IS 3103 For Ventilation
IS 3103 For Ventilation
@ Copy",III . 1976
• Cop:vri,hI IY76
BUREAU OF INDIAN STANDARDS
This publication IS protected under the India CopJriglrl' A&t ( XIV of 1957 J/ and
reproduclion in whole or in part by any mean. excepl wilh written permission 01 the
publisher shall be deemed to be an iolringement of copyrighl under the laid Act.
UREAU UNDER THE LICENSE FROM BIS FOR ANDHRA PRADESH POWER GENERATION CORPORATION LTD. - VIJAYAWADA ON 1/1/2021 12:09:56 PM (10.
ISBIS
ICENSE FROM : 3103 - 1975 PRADESH POWER GENERATION CORPORATION LTD. - VIJAYAWADA ON 1/1
FOR ANDHRA
(Contimudfrom page 1. )
Members Representing
SHRI R. L. SURI Suri & Suri Consulting Acoustical Engineers,
New Delhi
SHRI D. AJITHA SlHHA, Director General, lSI ( Ex-officio Mtmber )
Director ( Civ Engg )
Secretary
SHRI V. KALYAN.&SUNDAlU.M
Assistant Director (Civ Engg ), lSI
2
UREAU UNDER THE LICENSE FROM BIS FOR ANDHRA PRADESH POWER GENERATION CORPORATION LTD. - VIJAYAWADA ON 1/1/2021 12:09:56 PM (10.
IS : 3103·
ICENSE FROM BIS FOR ANDHRA PRADESH POWER GENERATION CORPORATION LTD. 1975
- VIJAYAWADA ON 1/1
Indian Standard
CODE OF PRACTICE FOR
INDUSTRIAL VENTILATION
( First Revision)
o. FOREWORD
0.1 This Indian Standard ( First Revision) was adopted by the Indian
Standards Institution on 31 December 1975, after the draft finalized by the
Functional Requirements h1- Buildings Sectional Committee had been
approved by the Civil Engineering Division Council.
0.2 Due consideration should .be given to the ventilation ' requirements in
designing factories and industrial buildings. Provision for ventilation
becomes necessary for dilution of inside air to prevent vitiation · by causes,
such as body odours, to remove contaminants in air released during
. manufacturing processes and to maintain satisfactory thermal enviroments.
The application of ventilation should be considered with other measures to
control heat gi~en ' off during industrial processes. Ventilation by natu~l
meahs may not be sufficient in certain industries to provide such thermal
environments as will assist the maintenance of heat balance of the body
a nd to prevent acute discomfort and injury to the health of the · wcrkers.
In such cases mechanical ventilation .and cooling systems, where neces-
sary, may be employed to achieve satisfactory results. Some principles of
industria:l ventilation are dealt with in this code in order to give 'guidance
to those concerned in this field. In .the preparation of . this code, the
requirements of the Factories' Act and Rules thereunder have been taken
into consideration.
0.3 This standard covers ventilation of industrial buildings only and was
first published in 1965.. The present revision waS taken up with a view to
incorporate necessary provisions regarding control of heat hazards due to
various processes in the industry. Some of the significant changes made
are given in 0.3.1.
0.3.1 In this code certain new definitions have been aided. The range
of recommended capture velocities and_the provisions for orientation of
buildings have been included. The design considerations for ventilation,
provisions for mechankal vent~lation have been modified: The re.guire-
ments for ventilation of buildings, natural ventilation and positive ventila-
tion have also been modified. . :'.
3
UREAU UNDER THE LICENSE FROM BIS FOR ANDHRA PRADESH POWER GENERATION CORPORATION LTD. - VIJAYAWADA ON 1/1/2021 12:09:56 PM (10.
ICENSE FROM BIS FOR
IS s 3103 ANDHRA PRADESH POWER GENERATION CORPORATION LTD. - VIJAYAWADA ON 1/1
- 1975
o.~, The current practice in this country regarding the threshold limit
values for contaminants ( see 2.21 <lnd 4.5.1 ) is .to refer to the latest pub-
lication of the American conference of Governmental Industrial Hygienists.
