Licence: Web Links
Licence: Web Links
for
AS 1530.4-2005 Methods for fire tests on building materials, components and structures - Fire-resistance test of elements of
construction
Licence Agreement
This is an agreement between the end user of the Product ("Licensee") and SAI Global Limited, 286 Sussex Street, Sydney
NSW 2000 AUSTRALIA, ABN 67 050 611 642.
Australian Standards means Australian Standards and includes Joint ISO/Australian Standards, Joint NZ/Australian Standards,
current Draft Australian Standards, and amendments to Australian Standards.
Concurrent Users means the maximum number of people able to access the Product at any one time, and is limited to the
number of Licences purchased.
ISO Standards means Standards published by the International Organization for Standardization (ISO), for which SAI Global is
an authorised distributor.
IEC Standards means Standards published by the International Electrotechnical Commission (IEC), for which SAI Global is an
authorised distributor.
Internal use means use of the Product within the Licensee’s organization.
Product means Australian Standards, ISO Standards and IEC Standards ordered and purchased through the infostore, and
downloaded as electronic PDF files.
2. Product Availability
3. Licence Agreement
WEB LINKS
3.1. By using the Product the Licensee agrees to be bound by the Licence Agreement for the Product.
3.3.b. Purchasers of network Licences for the Product may install and use the Product on a network with the number of
Concurrent Users permitted corresponding to the number of users specified in the SAI Global Infostore order. Licensees are
permitted to make paper copies of the Product for Internal use limited to the number of network users specified in the SAI Global
Infostore order only. Licensees are permitted to make one electronic copy of the Product for backup purposes.
3.4. SAI Global will not in any way provide the Licensee with an updating service for the Product. The Licensee agrees that SAI
AS 1530.4—2005
AS 1530.4—2005
Australian Standard™
Licensed to Mrs Pat Rogers on 21 September 2009. 1 user personal user licence only. Storage, distribution or use on network prohibited (10056147).
Additional Interests:
Australian Standard™
Licensed to Mrs Pat Rogers on 21 September 2009. 1 user personal user licence only. Storage, distribution or use on network prohibited (10056147).
COPYRIGHT
© Standards Australia
All rights are reserved. No part of this work may be reproduced or copied in any form or by
any means, electronic or mechanical, including photocopying, without the written
permission of the publisher.
Published by Standards Australia GPO Box 476, Sydney, NSW 2001, Australia
ISBN 0 7337 6866 0
AS 1530.4—2005 2
PREFACE
General
This Standard was prepared by the Joint Standards Australia/Standards New Zealand
Committee FP-018, Fire Tests on Building Components, Materials and Structures, to
supersede AS 1530.4—1997.
After consultation with stakeholders in both countries, Standards Australia and Standards
New Zealand decided to develop this Standard as an Australian Standard rather than an
Australian/New Zealand Standard.
Development and International Standards
This Standard follows the general principles and procedures contained in the ISO 834
Licensed to Mrs Pat Rogers on 21 September 2009. 1 user personal user licence only. Storage, distribution or use on network prohibited (10056147).
dampers for air distribution systems, for testing fire dampers and performance criteria
has been established in line with currently approved damper. This will also encourage
the development of combined heat and smoke dampers.
(e) The inclusion of test procedures for critical services.
(f) The inclusion of informative appendices to facilitate testing under alternate heating
regimes to provide data for evaluation of alternate building solutions for compliance
with the BCA.
(g) Details of test procedures for assessing the ability of ceiling systems to protect
structural elements.
(h) Provisions of additional guidance assist with the reporting of test results.
Building Code of Australia (BCA)
This Standard will be referenced in the Building Code of Australia (BCA) by way of
BCA 2006 to be published by 1 May 2006, thereby superseding the previous edition of
AS 1530.4—1997.
Referenced documents
This Standard references documents in clauses of both a normative and informative nature.
Normative referenced documents, are listed in Clause 1.5 and a complete list of both
normative and informative referenced documents are provided in Appendix H.
Normative and informative
The terms ‘normative’ and ‘informative’ have been used in this Standard to define the
application of the appendix to which they apply. A ‘normative’ appendix is an integral part
of the Standard, whereas an ‘informative’ appendix is only for information and guidance.
Notes and commentaries
The use of Notes in this Standard is of an advisory nature only. They provide explanations
and guidance on recommended design consideration or technical procedures, as well as an
informative cross-reference to other documents or publications.
CONTENTS
Page
Page
4.10 TEST RESULTS ....................................................................................................... 67
4.11 PERMISSIBLE VARIATION TO THE TESTED SPECIMEN ................................. 67
4.12 TEST REPORT ......................................................................................................... 68
SECTION 5 COLUMNS
5.1 GENERAL ................................................................................................................ 69
5.2 TEST SPECIMEN SIZE ............................................................................................ 69
5.3 INSTRUMENTATION ............................................................................................. 69
5.4 LOADING AND RESTRAINT ................................................................................. 69
5.5 TEST PROCEDURE ................................................................................................ 70
5.6 OBSERVATIONS ..................................................................................................... 70
5.7 CRITERIA OF FAILURE ........................................................................................ 70
5.8 DETERMINATION OF FIRE RESISTANCE........................................................... 70
Licensed to Mrs Pat Rogers on 21 September 2009. 1 user personal user licence only. Storage, distribution or use on network prohibited (10056147).
Page
9.7 TEST REPORT ......................................................................................................... 92
9.8 PERMISSIBLE VARIATIONS TO THE TESTED SPECIMEN............................... 92
APPENDICES
A RADIANT HEAT FLUX MEASUREMENTS ........................................................ 128
B ALTERNATIVE AND ADDITIONAL TEST PROCEDURES FOR ELEMENTS
OF CONSTRUCTION............................................................................................. 132
C GUIDELINES FOR THE ATTACHMENT OF SPECIMEN THERMOCOUPLES 144
D ELECTRICAL AND COMMUNICATIONS CABLES........................................... 147
E TEST PROGRAM FOR SEALING SYSTEMS PROTECTING METAL
PIPE PENETRATIONS........................................................................................... 150
F FIRE-RESISTANT DOORSETS............................................................................. 151
G REVIEW OF AS 1530.4.......................................................................................... 152
STANDARDS AUSTRALIA
Australian Standard
Methods for fire tests on building materials, components and structures
1.1 SCOPE
This Standard provides methods for determining the fire resistance of various elements of
construction when subjected to standard fire exposure conditions.
NOTES:
1 Radiant heat measurements are given in Appendix A.
2 Alternative heating and radiation exposure conditions, which may be used for evaluation of
alternative solutions, voluntary upgrades and other applications where the standard heating
regime may not be applicable, and additional procedures to meet special requirements are
given in Appendix B.
3 Unless one of the alternative heating regimes is specifically required, the standard time
temperature curve applies (see Figure 2.10.1).
4 AS 1720.4, AS 3600, AS 3700 and AS 4100 may also be used to determine the fire resistance
of an element of construction.
5 The assessment of smoke production and smoke spread when testing specimens is outside the
scope of this Standard. Significant smoke spread or smoke production can occur even though
an element of construction may have achieved high FRLs. Other test methods, such as
AS 1530.7, may be considered when evaluating the potential for smoke spread.
1.2 OBJECTIVE
The objective of this Standard is to provide building designers, manufacturers, test
laboratories and regulatory authorities with a set of uniform requirements for heating
conditions, test procedures, and criteria for the determination of fire resistance of an
element of building construction.
NOTE: Test reports include information that may assist building designers. Records of
temperature at critical times may be used by a designer to assess the fire resistance of a variant of
the tested prototype where the procedure for such an assessment is defined in the appropriate
design Standard or code. In certain cases, the test methods described herein provide information
for the determination of—
(a) resistance to the incipient spread of fire through ceiling systems;
(b) safe distances for the spacing of combustible materials from elements that provide a
separating function;
(c) radiant heat flux from doorsets, shutter assemblies, and glazing; and
(d) the cross-sectional area of air ducts to provide functional operation while providing fire
resistance.
1.3 PRINCIPLE
A representative specimen of an element of construction is exposed to heat under controlled
conditions in a furnace, which is operated to satisfy a specified time-temperature curve.
Where it is not possible to model the element or system of construction satisfactorily with
one specimen, it may be necessary to test more than one specimen. Observations are made
on the performance of the specimen while it is subjected to thermal and, where applicable,
physical loading. The elapsed times at which various failures occur are recorded.
NOTE: Where a specimen has been tested under a particular set of test conditions, an identical
specimen should not be resubmitted for test without modification unless the test is carried out for
surveillance on similar purposes to confirm the original performance.
1.4 APPLICATION
Licensed to Mrs Pat Rogers on 21 September 2009. 1 user personal user licence only. Storage, distribution or use on network prohibited (10056147).
AS
1530 Methods for fire tests on building materials, components and structures
1530.1 Part 1: Combustibility test for materials
1905 Components for the protection of openings in fire-resistant walls
1.6 DEFINITIONS
For the purpose of this Standard, the definitions below apply.
1.6.1 Access panels
A removable component protecting an opening in a fire-resistant vertical or horizontal
separating element used to access services and the like and may be either fixed or hinged.
1.6.2 Alternative solution
A Building Solution which complies with the Performance Requirements of the Building
Code of Australia other than by reason of satisfying the Deemed-to-Satisfy Provisions.
1.6.3 Applicant
A company, corporation, organization, association, partnership, individual or
manufacturer’s authorized agent that proposes a test in accordance with this Standard.
1.6.4 Approved
Accepted for use by the regulatory authority or other authority having jurisdiction.
1.6.5 Blank penetration seal
A component that seals an aperture of specified size in a fire-separating element but does
not incorporate any penetrating services.
1.6.6 Combustible
The classification of a material based on its reaction to defined elevated temperature
conditions and which—
(a) has been deemed combustible in accordance with the BCA; and
(b) has been subjected to the test conditions of AS 1530.1 and has exceeded flaming or
temperature rise limits specified in that Standard.
1.6.7 Connecting duct
The duct section between the damper or separating element and the flow-measuring station.
1.6.9.3 Insulation
The ability of an element of construction to maintain a temperature on the surface that is
not exposed to the furnace, below the limits specified, when tested in accordance with this
Standard.
1.6.10 Critical service
A system or component that operates to identify an emergency or intended to operate during
an emergency, and is primarily associated with—
(a) the safety of persons evacuating a building;
(b) firefighting operations; or
(c) fire suppression.
1.6.11 Damper-actuating system
The system that causes the damper to change from the ‘open’ to the ‘closed’ position.
1.6.12 Damper assembly
A movable closure in a duct or opening for the passage of air, which operates automatically
to restrict the passage of fire or products of combustion past the damper.
1.6.13 Damper, insulated
A damper that satisfies the integrity, leakage and insulation (temperature rise) requirements
of this Standard.
1.6.14 Damper, intumescent fire
A closure that operates by intumescing (swelling on application of heat), and is designed to
prevent the passage of fire through the duct.
1.6.15 Damper, mechanical fire
A mechanical closure operated automatically or manually and designed to prevent the
passage of fire through the duct.
1.6.16 Damper, smoke
A closure designed to prevent the passage of smoke through a duct.
1.6.17 Damper, uninsulated
A damper that satisfies the integrity and leakage requirements of this Standard.
1.6.18 Doorset
A complete assembly as defined in AS 1905.1.
NOTE: See also definition of terms related to fire-resistant doorsets in AS 1905.1.
1.6.29 Glazing
An element or elements of construction intended for transmission of light.
1.6.30 Heat flux
The quantity of heat energy per unit area incident on the target of the measuring device. It
includes heat transferred by convection and radiation.
1.6.31 Lift-landing door assembly
A complete assembly comprising multiple leaves, or single leaf, door that open(s) and
close(s) the landing entrance together with its associated frame and supports.
1.6.32 Loading
The load applied to an element of construction during a load-bearing test.
Licensed to Mrs Pat Rogers on 21 September 2009. 1 user personal user licence only. Storage, distribution or use on network prohibited (10056147).
training shall be given to relevant personnel. Laboratory personnel shall ensure that written
safety instructions are followed at all times.
SEC T I O N 2 G E N E RA L RE Q U IRE M E N T S
2.2.1 Thermocouples
All thermocouples used to measure temperature shall be Type K, in ‘standard’ tolerance,
i.e., ±2.2°C or 0.75%, whichever is the greater, complying with ANSI, MC96 or
IEC 60584.1. Each batch shall be calibrated by an accredited laboratory, for example a
laboratory with appropriate registration (see Note). Single point thermocouple calibration is
adequate using 200°C for specimen thermocouples and 900°C for furnace thermocouples.
NOTE: The appropriate registration in Australia is the National Association of Testing
Authorities (NATA).
The thermocouple insulation material shall be suitable for application; that is, consideration
shall be taken as to the melting temperature or moisture resistance of the insulation.
2.2.2 Furnace temperature measurement
2.2.2.1 General
The furnace thermocouples shall be mineral insulated, metal sheathed (MIMS) with a
stainless steel sheath having wire diameter less than 1.0 mm and an overall diameter of
3 mm, with the measuring junction insulated from the sheath to minimize ground-loop
problems. The MIMS thermocouple shall be supported by a heat-resisting tube with or
without additional insulation with the measuring junction protruding a minimum of 25 mm
as shown in Figure 2.2.2.1. The thermocouples shall be replaced every 40 h.
A visual inspection of thermocouples shall be made and any damaged thermocouples likely
to affect the accuracy of the measurement shall be discarded.
NOTE: If the plate thermometer is to be included in the test, reference should be made to
Appendix B.
DIMENSIONS IN MILLIMETRES
(e) In the case of non-planar surfaces, the disc and pad shall be deformed to follow the
surface profile. If there is difficulty in fixing the standard pad, the size of the pad,
shall be reduced subject to a minimum diameter of 12 mm.
2.2.3.4 Roving thermocouples
One or more roving thermocouples of the design shown in Figure 2.2.3.4 or alternative
temperature-measuring devices, which can be shown to have at least the accuracy and a
response time equal to or less than the design illustrated by Figure 2.2.3.4, shall be
available to measure the unexposed surface temperature during a test for a minimum period
of 90 s in positions where higher temperatures are suspected. If the temperature rise after
90 s exceeds 175 K, the roving thermocouple(s) shall continue to be applied for a further
90 s and then removed.
The measuring junction of the thermocouple consists of 1.0 mm diameter thermocouple
Licensed to Mrs Pat Rogers on 21 September 2009. 1 user personal user licence only. Storage, distribution or use on network prohibited (10056147).
wires soldered or welded to a 12 mm diameter, 0.5 mm thick copper disc. The thermocouple
assembly shall be provided with a handle so that it can be applied over any point on the
unexposed surface of the test specimen.
