30VDC
9 100mA 18 9 100mA OUT2 18
SOURCE: 100-240VAC 50/60Hz 7.1VA SOURCE: 1
00-240VAC 50/60Hz 7.5VA
24VAC 50/60Hz 6.2VA 24VAC 50/60Hz 6.3VA
24-48VDC 4W 24-48VDC 4.1W
M-44
LCD Display Counter/Timer
CX6S Series
48 6 64.5 Min. 65 CONTROLLERS
45 +0.6
0
MOTION DEVICES
Min. 65
44.8
+0.6
45 0
SOFTWARE
CX6M Series
72 6 64.5
CX6M Series
Min. 91
(J)
Temperature
Controllers
68 +0.7
0
67.5
(K)
Min. 91
SSRs
68 +0.7
0
(L)
Power
Controllers
(M)
Counters
Bracket
CX6S Series CX6M Series (N)
Timers
±0.2
48.6 30.6
3.3
(O)
45 +0.2
0 20 Digital
5 Panel Meters
16 +0.3
4
0
(P)
46
-0.05
44.9 +0.2
Indicators
36
37.5
(Q)
40.5
Converters
15
55 (R)
21 Digital
12 Display Units
23.9
(S)
Sensor
Controllers
56
(T)
Switching
Mode Power
Supplies
Terminal cover (sold separately)
C
X6S Series C
X6M Series (U)
Recorders
(RSA-COVER, 48×48mm) (RMA-COVER, 72×72mm)
22 4 70 10 (V)
3 48.4 13 HMIs
(W)
Panel PC
68.5
41
45
64
(X)
Field Network
Devices
18
22
13
M-45
CX Series
Unit Description
CX6S Series CX6M Series
1
1
7
2
8
3 7
9 2
4
10 5 8
11 6 9 3
4
10
12 13 14 5
11 6
12 13 14
※1: This is for the voltage input (PNP)/no-voltage input (NPN) selectable model (CX6 - ).
M-46
LCD Display Counter/Timer
Input Connections
No-voltage input (NPN) SENSORS
● Solid-state input (standard sensor: NPN output type sensor) ● Contact input
CONTROLLERS
Sensor Counter/Timer Sensor Counter/Timer Counter/Timer
Brown Brown
+12V +12V +12V
MOTION DEVICES
5.4kΩ 5.4kΩ 5.4kΩ
Black ※1 Inner circuit Black ※1 Inner circuit ※2 Inner circuit
of input part of input part of input part
SOFTWARE
Blue Blue
0V 0V 0V
(NPN output) (NPN open collector output)
※1: CP1, CP2 (INHIBIT), SET input part
※2: Set counting speed as 1 or 30cps.
(J)
Temperature
● Solid-state input (standard sensor: PNP output type sensor) ● Contact input (K)
SSRs
(Q)
Counter/Timer ※1
Counter/Timer
(S)
Sensor
Load (+) Power
Controllers
※Select the load which capacity is not over contact ※For solid state output, select load power and load not to be over
(U)
capacity. (max. 30VDC, 100mA), swithching capacity. Recorders
※Do not supply reverse polarity voltage.
※1: F
or using inductive load (relay, etc.), connect surge absorber
(V)
(diode, varistor etc.) at the both ends of load. HMIs
(W)
Panel PC
(X)
Field Network
Devices
M-47
CX Series
RESET
RESET PV RESET
(CX6 - F)
(RUN mode)
Reset TOTAL
counter
[Counter] 12:30:25
OUT1
Display PV
OUT2
SET2
1:25:47
TIMER
Display SET2
12:34:56
OUT1
Display PV
OUT2
5:43:50 Display SET1
[Timer]
SET1
TIMER
Counter mode
● Changing
SV mode
When input signal is ON during changing SV, it operates counting and output control.
It is available to set SV as '0' and the dedicated output for SV '0' occurs.
There are output mode which cannot set SV as '0'. (the setting value display component flashes three times when SV is set as '0')
RUN mode
SET2
value
After setting SV at each parameter, press the key to save SV and it moves
next parameter setting or returns to RUN mode.