0.5 For the purpose of deciding whether a particular requirement ofilthis
standard is com plied with, the final val ue, observed or calculated, express-
ing. the result of a test or analysis, shall be rounded off in accordance with
IS: 2-1960*. The number of..significant places retained in the rounded off
value should be the same as that of the specified value in this standard.
1. SCOPE
l.1 This standard covers certain 'basic requirements regardi9g !lafe design,
installation, operMion, testin,g and maintenance of venfilating systems with
respect to general ventilatiol!' and wherever appropriate dilution ventila-
tion for industrial process> This standard also briefly describes meaSures
to reduce the heat hazards due to industrial processes.
2. TERMINOLOGY
2.0 For the purpose of this standard, the following definitions shall apply.
2.1 Air ChaRge per Hour - The volume of outside air ~llowed into a
room in one hour compared with the volume of the room .•
2.~ AsialFlow Faa - A fan having a casing in whi<;h the,air enters and
leaves the hnpdler ina direction substantially parallel to its axis.
2.3 .C apa.reVelocity - Air velocity a;t any point in front of the exhaust
hood .necessary to overcome .opposing air currents and to capture the
contaminated air at that point by causing it to flow into the exhaust hood.
2.4 C.."trlf'..gal Paa - A fan in which the air leaves the impeller in a
direction substantially at right angles to its axis .
.), - .
2.5' _0 0*-;,.-,..":'" ~sts, fumes, gases, mists, vapours and such other
substances' present in air are 'likely to be injurious or offensive ,to the
occupants.
2.6 J)UutiOR VeaiiJatioa - Supply of outside air to reduce the air-borne
concentration of contaminants in the building.
2.7 .. 1bT Balb Tempuature - The temperature of the air read on a
thSmometer, placed in IUch a way as to avoid erron due to radiation .
• ,R ulea for rounding oft" numerical values ( reuisld ).
UREAU UNDER THE LICENSE FROM BIS FOR ANDHRA PRADESH POWER GENERATION CORPORATION LTD. - VIJAYAWADA ON 1/1/2021 12:09:56 PM (10.
ICENSE FROM BIS FOR ANDHRA PRADESH POWER GENERATION CORPORATION LTD. - VIJAYAWADA ON 1/1
is : 3103 - 1915
2.8 Eshaust 01 Air - Rem~val of air from-abuilding and its disposal
outside by means of mechanical device, such as a fan.
2~9 Geueral Ventilation --- Supply of outside air either by positive
ventilation or by infiltration into the building.
2.10 Humidification - The process whereby the absolute humidity of
the air in a building is maintained at a higher level than that of outside air
or at a level higher than that which would prevail naturally.
2.11 Humidity Absolute - The weight of water vapour per unit volume.
2.12 Humidity Relative - The ratio of the actual to the partial pressure
of the water vapour at the same temperature.
2.13 Local Exhaust Ventilation ~ Vt:ntilation effected by exaust of air
through an exhaust appliance, such as hood with or without fan located as
closely as possible to the point at which contaminants are released so as to
capture effectively the contaminants and convey them through ducts to a
safe point of dis~harge. .
2.14 Make Up Air - Outside air supplied into a building to replace the
air removed.
2.15 Mechanical Ventilation - Supply of outside air either by positive
ventilation or by infiltration by reduction of pressure inside due to exhaust
of air, or by a combination of positive ventilation and exhaust of air.
2.16 Natural Ventilation - Supply of outside air into a building through
window or other openings due to wind outside and convection effects
arising from temperature or vapour pressure differences ( or both) between
inside and outside of the building.
2.17 Positive Ventilation - The supply of outside air by means of a
mechanical device, such as a fan.
2.18 Propeller Type Fan - A fan in which the air leaves the impeller in
a direction substantially parallel to its axis designed to operate normally
under free inlet and outlet conditions.
2.19 Spray-head Systems.- A system of atomizing water so as to
introduce the moisture directly into a building.
2.20 Temperature Rise - Difference _of exit temperature and the
temperature of air at the inlet openings.