DIMENSIONS IN MILLIMETRES
NOTES:
1 When information concerning the internal temperature of a test specimen or particular
component is required, it should be obtained by means of thermocouples having
characteristics appropriate to the range of temperatures to be measured as well as being
suitable for the type of materials in the test specimen.
2 For concrete specimens, the thermocouple wires should be tied to the reinforcement, to ensure
that the thermocouple remains in position during placement of the concrete or if MIMS
thermocouples are used, the overall sheath diameter should not exceed 3.0 mm.
The relevant deflection of the test specimen shall be measured and recorded throughout the
test, at intervals adequate to present a history of movement during the test to an accuracy of
±2 mm.
NOTE: To comply with some international Standards, for load-bearing elements, horizontal and
vertical deflections are required to be measured at 1 min intervals.
There shall be no significant radiating surfaces other than the specimen within the field of
vision.
2.5.3.2 Specific locations
Measurements shall be taken at either one of the following locations:
(a) Opposite the geometric centre of the specimen, this is referred to as the average heat
flux.
(b) At the point at which the maximum heat flux can be expected. Often this follows
logically or can be calculated from the geometry of the specimen.
If the specimen is symmetrical about its centre and a uniform radiator, this will
coincide with position (a).
If the specimen has areas of differing insulation and/or transmission, then it may be
Licensed to Mrs Pat Rogers on 21 September 2009. 1 user personal user licence only. Storage, distribution or use on network prohibited (10056147).
difficult to predict the point of maximum intensity with any degree or certainty. In
these cases the following procedure shall be used:
(i) Identify all areas where it is anticipated that the temperature will exceed 300°C
and that also have an area in excess of 0.1 m2 (or 65 000 mm 2 for doorsets).
Measure the heat flux opposite the notional centre of each such area.
(ii) Two or more identical parts of the specimen having the same height or width,
separated by less than 0.1 m, may be treated as a single radiation surface.
(iii) Treat the area or sub-area as a single radiating surface if the area, or sub-area,
of the specimen, that is expected to remain below 300°C, is less than 10% of
the total area, or sub-area, under consideration. This allows for breaks such as
glazing bars.
2.5.3.3 Measurement data
Measurements taken at each of the locations specified in Clauses 2.5.3.1 and 2.5.3.2 shall
be recorded throughout the test at intervals not exceeding 1 min.
DIMENSIONS IN MILLIMETRES
DIMENSIONS IN MILLIMETRES
Accelerated conditioning is permissible, provided the method does not alter the properties
of component materials or the moisture distribution in the specimen so that it has influence
on the fire behaviour of the specimen. High temperature conditioning shall be below
temperatures critical for the materials.
NOTES:
1 Conditioning temperatures above 60°C are not recommended, unless it can be demonstrated
that the material properties are not significantly modified.
2 It is desirable that the moisture content of timber be between 10% and 15%.
3 It is desirable that the moisture content of concrete be less than 5%.
2.8.6 Specimen clearances inside the furnace
A minimum clearance of 200 mm shall be maintained between the wall, floor and ceiling of
the furnace and any specimen or part of the specimen internal to the furnace chamber (e.g.,
Licensed to Mrs Pat Rogers on 21 September 2009. 1 user personal user licence only. Storage, distribution or use on network prohibited (10056147).
(b) The characteristic material properties of the test specimen and a design method
specified in the appropriate Australian Standard or, where this does not exist, in a
recognized structural Standard. The relationship between the actual material
properties and the characteristic material properties of the test specimen shall be
given or shall be experimentally determined.
(c) A load nominated by the applicant.
2.9.3 Application of restraint
The role of the elements in service shall be considered so that the methods adopted for
supporting or restraining the ends or sides of a test specimen during a test are, as far as
practicable, similar in nature to those that would be applied to a similar element in service.
If restraint is applied in the test, then the restraint conditions shall be specified with regard
to free movements of the element and, as far as practicable, those external forces and
moments that are transmitted to the element by restraint during the test. Where the result is
Licensed to Mrs Pat Rogers on 21 September 2009. 1 user personal user licence only. Storage, distribution or use on network prohibited (10056147).
intended for general application, the specimen shall be tested in the least favourable
condition, as specified in the relevant section.
1 min.
(b) When emitted radiant heat flux is to be measured, the radiometer readings shall be
recorded at intervals not exceeding 1 min.
2.11.5 Structurally critical temperatures
Where design Standards specify methods of assessment of fire resistance based on
temperature, the temperature shall be measured at locations that are judged to be critical to
the structural adequacy of load-bearing elements, subject to the following:
(a) The applicant and the testing laboratory shall determine, prior to the test, the
particular steel bars, tendons and the like whose temperatures are to be monitored
throughout the test.
(b) The procedures shall be carried out as detailed in the applicable section of this
Standard.
These temperatures shall be recorded at intervals not exceeding 1 min.
NOTE: By reference to the appropriate design code, the fire resistance of a column or beam may
be deduced, account being taken of the particular grade of steel used, the degree of applied
loading, the condition of support and other relevant factors.
2.11.6 Additional observations
During loading and throughout the test, observations shall be made of changes and
occurrences, which, although not criteria of performance, could create hazards or impair
performance.
NOTE: Examples of such effects include cracking, fusing, change of colour, falling of material,
spalling, explosive spalling, melting, flaming, charring, and the emission of appreciable volumes
of smoke or noxious vapours from the unexposed face of a separating element.
2.11.7 Computation of radiant heat reflux
Where required, the average intensity of radiant heat flux emitted by the specimen shall be
determined by the following equation:
Io = I r /ϕ
where
I o = average intensity of radiant heat flux emitted by the specimens, in kilowatts per
square metre
I r = intensity of radiant heat flux recorded by the radiometer, in kilowatts per square
metre
ϕ = configuration factor applicable to the measurement
dt 1000
where h = the initial height
(b) When the following criteria for laterally loaded elements has been exceeded:
Deflection of L2/400d mm . . . 2.12(3)
Where the rate of deflection is (in millimetres per minute), calculated over 1 min
intervals, starting at 1 min from the commencement of the heating period, exceeds the
limit set by—
Rate of deflection = L2/9000d mm/min . . . 2.12(4)
where
L = clear span of the specimen, in millimetres
d = distance from the top of the structural section to the bottom of the design
tension zone, in millimetres
Since relatively rapidly deflections can occur before stable conditions are reached, the rate
of deflection limit shall not apply before a deflection of L/30 is exceeded.
2.12.2 Integrity
2.12.2.1 General
Failure in relation to integrity shall be deemed to have occurred when evaluated in
accordance with Clauses 2.12.2.2 to 2.12.2.4.
For an element intended to separate spaces and resist the passage of flame from one space
to another, failure in relation to integrity shall be deemed to have occurred upon collapse,
the development of cracks, fissures, or other openings through which flames or hot gases
can pass, or upon other occurrences as set out in the relevant section.
The measurement of the integrity of the test specimen shall be made by cotton pad, gap
gauges or sustained flaming. For uninsulated assemblies, other than service penetrations,
the use of the cotton pad is inappropriate and the gap gauges shall be used to determine
failure. If a specimen contains elements of different thermal resistance, the cotton pad may
be used against those parts deemed to be insulating.
C2.12.2.1 The radiant heat transfer from uninsulated specimens is likely to be sufficient
to cause unpiloted ignition of the cotton pad and, therefore, its use is not considered
appropriate. Users of this Standard should be aware that fire spread due to radiant heat
transfer could occur prior to the stated integrity period for uninsulated specimens.
Two gap gauges shall be employed, in turn, and without undue force to determine when—
(a) a 6 mm gap gauge can be passed through the specimen so that the gap gauge projects
into the furnace and can be moved a distance of 150 mm along the gap; or
(b) a 25 mm gap gauge can be passed through the specimen so that the gap gauge projects
into the furnace.
Any small interruptions to the passage of the gap gauge, which would have little or no
effect upon the transmission of hot gases through the opening, shall not be taken into
account; for example, small fastenings across a construction joint that has opened due to
distortion.
2.12.2.4 Flaming
Sustained flaming on the surface of the unexposed face for 10 s or longer constitutes
integrity failure.
2.12.3 Insulation
Failure in relation to insulation shall be deemed to have occurred when measurement of
insulation is made by thermocouples on the unexposed face, the initial temperature is the
average temperature on the unexposed face measured less than 5 min before commencement
of the test. The specimen is deemed to have failed when—
(a) the average temperature of the unexposed face of the test specimen, as measured by
the thermocouples specified in Clause 2.2.3.1, exceeds the initial temperature by
more than 140 K; or
(b) the temperature at any location on the unexposed face of the test specimen exceeds
the initial temperature by more than 180 K.
2.12.4 Radiation
Failure in relation to radiation shall be deemed to have occurred when the calculated total
heat flux at a distance of 365 mm exceeds 10 kW/m2 .
NOTES:
1 The following test results would indicate that a floor/ceiling system failed in respect of
resistance to incipient spread of fire, insulation and integrity after the stated times, but
complied with the requirements for structural adequacy when the test was terminated at
136 min:
2 The following test results would indicate that an uninsulated doorset failed in respect of
radiation and insulation after the stated times and that the structural adequacy criteria is not
applicable:
(s) The result stated in terms of time, in elapsed whole minutes, between the
commencement of heating and the time of failure with respect to the relevant criteria
including—
(i) the rate of deflection when this is the criterion used to assess load-bearing
capacity, including the value of d (see Clause 2.12.1) used in calculating the
limiting rate of deflection for flexural members;
(ii) the maximum deflection and the time and position at which it occurred,
supported by adequate graphical data;
(iii) the mode of failure with respect to all integrity criteria;
(iv) the position(s) at which the maximum temperature rise was measured should
this be the case of insulation failure; and
(v) any alternative and additional tests in accordance with Appendix B, e.g., plate
Licensed to Mrs Pat Rogers on 21 September 2009. 1 user personal user licence only. Storage, distribution or use on network prohibited (10056147).
thermometers.
(t) Tabulation or graphical depiction of the output from all pressure-measuring devices,
deflection measuring devices, radiometers, unexposed face thermocouples and, where
applicable, internal thermocouples.
NOTE: The report only needs to include a selection of the measured data sufficient to provide
a history of the performance of the test specimen. For example, it is not necessary to tabulate
the temperature of every thermocouple fixed to a beam at 1 min intervals for the whole
duration of a 90 min test; however, it is recommended that all of the measurements are
included at around the time of failure of all the criteria being considered. Before and after this
period, the interval at which measured data needs to be included in the report may be longer,
for example, 5 to 10 min.
(u) A description of any significant behaviour of the test specimen.
(v) The field of direct application of the results for the specimen to be evaluated, for
example, applicable for fire exposure from direction tested.
(w) The following statements:
THIS REPORT DETAILS METHODS OF CONSTRUCTION, THE TEST
CONDITIONS AND THE RESULTS OBTAINED WHEN THE SPECIFIC
ELEMENT OF CONSTRUCTION DESCRIBED HEREIN WAS TESTED
FOLLOWING THE PROCEDURE OUTLINED IN THIS STANDARD.
ANY SIGNIFICANT VARIATION WITH RESPECT TO SIZE,
CONSTRUCTIONAL DETAILS, LOADS, STRESSES, EDGE OR END
CONDITIONS, OTHER THAN THOSE ALLOWED UNDER THE FIELD
OF DIRECT APPLICATION IN THE RELEVANT TEST METHOD, IS
NOT COVERED BY THIS REPORT.
BECAUSE OF THE NATURE OF FIRE RESISTANCE TESTING AND
THE CONSEQUENT DIFFICULTY IN QUANTIFYING THE
UNCERTAINTY OF MEASUREMENT OF FIRE RESISTANCE, IT IS NOT
POSSIBLE TO PROVIDE A STATED DEGREE OF ACCURACY OF THE
RESULT.
NOTE: Appendix A provides guidelines on the measurement of radiant heat flux.
(x) The FRL assigned to the test specimen.
2.15.3 Regulatory information report
In addition to the full test report, a regulatory information report may be issued to provide
the minimum information required for regulatory compliance.
(g) The relevant properties of materials or components that have a bearing on the fire
performance of the test specimen. Where it is impractical to measure some of these
properties, this shall be reported.
(h) The method of assembly and installation of the test specimen.
(i) For load-bearing elements, the load applied to the test specimen.
(j) The support and restraint conditions employed and the rationale for their selection.
(k) For asymmetrical separating elements, the direction in which the specimen was tested
and the reason for this choice.
(l) Statement that conditions complied with the Standard.
The result stated in terms of time, in elapsed whole minutes, between the
commencement of heating and the time of failure with respect to the relevant criteria
(m) A description of any significant behaviour of the test specimen.
(n) The field of direct applicability of the results for the specimen to be evaluated, for
example, applicable for fire exposure from direction tested.
(o) The following statements:
THIS REPORT DETAILS THE METHODS OF CONSTRUCTION, TEST
CONDITIONS AND THE RESULTS OBTAINED WHEN THE SPECIFIC ELEMENT
OF CONSTRUCTION DESCRIBED HEREIN WAS TESTED FOLLOWING THE
PROCEDURE OUTLINED IN AS 1530.4. ANY SIGNIFICANT VARIATION WITH
RESPECT TO SIZE, CONSTRUCTIONAL DETAILS, LOADS, STRESSES, EDGE OR
END CONDITIONS, OTHER THAN THOSE ALLOWED UNDER THE FIELD OF
DIRECT APPLICATION IN THE RELEVANT TEST METHOD, IS NOT COVERED
BY THIS REPORT.
BECAUSE OF THE NATURE OF FIRE RESISTANCE TESTING AND THE
CONSEQUENT DIFFICULTY IN QUANTIFYING THE UNCERTAINTY OF
MEASUREMENT OF FIRE RESISTANCE, IT IS NOT POSSIBLE TO PROVIDE A
STATED DEGREE OF ACCURACY OF THE RESULT.
(p) The FRL assigned to the test specimen.
2.15.4 Test certificate
In addition to the full test report and short-form report, an abbreviated version may be
provided for commercial purposes, at the specific request of the applicant, which shall
include the following:
(a) Description of specimen (attach a drawing where appropriate).
(b) Test results, including the FRL.
S E C T I O N 3 W A L L S— V E RT I CA L
S E P A R A T I N G E L E M E N T S
3.1 GENERAL
3.1.1 Application
This Section sets out the procedures for determining the fire resistance of masonry,
prefabricated and framed walls, access panels, and insulated glazed elements when forming
part of a wall. It shall be read in conjunction with Section 2.
