Flow Technalco
Flow Technalco
INDEX
O INTRODUCTION 2
O DIFFUSER SPECIFICATION 3
O AIR PATTERNS 4
O CORNER SECTIONS 5
O PERFORMANCE DATA 6
O DIMENSIONS DIFFUSER 16
O INSTALLATION DETAILES 17
1
FLOWBAR TECNALCO
INDRODUCTION
FlowBar is an architecturally designed high capacity linear slot diffuser. It is designed to combine a high air
handling capacity with maximum flexibility and is suitable for either ceiling or sidewall applications. The
flexibility of the system can blend into a design or provide contrast with its striking but simple design.
FlowBar is a flexible system thatcan provide straight lines or curves to blend with other architectural
elements and enhance the overall concept of the project.
KEY FEATURES
High capacity single slot diffuser available in five slot of 25mm, 38 mm, 51mm, 63 mm and 76 mm
Choice of HT (High Throw) series horizontal or JT (Jet Throw) series vertical air patterns.
Concealed Fixing
2
SPECIFICATION TECNALCO
The High Throw series is primarily Standard slot sizes are 25mm,
Models : TFB-10-HT
designed for ceiling applications 38mm, 51mm, 63mm and 76mm
25mm Slot
and allows the air diffuser to with single section lengths
Models :TFB-15-HT become inconspicuous, whilst fully available up to 3000 mm.
38mm Slot integrating into the ceiling system.
Models : TFB-10-JT The jet Throw series has pattern flow Standard slot sizes are 25mm,
25mm Slot controllers to allow the airstream to 38mm, 51mm, 63mm and 76mm
be jetted in a horizontal direction with single section lengths
Models :TFB-15-JT (sidewall mounted) whilst fully available up to 3000 mm.
38mm Slot integrating into the wall system.
Models :TFB-20-JT
The FlowBar systems satisfy both
51mm Slot
architectural and engineering
Models :TFB-25-JT requirements for designing an air
63mm Slot distribution system that will maintain
optimum room air conditions whilst
Models :TFB-30-JT
being an integral component of the
76mm Slot
architectural concept of the project.
3
AIR PATTERNS TECNALCO
4
CORNER SECTIONS TECNALCO
* Specify Angle
Curved Supply
NB : HT Active curved section
JT Non active dummy section only
Key
B = Overall Width
T = Overall Length * Specify Radius
C = Overall Arc Length Minimum radius dependent on border
L = Slot Width styles. Please contact technical support
5
PERFORMANCE DATA TECNALCO
TFB -10 - HT
Air Flow, l/s-m 36 58 79 101 122 144 165
Static Pressure, Pa 7 18 34 55 81 112 148
25mm
Slot Width NC (Noise Criteria) <10 16 26 33 39 44 49
Throw, m 1.5 - 2.5 - 4.3 2.8 - 4 - 5.5 3.8 - 4.5 - 6.5 4.3 - 5.3 - 7.3 4.5 - 5.8 - 8.3 5.3 - 6 - 8.8 5.5 - 6.8 - 9.5
TFB -15 - HT
Air Flow, l/s-m 43 65 86 108 129 151 173
Static Pressure, Pa 8 18 32 51 73 99 129
38mm
Slot Width NC (Noise Criteria) <10 14 24 31 37 42 48
Throw, m 1.8 - 3 - 5 3 - 4.3 - 5.8 4 - 5 - 6.8 4.3 - 5.5 - 7.5 5 - 5.8 - 8.3 5.3 - 6.5 - 8.8 5.5 - 6.8 - 9.8
TFB - 20 - HT
Air Flow, l/s-m 43 72 101 129 158 187 216
Static Pressure, Pa 5 14 28 46 68 95 127
51mm
Slot Width NC (Noise Criteria) <10 11 22 30 36 41 46
Throw, m 1.5 - 2.8 - 5 2.8 - 4.3 - 6 4 - 5.3 - 7.3 5 - 5.8 - 8.3 5.3 - 6.5 - 9.3 5.8 - 7 - 10 6 - 7.5 - 10.8
TFB - 25 - HT
Air Flow, l/s-m 43 79 115 151 187 223 259
Static Pressure, Pa 3 10 22 38 58 82 110