2.21 Threshold Limit Values (TLV) - Refers to air-borne conr:entra-
tion of contaminant. and represent conditions, under which it is believed
that nearly all occupants may be repeatedly exposed, day after day, with- .
out adverse effect.
UREAU UNDER THE LICENSE FROM BIS FOR ANDHRA PRADESH POWER GENERATION CORPORATION LTD. - VIJAYAWADA ON 1/1/2021 12:09:56 PM (10.
ICENSEIS : 3103
FROM BIS- FOR
1975ANDHRA PRADESH POWER GENERATION CORPORATION LTD. - VIJAYAWADA ON 1/1
2.22 Ventilation "\ Supply of outside air into, or the removal of inside
air from an encloseo. space.
2.23 Wet Bulb Temperature - The steady temperature finally given by
a thermometer having its bulb covered with gauze or muslin moistened with
distilled water and placed in an air stream of not less than 4·5 m/s.
·3. ORIENTATION OF BUILDINGS
3.1 Solar Load Factors - In the tropics orientation for mInImUm solar
load during summer should be the main criterion. Wherever appropriate,
orientation to avoid the solar heat during summer and to take the desir-
able ·heat during winter should be preferred.
3.1.1 Wherever possible suitable sun-breakers have to be provided to cut
off the incursion of direct sunlight to prevent heat radiation and to avoid
glare.
4. DESIGN CONSIDERATION
4.1 General - Ventilation is required to supply fresh air for respiration,
to dilute inside air to prevent vitiation by body odours, to remove any
contaminants in air and to provide such thermal environments as will
assist in the maintenance of heat balance of the body in order to prevent
discomfort and injury to health of the occupants.
4.1.1 Respiration - Supply of fresh air to provide oxygen for the human
body for\elimination of waste products and to 'maintain carbon dioxide
concentration in the air within safe limits rarely calls for special attention
as enough outside air for this purpose normally enters the areas of occu-
pancy through crevices and other openings.
4.1.2 Vitiation by Body Odours - Where no contaminants are to be
removed from air, the amount of fresh air required for dilution of inside
air to prevent vitiation by body odours, depends on the air space available
per person and the degree of physical activity; the amount of air decreases
as the air space per person increases, and it may vary from 20m3 to 30 m a
per person per hour. In rooms occupied by only a small number of person
such an air change will automatically be attained in cool weather by
normal leakage around windows and other openings and this may easily
be secured in warm weather by keeping the openings open.
4.1.2.1 Recommended values for air cJzanges - No standards have been
laid down under the Factories Act (1948), as regards the amount of fresh
air required per worker or the number .of air changes per hour. Section.
16 relating to overcrowding requires that at least 14 m' to 16 tn' of space
shall be provided for every worker and for the purpose of that section no
account shaH be taken of spaces in a work room which is more than 4'25 m
above the floor level.
6
UREAU UNDER THE LICENSE FROM BIS FOR ANDHRA PRADESH POWER GENERATION CORPORATION LTD. - VIJAYAWADA ON 1/1/2021 12:09:56 PM (10.
ICENSE FROM BIS FOR ANDHRA PRADESH POWER GENERATION CORPORATION LTD. - VIJAYAWADA ON 1/1
IS : jl03 - 1915
4.1.2.2 The minimum fresh air required in a work room where there
are no contaminants to be removed from air, shall be such as to effect at
least three air changes per hour.
4.1.3 Heat BaianCl of Body - Specially in hot weather, when thermal
environment inside the room is worsened by heat given off by machinery,
occupants and other sources, the prime need for ventilation is to provide
such thermal environment as will assist the maintenance of heat balance of
the body in order to prevent discomfort and injury to health. Excess of
heat from a hot environment has to be offset to maintain normal body
temperature ( 37°C). Heat exchange of the human body with respect to
surroundings is determined by temperature and humidity gradient between
the skin and surroundings, and therefore depends on air temperature (dry
bulb temperature), relative humidity ( or wet bulb temperature), radia-
tion from the surroundings and air movement. The volume of outside
air to be calculated through the room is, therefore, governed by the
physical considerations of controlling the temperature, air distribution or
air movement.