NOTE: Access panels and insulated glazed elements are considered part of the separating
elements and are subject to the relevant criteria of failure.
Licensed to Mrs Pat Rogers on 21 September 2009. 1 user personal user licence only. Storage, distribution or use on network prohibited (10056147).
fixed in the centre of the specimen with smaller panels of equal width on both sides (see
Figures 3.2.3.2(A) and 3.2.3.2(B)).
Where through-joints occur in practice, at least one vertical joint in the test specimen shall
be arranged to simulate this condition.
3.2.3.3 Masonry walls
A masonry wall, for example, brickwork, concrete block work, and gypsum blocks, shall
generally be constructed from identical units. Where a bonding material is used, it shall be
of a type used with the masonry unit.
3.2.3.4 Framed walls
Where sheets are vertically installed, there shall be at least two vertical joints and one
horizontal joint in the specimen, if these are intended to be used in practice. Where sheets
are horizontally installed, there shall be at least two horizontal joints and one vertical joint
in the specimen, if these are intended to be used in practice.
Where the test specimen can incorporate at least two full width sheets, the outside edge of
the full size board on the exposed face shall be unrestrained.
Where the difference between the size of the furnace opening and the full width of the sheet
is less than 1000 mm, then one small sheet shall be attached to the restrained edge of the
specimen on the exposed face. Where the difference is greater than 1000 mm, then the full
size sheet shall be fixed in the centre of the specimen with smaller sheets of equal width on
both sides (see Figures 3.2.3.2(A) and 3.2.3.2(B)).
3.3 INSTRUMENTATION
3.3.1 Measurement of temperature
3.3.1.1 General
Specimen thermocouples shall comply with Clause 2.2.3 and shall be positioned in
accordance with Clauses 3.3.1.2 and 3.3.1.3 (see Figures 3.3.1.1(A) to 3.3.1.1(N)).
3.3.1.2 Average temperature measurement
To measure the average temperature rise on the unexposed face of the specimen, five
thermocouples shall be used. One thermocouple shall be placed close to the centre and the
rest shall be placed close to the centre of each quarter section. These thermocouples shall
not be attached to the specimen over thermal bridges, joints, junction, through connections
and fixings such as bolts, screws or nails. Thermocouples shall not be placed over a ridge or
Licensed to Mrs Pat Rogers on 21 September 2009. 1 user personal user licence only. Storage, distribution or use on network prohibited (10056147).
(f) At mid-width, where possible, with the centre of the pad 15 mm from the edge of a
horizontal joint (positive pressure zone).
(g) At mid-height, where possible, with the centre of the pad 15 m from the edge of a
vertical joint (positive pressure zone).
Examples of thermocouple positions are shown in Figures 3.3.1.1(A) to 3.3.1.1(N).
3.3.1.6 Inside wall temperatures
Thermocouples, which are used to measure temperatures inside the wall for additional
information or field of application purposes, shall be attached at appropriate positions
without damaging the specimen. The first 25 mm of each thermocouple, where practicable,
shall be in the isothermal plane.
3.3.2 Measurement of deflection
Licensed to Mrs Pat Rogers on 21 September 2009. 1 user personal user licence only. Storage, distribution or use on network prohibited (10056147).
3.3.2.1 General
Instrumentation complying with Clause 2.4 shall be used to measure horizontal and vertical
deflection.
3.3.2.2 Measurement of horizontal deflection—Both load-bearing and non-load-bearing
Measurements shall be made at mid-height, at the centre of the specimen and 50 mm from
the free edge.
NOTE: The Information on the deformation of the walls may be used to extend the application of
the test results.
3.3.2.3 Measurement of vertical deflection—Load-bearing only
At least two measurements shall be made, one at each vertical edge of the specimen (see
Figures 3.3.1.1(A) to 3.3.1.1(N)).
AS 1530.4—2005
Standards Australia
42
LOAD-BEARING
FIGURE 3.3.1.1(A) TYPICAL CONFIGURATION FOR MASONRY WALLS—
www.standards.com.au
Licensed to Mrs Pat Rogers on 21 September 2009. 1 user personal user licence only. Storage, distribution or use on network prohibited (10056147).
www.standards.com.au
43
LOAD-BEARING
FIGURE 3.3.1.1(B) TYPICAL CONFIGURATION FOR MASONRY WALLS—
Standards Australia
AS 1530.4—2005
Licensed to Mrs Pat Rogers on 21 September 2009. 1 user personal user licence only. Storage, distribution or use on network prohibited (10056147).
AS 1530.4—2005
Standards Australia
44
NON-LOAD-BEARING
FIGURE 3.3.1.1(C) TYPICAL CONFIGURATION FOR MASONRY WALLS—
www.standards.com.au
45 AS 1530.4—2005
Licensed to Mrs Pat Rogers on 21 September 2009. 1 user personal user licence only. Storage, distribution or use on network prohibited (10056147).
DIMENSIONS IN MILLIMETRES
AS 1530.4—2005
Standards Australia
46
LOAD-BEARING
FIGURE 3.3.1.1(E) TYPICAL CONFIGURATION FOR PREFABRICATED WALLS—
www.standards.com.au
Licensed to Mrs Pat Rogers on 21 September 2009. 1 user personal user licence only. Storage, distribution or use on network prohibited (10056147).
www.standards.com.au
47
LOAD-BEARING
FIGURE 3.3.1.1(F) TYPICAL CONFIGURATION FOR PREFABRICATED WALLS—
Standards Australia
AS 1530.4—2005
Licensed to Mrs Pat Rogers on 21 September 2009. 1 user personal user licence only. Storage, distribution or use on network prohibited (10056147).
AS 1530.4—2005
Standards Australia
48
NON-LOAD-BEARING
FIGURE 3.3.1.1(G) TYPICAL CONFIGURATION FOR PREFABRICATED WALLS—
www.standards.com.au
Licensed to Mrs Pat Rogers on 21 September 2009. 1 user personal user licence only. Storage, distribution or use on network prohibited (10056147).
www.standards.com.au
49
NON-LOAD-BEARING
FIGURE 3.3.1.1(H) TYPICAL CONFIGURATION FOR PREFABRICATED WALLS—
Standards Australia
AS 1530.4—2005
Licensed to Mrs Pat Rogers on 21 September 2009. 1 user personal user licence only. Storage, distribution or use on network prohibited (10056147).
AS 1530.4—2005
Standards Australia
50
www.standards.com.au
51 AS 1530.4—2005
Licensed to Mrs Pat Rogers on 21 September 2009. 1 user personal user licence only. Storage, distribution or use on network prohibited (10056147).
DIMENSIONS IN MILLIMETRES
www.standards.com.au
53
NON-LOAD-BEARING
FIGURE 3.3.1.1(L) TYPICAL CONFIGURATION FOR FRAMED WALLS—
Standards Australia
AS 1530.4—2005
AS 1530.4—2005 54
Licensed to Mrs Pat Rogers on 21 September 2009. 1 user personal user licence only. Storage, distribution or use on network prohibited (10056147).
DIMENSIONS IN MILLIMETRES
3.4 LOADING
3.4.1 General
When subjected to loads, all load-bearing walls shall be tested and calculated in accordance
with Clause 2.9 and in consultation with the applicant.
3.4.2 Vertical load
Vertical load shall be applied to either the top or bottom edge, with the vertical edges left
free to deform.
3.4.3 Method of loading
The load shall be applied either uniformly across the width of the specimen by a loading
beam or by individual loading jacks at selected points, where this is more representative of
Licensed to Mrs Pat Rogers on 21 September 2009. 1 user personal user licence only. Storage, distribution or use on network prohibited (10056147).
the use of the construction. If the test specimen is designed to be eccentrically loaded, or if
only one leaf of a cavity construction is to be loaded, these conditions shall be reproduced
in the specimen.
3.4.4 Loading frame
The test specimen shall be erected within a loading frame having appropriate stiffness in
relation to the test construction and to the loads that will be imposed upon it during the test.
As a guide, the load distribution members should not deflect more than 1 mm under a force
of 10 kN applied at the centre span, in the plane of the frame.
3.4.5 Loading system
The loading system shall be capable of compensating for the maximum allowable
deformation of the specimen.
4.1 GENERAL
4.1.1 Application
This Section sets out the procedures for determining the fire resistance of load-bearing and
non-load-bearing horizontal separating elements when exposed to heating from the
underside. It applies to floors, roofs, ceilings, combinations of floor/ceiling systems,
roof/ceiling systems, access panels, and insulated glazed elements when forming part of a
horizontal separating element.
Licensed to Mrs Pat Rogers on 21 September 2009. 1 user personal user licence only. Storage, distribution or use on network prohibited (10056147).
(g) Ceiling system for protection of structural members A ceiling system that is
designed to act as a horizontal separating element to provide full or partial protection,
supplementing other forms of protection, to maintain the structural adequacy
requirements of a structural member.
NOTES:
1 A ceiling system may be used to supplement spray protection, or the like, already applied
to a structural member.
2 A ceiling system that has an established level of performance to the resistance of the
incipient spread of fire will provide structural protection for at least an equivalent period
of time.
Licensed to Mrs Pat Rogers on 21 September 2009. 1 user personal user licence only. Storage, distribution or use on network prohibited (10056147).
4.3.2 Size
This specimen size shall comply with Clause 2.8.2.
4.3.3 Floor systems
Floor systems, acting as horizontal separating elements without the aid of a protective
membrane, shall comprise a representative portion of the proposed system including all
structural, support and suspension systems.
4.3.10 Construction
4.3.10.1 General
The specimen shall incorporate—
(a) longitudinal and transverse joints;
(b) services, such as lighting or air-handling systems, that are an integral part of the
design of the element; and
(c) beams that are an integral part of the design of the element, instrumented as required
by Section 6.
4.3.10.2 Ceilings
Where the ceiling design includes longitudinal and transverse joints, the test specimen shall
include such joints in both longitudinal and transverse directions. The profiles bearing the
various components or panels of the ceiling shall be installed against each other without any
gap, unless a gap (or gaps) is required for design purposes. In this case, the gap (or gaps)
shall be installed within the specimen and not at its perimeter.
The test specimen shall be mounted in a test frame, to prohibit thermal elongation of the
specimen and component members so that the thermal expansion behaviour of grid
members and expansion devices can be correctly evaluated.
If the horizontal and transverse components vary in cross-section, the component that is
closer to the ceiling membrane shall be orientated parallel to the longitudinal axis.
Self-supporting ceilings, smaller than full size, shall incorporate one free edge at the end of
the longest span and no allowance shall be made for longitudinal movement or thermal
expansion around the perimeter.
Supported ceilings smaller than full size shall be fixed to the specimen support frame and
no allowance shall be made for longitudinal movement or thermal expansion around the
perimeter.
The ratio of the exposed surface area of the steel beams and the plan area of the suspended
ceiling shall be less than 0.8:1.
For the protection of timber members, the beams shall be of sufficient size to determine
char depths for the duration of the test.
4.4 INSTRUMENTATION
4.4.1 Measurement of temperature
Temperatures shall be measured using thermocouples complying with Clause 2.2.3 and
positioned in accordance with Clause 2.2.3 at the locations given in Clauses 4.4.2 to 4.4.5.
4.4.2 Temperature measurement of the unexposed specimen surface
4.4.2.1 General
The following applies:
(a) Surface thermocouples of the type specified in Clause 2.2.3 shall be attached to the
unexposed surface of the test specimen to measure the average and maximum
temperature rise.
(b) The thermocouples shall not be placed closer than 100 mm from an uninsulated
glazed element or 100 mm from the free edge(s) of the test specimen.
4.4.2.2 Thermocouples for measuring the average temperature rise
The following applies:
(a) Five thermocouples shall be evenly distributed over the test specimen to monitor the
temperature of the unexposed surface of the specimen as defined in Clause 4.2. They
shall be placed one in the centre of the specimen and one at the centre of each quarter
section.
(b) For test specimens that contain discrete areas ≥0.1 m 2 and expected to exhibit
different levels of insulation performance, e.g., glazing, each discrete area shall be
individually monitored for average temperature rise. The average temperature rise
shall be measured by thermocouples distributed over each discrete area. One
thermocouple shall be provided for every 1.5 m2 , or part thereof, of the test specimen.
A minimum of two thermocouples for each discrete area shall be provided.
(c) For wooden floors or roof constructions, the distance of these thermocouples to the
side of the nearer joist shall be at least 50 mm.
(d) For wooden floors or roof constructions, the distance of the thermocouples to the
joints of the floorboards, panels or slabs shall be at least 50 mm.
(e) Where the test specimen is covered only with one layer of floorboards with a board
width of less than 100 mm, the distance shall be half the width of the boards.
(f) Where the test specimen has insulated parts of differing thicknesses, the number of
thermocouples on the unexposed face shall be increased to six to provide equal
numbers of thermocouples at the maximum and minimum thicknesses.
4.4.2.3 Thermocouples for measuring the maximum temperature rise
The following applies:
(a) If the test specimen incorporates discrete areas of different thermal insulation, which
are evaluated separately, the evaluation of maximum exposed face temperature of
these areas shall also be undertaken separately. This may require additional
unexposed surface thermocouples.
(b) For floors or roofs with wooden beams or joists, the distance to the nearest side of the
Licensed to Mrs Pat Rogers on 21 September 2009. 1 user personal user licence only. Storage, distribution or use on network prohibited (10056147).
4.5 LOADING
4.5.1 Loading of suspension devices
In addition to the requirements of Clause 2.9, a static load shall be applied to any
Licensed to Mrs Pat Rogers on 21 September 2009. 1 user personal user licence only. Storage, distribution or use on network prohibited (10056147).
suspension rod, or the like, that penetrates ceilings, where such suspension devices in
service support loads that may influence the behaviour of these devices during a fire
exposure and consequently affect the fire endurance of the ceiling system.
4.5.2 Load distribution
The contact area between a loading point and the surface of a floor or trafficable roof shall
be through a pad not less than 100 mm × 100 mm and no more than 200 mm × 200 mm
individually and shall not exceed 16% of the total surface area.
4.6 RESTRAINT
4.6.1 General
Where restraint conditions required under Clause 2.9.3 cannot be defined, the test specimen
shall be simply supported and unrestrained.
4.6.2 Horizontal separating elements
Test specimens representing horizontal separating elements shall be tested simply supported
unless the boundary conditions (with respect to restraint and number of edge supports)
representative of practice can be simulated.