SET1
value (CX6 - F)
M-48
LCD Display Counter/Timer
● Function setting mode
※1: In case of free voltage input model (CX6 - F), these parameters do not appear due to fixed setting.
※2: This parameter is for the voltage input(PNP)/no-voltage input(NPN) selectable model (CX6 - ). SENSORS
※ : When changing the setting of shaded parameters, all output turn OFF.
RUN mode
CONTROLLERS
3 sec -Hold the key over 3 sec in RUN mode and it enters
3 sec
function setting mode.
-Hold the key over 3 sec in function setting mode
Counter/Timer [C-T] MOTION DEVICES
Function setting mode
(K)
Min. reset time※1 [RESET] SSRs
(P)
Key lock [LOCK] Indicators
(Q)
Converters
● Function setting check mode (only for free voltage input model (CX6 - F))
-When checking the saved parameters, press the , key to check next item. (R)
Digital
-At function setting check mode, the counting value display component displays the parameters and the setting value display Display Units
SV are different, the prescale value is not the 1/n time of SV.
(X)
● RESET Field Network
Devices
-In RUN mode, function setting mode, press the RESET key to reset the current value and the output turns OFF.
-At TOTAL counter display mode, press the RESET key to reset TOTAL counter counting value and the current counting value.
M-49
CX Series
※If max. counting speed is 5kcps, and output mode is D, max. counting speed is automatically changed as 30cps,
factory default.
※Max. counting speed is when duty ratio of INA or INB input signal is 1:1.
Max. counting
30 300 1K 5K 1 It is applied for INA, or INB input as same.
speed※2
※When output mode is D, set max. counting speed one among 1cps, 30cps, 300cps, or
[CPS]
1kcps.
OUT 2 ※Set one-shot output time of OUT 2.
※
output time 3 ※Setting range: 00.01 to 99.99 sec
[OUT2] ※When output mode is F, N, S, T, D, this parameter does not appear. (fixed as HOLD)
※Set one-shot output time of OUT 1.
OUT 1
※ ※Setting range: 00.01 to 99.99 sec, Hold
output time 3
※When number of tens digit is flashing, press the key once and HOLD appears.
[OUT1]
※When output mode is S, T, D, this parameter does not appear. (fixed as HOLD)
OUT
※ ※Setting range: 00.01 to 99.99 sec
output time 3
※When output mode is F, N, S, T, D, this parameter does not appear. (fixed as HOLD)
[OUtT]
※4 ------ -----.- ----.-- ---.--- --.---- -.-----
Decimal point
[DP]
※Decimal point is applied to PV and SV.
※2
Min. reset time 1 20, unit: ms
[RESET] ※Set min. width of external reset signal input.
※2
Input logic
NPN: No-voltage input, PNP: Voltage input
[SIG]
Prescale -.----- -----.- ----.-- ---.--- --.----
decimal point※4
[SClDP] ※Decimal point of prescale should not set smaller than decimal point [DP].
Prescale value ※Setting range: 0.00001 to 99999.9
[SCL] ※Setting range of prescale is linked with prescale decimal point [SClDP] setting.
※1
TOTAL counter
ㅐㅜON OFF
[TOTAL]
※Setting range of start point value is linked with decimal point [DP] setting. (0.00000 to 999999)
Start point value
※When input mode is DN, DN-1, DN-2, this parameter does not appear.
[START] ※1
※When total count function is ON, this parameter does not appear.
Memory protection ※CLR: Resets the counting value when power OFF.
CLR REC
[DATA] REC: Maintains the counting value when power OFF. (memory protection)
※lOFF: Unlock keys, key lock indicator turns OFF
Key lock lOFF LOc1 LOc1: Locks RESET key, key lock indicator turns ON
[LOCK] LOc3 LOc2 LOc2: Locks , keys, key lock indicator turns ON
LOc3: Locks RESET , , keys, key lock indicator turns ON
※1: For voltage input (PNP), no-voltage input (NPN) model (CX6 - ).