63mm
Slot Width NC (Noise Criteria) <10 11 23 31 38 43 48
Throw, m 1.3 - 2.5 - 5 3 - 4.5 - 6.5 4.3 - 5.5 - 8 5.3 - 6.5 - 8.8 5.8 - 7 - 10 6.5 - 7.5 - 11 6.8 - 8.3 - 12.8
TFB - 30 - HT
Air Flow, l/s-m 43 86 129 173 216 259 302
Static Pressure, Pa 3 11 25 44 69 99 135
76mm
Slot Width NC (Noise Criteria) <10 <10 18 27 34 40 45
Throw, m 1 - 2.3 - 4.5 3 - 4.5 - 6.8 4.5 - 5.8 - 8.3 5.5 - 6.8 - 9.8 6 - 7.5 - 10.8 6.8 - 8.3 - 12 7.3 - 8.8 - 12.8
Supply -3 0 +2 +3 +5
Return 0 +3 +5 +6 +8
Pressures are given in Pascal (Pa) 3000mm continuous length, the throw The tests were conducted with no Plenum
values are 1.7 times those shown and 1.8 effect for pressure or sound.
Pressure loss data assumes a duct velocity for 3600mm units.
is less than 4m/sec in the inlet duct Throw values for High Throw units are
Each NC value represents the noise criteria based on a 1-way discharge from the slot.
Isothermal throw values are given for curve which will not be exceeded by the
terminal velocities of 0.8, 0.5 and sound pressure in any of the octave bands, Throws listed are for the 1-way air pattern.
0.3m/sec respectively. 2nd through 7th, with a room absorption For divided airflow, select the air flow in
-12 each direction according to the number of
of 10dB, re 10 watts, for a 1200mm
Throw data are based on 1200mm active section. (See Table A for other lengths.) slots aimed in that direction, with the total
section. For a 600mm section the throw For supply units used as a return, airflow apportioned between slots.
values are 0.72 times those shown. For a (add 3 NC.)
6
PERFORMANCE DATA TECNALCO
Throw, m 0.3 - 0.5 - 2.3 1 - 2.3 - 4.3 2.3 - 3.3 - 5.5 3 - 4.3 - 6 3.8 - 5 - 7 4.3 - 5.5 - 7.5 5 - 5.8 - 8.3
7
PERFORMANCE DATA TECNALCO
8
PERFORMANCE DATA TECNALCO
Pressures are given in Pascal (Pa) The tests were conducted with the Plenums not provided by Air Diffusion
FlowBar and plenums as a composite may demonstrate performance variations
Isothermal throw values are given for assembly. from the published data and therefore
terminal velocities of 0.8, 0.5 and Air Diffusion would not be able to
0.3m/sec respectively. Throw values for High Throw units are subsequently guarantee that performance
based on a 1-way discharge from the slot. matches our data.
Each NC value represents the noise criteria
curve which will not be exceeded by the Throws listed are for the 1-way air pattern.
sound pressure in any of the octave bands, For divided air flow, select the airflow in
2nd through 7th, with a room absorption each direction according to the number of
of 10dB, re 10 -12 watts. slots aimed in that direction, with the total
airflow apportioned between slots.
9
PERFORMANCE DATA TECNALCO
Pressures are given in Pascal (Pa) The tests were conducted with the Plenums not provided by Air Diffusion
FlowBar and plenums as a composite may demonstrate performance variations
Isothermal throw values are given for assembly. from the published data and therefore
terminal velocities of 0.8, 0.5 and Air Diffusion would not be able to
0.3m/sec respectively. Throw values for High Throw units are subsequently guarantee that performance
based on a 1-way discharge from the slot. matches our data.