4.6.3 Simply supported constructions
Test specimens representing simply supported constructions shall rest on a smooth bearing
surface.
4.6.4 Sealing of gaps
Where gaps exist at the boundaries, they shall be sealed with a non-restraining and non-
combustible material.
S E C T I O N 5 CO L U M N S
5.1 GENERAL
This Section sets out the procedure for determining the fire resistance of columns. It shall
be read in conjunction with Section 2.
5.3 INSTRUMENTATION
5.3.1 Thermocouples for structurally critical temperatures
Where temperature-measurement procedures in accordance with Clause 2.11.5 are adopted,
thermocouples shall be attached in accordance with Clause 2.2.4 and positioned as follows:
(a) For a 3000 mm steel specimen, a minimum of four transverse sections shall be
selected. At each of these sections, a minimum of two thermocouples shall be
positioned. For a steel specimen less than 3000 mm long, a minimum of two
transverse sections shall be selected not closer than 300 mm from the ends of the
specimen. At each of these sections a minimum of four thermocouples shall be
positioned.
NOTE: Figure 6.3.1.2 provides recommended locations for thermocouples.
(b) For other than a steel specimen, thermocouples shall be positioned at all locations
considered to be critical.
5.3.2 Deflection measurement
Deflection-measuring equipment shall be positioned to measure the axial movement.
(c) The requirements for loading specimens with the maximum and minimum protection
thicknesses may be waived subject to agreement between the test laboratory and
applicant, provided the following is observed:
(i) The columns are subjected to the specified axial load in accordance with
Clause 2.9.2.
(ii) The height of each test specimen is 3 m ±200 mm.
5.6 OBSERVATIONS
Licensed to Mrs Pat Rogers on 21 September 2009. 1 user personal user licence only. Storage, distribution or use on network prohibited (10056147).
5.6.1 Displacement
The longitudinal displacement versus time shall be recorded.
5.6.2 Structurally critical temperatures
Where temperature-measurement procedures in accordance with Clause 2.11.5 are adopted,
a record shall be made of temperature versus time for all the thermocouples positioned in
accordance with Clause 5.3.1.
6.1 GENERAL
This Section sets out the procedures for determining the fire resistance of beams, girders
and trusses including those incorporated in or supporting floors or roofs. It shall be read in
conjunction with Section 2.
test equipment, the testing authority shall test a representative portion of the full-sized
element in which the curtailed length is not less than 3000 mm.
Subject to the requirements of Clause 6.4.2.2, specimens of minimum length of 1000 mm
may be used to determine the effectiveness of different thicknesses of protective material.
6.2.2 Beams to be incorporated in concrete roof or floor systems
Where a beam(s) is to be incorporated in a concrete floor or roof system for which the
design details are not available to the testing authority, the test specimen shall comprise—
(a) the beam(s) and its fire-protective material, if any; and
(b) a symmetrically located concrete deck or slab in intimate contact with the beam,
which is—
(i) not less than 1000 mm wide; and
(ii) 100 mm thick.
NOTE: It has been established that certain types of lightweight concrete offer less of a heat sink
than other concrete, and this results in appreciably higher temperatures in supporting steel
members. Consequently, a test carried out using lightweight aggregate concrete will produce a
result that may be applied conservatively if dense aggregate concrete is used in practice.
6.3 INSTRUMENTATION
6.3.1 Thermocouples for structurally critical temperatures
6.3.1.1 General
Where temperature-measurement procedures in accordance with Clause 2.11.5 are adopted,
Clause 6.3.1.2, 6.3.1.3 or 6.3.1.4 shall apply, as appropriate (see also Clause 2.2.4).
6.3.1.2 Steel elements
For a 3000 mm steel specimen, a minimum of four transverse sections shall be selected. At
each of these sections, a minimum of two thermocouples shall be positioned. For a steel
specimen less than 3000 mm long, a minimum of two transverse sections shall be selected
not closer than 300 mm from the ends of the specimen. At each of these sections a
minimum of four thermocouples shall be positioned.
Where the element is a truss, at least one thermocouple shall be positioned on each member
of the truss.
NOTE: Figure 6.3.1.2 shows recommended locations for thermocouples.
AS 1530.4—2005
Standards Australia
72
STRUCTURAL SECTIONS
FIGURE 6.3.1.2 RECOMMENDED LOCATION OF THERMOCOUPLES ON TYPICAL
www.standards.com.au
73 AS 1530.4—2005
6.6 OBSERVATIONS
6.6.1 Structurally critical temperatures
Where temperature-measurement procedures in accordance with Clause 2.11.5 are adopted,
a record shall be made of temperature versus time for all the thermocouples positioned in
accordance with Clause 6.3.1.
6.6.2 Deflection
A record shall be made of deflection versus time for each point of measurement.
7.1 GENERAL
This Section sets out the procedures for determining the fire resistance of—
(a) doorsets with hinged or pivoted leaves;
(b) doorsets with horizontally sliding or vertically sliding leaves or panels, including
articulated sliding panels or sectional leaves;
(c) steel, single-skin folding shutters;
(d) other sliding folding door leaves or panels;
Licensed to Mrs Pat Rogers on 21 September 2009. 1 user personal user licence only. Storage, distribution or use on network prohibited (10056147).
7.3 INSTRUMENTATION
7.3.1 Heat flux meter
A heat flux meter shall be positioned in accordance with Clause 2.5.2, to measure the total
heat flux from the specimen or any feature of the specimen (see Clause 2.5).
NOTE: This measurement provides data for an assessment of a safe distance for the location of
combustible materials from a protected opening together with the passage of people. Sufficient
information should be included in the report to identify the nature of the radiating surface and any
non-uniform features shall be specifically identified.
7.3.2 Thermocouples
7.3.2.1 General
Thermocouples complying with Clause 2.2.3.1 shall be attached in accordance with
Clause 2.2.3.2 on the unexposed face of the doorset or shutter assembly. Thermocouple
Licensed to Mrs Pat Rogers on 21 September 2009. 1 user personal user licence only. Storage, distribution or use on network prohibited (10056147).
At each of the positions, thermocouples shall be fixed as close as possible to the edge
of the frame at the junction between the frame and the supporting construction, i.e.,
with the centre of the disc 15 mm from the edge and the pad flush with the edge,
except that the distance of these thermocouples from the inside edge of the frame
shall be not greater than 100 mm.
(c) The thermocouple shall be fixed on the unexposed face of the element where the
specimen is mounted as follows, but subject to the requirements of Clause 7.3.2.4:
(i) Before the heating period—at the locations shown in Figure 7.3.2.3 and at any
point, including a joint, which, in the opinion of the testing laboratory, the
temperature rise is likely to be more than 180°C.
(ii) During the heating period—at any point, including a joint, where the
temperature rise appears to be more than 180°C.
Licensed to Mrs Pat Rogers on 21 September 2009. 1 user personal user licence only. Storage, distribution or use on network prohibited (10056147).
(d) Thermocouples shall be fixed to the face of any over panels and transom panels above
the door leaves and any side panels on the basis of one thermocouple per 0.3 m2 of
panel area.
7.3.2.5 Positioning of thermocouples
The thermocouples specified in Clause 7.3.2.2 and Clause 7.3.2.3, Item (a) and (b), shall be
located not less than 100 mm to the edge of the leaf/leaves or curtain or any standard item
of hardware and shall not be located on any metal through-fastenings or uninsulated glazed
areas (see Figure 7.3.2.5).
The thermocouples specified in Clause 7.3.2.3(c) and Clause 7.3.2.3(d) shall be located not
less than 100 mm from the edge of the doorframe.
DIMENSIONS IN MILLIMETRES
7.5 OBSERVATIONS
7.5.1 Average temperature of unexposed face of door leaf or shutter
The mean of the temperatures measured by the thermocouples positioned in accordance
with Clause 7.3.2.2 shall be determined and recorded.
7.5.2 Maximum temperature of unexposed face of leaf or shutter or side/over panels
The temperature measured by the thermocouples positioned in accordance with
Clause 7.3.2.3(a) and, where applicable, Clause 7.3.2.3(d) shall be recorded.
7.5.3 Maximum temperature of unexposed face of frame
The temperature measured by the thermocouples positioned in accordance with
Clause 7.3.2.3(b) shall be recorded.
7.5.4 Maximum temperature of unexposed face of surrounding element
The temperature measured by the thermocouples positioned in accordance with
Clause 7.3.2.3(c) shall be recorded.
7.5.5 Cracks and openings
A record shall be made of any cracks, fissures or openings that develop—
(a) in the unexposed face of the leaf/leaves or curtain;
(b) between the leaf/leaves or curtain and the frame;
(c) between the frame and the wall; and
(k) Result, stated in terms of the elapsed whole minutes, from the commencement of
heating before failure with respect to the relevant criteria given in Clause 7.6.
(b) other dimensions of the doorframe or component parts of the door leaf; or
(c) the nominal clearances as tested.
7.9.3 Door leaf
Variations to the door leaf may be made as follow:
(a) Facings of low-carbon steel may be substituted for facings of stainless steel provided
that—
(i) such facings are fixed by adhesive to the face or faces of the door leaf and are
not returned around any edge; and
(ii) the clearances between the main body of the door leaf and the doorframe are
not increased.
(b) Decorative laminates and timber veneers up to 1.5 mm thick may be added to the
faces (but not edges) of hinged doors that satisfy the insulation criteria for the full
period to which the Integrity rating applies. For all products tested with decorative
laminate faces the only variations shall be within similar types and thickness of
material, e.g., colour, pattern, manufacturer.
7.9.4 Doorframe
Variations to the doorframe may be made as follows:
(a) Interchanging single-rebated and double-rebated doorframes.
(b) Increasing the doorstop depth and width.
(c) Increasing or decreasing the metal thickness by ±15%.
(d) Fixing in accordance with AS 1905.1.
The dimensions of steel wrap around frames may be increased to accommodate increased
supporting construction thickness. Where the paint finish is not expected to contribute to
the fire resistance of the door, alternative paint or surface finish is acceptable and may be
added to the door leaves or frame provided it does not exceed 0.5 mm thickness, or have a
nitro-cellulose base.
7.9.5 Wall of masonry or concrete construction
Fire-resistant doorsets tested in walls of masonry or concrete construction may be installed
in any one of such types of walling having the same fire resistance level (FRL).
7.9.6 Fixings
The number of fixings used to attach fire-resisting doorsets to supporting constructions may
be increased but not decreased and the distance between fixings may be reduced but may
not be increased.
7.9.7 Hardware
Variations to hardware may be made as follows:
(a) Variations may be made in electroplated or other metallic finishes and in powder
coats and non-nitrocellulose paint finishes not greater than 0.5 mm thick.
(b) Any push-plate, metallic plate for a hold-open device, or kickplate, which is not held
on by and which does not form part of the latchset or lockset furniture, may be
reduced in either dimension but may not vary in material of construction.
Licensed to Mrs Pat Rogers on 21 September 2009. 1 user personal user licence only. Storage, distribution or use on network prohibited (10056147).
(i) it adds no additional load to the brackets and barrel assembly from that in the
tested specimen; and
(ii) it does not alter the automatic operation of the fire resistant roller shutter.
(g) An alternative construction of the threshold may be used, provided that the material is
not deemed combustible in accordance with AS 1530.1, or forms a fire barrier of
same FRL to the fire resistant roller shutter, and the dimensions of the threshold are
maintained in accordance with AS 1905.2.
Licensed to Mrs Pat Rogers on 21 September 2009. 1 user personal user licence only. Storage, distribution or use on network prohibited (10056147).
8.1 GENERAL
This Section sets out the procedure for determining the fire resistance of uninsulated
glazing systems. It shall be read in conjunction with Section 2.
Insulated glazing shall be evaluated in accordance with Sections 3 and 4 and vision panels
within doorsets shall be evaluated in accordance with Section 7.
The glazing system shall be installed and tested in a manner representative of the intended
application.
8.2.2 Size of specimen
The size specimen shall be in accordance with Clause 2.8.2.
8.2.3 Number of specimens
8.2.3.1 General
In addition to Clause 2.8.7, the fire resistance may be determined from a single test
where—
(a) one-way fire resistance is specified by the applicant;
(b) the assembly, including the hardware, fixings and seals, is fully symmetrical; or
(c) the side that is the weaker against fire attack can be clearly identified on the basis of
previous experience of the behaviour in test of the specific window design, and that
side is subject to the test.
If testing is carried out from one side only, i.e. one specimen, the reason for this shall be
clearly stated in the report and, where applicable, in accordance with Items (b) and (c)
above, provide the basis of a classification for fire resistance for exposure from either
direction.
NOTE: An openable component or a glazing bead to one side only renders the glazing
asymmetrical.
8.2.3.2 Horizontal or inclined specimens
Horizontal specimens shall be orientated in accordance with Clause 2.8.7. For inclined
specimens, where it is intended that exposure may occur from either side, then both sides
shall be tested.
8.2.4 Test construction
8.2.4.1 Specimen holder
Where the test specimen is both the same size as the opening in the specimen holder and
installed in masonry, concrete or a similar rigid element of construction, then the specimen
shall be installed directly into the specimen holder.
8.2.4.2 Other instances
In all other instances, the specimen shall be surrounded with construction representative of
that intended to be used in practice.
intended to be used in practice and shall be regarded as part of the system under test. The
exposed face shall be flush with the frame unless the fixing system requires it to be set
back. The whole area of the test construction shall be exposed to the heating conditions of
the furnace.
8.2.5.3 Restraint
Where the test specimen is not larger than the test furnace opening, the edges of the
specimen shall be restrained as intended in practice. Where the construction is likely in
practice to exceed the furnace size, a vertical edge shall be unrestrained and have freedom
of movement. The remaining edges shall be restrained as intended in practice.
8.3 INSTRUMENTATION
8.3.1 Heat flux meter
A heat flux meter shall be positioned in accordance with Clause 2.5.2, to measure the total
heat flux from the specimen or any feature of the specimen (see Clause 2.5).
For heat flux measurements of vertical or horizontal specimens, the heat flux meter shall be
placed on the line normal to the geometric centre of the specimen and with the plane of the
measuring element parallel with the plane of the specimen.
For heat flux measurements of inclined specimens, the heat flux meter shall be placed on a
line passing through the geometric centre of the specimen but normal to the plane of the
furnace.
8.3.2 Deflection measurement
Although deflection of the specimen is a not a criteria of failure, measurements may be
taken to enable greater application of the results.
(c) Graphs of the radiation measured at the position of the measuring device.