※2: For free voltage input model(CX6 - F), these parameters do not appear due to fixed setting.
※3: For 1-stage setting model (CX6 -1P ), OUT1 does not appear.
The OUT2 output time is displayed as OUtT.
※4: Decimal point and prescale decimal point
-Decimal point: Set the decimal point for display value regardless of prescale value.
-Prescale decimal point: Set the decimal point for prescale value of counting value regardless of display value.
M-50
LCD Display Counter/Timer
H No counting
INA
L
CONTROLLERS
H
INA
L
H ※When INA input signal is rising ( ),
INB
UP-1 L it counts.
[UP-1] No counting 5 ※INA: Counting input
4
3 ※INB: No counting input
Count 2 (J)
1 Temperature
0 Controllers
H
INA L (K)
SSRs
H
INA (N)
L Timers
H No counting
INA L (Q)
Converters
M-51
CX Series
H
INA
L ※INA: Up counting input
Up/ H INB: Down counting input
INB
Down-B L 4 4 ※When INA and INB input signals are rising
[UD-B] 3 3 3 ( ) at the same time, it maintains previ-
Count 2 2 2
1 ous value.
0
H
INA
L
Up/ ※When connecting encoder output A, B
H
INB phase with counter input, INA, INB, set
Down-C L 3 3 input mode [InM] as phase different input
[UD-C] 2 2 2 [UD-C] for counter operation.
Count 1 1
0
※A: over min. signal width, B: over than 1/2 of min. signal width. If the signal is smaller than these width, it may cause counting error (±1).
INA H
(INB) L ON OFF ON OFF
T.on T.off
T
M-52
LCD Display Counter/Timer
SENSORS
Output Input mode
Operation
mode Up, Up-1, 2, 3 Down, Down-1, 2, 3 Up/Down A, B, C
RESET CONTROLLERS
999999
SET 2 ※After count-up, counting display val-
F SET 1 ue increases or decreases until reset
MOTION DEVICES
[F] 0 signal is applied and retained output
OUT1 is maintained.
OUT2
(OUT) SOFTWARE
RESET
999999
SET 2
※After count- up, counting display
N SET 1
value and retained output are main-
[N] 0
tained until reset signal is applied.
OUT1
OUT2
(OUT)
M-53
CX Series
RESET
※OUT1 output is off
999999
SET2 : Counting display value ≥ SET1
(when SET1 is 0, OUT1 output maintains
T SET1
0 ON state.)
[T] -99999 ※OUT2 keeps ON status in following con-
OUT1 dition
OUT2 : Counting display value ≥ SET2
(OUT)
※OUT1 is available to set as ‘0’ regardless of output mode. The output for '0' setting executes.
※In case of C, R, P, Q output mode for OUT2, setting ‘0’ is not available.
When SET2=SET1
-Output of OUT1 turns ON for RESET OFF.
M-54
LCD Display Counter/Timer
Pulley
MOTION DEVICES
Cutter
(J)
3.1416 × 22
= Temperature
Controllers
1000
Motor conlrol system
Counter = 0.069mm/pulse (K)
SSRs
(L)
Power
Set decimal point[DP] as [-----.-], prescale decimal point [SClDP] as [---.---], prescale value [SCL] as [0.069] at function setting mode. Controllers
(N)
Timers
(Q)
Converters
(R)
Digital
Display Units
(S)
Sensor
Controllers
(T)
Switching
Mode Power
Supplies
(U)
Recorders
(V)
HMIs
(W)
Panel PC
(X)
Field Network
Devices
M-55
CX Series
Timer mode
● Changing
SV mode
When input signal is ON during changing SV, it operates counting and output control.
It is available to set SV as '0' and the dedicated output for SV '0' occurs.
There are output mode which cannot set SV as '0'. (the setting value display component flashes three times when SV is set as '0')
RUN mode
12:30:25
OUT1
Display PV
OUT2
1:25:47 Display SET2
SET2 TIMER
M-56
LCD Display Counter/Timer
● Switching display of the setting value display component
Select the display value at the setting value display component.
