1) The document discusses input and output profiles for data points in a power system. 2) Input profiles include profiles for single point status (SPS), double point status (DPS), and multi point status (MPS) data points, which define states, labeling, archiving, and alarm settings. 3) Output profiles include profiles for single point controls (SPC) and define similar configuration options as the input profiles.

Uploaded by

PABITRA PATRA
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
4K views24 pages

03-Datapoints Profiles - Rev G

1) The document discusses input and output profiles for data points in a power system. 2) Input profiles include profiles for single point status (SPS), double point status (DPS), and multi point status (MPS) data points, which define states, labeling, archiving, and alarm settings. 3) Output profiles include profiles for single point controls (SPC) and define similar configuration options as the input profiles.

Uploaded by

PABITRA PATRA
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 24

Datapoints Profiles

DS Agile Training Level 2


Global Systems Engineering
03/05/2012

GRID

GSE
SAM
Summary

1) Generalities Page 3

2) Inputs Profiles Page 6

3) Outputs Profiles Page 19

GSE
L2-03-DATAPOINTS PROFILES - Rev G - P 2
1.1) SCE Profiles : Input Profiles

Supervision Profiles … What are Supervision DataPoint?

xPS SPS, SPS_Profile FSS, SBMC dependency


DPS, DPS_Profile Few acquisition options
MPS, MPS_Profile
MV State labels
MV, MV_Profile
FOR Archive&Logging/state
(6)
xCT Interlock boolean/state
Counter, Counter_Profile
Alarm/state

GSE
L2-03-DATAPOINTS PROFILES - Rev G - P 3
1.2) SCE Profiles : Output Profiles

Control Profiles … What are Control DataPoint?

xPC SPC, SPC_Profile DE / SBO


DPC, DPC_Profile Few acquisition options

SetPoint State labels


SetPoint, SetPoint_Profile
FOR Archive&Logging on event
(6)
Interlock boolean / state

Alarm on Negative Ack.

GSE
L2-03-DATAPOINTS PROFILES - Rev G - P 4
Summary

1) Generalities Page 3

2) Inputs Profiles Page 6

3) Outputs Profiles Page 19

GSE
L2-03-DATAPOINTS PROFILES - Rev G - P 5
2.1) xPS Profiles (1)

Single, Double, Multi Point Status : General Tab


Allow FSS on DP Initial Status
Yes/No For software info => status at start-up
No Never use Motion

Allow SBMC on DP Toggling Filtering for SPS, DPS


(Yes/No) Yes/No
when bay has SBMC ON :
SBMC Substitute value to RCP
SPS : Set/Reset/Suppressed
DPS : Jammed/Open/Close/Suppressed
MPS : Undefined/Suppressed
GSE
L2-03-DATAPOINTS PROFILES - Rev G - P 6
2.1) xPS Profiles (2)

Single, Double, Multi Point Status : State Labels tab : Alarms / Log Print
SPS : Set/Reset
DPS : Jammed/Open/Close/Undefined
MPS : 1 among N(<16) State0..State15/
Undefined

All Invalid States or FSS Label


1) Labels are Business Language dependant
2) On OI : printer and viewers labels are concatenation of
Force/Substitute & Value (open/close) : “forced open”
3) Profile is linked to DP then words can change
DPS Switch gear => Open/Close
R/L => Remote/Local
MPS N and associate DP impact labels GSE
L2-03-DATAPOINTS PROFILES - Rev G - P 7
2.1) xPS Profiles (3)

Single, Double, Multi Point Status : State Treatment Tab (1)


State by State, archiving policy
For OI :
- No Archive, No logging = nothing in SQL Historian database
- Archive only = all states in VTQ (states/values) SQL Historian database tables (Trend Viewer)
- Archive & Logging = all states in VTQ (states/values) SQL Historian database tables + states marked with
“Logging” in Events SQL database table (Event Viewer + Archive viewer + printer)

GSE
L2-03-DATAPOINTS PROFILES - Rev G - P 8
2.1) xPS Profiles (4)

Single, Double, Multi Point Status : State Treatment Tab (2)

For C264 :
- Archive & Logging = Archive means stored in event list (2048 events in memory) & Logging means
displayed in event list of front face (200 events).