TABLE 8.1
VARIATIONS TO THE ANGLE OF TESTED INCLINATION
Test specimen angle Applicable to glazed element angles in use
Between 80º and 90º 80º to 90º
25º to ≤ 80º α ±15º
0 ≤ 25º 0º to 25º
NOTE: If tests are conducted at 0º, 45º and 90º on the same glazing system, the
minimum rating for the three tests applies to all angles (0º to 90º).
S E C T I O N 9 A IR D U CT S
9.1 GENERAL
This Section sets out the procedure for determining the fire resistance of ducts that are
required to—
(a) operate while exposed to an external fire, e.g., air-pressurization or supply ducts; or
(b) conduct hot products of combustion, e.g., smoke-spill or exhaust ducts.
This Section shall be read in conjunction with Section 2.
Penetration details of the air duct shall be evaluated during the fire test.
Licensed to Mrs Pat Rogers on 21 September 2009. 1 user personal user licence only. Storage, distribution or use on network prohibited (10056147).
NOTE: As well a determining the fire resistance of the duct under fire conditions, the test may
provide information about reduction in cross-section and heat transfer from the duct walls, which
could allow the designer to determine the duct’s ability to function under fire conditions.
mentioned locations. Where it is not practicable to position thermocouples inside the duct,
and the duct is of sheet metal construction, the thermocouples may be positioned on the
outside wall of the duct without pad covering and welded in position in accordance with the
provisions of Clause 2.2.4 before placing any layer of insulating material to cover the duct.
Thermocouples to assess the performance of the penetration sealing system shall be
provided in accordance with Section 10 of this Standard.
9.3.2 Internal fire testing
9.3.2.1 Gas temperatures inside the duct
At least two thermocouples complying with Clause 2.2.2.1 shall be positioned inside the
duct so as to obtain a representative measurement of the temperature of the hot gases
passing through the duct, at a cross-section situated at 100 mm from both ends of the duct.
For vertical ducts, the thermocouple shall be located centrally in the duct. For horizontal
ducts, the thermocouple shall be located halfway between the centre of the duct and its top.
9.3.2.2 Insulation measurement
Thermocouples complying with Clause 2.2.3 shall be positioned in accordance with
Clause 2.2.3 on the external face of the duct, as follows:
(a) Groups of not less than two thermocouples at cross-sections located 25 mm and
400 mm from the unexposed face of the penetrated element, and one additional group
at the end of any step or taper on the external duct insulation at the likely hottest
position of the step or taper.
(b) Additional thermocouples at any point where, in the opinion of the testing laboratory,
that point is likely to become hotter than the locations specified in Item (a).
(c) During the heating period, additional thermocouples at any point, which, at any time
during the test, appears to be hotter than those being measured.
Thermocouples to assess the performance of the penetration sealing system shall be
provided in accordance with Section 10 of this Standard.
9.4 PROCEDURE
9.4.1 External fire testing
The specimen shall be heated on the outside. Airflow of 1 ±0.1 m/s shall be established
prior to the start of the test and the fan speed maintained for the duration of the test. It shall
be measured at the mid cross-section of the duct at the air inlet point.
9.5 OBSERVATIONS
9.5.1 Structural adequacy
A record shall be made of the time when the suspension or fixing devices can no longer
retain the duct in its intended position or when sections of the duct collapse.
9.5.2 Integrity
Licensed to Mrs Pat Rogers on 21 September 2009. 1 user personal user licence only. Storage, distribution or use on network prohibited (10056147).
The following shall be observed and recorded together with the time of the observations:
(a) For external fire testing, any hot gases passing into the duct.
(b) For internal fire testing, any hot gases passing to the unexposed side, except for the
open end.
NOTE: Provision may be made to introduce into the furnace a tracer gas or a substance that
will produce a clearly discernible coloured smoke or gas.
9.5.3 Temperatures
For external fire testing, the temperatures measured by thermocouples located in accordance
with Clause 9.3.1 shall be recorded at maximum 1 min intervals.
9.5.4 Cross-sectional area
Significant changes in the cross-section of the specimen shall be observed and recorded
together with the time of the observation.
exceed those tested and that the components remain in the same orientation as that tested.
SECT I ON 1 0 S E RV ICE PE N E T RA T I O N S A N D
C O N T RO L J O I N T S
10.1 GENERAL
This Section sets out the procedure for determining the fire resistance of elements of
construction penetrated by services such as electrical and plumbing services, pipes,
conduits and control joints. It shall be read in conjunction with Section 2.
Dampers are covered by Section 11.
This test does not supply any information on the ability of the penetration sealing system to
withstand stress caused by movements or displacements of the penetrating services.
NOTE: AS 4072.1 should be read in conjunction with this Standard in order to determine any
provisions dealing with orientation and mounting of the test specimen. Definitions given in that
Standard apply herein.
10.4.2 Size
The specimen shall comply with Clause 2.8.2
For control joints, the specimen shall be not less than 1 m × 1 m and the length of the
control joint exposed to the furnace chamber shall be not less than 1 m.
The service(s) shall be installed so that it projects a minimum of 500 mm on each side of
the supporting construction, of which at least 200 mm shall extend beyond the extremities
of the penetration sealing system. The penetration sealing system shall include any coating,
wrapping or other protection to the services. The length of unprotected service on the
unexposed face shall not be greater than 500 mm. For plastic pipes, the external projection
away from the furnace shall be increased to a minimum of 2000 mm. These measurements
shall not include any part of the plug or cap used to seal a pipe within the furnace.
10.4.3 Test mounting
Licensed to Mrs Pat Rogers on 21 September 2009. 1 user personal user licence only. Storage, distribution or use on network prohibited (10056147).
10.4.3.1 General
Where a particular penetration sealing system is intended for use in both horizontal and
vertical elements of construction, each orientation shall be tested.
Where multiple penetrations through the one specimen are to be tested, the configuration
shall be such that an unimpeded view of all parts of the sealing system is possible for the
purpose of determining integrity failure.
Control joints may only need to be tested horizontally, if, in the opinion of the testing
authority, the horizontal orientation represents the most severe test.
10.4.3.2 Vertical elements
For vertical elements, where the fire risk can be identified as being from one nominated
side only, or the sealing system is fully symmetrical, the specimen need only be tested with
the appropriate face exposed to the furnace.
For asymmetrical constructions, where it can be clearly established that there is a weaker
direction of exposure, the specimen may only need to be tested with the weaker face
exposed to the furnace. A full justification for the adopted procedure shall be included in
the test report or letter of opinion obtained from the registered testing authority.
In all other cases, not less than two tests shall be carried out, with at least one being from
each direction of exposure.
10.4.3.3 Horizontal elements
For horizontal elements, the test specimen shall be exposed to heating from the underside
only.
10.4.4 Supporting construction
The supporting construction shall have a fire resistance level equal to or greater than that of
the proposed penetration and representative of that used in practice. The fire resistance
level obtained shall apply only to that particular type of separating element except for
variations permitted in Clause 10.11 and AS 4072.1.
10.4.5 Service end conditions
Service end conditions shall be representative of those intended to be used in practice.
For general pipe systems, e.g., SWV (soil waste vent), water supply and reticulation, the
fire side capped non-fire side open configuration shall be adopted, i.e., closed/open.
The pipe shall be capped on the exposed side only by welding, gluing or mechanically
fixing a disc or cap of the same material as the pipe, onto the end of the pipe or
ceramic/mineral fibre disc.
NOTE: Standard configurations for general cable applications should be as given in Appendix D.
10.4.6.1 Electrical and communication cables
The maximum and minimum sizes of electrical and communication cables shall be tested to
evaluate the performance of a fire-stopping system. If the fire-stopping system is to be used
to protect bundles of cables penetrating an opening, then the maximum bundle size shall be
tested.
Cables shall be allocated to the groupings by type, conductor materials and
sheathing/insulating materials, in accordance with Table 10.4.6.1.
TABLE 10.4.6.1
CABLE GROUPINGS
Type Conductor material Sheathing/insulating material
Single core power PVC
Multicore power (e.g., two core XLPE
plus earth) Copper
Multicore communications Aluminium Rubber
Mineral insulated Others Copper/steel
(mineral-insulated cables)
Others Others
10.4.6.2 Conduits
The maximum and minimum size of cable enclosure and support systems (cable trays and
the like) shall be tested with the maximum and minimum (usually empty) fill of cables (see
Note) that unless a registered test laboratory is able to ascertain that a particular
configuration represents the worst case.
NOTE: The cables may be selected from the provisions given in Appendix D.
For plastic pipes and enclosures, the requirements set out in AS 4072.1 shall apply when
determining suitable test configurations.
10.4.6.3 Busbars and busways
The maximum and minimum size and number of conductors shall be tested to evaluate a
type of busbar or busway over a range of sizes, unless a registered test laboratory is able to
ascertain that a particular configuration represents the worst case.
NOTE: In some instances the performance of busbars may be assessed using test data on pipes of
the same material (e.g., copper).
(b) At the discretion of the testing authority and at the point or points on the surface of
any exposed framing members that support the penetrating service on the penetrated
element.
(c) At points on the surface of the penetrating service or its fire-stopping encasement,
located as follows:
(i) At least two thermocouples located approximately 25 mm from the plane of the
general surface of the penetrated element and its insulating topping, if any.
(ii) Where the insulation of packing is tapered or stepped, two additional
thermocouples beyond the step or the end of any taper if it is expected that
temperatures will be higher at these points.
(d) Where practicable, at two points on the packing around the penetrating service.
(e) During the heating period, additional thermocouples at any point, which, at any time
during the test, appears to be hotter than those being measured.
(f) For unpenetrated blank seals and control joints, as follows:
(i) At least three on the surface of the seal, with one thermocouple for each 0.3 m2
of surface area, up to a maximum of five, uniformly distributed over the area
(one thermocouple being located at the centre of the seal).
(ii) On the surface of the seal 25 mm from the edge of the opening, with one
thermocouple for each 500 mm of the perimeter.
(iii) On the surface of the separating element 25 mm from the edge of the opening,
with one thermocouple for each 500 mm of the perimeter.
(g) Where the service passes through a vertical separating element, one thermocouple of
the pair located on the service 25 mm distant from the element shall be located
uppermost in the vertical plane. Similarly, one thermocouple of each pair on the
element and penetration seal shall be located in the uppermost position in the vertical
plane relative to the service.
(h) For floor waste configurations, where the insulation criterion is applied,
thermocouples shall be fitted to the centre of the grating (unless in the opinion of the
test laboratory another position is likely to record a higher temperature in which case
the thermocouple may be offset from the centre of the grating) and on the separating
element 25 mm from the penetration opening.
DIMENSIONS IN MILLIMETRES
DIMENSION IN MILLIMETRES
10.6 INTEGRITY
In addition to the cotton pads specified in Clause 2.6.1, additional cotton pads shall be
provided with a reduced size of 30 mm × 30 mm × 20 mm. An additional wire frame holder
as described in Clause 2.6.1 modified to accommodate the smaller cotton pad shall also be
provided.
All service penetration systems are deemed to be insulated for the purposes of assessing
integrity and therefore, the cotton pad test is applicable for the duration of the test.
C10.6 Without the cotton wool pad there would be no control over gaps less than 6 mm
around services and the application of grilles with openings less than 150 mm which would
allow fire spread. The introduction of the cotton wool pad test is a relaxation of the existing
requirements.
10.7 INSULATION
10.7.1 General
At the request of the applicant and with the agreement of the testing authority, the
Licensed to Mrs Pat Rogers on 21 September 2009. 1 user personal user licence only. Storage, distribution or use on network prohibited (10056147).
performance of a penetration system with respect to the criterion of insulation failure need
not be evaluated. Under these circumstances, thermocouples on the non-fire side may be
omitted and a zero insulation rating recorded in the test report.
10.7.2 Cable penetrations
If during the test, fissuring of the insulating materials occurs, exposing conductors before
the temperature rise measured on the cables has exceeded 180 K, the temperature of the
exposed conductors shall be measured by a roving thermocouple, provided that the fissure
is wider than 12 mm. This temperature shall be used in the determination of the insulation
rating.
10.8.4 Insulation
Temperatures recorded from thermocouples that become embedded in softening material or
covered by intumescent material shall be disregarded.
10.8.5 Additional observations
Any occurrences in the furnace of any artificial support to a service under test, for example,
if it sags and is supported by the floor or the furnace or another test specimen, shall be
recorded.
(c) Results obtained from framed wall systems may be applied to the performance of a
system in concrete, masonry or solid gypsum blocks of greater or equal thickness to
that of the tested prototype. The reverse does not apply.
(d) Results obtained from framed wall systems may be applied to similar walls having
studs of the same material with sizes greater than the tested prototype.
(e) Results obtained from a prototype test may be applied to framed wall systems of
similar construction but having thicker facings of the same material applied to the
studs.
10.11.3 Metal pipes
10.11.3.1 Sealing systems tested in accordance with Appendix E
The results may be applied to brass pipes of the same composition up to maximum outside
Licensed to Mrs Pat Rogers on 21 September 2009. 1 user personal user licence only. Storage, distribution or use on network prohibited (10056147).
diameter of 101.6 mm (normally 70/30 arsenical brass) and to copper and ferrous metal
pipes having wall thicknesses greater than or equal to those listed in Table 10.11.3.1.
Provided that the same penetration sealing system was used for the above penetrations in
the same type of separating element and all the specimens achieved the required FRL.
TABLE 10.11.3.1
METAL PIPE DEEMED TO HAVE EQUIVALENT
FIRE RESISTANCE LEVELS
Nominal size Actual OD Actual wall thickness
(mm) (mm) (mm)
32 31.75 0.91
40 38.10 0.91
50 50.80 0.91
65 63.50 0.91
80 76.20 1.22
90 88.90 1.22
100 101.60 1.22
125 127.00 1.42
150 152.40 1.63
Results obtained from tests on penetrations through vertical separating elements shall not be
used to assess performance in horizontal elements, and vice versa.
As penetration seals for plastic pipes are dependent for activation upon exposure to fire
conditions, they shall always be installed with the same orientation and fire exposure as was
established in the fire-resistance test.
10.11.5.2 Services not perpendicular to the fire separation
Penetrations not perpendicular to the plane of the element are acceptable provided that the
fire-stopping system has similar exposure and dimensions to the tested prototype.
10.11.6 Control joints
The following variations are permitted:
(a) Results obtained with butt-joints may be applied to contoured joints (see
Licensed to Mrs Pat Rogers on 21 September 2009. 1 user personal user licence only. Storage, distribution or use on network prohibited (10056147).