Depends on output mode, there are manual display switching and auto display switching. SENSORS
-Manual display switching
1) In case of 2-stage setting model (CX6 -2P ) and OND, ONd1, ONd2, ONd3 output mode, it is available.
2) In run mode, whenever pressing the key, the setting value display component displays SET1, SET2 SV in turn. CONTROLLERS
In case of 1-stage setting model (CX6 -1P ), it is not available.
-Auto display switching
1) When output mode is FLK, NFD, NFd1for 1-stage or 2-stage setting model (CX6 -1/2P ) and INt2 mode for 2-stage setting MOTION DEVICES
model (CX6 -2P ), the setting value display component automatically displays the set times depends on the operation status.
● RESET SOFTWARE
-In RUN mode, function setting mode, press the RESET key to reset the current value and the output is also reset.
It displays as “0:04.05”.
(M)
Counters
(N)
Timers
(O)
Digital
Panel Meters
(P)
Indicators
(Q)
Converters
(R)
Digital
Display Units
(S)
Sensor
Controllers
(T)
Switching
Mode Power
Supplies
(U)
Recorders
(V)
HMIs
(W)
Panel PC
(X)
Field Network
Devices
M-57
CX Series
Parameter Setting (Timer) ( key: moves parameters, key: changes parameter setting value)
Parameter Parameter setting value
Counter/Timer ※COUNT: Counter
COUNT TIME
[C-T] TIME: Timer
UP DN
Up/Down mode
※UP: Time progresses from '0' to the setting time.
[U-D]
DN: Time progresses from the setting time to '0'.
Output mode OND ONd1 ONd2 ONd3 FLK FLk1 FLk2 INT
[OUtM] ONtD TOTAL ※1
INTG NFd1 NFD OFD INt2※2 INt1
Time range
[tRNG]※3 999.999 9999.99 99999.9 999999 99:59.99 999:59.9
output ON TIME range
TIMER s TIMER s TIMER s TIMER s TIMER m:s TIMER m:s
[OnRNG]※4,
output OFF TIME range 99999.9 9999:59 99:59:59 999999 99999.9 9999:59
TIMER h TIMER h:m TIMER h:m:s TIMER m TIMER m TIMER m:s
[OFfRNG]※4
※Set one-shot output time of OUT 2.
OUT 2 output time※5 ※Setting range: 00.01 to 99.99 sec, Hold
[OUT2] ※When number of tens digit is flashing, press the key once and HOLD appears.
※5 ※Set one-shot output time of OUT 1.
OUT 1 output time ※Setting range: 00.01 to 99.99 sec, Hold
[OUT1] ※When number of tens digit is flashing, press the key once and HOLD appears.
M-58
LCD Display Counter/Timer
One-shot output (0.01 to 99.99 sec)
One-shot output Retained output
Output Operation Mode (Timer) Retained output
Output SENSORS
Time chart
mode Operation
Signal On Delay (Power RESET)
CONTROLLERS
POWER 1)Time starts when INA signal turns ON.
2)When INA signal turns OFF,
INA(START) time resets.
INH(INHIBIT) 3)When INA signal is ON MOTION DEVICES
RESET
:P ower ON Time Start is operated.
RESET OFF Time Start is operated.
Setting time 2
OND 4)Control output operates as retained SOFTWARE
[OND] UP
Setting time 1 (Hold) or one-shot output.
0
Display
Setting time 2 INA
T1
Down
Setting time 1 OUT1
0 T2
OUT2
OUT1 (OUT) T1: Setting time 1
OUT2 T2: Setting time 2
Signal On Delay 1 (Power RESET) 1)Time starts when INA signal turns ON. (J)
Temperature
2)When INA signal is ON Controllers
POWER :P
ower ON Time Start is operated.
INA(START) RESET OFF Time Start is operated. (K)
3)Control output operates as retained SSRs
INH(INHIBIT)
(Hold) or one-shot output.
RESET 4)Only first INA input signal is valid in (L)
OND.1 Setting time 2 case INA input signal is repeatedly Power
Controllers
[ONd1] UP Setting time 1
applied.
