The document provides technical specifications for the design of a 10,000 MT capacity ammonia storage tank. Some key points: 1) The mechanical design of the tank shall follow API 620 standards for double wall, double integrity tanks with domed roofs and suspended decks. 2) The inner tank roof shall be a suspended deck design following frame membrane analysis. 3) Anchoring of the inner and outer tanks and expansion joints between them must be adequately designed to account for thermal expansion/contraction. 4) Detailed design calculations and drawings must be submitted and approved, addressing all loading conditions like wind, piping, and platforms. Thickness must provide for corrosion and thinning allow

Uploaded by

VPNN 789
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
29 views1 page

LSTK D1003am1

The document provides technical specifications for the design of a 10,000 MT capacity ammonia storage tank. Some key points: 1) The mechanical design of the tank shall follow API 620 standards for double wall, double integrity tanks with domed roofs and suspended decks. 2) The inner tank roof shall be a suspended deck design following frame membrane analysis. 3) Anchoring of the inner and outer tanks and expansion joints between them must be adequately designed to account for thermal expansion/contraction. 4) Detailed design calculations and drawings must be submitted and approved, addressing all loading conditions like wind, piping, and platforms. Thickness must provide for corrosion and thinning allow

Uploaded by

VPNN 789
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Annexure- 4

Technical Specifications for 10,000 MT Capacity Ammonia Storage Tank

4.00 MECHANICAL DESIGN OF TANK:

4.01 Complete Mechanical design of the Ammonia Storage Tank shall be as per the
API 620 including Appendix-R (latest edition). Strict compliance with the
requirements of codes, tank specification sheets and any other referred
documents enclosed with this tender shall be ensured.

4.02 The tank shall be double wall double integrity type with dome roof having
suspended deck and shall be designed in accordance with API 620 (including
Appendix-R, latest version).

4.03 The inner tank roof shall be suspended deck type and shall be designed as per
frame membrane analogy.

4.04 The anchorage of inner & outer tank shall be adequately designed.

4.05 Design of the pipe between inner and outer tank shall be checked for adequate
expansion/ contraction. If required, expansion bellow to be suitably designed &
provided. Design calculations shall be submitted.

4.06 Detailed design calculations for adequacy of strength of all individual parts along
with fabrication drawings & other related documents as per documents Design
Basis attached at Annexure-2 and other documents enclosed with ITB shall be
prepared by contractor and shall submit the same to GNFC for comment &
approval. After approval of design & fabrication drawings, fabrication activity to
be taken up. Any change / comment made on design calculations and drawing to
satisfy the requirement of code & enquiry documents to make the Ammonia
Storage Tank perfectly fit for smooth operation shall have to be incorporated by
Contractor without any delivery / commercial implications.

4.07 Design conditions for the ammonia storage tank shall be as per Ammonia
Storage Tank datasheet & Technical Specification enclosed with the enquiry.
Minimum required thicknesses of various components shall be calculated based
on design parameters considering different types of loadings conditions including
effect of wind pressure, force of moment owing to connected piping & other
attachments as platform etc. Ammonia Storage Tank shall also be designed for
hydrostatic condition. Final thickness of tank shall be decided giving due
consideration for corrosion allowance & thinning allowance.

4.08 Wind analysis shall be performed as per IS-875 (Latest Edition). Wind velocity of
158.4 Km/Hr shall be considered in design. Contractor shall also refer Project
Design Basis of site.

4.09 Seismic analysis shall be performed by Response Spectrum Method (RSM)


considering seismic zone-III as per code IS-1893.