Figure 10.11.6) provided that, if only one specimen has been tested, the results may
be applied to joints of the same configuration having—
(i) equal width and equal or greater depth of sealant; and
(ii) equal or greater thickness of fire-separating element.
(b) Facings may be applied to the surface of the fire-stopping system.
AS 1530.4—2005
Standards Australia
104
www.standards.com.au
Licensed to Mrs Pat Rogers on 21 September 2009. 1 user personal user licence only. Storage, distribution or use on network prohibited (10056147).
www.standards.com.au
105
Standards Australia
AS 1530.4—2005
AS 1530.4—2005 106
SE C T I ON 1 1 F I RE D A M PE R A N D A I R
T R ANS F E R G R I L L E A SSE M B L I E S
11.1 GENERAL
This Section specifies the procedure for determining the fire resistance of fire dampers and
air transfer grilles that are used to prevent the passage of fire from one fire compartment to
another. It shall be read in conjunction with Section 2.
This Section may also be used to provide data for the assessment of the ability of dampers
to resist the spread of hot smoke, although limiting leakage rate for these purposes are not
specified in this Standard.
This Section does not include the evaluation of smoke control dampers under ambient and
Licensed to Mrs Pat Rogers on 21 September 2009. 1 user personal user licence only. Storage, distribution or use on network prohibited (10056147).
11.3 APPARATUS
11.3.1 General
The test apparatus specified in Clause 11.3.1 to 11.3.7, including the instrumentation, shall
be in accordance with Section 2 except where specifically stated otherwise in
Clauses 11.3.2 to 11.3.8.
An example of a test arrangement is shown in Figure 11.3.1.
www.standards.com.au
107
DIMENSIONS IN MILLIMETRES
Standards Australia
AS 1530.4—2005
AS 1530.4—2005 108
Licensed to Mrs Pat Rogers on 21 September 2009. 1 user personal user licence only. Storage, distribution or use on network prohibited (10056147).
DIMENSIONS IN MILLIMETRES
DIMENSIONS IN MILLIMETRES
www.standards.com.au
111
DIMENSIONS IN MILLIMETRES
Standards Australia
AS 1530.4—2005
AS 1530.4—2005 112
Licensed to Mrs Pat Rogers on 21 September 2009. 1 user personal user licence only. Storage, distribution or use on network prohibited (10056147).
DIMENSIONS IN MILLIMETRES
DIMENSIONS IN MILLIMETRES
DIMENSIONS IN MILLIMETRES
DIMENSIONS IN MILLIMETRES
installed in such a way that it can only be exposed to fire from one side.
If testing is carried out from one side only (that is, one specimen), the reason for one side
testing shall be clearly stated in the report.
11.4.3 Dampers installed in both walls and floors
Dampers that are to be employed in both walls and floors shall be tested in both the vertical
and horizontal orientations.
11.4.4 Dampers installed within a structural opening
Dampers to be positioned within a structural opening shall be tested as shown in
Figure 11.3 when installed in a wall, and as shown in Figure 11.3.2 when installed in a
floor.
11.4.5 Dampers mounted onto face of wall or floor
Uninsulated dampers mounted on a wall or floor and attached to the face of a structure shall
be tested with the damper positioned within the furnace as shown in Figure 11.3.6(C).
Insulated dampers shall be tested from both sides so that the insulation properties of the
damper body and where appropriate the duct can be evaluated. An example of a damper
mounted to the wall/floor outside the furnace is shown in Figure 11.3.6(D).
11.4.6 Dampers remote from wall or floor
11.4.6.1 Within the furnace
Dampers mounted remote from the wall or floor and separate from the structure shall be
attached to a length of ductwork. For test purposes, the duct shall be attached to the
supporting construction with the damper installed at the duct end within the furnace, as
shown in Figure 11.3.6(E). This length of ductwork shall be 150 ±50 mm long and insulated
to the extent necessary to ensure that it remains intact throughout the test. The distance
between the outer surface of the duct and the furnace wall or floor shall be not less than
500 mm.
11.4.6.2 Outside the furnace
For dampers that are to be mounted onto a section of duct outside the furnace, as shown in
Figure 11.3.6(F), the length of duct shall be 500 ±50 mm.
11.4.7 Minimum separation between dampers
Where more than one specimen is to be tested at the same time, the distance between the
dampers shall be not less than 200 mm, as shown in Figure 11.4.7(A). Where the dampers
are mounted in a wall and are not located in the same horizontal plane, the required furnace
pressure shall be determined at the horizontal plane of the lower damper Figure 11.4.7(B).
DIMENSIONS IN MILLIMETRES
DIMENSIONS IN MILLIMETRES
11.5 TEST
11.5.1 Determination of background leakage of connecting duct and measuring
station
The procedure for determining the background leakage of connecting duct and measuring
station is as follows:
(a) Shut the fire damper manually and seal the inlet aperture using impervious material.
(b) Assemble the connecting duct, measuring station and exhaust fan as shown in
Figure 11.3.1 or Figure 11.3.2. The joints between each component shall be well
sealed with high temperature gaskets and/or sealants.
(c) Connect the flow-measuring device to a suitable recording instrument calibrated and
complying with the requirements of ISO 5167-1 and ISO 5221. It may be necessary to
use a different size of orifice plate, venturi or other suitable device for the
determination of the leakage of the connecting duct to that used for the leakage tests
described in Clause 11.5. The leakage shall be calculated from the recorded pressure
differential from the flow-measuring device using the formulae for volume flow rates
given in ISO 5167-1 and ISO 5221 or by calibration.
(d) Adjust the exhaust fan so that the air leakage through the connecting duct and
measuring station can be measured at 200 Pa, 300 Pa, 400 Pa and 500 Pa. The
pressure differential at each value should be maintained for 60 s before the leakage is
recorded.
(e) Plot the values on graph paper or use a regression analysis to determine the leakage at
300 Pa.
Licensed to Mrs Pat Rogers on 21 September 2009. 1 user personal user licence only. Storage, distribution or use on network prohibited (10056147).
(f) If the leakage at 300 Pa is more then 12 m 3/h, improve the sealing of joints and
stability of the test construction until the leakage criterion referred to above can be
met.
(g) Remove the sealing from the inlet aperture of the damper.
11.5.2 Combined fire and leakage test
11.5.2.1 Test set-up
The combined fire and leakage test shall be conducted in accordance with the following:
(a) Subject the damper to 50 opening and closing cycles.
(b) Mount the test specimen onto the furnace with the fire damper in the open position.
(c) Connect all instrumentation required by this Section.
(d) With the damper fully open, set the exhaust fan system to produce an air velocity of
0.15 m/s through the damper. This may be measured by the flow-measuring device
located within the measuring duct. The air velocity shall be maintained to an accuracy
of ±15%.
(e) Switch off the exhaust fan, but leave at its pre-set value given in Clause 11.5.2.1(d).
(f) Ignite the furnace. Start the timing device and switch on all measuring devices.
(g) Switch on the exhaust fan as soon as the furnace has ignited.
(h) When the damper has closed or at 300 s, whichever occurs first, adjust the exhaust
fan to maintain an under-pressure of 300 Pa in the connecting duct, relative to the
furnace.
11.5.2.2 During the test
During the test the following shall be carried out:
(a) Control and record the furnace temperature and pressure in accordance with
Section 2. The furnace pressure at the horizontal centre-line of a vertical damper shall
be maintained at 15 ±3 Pa.
(b) Maintain a pressure differential between the connecting duct and the furnace of
−300 ±15 Pa.
(c) Record the pressure differential across the flow-measuring device and the local gas
temperature at not more than 1 min intervals.
Constants for flow measuring shall be calculated in accordance with ISO 5167-1 over
the range of anticipated gas temperatures. As a function of time and measured gas
temperatures, select the corresponding flow-measuring device constant and calculate
the volume flow rate at the measuring station gas temperatures using the formulae for
volume flow rates given in ISO 5167-1 and ISO 5221.
(d) Record the temperature on the external surface of the connecting duct.
(e) The effect of gaps, orifices or openings on the integrity at the junction between the
supporting construction and connecting duct shall be determined by the use of the
cotton pad and/or gap gauges as defined in Section 2.
(f) Where practicable, record any observations of the general behaviour of the damper
assembly during the test. In practice this will be limited to observations taken on the
furnace side and to the duct/damper junction and on the non-furnace side.
Licensed to Mrs Pat Rogers on 21 September 2009. 1 user personal user licence only. Storage, distribution or use on network prohibited (10056147).
C11.6.2 Tests in accordance with the test method described in ISO 10294-1 were
undertaken on a range of European and North American fire dampers, all of which satisfied
conventional measurements for integrity. It was established that the existing products were
capable of satisfying a leakage limit of 360m3/(h/m 2 ), and this limit was adopted for
evaluation of compliance of integrity using gas flow measurements (E designation). In
relation to smoke leakage, available analytical data was examined, taking into account
such parameters as acceptable concentrations of smoke, required degree of dilution, time
for escape, which led to an acceptable smoke leakage of 200 m3/(h/m2 ) being derived. This
is the limit used for checking compliance with the S designation.
11.6.2.2 Insulation
Only the maximum temperature criterion of Section 2 shall apply, taking into consideration
the temperatures measured by the thermocouples specified in Clause 11.3.5.
11.6.2.3 Leakage
The leakage rate specified in Clause 11.6.2.1(c) shall apply to the assessment of the
potential for fire spread under the criteria for integrity only.
Substantially lower leakage rates may be specified for applications where the damper is
required to resist the spread of hot smoke in addition to resisting the spread of fire.
S E C T I O N 1 2 CR IT I CA L SE RV I CE S
12.1 GENERAL
This Section sets out the procedure for determining the test method for assessing the ability
of systems to protect critical services under fire conditions. It shall be read in conjunction
with Section 2.
This Section is applicable to, but is not limited to, the following services:
(a) Current-carrying cables and busways.
(b) Fibre optical cables.
Licensed to Mrs Pat Rogers on 21 September 2009. 1 user personal user licence only. Storage, distribution or use on network prohibited (10056147).
(f) The minimum clearances between the specimen and the furnace lining or other
specimens shall be at least 200 mm except at the position where the service penetrates
the furnace unless the application being evaluated requires the service or enclosure to
be in contact or in close proximity to the slab (e.g., three-sided exposure).
(g) The specimen shall incorporate access panels if appropriate to the system.
(h) For safety requirements temperature measurements on services shall be taken on (non
active) service(s), which shall be representative of the active services being tested.
For enclosed systems, these services shall be placed within the enclosure and shall
have a minimum length of 500 mm. For coated systems, these services shall be coated
in the same manner as and fixed alongside the active services and shall have a
minimum length of 500 mm.
NOTE: For other services, representative configurations should be selected.
Licensed to Mrs Pat Rogers on 21 September 2009. 1 user personal user licence only. Storage, distribution or use on network prohibited (10056147).
(c) Thermocouples complying with Clause 2.2.4 shall be positioned on each non-active
service on the upper and lower surfaces, at the quarter and mid-span positions as
shown in Figure 12.2 and at any other positions considered to have the potential for
higher heat transfer.
For additional information, the internal temperatures of an enclosure may be
measured at the quarter and mid-span positions and at any other positions considered
to have the potential for higher heat transfer using thermocouples complying with
Clause 2.2.3.
12.4 PRINCIPLE
A specimen is placed in a furnace, and exposed to the standard time-temperature heating
regime (or other regime as selected) and pressure conditions in order to determine the
ability of the system to operate at design capacity under fire conditions.
Licensed to Mrs Pat Rogers on 21 September 2009. 1 user personal user licence only. Storage, distribution or use on network prohibited (10056147).
12.5 PROCEDURE
The procedure shall be as follows:
(a) Mount the test specimens on the slab, forming the roof of the furnace.
(b) Activate services at least 5 min before the commencement of the test if required to be
operational during the test.
(c) Operate furnace in accordance with the test procedures of Section 2.
(d) Record the performance of the protection system and service(s) under test at intervals
of no more than 1 min.
(e) The test may be terminated, subject to agreement between the testing authority and
the test sponsor.
TABLE 12.6
THERMAL FAILURE CRITERIA
Critical temperature,
Service
°C
Steel pipe at design capacity (with pressure relief) 550
Copper pipe at design capacity (with pressure relief) 250
PVC insulated/PVC sheathed power cables at design capacity 75 (see Note)
NOTE: Refer to cable rating for continuous use
TABLE 12.7
TYPICAL RESULTS TO BE REPORTED
Average
Licensed to Mrs Pat Rogers on 21 September 2009. 1 user personal user licence only. Storage, distribution or use on network prohibited (10056147).
APPENDIX A
RADIANT HEAT FLUX MEASUREMENTS
(Informative)
A1 SCOPE
This Appendix provides guidelines on the use of measurements of radiant heat flux emitted
by an element of construction that undergoes the fire-resistance test.
A2 GENERAL
In a fire, radiant heat emitted from the unexposed face of an element of construction can
Licensed to Mrs Pat Rogers on 21 September 2009. 1 user personal user licence only. Storage, distribution or use on network prohibited (10056147).
Alternatively, if what is needed is to limit to a safe value the received radiant heat flux, a
safe distance can be evaluated at which the configuration factor will yield sufficient
attenuation of the emitted radiant heat flux.
Typical radiant heat flux intensities to cause various phenomena are tabulated in Table A3.
TABLE A3
TYPICAL RADIANT HEAT INTENSITIES FOR VARIOUS PHENOMENA
Phenomena kW/m 2
Maximum for indefinite exposure for humans
4
Pain after 10 s to 20 s
Pain after 3 s 10
Licensed to Mrs Pat Rogers on 21 September 2009. 1 user personal user licence only. Storage, distribution or use on network prohibited (10056147).
A4 CONFIGURATION FACTOR
Means for calculating the configuration factor for a specific situation are outlined in Heat
Transfer by Radiation by J H McGuire, DSIR FOC HMSO Special Report No. 2 1953. Two
special cases are as follows:
(a) Circular source with receiver on axis of source and with plane of receiver and source
parallel—
R2
φ= . . . A4(1)
R2 + D 2
where
φ = configuration factor
R = radius of source
D = distance between source and receiver
(b) Rectangular source with receiver on centre-line of source and with plane of receiver
parallel to plane of source—
2 W H H W
φ= tan −1 + tan −1 . . . A4(2)
π
(W 2
+ 4D 2 ) (W 2
− 4D 2 ) (H 2
+ 4D 2 ) (H 2
+ 4D 2 )
where
φ = configuration factor
W = width of source
H = height of source
D = distance between source and receiver
Licensed to Mrs Pat Rogers on 21 September 2009. 1 user personal user licence only. Storage, distribution or use on network prohibited (10056147).