Display 0 INA (M)
Setting time 2 T1 Counters
Down Setting time 1
OUT1
T2
0
(N)
OUT2 Timers
OUT1 (OUT) T1: Setting time 1
OUT2 T2: Setting time 2
(O)
Power On Delay 2 (Power Hold) 1)Power ON Time Start Digital
Panel Meters
(there is no INA function)
POWER 2)RESET ON: Time RESET
INA(START) RESET ON→OFF: Time Start (P)
Indicators
INH(INHIBIT) 3)Control output operates as retained
(Hold) or one-shot output.
RESET
4)It memorizes display value at the (Q)
Setting time 2 moment of power OFF. Converters
Setting time 2
4)If time reached setting time at the
OND.3 UP moment of power ON, it is automati-
Setting time 1
[ONd3] cally reset.
(W)
Panel PC
0
Display HOLD
Setting time 2
Down Setting time 1 POWER (X)
0 Field Network
OUT2 Devices
(OUT)
OUT1
OUT2
※Power RESET: There is no memory protection. (resets the display value when power is off)
※Power Hold: There is memory protection.
(memorizes the display value at the moment of power off, indicates the memorized display value when power is resupplied.)
M-59
CX Series
One-shot output (0.01 to 99.99 sec)
One-shot output Retained output
Output Operation Mode (Timer) Retained output
Output
Time chart
mode Operation
Flicker (Power RESET)
1)Time starts when INA signal turns ON.
2)When INA signal is ON
:P ower ON Time Start is operated.
POWER RESET OFF Time Start is operat-
INA(START)
ed.
3)Control output operates as retained
INH(INHIBIT)
output, output turns off for the
RESET T.off time and turns off for the T.off
T.off time and turns on for the T.on time
Setting time
repeatedly.
FLK T.on
Setting time Ta+Tb = T.off
[FLK] UP
4)The T.on time and T.off time must be
0
Display set individually.
T.off
Setting time 5)In case of using the contact output,
Down T.on min. setting time must be set over
Setting time 100ms.
0
T.off T.on Ta Tb T.on T.off T.on T.off T.on T.off POWER
OUT2(OUT) INA
T.off T.on T.off
OUT2
(OUT)
Flicker 1 (Power Reset) 1)Time starts when INA signal turns ON.
2)When INA signal is ON
Retained (Hold) output :P ower ON Time Start is operated.
RESET OFF Time Start is operat-
POWER ed.
INA(START) 3)Control output operates as retained
INH(INHIBIT)
(Hold) output.
4)In case of using the contact output,
RESET min. setting time must be set over
Setting time 100ms.
Up
POWER
0
Display INA
Setting time T T T
Down
OUT2
0 (OUT) T: Setting time
FLK.1 OUT2(OUT)
[FLk1]
One-shot output 1)Time starts when INA signal turns ON.
2)When INA signal is ON
POWER :P ower ON Time Start is operated.
INA(START)
RESET OFF Time Start is operat-
ed.
INH(INHIBIT) 3)Control output operates as one-shot
RESET output.
Setting time 4)In case of using the contact output,
Up min. setting time must be set over
0 100ms.
Display
Setting time POWER
Down INA
0 T T T
t t t
OUT2
OUT2(OUT) (OUT) T: Setting time
※Power RESET: There is no memory protection. (resets the display value when power is off)
※Power Hold: There is memory protection.
(memorizes the display value at the moment of power off, indicates the memorized display value when power is resupplied.)
M-60
LCD Display Counter/Timer
One-shot output (0.01 to 99.99 sec)
One-shot output Retained output
Output Operation Mode (Timer) Retained output
Output
Time chart SENSORS
mode Operation
Flicker 2 (Power Hold)
1)Time starts when INA signal turns ON CONTROLLERS
and the display value at the moment
Retained (Hold) output when power is off is memorized.
2)When INA signal is ON
MOTION DEVICES
POWER :P ower ON Time Start is operated.
RESET OFF Time Start is operated.