4.1.3.1 Proper air movement and fresh Mr supply will reduce heat
stress by dissipating heat from body by evaporation of the sweat particu-
larly when relative humidity is high and the air temperature is below or
.near body temperature. Air movement and distribution may, however;
be achieved by recirculation of the inside and/or outside air.
4.1.3.2 In industrial buildings where workers wearing light clothing
are expected to do work of moderate severity with the energy expenditure
in the range 235 to 330 kcal/h, the maximum wet bulb temperature shall
not exceed 29°C and adequate air movement subject to a minimum of air
velocity of 30 m/min shall be provided; and in relation to the dry bulb
temperature, the wet bulb temperature of air in the work room as far as
practicahle, shall not exceed to that given in Table I.
4.2 Control of Heat - Although it is recognised that ventilation is one
of the most effective methods of controlling the thermal conditions in
factories. in many situations, the application of ventilation should be
preceded by and considered along with some of the following other methods
of control. This would facilitate better design of ventilation systems and
also reduce their cost.
4.2.1 Isolation - Sometimes it is possible to locate heat producing
equipment, such as furnaces in such a position as would expose only a
small number of work en to hot environments. As far as practicable
such sources of heat in factories should be isolated.
4.2.1.1 In situations where relatively few people are exposed to . severe
heat stress and their activities are confined to limited areas as in the case
of rolling mill operators and crane operators, it may be possible to enclose
the work areas and supply conditioned air to such enclosures.
7
UREAU UNDER THE LICENSE FROM BIS FOR ANDHRA PRADESH POWER GENERATION CORPORATION LTD. - VIJAYAWADA ON 1/1/2021 12:09:56 PM (10.
ICENSE FROM BIS FOR
.IS : 3103 ANDHRA PRADESH POWER GENERATION CORPORATION LTD. - VIJAYAWADA ON 1/1
• 1975
NOTE I - The .limits indicated in the table are based on the upper safe limits
recommended in the report Thermal Stress on Textile Industry (Report No. 17 )
issueq. by the Chief Adviser Factories, Government of India, Ministry of .Labour and
Employment, New Delhi; these aFe limits beyond which the indu~try should not allow
the thermal conditions to go for more than one hour continuously. The limits are
baled on a series of studies conducted on Indian subjects in a psychrometric chamber
and on other data on heat casualties in earlier studies conducted in Kolar Gold Fields
and elsewhere.
NOTE 2 - Figures given in the table are not intended to cOllvey that human efficiency
at 50°C will remain the same as at 30·C provided appropriate wet bulb temperatures
are maintained. Efficiency decreases with rise in the dry bulb temperature for a
given wet bulb temperatures attained and efforts should be made to bring down the
dry bulb temperatures as well, as much as possible. Long exposures to temperature
of 50°C dry bulb/27·C wet bulb may prove dangerous.
NOTE.3 ~ Refrigeration or other method of cooling is recommended in all cases
where conditions would be worse than those shown in this table.
8
UREAU UNDER THE LICENSE FROM BIS FOR ANDHRA PRADESH POWER GENERATION CORPORATION LTD. - VIJAYAWADA ON 1/1/2021 12:09:56 PM (10.
ICENSE FROM BIS FOR ANDHRA PRADESH POWER GENERATION CORPORATION LTD. - VIJAYAWADA ON 1/1
IS : 3103 - 1975
lighly reflecting surface between the source of heat and the worker so
:hat a major portion of the heat falling on the shield is reflected back to
,he source. Surfaces, 'Such as, of tin and aluminium have been used as
materials for shields. The efficiency of the shield does not depend on its
thic}{ness but on the reflectivity and emissivity of its surface. Care should
be taken to see that the shield is not heated up by conduction and for this
purpose adequate provision should be made for the free flow upwards of
the heated air between the hot surface and the shield by leaving the
necessary air space and providing opening at the top and the bottom of
the sides.
4.3 Ventilation of Buildings - In the case of an industrial building
having a significant internal heat load due to manufacturing processes, the
following items may be considered when designing for the maximum
possible control of thermal environment:
a) Orientation of the building with respect to the direction of the
prevailing winds and of the path of the sun in the sky and to the
location of adjoining buildings.
b) Configuration of the building and the manufacturing processes
in it.
c) Proper inlets (windows and other openings) and their location
with respect to outlet openings.
d) Mechanical ventilation including selection and disposition of fans,
inlet grilles and arrangement of ducts.