TABLE A5
FACTOR C FOR USE IN THE DETERMINATION OF SAFE DISTANCE
Factor C
Configuration
Aspect ratio
factor
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
0.001 17.8 17.8 17.8 17.8 17.8 17.8 17.8 17.8 17.8 17.8
0.002 12.6 12.6 12.6 12.6 12.6 12.6 12.6 12.6 12.6 12.6
0.003 10.2 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3
0.004 8.82 8.88 8.89 8.89 8.89 8.89 8.89 8.91 8.91 8.91
Licensed to Mrs Pat Rogers on 21 September 2009. 1 user personal user licence only. Storage, distribution or use on network prohibited (10056147).
0.005 7.88 7.93 7.94 7.95 7.95 7.95 7.96 7.96 7.96 7.96
0.006 7.16 7.23 7.25 7.25 7.26 7.26 7.26 7.26 7.27 7.27
0.007 6.62 6.68 6.70 6.71 6.71 6.72 6.72 6.72 6.72 6.72
0.008 6.17 6.24 6.26 6.26 6.28 6.28 6.28 6.28 6.28 6.28
0.009 5.80 5.87 5.89 5.90 5.91 5.91 5.92 5.92 5.92 5.92
0.010 5.50 5.56 5.59 5.60 5.60 5.60 5.61 5.61 5.61 5.61
0.020 3.78 3.88 3.92 3.93 3.94 3.94 3.94 3.94 3.94 3.94
0.030 3.00 3.13 3.17 3.18 3.19 3.20 3.20 3.20 3.21 3.21
0.040 2.53 2.67 2.71 2.74 2.75 2.75 2.76 2.76 2.76 2.76
0.050 2.20 2.35 2.40 2.43 2.44 5.45 2.45 2.45 2.46 2.46
0.060 1.95 2.12 2.17 2.20 2.21 2.22 2.23 2.23 2.23 2.23
0.007 1.76 1.93 1.99 2.02 2.03 2.04 2.05 2.05 2.05 2.05
0.080 1.60 1.78 1.85 1.87 1.89 1.90 1.90 1.91 1.91 1.91
0.090 1.47 1.66 1.72 1.75 1.77 1.78 1.78 1.79 1.79 1.79
0.100 1.35 1.55 1.62 1.65 1.67 1.68 1.68 1.69 1.69 1.69
0.200 0.75 0.94 1.02 1.07 1.09 1.11 1.12 1.12 1.12 1.12
0.300 0.50 0.66 0.75 0.79 0.82 0.84 0.85 0.85 0.85 0.86
0.400 0.36 0.49 0.57 0.62 0.65 0.66 0.67 0.68 0.68 0.68
0.500 0.27 0.38 0.45 0.49 0.52 0.54 0.55 0.55 0.56 0.56
0.600 0.21 0.29 0.35 0.39 0.42 0.43 0.44 0.45 0.45 0.45
0.700 0.16 0.23 0.27 0.31 0.33 0.34 0.35 0.36 0.36 0.36
0.800 0.12 0.17 0.20 0.23 0.25 0.26 0.27 0.27 0.28 0.28
0.900 0.08 0.11 0.13 0.15 0.16 0.17 0.18 0.18 0.18 0.18
APPENDIX B
ALTERNATIVE AND ADDITIONAL TEST PROCEDURES FOR ELEMENTS OF
CONSTRUCTION
(Informative)
B1 SCOPE
This Appendix provides alternative heating conditions and other procedures, which may
need to be adopted to evaluate the performance of elements of construction under fire
conditions when specified by the applicant. It should be read in conjunction with Section 2.
In circumstances where the alternative and additional test procedures for elements of
Licensed to Mrs Pat Rogers on 21 September 2009. 1 user personal user licence only. Storage, distribution or use on network prohibited (10056147).
construction are applicable, the procedures set out in this Appendix should be adopted and
read in conjunction with this Standard.
The additional procedures contained in this Appendix fall into the following categories:
(a) Alternate heating regimes/exposure conditions.
(b) Additional measurements to provide data to assess compliance with other Standards
and/or provide data for fire safety engineering purposes.
(c) Supplementary test methods.
Since the use of alternate solutions is optional and methods of demonstrating compliance
are subject to approval by the relevant regulatory authorities, this Appendix has been
classified as informative.
An idealized time/temperature curve for the enclosure of fire origin is shown in
Figure B2(A). For simplicity, the fire can be characterized into the following phases:
(a) Establishment phase—slow heating where radiative feedback from the hot layer is
relatively low (typically below 200°C). The period of the establishment phase can
vary from less than 1 min to several hours depending upon fuel and ignition sources,
enclosure size, etc. Most fires will never progress beyond the establishment phase due
to self-extinguishment/manual or automatic fire suppression. The slow heating
establishment phase fire may be adopted to assess barriers under these conditions
(b) Rapid growth phase—typically where radiative feedback increases rapidly which if
Licensed to Mrs Pat Rogers on 21 September 2009. 1 user personal user licence only. Storage, distribution or use on network prohibited (10056147).
the fire progresses unchecked may quickly lead to flashover (the transition from a
localized fire to general conflagration within the compartment when all fuel surfaces
are burning).
(c) Fully developed phase—general conflagration within the compartment when all fuel
surfaces are burning
(d) Decay phase—commonly defined as the period when the average enclosure
temperature has decreased to 80% of its peak.
The standard fire resistance test heating regime and/or the hydrocarbon heating regime may
be used to provide data to assess the performance of barriers during the rapid growth, fully
developed and decay phases.
The Hydrocarbon and slow heating regimes specified in this Appendix are shown in
Figure B2(B).
NOTE: The hydrocarbon heating regime is based on EN 1363.2; however, the equivalent regimes for slow
heating/external exposure specified in EN 1363 Part 2 were not considered appropriate or consistent with the
BCA and Australian building/design practices for the particular applications. Therefore, more appropriate
regimes have been specified.
B3 ADDITIONAL MEASUREMENTS
Requirements for the following additional measurements are included
(a) Radiant heat from the non-fire-exposed face of specimens.
(b) Radiant heat exposure measurements during fire-resistance tests.
(c) Furnace plate thermocouple measurements for compatibility with ISO 834.
B5 HYDROCARBON CURVE
B5.1 General
Section 2 defines the heating conditions, in terms of a specified temperature-time
relationship, for the determination of fire resistance.
It is recognized that, whilst the heating conditions specified are related to those occurring in
real fires, it is not the intent to define an ‘average’ fire for universal application but
generally to rank elements of construction for regulatory purposes. In some practical cases
it is possible to identify scenarios where significant variation from the standard conditions
could exist.
One such example is in the petrochemical and offshore oil industries where there is a threat
of exposure to very intense fires such as liquid pool fires or well-insulated buildings
containing modern furnishings. Such fires are characterized by higher temperatures and a
rapid rate of growth.
Where there is an identified requirement for such a fire exposure, the following
hydrocarbon curve should be considered.
NOTE: If a form of construction has been tested to the hydrocarbon and standard heating regimes,
it may be possible to model the performance of the barrier to enable interpolation of results for
intermediate exposure conditions.
Many modern fully developed fires in buildings and industrial applications are
characterized by a very rapid growth to temperatures significantly higher than those
specified for the standard fire resistance test. The times to failure from the fire resistance
test cannot therefore be applied directly to time lines for fire scenarios when evaluating an
Licensed to Mrs Pat Rogers on 21 September 2009. 1 user personal user licence only. Storage, distribution or use on network prohibited (10056147).
alternative solution. Since heat transfer during a fully developed fire is likely to be
predominately by radiation and will, therefore, vary approximately in proportion to
temperature to the power four, substantial reductions in performance of elements of
construction would be expected. In addition some elements of construction may be
susceptible to thermal shock.
The hydrocarbon heating curve has been included to provide a means for the evaluation of
elements of construction under more rapid heating conditions.
B5.2 Expression of temperature-time curve
A temperature-time curve to be designated as the hydrocarbon curve is to be defined by the
following expression:
[
T = 1080 1 − 0.325e −0.167 t − 0.675e −2.5t + 20] . . . B5(1)
where
t = time from start of test, in minutes
T = average required furnace temperature, in degrees centigrade
See Figure B2(B).
B5.3 Tolerances
The percentage deviation (de) in the area of the curve of the average temperature recorded
by the specified furnace thermocouples versus time from the area of the specified
temperature-time curve should be within—
(a) 15% .....................................................................................................for 5 < t < 10.
(b) (15 – 0.5 (t-10))%...............................................................................for 10 < t < 30.
(c) (5 − 0.083 (t-30))%.............................................................................for 30 < t < 60.
(d) 2.5% ......................................................................................................... for t > 60.
where
A − AS . . . B5(2)
de × 100
AS
de = percentage deviation
A = area under the actual furnace temperature-time curve
A S = area under the specified temperature-time curve
t = time, in minutes
All areas are to be computed by the same method, that is, by the summation of areas at
intervals not exceeding 1 min and should be calculated from time zero.
At any time after the first 10 min of test, the temperature recorded by any thermocouple in
the furnace should not differ from the corresponding temperature of the specified
temperature-time curve by more than 100ºC.
For test specimens that burn rapidly, a deviation in excess of 100ºC above the specified
temperature/time curve may be exceeded for a period not in excess of 10 min provided that
such excess deviation is clearly identified as being associated with the sudden ignition of
significant quantities of combustible materials increasing the gas temperature in the
furnace.
B5.4 Expression of results
The fire performance determined when exposed to the hydrocarbon fire should be expressed
Licensed to Mrs Pat Rogers on 21 September 2009. 1 user personal user licence only. Storage, distribution or use on network prohibited (10056147).
in a statement as follows:
‘Fire performance of the building element when exposed to hydrocarbon curve—
(a) structural adequacy xx minutes;
(b) integrity yy minutes; and
(c) insulation zz minutes.
NOTE: An alternate heating regime to the standard heating regime specified in Section 2 has
been adopted. The results above should not be used as evidence of performance when subjected to
the standard heating regime.
The percentage deviation (de) in the area of the curve of the average temperature recorded
by the specified furnace thermocouples versus time from the area of the specified
temperature-time curve should be within—
(a) 15% .....................................................................................................for 5 < t < 10.
(b) (15 – 0.5 (t-10))%...............................................................................for 10 < t < 30.
(c) (5 − 0.083 (t-30))%.............................................................................for 30 < t < 60.
(d) 2.5% ......................................................................................................... for t > 60.
where
A − AS . . . B6(3)
de × 100
AS
de = percentage deviation
A = area under the actual furnace temperature-time curve
A S = area under the specified temperature-time curve
t = time, in minutes
All areas are to be computed by the same method, that is, by the summation of areas at
intervals not exceeding 1 min and are to be calculated from time zero.
At any time after the first 10 min of test, the temperature recorded by any thermocouple in
the furnace should not differ from the corresponding temperature of the specified
temperature-time curve by more than 100ºC.
The performance determined when exposed to the establishment phase fire is to be
expressed in terms contained in Paragraph B3.4.
B6.4 Expression of results
The fire performance determined when exposed to the slow heating establishment phase fire
for barrier systems should be expressed in a statement as follows:
‘Fire performance of the building element when exposed to slow heating establishment
phase fire for barrier systems—
(a) structural adequacy xx minutes; and
(b) integrity yy minutes; and
(c) insulation zz minutes.’
NOTE: An alternate heating regime to the standard heating regime specified in Section 2 has
been adopted. The results above should not be used as evidence of performance when subjected to
the standard heating regime.
construction to radiant heat when evaluating their resistance to fire spread rather than rely
on exposure to furnace conditions.
Typical examples of the application of this method would be external walls to buildings
close to fire source features and the external facades of buildings exposed to bushfires
where vegetation has been cleared around the perimeter of a building reducing the potential
for direct flame impingement.
The BCA verification methods CV1 and CV2 recognize such an approach by specifying that
openings in external walls must be able to resist nominated radiant heat fluxes depending
upon the proximity to a fire source feature.
This method provides a means of generating data in a consistent manner in order to assess
the performance of elements of construction exposed to radiant heat, which could be used in
part to assess compliance with CV1 and CV2.
B7.2 General description of the apparatus
The test apparatus is to comprise the following:
(a) A fire resistance furnace with a sheet steel closure or equivalent forming a radiant
heat source at least 3 m × 3 m. If the plate extends beyond the furnace enclosure, the
external face is to be insulated by 25 mm thick ceramic fibre blanket. The steel sheet
is to be stiffened to prevent excessive distortion.
(b) An insulated test frame to house a representative section of wall at least 3 m × 3 m
constructed in accordance with Section 3 but with a central mounting provided for a
radiometer to measure the incident radiation at approximately the centre of the
specimen.
(c) Shielding panels to prevent exposure of personnel to radiant heat.
B7.3 Instrumentation
B7.3.1 Furnace temperature measurements
The furnace temperature is to be measured using Type K thermocouples as prescribed in
Section 2.
B7.3.2 Furnace pressure measurements
The furnace pressure need not be measured since it is not a critical component of the test.
B7.3.3 Specimen temperatures
Surface temperatures on the non-fire side of each specimen are to be measured in
accordance with Section 3.
Prior to commencement of the test the furnace is to be preheated with the specimen shielded
from the radiant heat to ensure the rate of increase of radiant heat specified in
Paragraph B4.4.2 can be achieved.
B7.4.2 Specimen exposure
The set-up panel is to be removed and the test assembly progressively moved towards the
furnace such that the radiant heat flux 5 min, after the start of the test, is 75 ±5% of the
prescribed level and 10 min after the start of the test is maintained at the prescribed radiant
heat flux ±5% for the remainder of the test period. After 10 min, the exposed face of the
specimen should be maintained at a distance of 300 ±150 mm from the initial plane of the
radiant panel to ensure a substantial proportion of the specimen is exposed to the prescribed
radiant heat flux.
Precautions should be taken to ensure personnel are not exposed to hazardous conditions.
The furnace temperature is to be controlled, so that the heat flux measured at the centre of
the panel is maintained within the prescribed radiant heat flux limits.
The average radiant heat flux at the centre of the specimen during the test period after the
first 10 min is to be equal to the prescribed radiant heat flux ±5.0%.
B7.4.3 Observations
Temperature data and the radiant heat flux should be recorded at a maximum of 60 s
intervals to the levels of accuracy as defined in this Standard and ISO 834.
Any significant visible event is to be recorded.
B7.4.4 Exposure conditions
The heat flux is to be agreed between the laboratory and the applicant prior to
commencement of the test. The levels given in Table B7.4.4 have been extracted from the
BCA for a building element at a specified distance from a boundary or another building on
the same allotment.