GSE
L2-03-DATAPOINTS PROFILES - Rev G - P 9
2.1) xPS Profiles (5)

Single, Double, Multi Point Status : Interlock tab : Boolean value by state
SPS Set and Reset Boolean value in all PSL and interlockings :
convention : SET=TRUE, RESET=FALSE

DPS Jammed, Open and Closed Boolean value in all PSL and interlockings :
convention : CLOSED=TRUE, OPEN=FALSE, JAMMED=INVALID, UNDEFINED = INVALID

Note : For MPS, no convention => depends on context of use

GSE
L2-03-DATAPOINTS PROFILES - Rev G - P 10
2.1) xPS Profiles (6)

Single, Double, Multi Point Status : Alarm tab, Alarm definition state by
state
Delay before alarm generation
Alarm not generated
(if DP reset for example)
if state follow control (RFI SBUS)
Gravity 1->5
Audibility (klaxon)

Alarm Generation Alarmed state or not Alarms are acknowledged by


Appearance/Appearance disappearance operator, but clearing can be manual
1 / 2 alarms or automatic

GSE
L2-03-DATAPOINTS PROFILES - Rev G - P 11
2.2) MV Profile (1)

Measurement Values : General tab

Allow FSS on MV No Allow SBMC on MV


Yes/No (Yes/No)
(when bay in SBMC ON)
Substitutes values by Suppressed

MV value display on OI Mimic


No # after decimal
U to display unit
GSE
L2-03-DATAPOINTS PROFILES - Rev G - P 12
2.2) MV Profile (2)

Measurement Values : State Labels tab Alarms / Log /Print

IED disconnected Board acquisition saturated Threshold violation

Digital Measurement coding error 4-20mA DC input when under


4mA

GSE
L2-03-DATAPOINTS PROFILES - Rev G - P 13
2.2) MV Profiles (3)

Measurement Values : State Treatment Tab


State by State, archiving policy
For OI :
- No Archive, No logging = nothing in SQL Historian database
- Archive only = all states in VTQ (states/values) SQL Historian database tables (Trend Viewer)
- Archive & Logging = all states in VTQ (states/values) SQL Historian database tables + states marked
with “Logging” in Events SQL database table (Event Viewer + Archive viewer + printer)

Note :
- Archive only for valid => value will be available for trend viewer
- Archive & Logging for SelfCheckFlt and Unknown to store acquisition errors
GSE
L2-03-DATAPOINTS PROFILES - Rev G - P 14
2.2) MV Profile (4)

Measurement Values : Interlocking tab

Note : Goal is use MV associated status in PSL.


No convention => depends on context of use

GSE
L2-03-DATAPOINTS PROFILES - Rev G - P 15
2.2) MV Profile (5)

Measurement Values : Alarm Management tab


Alarm Generation Alarmed state or not
Appearance/Appearance disappearance
1 / 2 alarms

Alarms are acknowledged by


Delay before alarm generation operator, but clearing can be manual
Gravity 1->5 or automatic
Audibility (klaxon)

GSE
L2-03-DATAPOINTS PROFILES - Rev G - P 16
2.2) MV Profile (6)

Measurement Values : Mean Value tab cf. PS06


Reference hour :
-Hour of daily min/max/average values calculation
-Daily mean values stored in monthly VTQ table for 15
.csv VTQ tables month.
SQL
HISTORIAN 35 days storing
Daily
VTQ

SQL
HISTORIAN Monthly 15 months storing
Event

Yearly 5 years storing


Reference day :
-Day of monthly min/max/average values calculation
-Monthly mean values stored in yearly VTQ table for
about 5 Years

GSE
L2-03-DATAPOINTS PROFILES - Rev G - P 17
2.3) Counter Profile

Single, Double CounTer: Status…  Like MV Except :

Pulse value
multiplicative coefficient

Counter over max value

Double Counter invalidity

GSE
L2-03-DATAPOINTS PROFILES - Rev G - P 18
Summary

1) Generalities Page 3

2) Inputs Profiles Page 6

3) Outputs Profiles Page 19

GSE
L2-03-DATAPOINTS PROFILES - Rev G - P 19
3.1) xPC Profiles (1)

Single, Double Point Control: General tab

Define SBUS control sequence in one or two steps :


In DE : In SBO :
Client send control to Server - Step Selection
Server send back Ack to Client kept by Server with Time Out [0..600](s)
- Step Execution
SBO Many => transformer

Note : At DS Agile OI Level, DE/SBO pop-up.


DE with SBO popup = Control is DE appearing in SBO-like popup

GSE
L2-03-DATAPOINTS PROFILES - Rev G - P 20
3.1) xPC Profiles (2)

Single, Double Point Control: use and labels


Set Point => no order Usage :
Some controls are using only one
“channel” e.g. Master Trip Reset

Labels “status” for control send


logging, alarms, popup buttons
On Control

GSE
L2-03-DATAPOINTS PROFILES - Rev G - P 21
3.1) xPC Profiles (3)

Single, Double Point Control: interlocking and FBD tab

PSL status on control False/True

Note : Goal is use xPC associated status in PSL.

GSE
L2-03-DATAPOINTS PROFILES - Rev G - P 22
3.1) xPC Profiles (4)

Single, Double Point Control: Alarm on NACK

Alarm on control Yes/No Clearing Acknowledged alarms

Delay [0..120]
Gravity [1..5]
Klaxon [Yes/No] + Relation

GSE
L2-03-DATAPOINTS PROFILES - Rev G - P 23
www.alstom.com