In the case of industrial buildings wider than 30 m, the ventilation
may be augmqlted by roof ventilation.
4.3.1 The volume of air required shall be calculated by u~ing both the
sensible heat or latent heat all the basis. The larger of the two figures
obtained should be used in actual practice.
4.3.1.1 Volume of air required for removing sensible heat when the
amount of sensible heat given off by different sources namely the sun, the
manufacturing processes machinery, occupants and other sources is known
and a suitable value for the allowable temperature rise is assumed, the
volume of outside air. to be provided for removing the sensible heat may
be calculated from:
3'462 X K.
Ql=---~-
where
Ql = quantity of air in m 3/h,
K. = sensible heat gained in kcal/h, and
t = allowable temperature rise in °e.
9
UREAU UNDER THE LICENSE FROM BIS FOR ANDHRA PRADESH POWER GENERATION CORPORATION LTD. - VIJAYAWADA ON 1/1/2021 12:09:56 PM (10.
ICENSE FROM BIS FOR ANDHRA PRADESH POWER GENERATION CORPORATION LTD. - VIJAYAWADA ON 1/1
IS: 31~3 - 1975
4.3.1.2 Temperature rise refers mainly to the difference between the
air temperature!\ at the outside and at the inlet openings. As very little
data exist on allowable temperature-rise values for supply of outside air
in summer months, the values given in Table 2 rela.ted to industrial
buildings may be used for general guidance.
6 3 to 4'5
9 4'5 to 6'5
12 6'5 to 11
NOTE 1 - The conditions are limited to light or medium heavy manufacturing pro-
cesses, freedom from radiant heat and inlet openings not more than 3 to 4'5 m above
floor level.
NOTE 2 - At the working zone between Boor leVel and 1'5 m above Boor level the
recommended maximum allowable temperature rise for air is 2 to 3°e above th~ air
temperature' at the inlet openings,
4.3.1.3 Volume of ai( required for removing latent heat - If the latent
heat gained from the manufacturing proces~es and occupants is also
known and.a suitable value for the allowable rise in the vapour pressure
is assumed:
where
Q2 = quantity of air in m'/h,
kl = latent heat gained in k cal/h, and
h = allowab~e vapour pressure difference in mm of mercury.
NOTE - In majority of the casel the sensible heat gain will far exceed the latent
heat gain so that the amount of outside air to be drawn by ventilating equipment can
be calculated in mod cases on the basis of the equation given in 4.3.1.1.
II
UREAU UNDER THE LICENSE FROM BIS FOR ANDHRA PRADESH POWER GENERATION CORPORATION LTD. - VIJAYAWADA ON 1/1/2021 12:09:56 PM (10.
rs :3103
ICENSE FROM BIS - 1975
FOR ANDHRA PRADESH POWER GENERATION CORPORATION LTD. - VIJAYAWADA ON 1/1
12
UREAU UNDER THE LICENSE FROM BIS FOR ANDHRA PRADESH POWER GENERATION CORPORATION LTD. - VIJAYAWADA ON 1/1/2021 12:09:56 PM (10.
ICENSE FROM BIS FOR ANDHRA PRADESH POWER GENERATION CORPORATION
18 :LTD.
3103- VIJAYAWADA
- 19'15 ON 1/1
13
UREAU UNDER THE LICENSE FROM BIS FOR ANDHRA PRADESH POWER GENERATION CORPORATION LTD. - VIJAYAWADA ON 1/1/2021 12:09:56 PM (10.
ICENSE FROM BIS FOR ANDHRA PRADESH POWER GENERATION CORPORATION LTD. - VIJAYAWADA ON 1/1
IS : 3103 - 1915
14
UREAU UNDER THE LICENSE FROM BIS FOR ANDHRA PRADESH POWER GENERATION CORPORATION LTD. - VIJAYAWADA ON 1/1/2021 12:09:56 PM (10.