TABLE B7.4.4
HEAT FLUX
Location Heat flux (kW/m 2 )
On boundary 80
1 m from boundary 40
3 m from boundary 20
6 m from boundary 10
0 m between buildings 80
2 m between buildings 40
6 m between buildings 20
Licensed to Mrs Pat Rogers on 21 September 2009. 1 user personal user licence only. Storage, distribution or use on network prohibited (10056147).
12 m between buildings 10
0.7 ±0.1 mm thick nickel alloy sheet strips folded to the design as shown in Figure B6.1.
The measuring junction is to consist of nickel chromium/nickel aluminium (Type K) wire as
defined in IEC 60584-1, contained within mineral insulation in a heat-resisting steel alloy
sheath of nominal diameter 1 mm, the hot junctions being electrically insulated from the
sheath. The thermocouple hot junction is to be fixed to the geometric centre of the plate in
the position shown in Figure B6.1 by a small steel strip made from the same material as the
plate. The steel strip can be welded to the plate or may be screwed to it to facilitate
replacement of the thermocouple. The strip should be approximately 18 mm by 6 mm if it is
spot-welded to the plate, and nominally 25 mm by 6 mm if it is to be screwed to the plate.
The screw is to be 2 mm in diameter.
The assembly of plate and thermocouple should be fitted with a pad of inorganic insulation
material 97 ±1 mm by 97 ±1 mm by 10 ±1 mm thick, density 280 ±30 kg/m 3 .
Before the plate thermometers are first used, the complete plate thermometer is to be aged
by immersing in a pre-heated oven at 1 000°C for 1 h.
NOTE: Exposure in a fire resistance furnace for 90 min under the standard time-temperature
curve is considered to be an acceptable alternative to using an oven. When a plate thermometer is
used more than once, a log of its use should be maintained indicating, for each use, the checks
made and duration of use. The thermocouple and the insulation pad should be replaced after 50 h
of exposure in the furnace.
At the commencement of the test the plate thermometers should be 100 ±50 mm from the
exposed face of the test construction and they should be maintained at this distance during
the test, as far as possible.
The method of support should ensure that plate thermometers do not fall away or become
dislodged during the test.
At the commencement of the test, the furnace is to include at least the number of plate
thermometers (n) that are required by the specific test method. If plate thermometers fail so
that they are n − 1 in the furnace, then the laboratory need take no action. If the number
falls below n − 1 during the test then the laboratory is to replace these to ensure that at least
n − 1 are present.
Plate thermometers are resistant to damage but are subject to damage by falling debris and
deteriorate in continued use, becoming slightly less sensitive with age. Before every test
Licensed to Mrs Pat Rogers on 21 September 2009. 1 user personal user licence only. Storage, distribution or use on network prohibited (10056147).
they are to be inspected and checked for proper operation. If there is any evidence of
damage, deterioration or improper operation, they should not be used and should be
replaced.
The support for the plate thermometers should not penetrate or be attached to the specimen
unless the specific requirements for the position of the measuring junction cannot otherwise
be ensured. If the support for the measuring junction has penetrated or been attached to the
specimen, it is to be arranged so as to have minimal effect on the behaviour of the specimen
in relation to the relevant failure criteria or the supplementary information being
determined.
APPENDIX C
GUIDELINES FOR THE ATTACHMENT OF SPECIMEN THERMOCOUPLES
(Informative)
C1 INTERNAL THERMOCOUPLES
C1.1 General
Where information is required about the temperatures reached by individual components or
parts of a specimen within its construction, thermocouples of the appropriate type and
design, to suit the type of measurement to be made, should be chosen.
Licensed to Mrs Pat Rogers on 21 September 2009. 1 user personal user licence only. Storage, distribution or use on network prohibited (10056147).
C1.2 Specification
Internal thermocouples for measuring cavity temperatures within test specimens or of
temperatures within materials such as concrete, steel, timber, etc., should be made from
double glass-fibre-insulated bare wire with wires of diameter 0.5 mm and crimped or
welded junctions. The wires should remain insulated as close as possible to the junction.
Any bare wires should be kept as far apart as possible to minimize electrolytic effects. They
should be used once only.
C1.3 Fixing methods and positioning
Appropriate methods should be adopted for fixing the measuring junctions securely to the
components or the construction so that the thermal behaviour is not greatly disturbed.
For example, a junction can be peened to a heavy metal section by drilling a hole in the
section only slightly larger in diameter than the thermocouple junction and deep enough to
accommodate the junction below the surface. The junction may be inserted into the hole and
burred over the edge of the hole with a punch to retain the wires in position. Alternatively,
the hot junction may be welded to the section.
A similar junction may be attached to small metal components, such as screws or wires, by
wrapping the tail around the component. In these applications the first contact between the
pair of thermocouple wires has to be close to the surface whose temperature is being
measured. The thermal contact can be improved by applying a little solder, which will
remain effective even at temperatures above its melting point.
The thermal contact may be made by inserting the junction and the insulated leads into a
hole with a suitable material of similar properties. Junctions and their leads may also be
cast in to materials such as concrete.
The wires from the junctions should, where possible, be taken along an isotherm for a
distance of at least 50 mm and then to the outside of the specimen in such a way that they
do not experience temperatures higher then the hot junction. There should be no joint or
junction made in the wires until they emerge from the specimen.
The thermocouple wires should be protected against—
(a) excessive temperature rise;
(b) condensation;
(c) short circuiting by any aspect of the specimen construction or resulting from the
heating conditions of test; and
(d) damage resulting form the deformation of the specimen during the test.
construction is to staple them through the pad into the timber. Care should be taken that the
staples do not go through the disc or thermocouple wires or contact them in any way.
Alternatively, a water-based ceramic cement may be used as for attaching to steel
constructions above.
C2.2.8 Surfaces with applied finishes
Where a thermocouple is to be placed on a surface with a thin surface finish, e.g., paint, it is
recommended that the surface finish is removed with an abrasive before fixing the
thermocouple.
C2.2.9 Surfaces subject to swelling
The critical epoxy and resorcinol adhesive are useful for avoiding gaps and conforming to a
curved surface. A thermocouple wire would render the surface at a shallow angle and
provide a slight pressure, thus allowing for swelling and flowing.
APPENDIX D
ELECTRICAL AND COMMUNICATIONS CABLES
(Informative)
AS 1530.4—2005
Standards Australia
148
DIMENSIONS IN MILLIMETRES
www.standards.com.au
Licensed to Mrs Pat Rogers on 21 September 2009. 1 user personal user licence only. Storage, distribution or use on network prohibited (10056147).
www.standards.com.au
149
Standards Australia
AS 1530.4—2005
AS 1530.4—2005 150
APPENDIX E
TEST PROGRAM FOR SEALING SYSTEMS PROTECTING METAL PIPE
PENETRATIONS
(Informative)
The following test program is recommended for use for sealing systems protecting metal
pipe penetrations of various materials wall thickness and outside diameter (OD):
(a) Service A Copper pipe, nominal diameter 150 mm, actual OD 152.4 mm and wall
thickness 1.63 mm, or nominal diameter 200 mm, actual OD 203.2 mm and wall
thickness 2.03 mm.
(b) Service B Brass pipe, nominal diameter 100 mm, actual OD 101.65 mm, wall
Licensed to Mrs Pat Rogers on 21 September 2009. 1 user personal user licence only. Storage, distribution or use on network prohibited (10056147).
APPENDIX F
FIRE-RESISTANT DOORSETS
(Informative)
F1 TESTING IN ADVANCE
Where an application is to be made to a regulatory authority for approval to use fire-
resistant doorsets of a particular design for the protection of openings in walls, the
specimen doorset should be tested in a wall agreed in advance by a registered testing
authority as being indicative of the doorset’s potential when ultimately mounted in its
intended location.
Licensed to Mrs Pat Rogers on 21 September 2009. 1 user personal user licence only. Storage, distribution or use on network prohibited (10056147).
F3 PILOT TESTS
For pilot tests, where the purpose of the test is to validate a variation, the direction of fire
exposure and the specimen mounting may differ from the provisions at full scale. In each
instance the mounting and direction may be arranged to gather data needed for the
validation, subject to each feature under examination for the least favourable conditions.
APPENDIX G
REVIEW OF AS 1530.4—1997
(Informative)
G1 GENERAL
The review of AS 1530.4 for this edition considered many factors and issues including
development of international Standards, such as ISO 834, and the referencing of AS 1530.4
in the BCA.
The following information was included in the Public comment Draft, DR 04100, issued on
18 February 2004 and is included for information and future reference.
Licensed to Mrs Pat Rogers on 21 September 2009. 1 user personal user licence only. Storage, distribution or use on network prohibited (10056147).
TABLE G1
SPECIFIC CONSIDERATIONS AND IMPACT ASSESSMENT OF THE REVISED
AS 1530.4—1997
Potential negative
Clause Description/Reason Benefit
impact
General AS 1530.4 has retained a single Lower production costs Increase in price of
document format unlike making AS 1530.4 cheaper to the Standard due to its
ISO/European Standards that purchase for all users and larger size. However,
publish approximately 10 reduces the risk of a part of this represents a
Standards to cover the same the Standard being unavailable fraction of the cost of
material; however, the page to a user when required. the ISO suite of
numbers of AS 1530.4 have Improved clarity and Standards
Licensed to Mrs Pat Rogers on 21 September 2009. 1 user personal user licence only. Storage, distribution or use on network prohibited (10056147).
TABLE G1 (continued)
Potential negative
Clause Description/Reason Benefit
impact
2.6 Inclusion of cotton pad test to be Consistent method of judging Potentially slightly
consistent with international integrity performance of all less onerous for most
Standards and provide an elements of construction elements since a very
appropriate method for assessing small through-gap
the risk of fire spread due to may not cause ignition
integrity failure. of a cotton pad. The
impact on industry
Current and previous editions of Clearer specification of and life safety due to
AS 1530.4 did not give clear integrity failure criteria this relaxation is
advice on assessing integrity leading to consistent expected to be
performance, which has led to application/interpretation minimal. The criteria
different interpretations being
is more onerous for
Licensed to Mrs Pat Rogers on 21 September 2009. 1 user personal user licence only. Storage, distribution or use on network prohibited (10056147).
TABLE G1 (continued)
Potential negative
Clause Description/Reason Benefit
impact
2.12 Criteria of failure: Limiting Improved repeatability of None
deflections and rates introduced testing for structural adequacy
for consistent assessment of
Structural Adequacy in line with
international Standards.
See Clause 2.6 for introduction of
cotton pad test for integrity
Clarification of failure criteria for Clear specification of None
radiation, which required radiation criteria in one place
reference to BCA and AS 1530.4
and some interpretation to
Licensed to Mrs Pat Rogers on 21 September 2009. 1 user personal user licence only. Storage, distribution or use on network prohibited (10056147).
TABLE G1 (continued)
Potential negative
Clause Description/Reason Benefit
impact
Section 4 More detailed description of Greater consistency between None
method of test for floors roofs laboratories
and ceilings
Use of standard thermocouples in The failure criteria is None
lieu of thermocouples attached to unchanged; however, the
timber blocks and modification of determination of incipient
incipient spread of fire criteria spread has been modified to
for failure to simplify test improve repeatability
procedures
Inclusion of permissible Greater efficiency of None
variations regulatory assessment
Licensed to Mrs Pat Rogers on 21 September 2009. 1 user personal user licence only. Storage, distribution or use on network prohibited (10056147).
TABLE G1 (continued)
Potential negative
Clause Description/Reason Benefit
impact
Section 9 The test specification has been Greater consistency between None
clarified laboratories
An internal airflow has been Greater consistency between None
specified for ducts under external laboratories and more efficient
fire conditions to simulate a duct designs
supply air application. This
approach had been adopted on an
ad-hoc basis leading to
differences in reporting
requirements and result
interpretations
Licensed to Mrs Pat Rogers on 21 September 2009. 1 user personal user licence only. Storage, distribution or use on network prohibited (10056147).
TABLE G1 (continued)
Potential negative
Clause Description/Reason Benefit
impact
Section 12 A new section has been provided The resulting classification of None
for the protection of critical critical services will depend
services. This has been added on the actual properties of the
because applications occur where material being protected and is
services need to carry out a consistent with a performance-
critical function during a fire based building code approach.
emergency. These are quite The provision of the test
common when major method will facilitate the
refurbishments are being evaluation of protection
undertaken as well in as new systems providing cost
buildings. A simple specification effective solutions
of construction having an FRL of
Licensed to Mrs Pat Rogers on 21 September 2009. 1 user personal user licence only. Storage, distribution or use on network prohibited (10056147).
BIBLIOGRAPHY
AS 1428.1 Design for access and mobility, Part 1: General requirements for
access—New building work
AS 1720.4 Timber structures, Part 4: Fire resistance of structural timber
members
AS 1735.11 Lifts, escalators and moving walks, Part 11: Fire rated landing doors
AS 3600 Concrete structures
Licensed to Mrs Pat Rogers on 21 September 2009. 1 user personal user licence only. Storage, distribution or use on network prohibited (10056147).
Standards Australia
Standards Australia is an independent company, limited by guarantee, which prepares and publishes
most of the voluntary technical and commercial standards used in Australia. These standards are
developed through an open process of consultation and consensus, in which all interested parties are
invited to participate. Through a Memorandum of Understanding with the Commonwealth government,
Standards Australia is recognized as Australia’s peak national standards body. For further information
on Standards Australia visit us at
www.standards.org.au
Australian Standards
Australian Standards are prepared by committees of experts from industry, governments, consumers
and other relevant sectors. The requirements or recommendations contained in published Standards are
a consensus of the views of representative interests and also take account of comments received from
other sources. They reflect the latest scientific and industry experience. Australian Standards are kept
under continuous review after publication and are updated regularly to take account of changing
technology.
International Involvement
Standards Australia is responsible for ensuring that the Australian viewpoint is considered in the
formulation of international Standards and that the latest international experience is incorporated in
national Standards. This role is vital in assisting local industry to compete in international markets.
Standards Australia represents Australia at both ISO (The International Organization
for Standardization) and the International Electrotechnical Commission (IEC).
Electronic Standards
All Australian Standards are available in electronic editions, either downloaded individually from our web
site, or via On-Line and DVD subscription services. For more information phone 1300 65 46 46 or visit
Standards Web Shop at
www.standards.com.au
Licensed to Mrs Pat Rogers on 21 September 2009. 1 user personal user licence only. Storage, distribution or use on network prohibited (10056147).