INA(START) 3)Control output operates as retained
INH(INHIBIT) (Hold) output. SOFTWARE
4)Control output will be reversed when
RESET it reaches to setting time.
Setting time (at the initial start, OUT2 control
Up output is OFF).
0 5)In case of using the contact output,
Display min. setting time must be set over
Setting time
100ms.
Down
0 POWER
INA
FLK.2 OUT2(OUT) T T-c c T
(J)
Temperature
[FLk2] OUT2 Controllers
※Power RESET: There is no memory protection. (resets the display value when power is off)
※Power Hold: There is memory protection.
(memorizes the display value at the moment of power off, indicates the memorized display value when power is resupplied.)
M-61
CX Series
One-shot output (0.01 to 99.99 sec)
One-shot output Retained output
Output Operation Mode (Timer) Retained output
Output
Time chart
mode Operation
Interval 2 (Power RESET)
1)Time starts when INA signal is ON,
and resets when INA signal is OFF.
2)INA signal is ON, OUT1 output is ON
POWER during T1 (HOLD) or t1.
INA(START)
3)When it reaches setting time 1, dis-
play value resets and OUT2 output
INH(INHIBIT) is ON during T2 (HOLD) or t2 output
RESET time.
※Output turns OFF when reaching
Setting time 1
INT.2 the setting time even if one-shot is
Setting time 2
[INt2] Up
longer than setting time.
0
Display INA
T1
Setting time 2
Down OUT1 T1: Setting time 1
Setting time 1 T2
t1 T2: Setting time 2
0 OUT2 t1: One-shot1
t2 t1: One-shot2
OUT1
(1-stage SET model has no INt2 mode)
OUT2
Signal Off Delay (Power RESET) 1)If INA is ON, control output remains
ON. (except when power is off and
POWER
reset is on)
2)When INA signal is OFF, time pro-
INA(START) cesses.
INH(INHIBIT) When it reaches setting time, indica-
RESET
tion value and control output are auto
OFD reset automatically.
Setting time
[OFD] Up POWER
0
Display INA
Setting time T
Down
0 OUT2
(OUT) T: Setting time
OUT2(OUT)
OUT2(OUT)
※Power RESET: There is no memory protection. (resets the display value when power is off)
※Power Hold: There is memory protection.
(memorizes the display value at the moment of power off, indicates the memorized display value when power is resupplied.)
M-62
LCD Display Counter/Timer
One-shot output (0.01 to 99.99 sec)
One-shot output Retained output
Output Operation Mode (Timer) Retained output
Output
Time chart SENSORS
mode Operation
On-Off Delay1 (Power RESET)
1)When INA input turns ON, time CONTROLLERS
OUT2(OUT)
When memory protection setting is OFF 1)Time starts when INA input is ON. (O)
Digital
2)When RESET signal is ON, the Panel Meters
POWER
display value is reset.
INA(START)
3)Time progress stops when INHIBIT (P)
INH(INHIBIT) signal is ON. Indicators
RESET 4)The progressed time is reset when
Max. power OFF.
time range (Q)
Up Converters
0
Display Max.
(R)
Down time range Digital
Display Units
TOTAL 0
[TOTAL] When memory protection setting is ON 1)Time starts when INA input is ON.
(S)
2)When RESET signal is ON, the Sensor
POWER
display value is reset. Controllers
INA(START)
3)Time progress stops when INHIBIT
(T)
INH(INHIBIT) signal is ON. Switching
Mode Power
RESET 4)The progressed time at the moment Supplies
Max. of power OFF is memorized.
Up time range
(U)
0 Recorders
Display
Max.
Down time range
(V)
0 HMIs
※Power RESET: There is no memory protection. (resets the display value when power is off)
※Power Hold: There is memory protection. (W)
(memorizes the display value at the moment of power off, indicates the memorized display value when power is resupplied.) Panel PC
※When memory protection setting is OFF, it does not memorize the display value when power turns OFF.
(the display value is reset when power turns OFF) (X)
※When memory protection setting is ON, it memorizes the display value when power turns OFF. Field Network
Devices
When re-suppling the power, it displays the memorized value.