ICENSE FROM BIS FOR ANDHRA PRADESH POWER GENERATION CORPORATION
IS :LTD.
3103- -VIJAYAWADA
1915 ON 1/1
confine the contaminants as much as possible and openings for ac~ess shall
be located, wherever possible, away from the natural path of the contami-
nants travel.
4.5.1.1 When an exhaust appliance is provided to enclose the point
at which contaminants are released, the volume of air required is cal-
culated from the area of openings 'and the capture velocity sufficient to
prevent outward escapement. In other cases, the volume of air required
and pattern of air flow in front of the exhaust appliance shall be such that
the capture velocities necessary to overcome air currents and convey the
contmninants by causing the air recommended capture velocities are
listed .out in Table 3.
15
UREAU UNDER THE LICENSE FROM BIS FOR ANDHRA PRADESH POWER GENERATION CORPORATION LTD. - VIJAYAWADA ON 1/1/2021 12:09:56 PM (10.
ICENSE FROM BIS FOR ANDHRA PRADESH POWER GENERATION CORPORATION LTD. - VIJAYAWADA ON 1/1
IS : 3103 - 1915
4.5.2.1 The exhaust outlets and the air supply inlets shall be so located
that air passes through the zone of contamination with the points at which
the contaminants are released between the worker and the exhaust outlets.
The workers should not stand too close to the zone where contaminants
are released.
4.5.2.2 If the rate of vapour generation of rate of liquid evapora.tion
is known, the dilution air requirements is calculated from:
Air required in mS/kg 24 X 10 6 X k
of evaporation
molecular weight of liquid X 7 LV
where
k = constant varying from 3 to 10 depending on soivent in
question, uniformity of air distribution, dilution of va pours
in air, location of exhaust plant and its proximity to
evolved vapours, and
TLV = Threshold Limit Value of the sol vent
4.5.3 Make-Up-Air- Sufficient make-up-air shall be brought into th('!
work room by natural infiltration or by positive ventilation at suitable
points in relation to the exhaust points to replace the air exhausted by
local exhaust ventilation or by dilution ventilation, and the air may be
efficiently filtered or treated, when necessary.
5. INSTALLATION AND OPERATION
5.1 Location - Fans and other <,;quipment may be located in convenient
positions considering the intake offresh air, accessibility for maintenance
and noise control.
5.1.1 Where the exhaust of air laden with inflammable dusts, gases or
vapours is conveyed through ducts, the electric motor and fan shall be
situated outside in such a way that an explosion will not vent into the
work' room. The fan should be of non-sparking construction and the
motor, if not located outside the air stream, should be of flame proof
construction.
5.2 Ducts' - Where positive ventilation requires ducts for proper air
distribution considerable advantage may be achieved by incorporating the
ducts into the building structure and by having the interior surfaces care-
fully finished to render them smooth and air-tight and treated, to prevent
the possibility of dust being scoured from the walls by the passing' air.
For removal of corrosive or dust laden contaminants, ducts shall be pro-
tected against corrosion and erosion and shall be installed for easy
inspection, maintenance, repair and replacement.
5.2.1 Where metal duct work is installed, it shall conform to IS: 655-
1963*.
*Specification for metal air ducts( wlis,d).
16
UREAU UNDER THE LICENSE FROM BIS FOR ANDHRA PRADESH POWER GENERATION CORPORATION LTD. - VIJAYAWADA ON 1/1/2021 12:09:56 PM (10.
IS: 3103
ICENSE FROM BIS FOR ANDHRA PRADESH POWER GENERATION CORPORATION LTD.- -1975
VIJAYAWADA ON 1/1
6. TESTING
6.1 All parties concerned shall agre~ to the cbjects of test, methods and
(\uration of test, degree of accuracy .required and state of ventilating
equipment under test. The plant should be run during normal working
hours and adjusted properly rrior to the test.
6.2 Amount of Air
6.2.1 Positive Ventilation - The volume of outside air by positive ventila-
tion shall be measured hy appropriate instruments, such as a properly
calibrated, 'anemometer', velocity'meter and pitot tube. To measure the
average velocity of "ir flow, it is necessary to make a tiavers~ of the
instrument over the cross-sectional drea of the intake openings or ducts
and obtain the average velocity from these results. The volume of air is
given by:
Q=AV
where
Q = volume of air in ma/mirt"
A = free area of intake openings of ducts in rna, and
V = average velocity of air in m/min.
6.2.2 Exhaust of Air - The volume of exhaust air shall be measured in
the same manner as in the case of positive ventilation by measurement of
air ~elocity and area of exhaust ducts or IJpenings, and multiplying the
one with the other.
17
UREAU UNDER THE LICENSE FROM BIS FOR ANDHRA PRADESH POWER GENERATION CORPORATION LTD. - VIJAYAWADA ON 1/1/2021 12:09:56 PM (10.
IS: 3103
ICENSE FROM - 1975
BIS FOR ANDHRA PRADESH POWER GENERATION CORPORATION LTD. - VIJAYAWADA ON 1/1
6.2.3.3 When areas of inlet and outlet openings are unequal, 'A' given
in equations under 6.2.3.1 a-nd 6.2.3.2 will be the smaller area and the
volume of air will be increased according to the percentage given in Fig. I.
6.2.3.4 Ventilation by combined effect of wind outside and tempera-
ture difference may be evaluated as follows:
a) Calculate the amount of outside air by methods given under 6.2.3.1
and 6.2.3.2,
b) Express the amount of air due to method 6.2.3.2 as a percentage
of the total, and
c) Use Fig. 2 to determine actual fl6w caused by the combined effect
of both.
18
UREAU UNDER THE LICENSE FROM BIS FOR ANDHRA PRADESH POWER GENERATION CORPORATION LTD. - VIJAYAWADA ON 1/1/2021 12:09:56 PM (10.
IS: 3103
ICENSE FROM BIS FOR ANDHRA PRADESH POWER GENERATION CORPORATION LTD. -·1975
VIJAYAWADA ON 1/1
40
L,....-
y
30
/
II
I
I
1
RATIO OF OUTLET TO ME T Of! vICE ·VERSA
FIG. 1 INCREASE IN FLOW CAUSED BY EXCESS OF ONE
OPENING OVER AI,OTHER
7' .
6
\
,
2
1
" .....
0
~ U EO eo 11 o
FLOW DUE TO TEMPERATURE
OFFEAE;lf(;l AS PERCENT OF TOTAl
19
UREAU UNDER THE LICENSE FROM BIS FOR ANDHRA PRADESH POWER GENERATION CORPORATION LTD. - VIJAYAWADA ON 1/1/2021 12:09:56 PM (10.
ICENSE FROM BIS FOR ANDHRA PRADESH POWER GENERATION CORPORATION LTD. - VIJAYAWADA ON 1/1
IS: 3103 - 1975
6.3 Air Movement - Turbulent air movement at the workitig zone may
be measured either by Kata the~mometer (dry silvered type), heated
thermo anemometer or properly calibrated thermocouple anemometer.
Kata thermometer and heated thermometer give cooling, power rather
than the velocity of air, and the rate of air movement is found out
from the cooling power by reference to a nomogram using the ambient
temperature. .
6.4 Tolerances - The rate of air flow as measured in the duct or at a
grille either by positive ventilation or exhaust of air shall be within
10 percent of the amount required.
6.4.1 Variation of air flow through filters and grilles shall not at any
time be more than ± 20 percent of the meim value.
7. MAINTENANCE
7.1 All ventilating equipm.ent shall be checked periodically and bearings
of various moving parts lubdcated. The equipment shall also be tcstcu
for air delivery. Such tests sllaJl be made at lcast once in a year.
7.2 The surfaces of any cooling or heating units and air cleaning devices
( including filters) shall be inspected at frequent intervals for corrosion
and dirt and when corrosion occurs the cor~oded parts shall be carefully
cleaned and prote.cted with anti-corrosion paint or other suitable medium.
Cleanillg of filters and heat transfer units shall be carried .out regularly to
promote their efficient use.