M-63
CX Series
One-shot output (0.01 to 99.99 sec)
One-shot output Retained output
Output Operation Mode (Timer) Retained output
Output
Time chart Operation
mode
When memory protection setting is OFF ※ON time indicate mode of INA signal.
1)Time reset start operates when INA
POWER
signal turns ON.
INA(START)
2)Time progress stops while INA signal is
INH(INHIBIT) OFF.
RESET 3)When INA signal is OFF, if INA input
OUT2(OUT) time is greater than the setting time,
Setting time the display value flashes and the opera-
Up
tion stops until RESET signal ON.※1
0
Display 4)When time progress stops and power
Setting time turns OFF, the progressed time is reset.
Down
On Time 0
Display When memory protection setting is ON ※ON time indicate mode of INA signal.
[ONtD] 1)Time reset start operates when INA
POWER signal turns ON.
INA(START) 2)Time progress stops while INA signal is
INH(INHIBIT) OFF.
RESET 3)When time progress stops and power
OUT2(OUT) turns OFF, the progressed time at the
Setting time
moment of power OFF is memorized.
Up
0
Display
Setting time
Down
0
※1: For free voltage input model (CX6 - F).
※Power RESET: There is no memory protection. (resets the display value when power is off)
※Power Hold: There is memory protection.
(memorizes the display value at the moment of power off, indicates the memorized display value when power is resupplied.)
※When memory protection setting is OFF, it does not memorize the display value when power turns OFF.
(the display value is reset when power turns OFF)
※When memory protection setting is ON, it memorizes the display value when power turns OFF.
When re-suppling the power, it displays the memorized value.
M-64
LCD Display Counter/Timer
One-shot output (0.01 to 99.99 sec)
Timer '0' Time Setting Retained output
A
vailable output operation mode to set '0' time setting SENSORS
OND, ONd1, ONd2, ONd3, NFD, NFd1 One-shot output Retained output
Operation according to output mode (at 0 time setting) CONTROLLERS
0 0
OUT 1 OUT 1
OUT 2 OUT 2
(L)
0 0 Power
Controllers
OUT 1 OUT 1
OUT2 OUT2
● Set '0' for Off_Delay setting time. ● Set '0' for On_Delay setting time.
(W)
INA (START) INA (START) Panel PC
RESET RESET
On_Delay UP Off_Delay (X)
UP Field Network
Devices
DISPLAY 0 DISPLAY 0
DOWN On_Delay DOWN Off_Delay
0 0
OUT 2 OUT 2
(OUT) (OUT)
M-65
CX Series
6) NFD.1 (ON-OFF Delay1) mode [NFd1]
Set ‘0’ for Off_Delay setting time. Set ‘0’ for On_Delay setting time.
INA (START) INA (START)
RESET RESET
On_Delay Off_Delay
Up
Up 0 0
Display Display
On_Delay Off_Delay
Down Down
0 0
OUT2 OUT2
(OUT) (OUT)
Factory Default
Factory default
- Parameter
CX6 - CX6 - F
InM UD-C UD-A
OUtM F F
CPS 30 -
OUT2 (OUtT※1) HOLD (fixed) HOLD (fixed)
OUT1※1 0)10 0)10
DP ------ ------
Counter RESET 20ms -
SIG NPN -
SClDP -.-----, -.-----,
SCL !00000 !00000
TOTAL※2 OFF -
START 000000 000000
DATA CLR CLR
U-D UP UP
OUtM OND OND
OUT2 (OUtT※1) HOLD HOLD
Timer OUT1※1 0)10 0)10
tRNG 99(999s 99(999s
SIG※2 NPN -
IN-T 20ms -
LOCK lOFF lOFF
SET1 1000 1000
SET2 5000 5000
※1: For 1-stage setting model (CX6 -1P ), OUT1 does not appear.
The output time of OUT2 is displayed as OUtT.
※2: This is for the voltage input (PNP)/no-voltage input (NPN) selectable model (CX6 - ).
M-66