8. SAFETY REQUIREMENTS FOR ELECTRICAL EQ.UIPMENT
8.1 Electr{cal Equipment- Electrical wiring and installation of electrical
equipment shall be in accordance with the requirements of Indian Electri-
city Act ;.nd Rules and shall also conform to IS: 732-1963* arid
IS : 2274-1963t as applicable.
8.2 Fire Safety - Due consideration shall be given to the" fire safety
aspects as given in IS : 1646.196Q .
• Code of practice for eleclrical wiriz\g "ii'iiltal1ations (ayst"m vohage not exct':edil.g
6~O volts )' ( revised). .,
tcode of practice for electrical wiring installation. (syatrm voltage excet'ding
650volb).
tCode of pr,actice for fire safely' of buildings <. general) electrical installations.
. 20
UREAU UNDER THE LICENSE FROM BIS FOR ANDHRA PRADESH POWER GENERATION CORPORATION LTD. - VIJAYAWADA ON 1/1/2021 12:09:56 PM (10.
ICENSE FROM BIS FOR ANDHRA PRADESH POWER GENERATION CORPORATION LTD. - VIJAYAWADA ON 1/1
BUREAU OF INDIAN STANDARDS
HII.dquBrters :
ManalU !havan. 9 Bahadur Shah Zafar Marg. NEW DELHI 110002
Telephones: 331 01 31 Telegrams: Manaksanlth6
331 1315 (Common to all Offices)
R'gionBI Offices: TlIlBphone
Central : Manak Bhavan. 9. Bahadur Shah Zatar Marg , 1331 01 31
NEW DELHI 110002 l331 1376
• Eastern : 1/14 C.I.T. Scheme VII M. 378662
V.I:P. Road. Maniktola. CALCUTTA 700054
Northe'm : SCO 445-446. Sector 35-C. CHAND/GARH 160036 21843
,Southern : C.I.T. Campus. IV Cross Road. MADRAS 600113 41 2916
t Western : Manakalaya. E9 MIDC. Marol. Andheri (East). 6329295
BOMBAY 400093
S"nch Office, :
'Pushpak', Nurmohamed Shaikh Marg. Khanpur. AHMADABAD 380001 26348
t Peeilya Industrial Area. 1st Stage. Bangalore-Tumkur Road, 394955
BANGALORE 560058
Gangotri Complex, 5th Floor, Bhadbhada Road. T.T. Nagar. 554021
BHOPAL 462003 ' ,
PIOI No· 82/83. Lewis Road. BHUBANESHWAR 751002 53627
Kalai Kathir Building. 6/48- A Avanasi Road. COIMBATORE 641037 26705
Quality Marking Centre. N·H· IV. N.I.T .• FARIDABAD 121001
Savitri Complex. 116 G,. T. Road. GHAZIABAD 201001 8·711996
53/5 Ward No. 29. R.G. Barua Road. 5th By-lane. 33177
GIJWAHATl781003 '
5-8-56C L. N. Gupta Marg. (Nampally Station Road) 231083
HYDERABAD 500001
R14 Yudhister Marg. C Scheme. JAIPUR 302005 63471
117/418 B Sarvodaya Nagar. KANPUR 208005 216876
Plot No. A-9. House No. 561/63. Sindhu Nagar . Kanpur RoaO. 55501
LUCKNOW 226005 ! .
Palliputra i'ndustrial Estate. PATNA 800013 62305
District Industries Centre Complex. Bagh-e-Ali Maidan.
SR/NAGAR 190011
T. C. No. 14/1421. University P.O •• Palayam. 621 ~
TH IR UVANANTHAPU RAM 695034
InspBction Offices (With Sale ·.e,oint) :
Pushpanjali. First Floor. 205· A w'6st High Court ROad. 625111
Shankar Nagar Square. NAGPUR 440010
Institution of Engineers (India) Bui~ng. 1332 Shivaji Nagar. 52435
PUNE 411005 '
·Sales Office Calcutta is at 5 Chowringhee Approach. 276800
P. O. Princep Street, CALCUTTA
t Sales Office is at Novelty Chambers. Grant Road. BOMBAY 896528
t Sales Office is at Unity Building. Narasimharaja Square. 223971
BANGALORE