Each NC value represents the noise criteria
curve which will not be exceeded by the Throws listed are for the 1-way air pattern.
sound pressure in any of the octave bands, For divided air flow, select the airflow in
2nd through 7th, with a room absorption each direction according to the number of
of 10dB, re 10 -12 watts. slots aimed in that direction, with the total
airflow apportioned between slots.
10
PERFORMANCE DATA TECNALCO
TFB - 10 - JT
Air Flow, l/s-m 31 62 93 124 155 186 217
Static Pressure, Pa 2 7 15 27 42 61 83
25mm Slot Width
NC (Noise Criteria) <10 <10 17 24 28 32 36
Throw, m 0.5 - 1 - 2.3 1.3 - 2.3 - 4 2.3 - 3 - 5.8 2.8 - 4 - 6.8 3.3 - 5.3 - 7.3 4 - 5.8 - 8 4.5 - 6 - 8.8
TFB - 15 - JT
Air Flow, l/s-m 46 93 139 186 232 279 325
Static Pressure, Pa 2 8 18 31 49 70 95
38mm Slot Width
NC (Noise Criteria) <10 <10 13 22 28 34 40
Throw, m 0.5 - 1.3 - 2.3 1.5 - 2.3 - 4.5 2.3 - 3.3 - 6.8 3 - 4.5 - 8 3.8 - 5.5 - 9.3 4.5 - 6.8 - 9.8 5.3 - 7.5 - 10.8
TFB - 20 - JT
Air Flow, l/s-m 54 116 178 240 302 364 426
Static Pressure, Pa 1 7 15 28 44 64 88
51mm Slot Width
NC (Noise Criteria) <10 18 24 28 32 37 40
Throw, m 0.3 - 1 - 2.3 1.5 - 2.5 - 4.5 2.5 - 3.8 - 7 3 - 5.- 9.3 4 - 6 - 10.3 5 - 7.3 - 11.3 5.5 - 8.5 - 12.3
TFB - 25 - JT
Air Flow, l/s-m 62 147 232 317 402 488 573
Static Pressure, Pa 1 7 17 31 51 74 102
63mm Slot Width
NC (Noise Criteria) <10 <10 18 25 30 35 39
Throw, m 0.3 - 1 - 2.3 1.8 - 2.5 - 5.3 2.8 - 4 - 8 3.8 - 5.5 - 10.8 4.5 - 7 - 12 5.5 - 8.5 - 13 6.8 - 10 - 14
TFB - 30 - JT
Air Flow, l/s-m 77 178 279 379 480 580 681
Static Pressure, Pa 1 7 17 31 50 73 100
76mm Slot Width
NC (Noise Criteria) <10 <10 15 24 30 35 40
Throw, m 0.3 - 1 - 2.5 1.8 - 2.8 - 5.5 2.8 - 4.3 - 8.5 4 - 5.8 - 11.5 5 - 7.3 - 12.8 6 - 8.8 - 14.3 7 - 10.3 - 15.5
Supply -3 0 +2 +3 +5
Return 0 +3 +5 +6 +8
Throw
0.72 1 1.5 1.7 1.8
Correction
Pressures are given in Pascal (Pa) values are 0.72 times those shown. For a For supply units used as a return,
3000mm continuous length, the throw add 3 NC.
Pressure loss data assumes a duct velocity values are 1.7 times those shown and 1.8
is less than 4m/sec in the inlet duct for 3600mm units. The tests were conducted with no Plenum
effect for pressure or sound.
Isothermal throw values are given for Each NC value represents the noise criteria
terminal velocities of 0.8, 0.5 and curve which will not be exceeded by the Throws listed are for the 1-way air pattern.
0.3m/sec respectively. sound pressure in any of the octave bands, For divided airflow, select the air flow in
2nd through 7th, with a room absorption each direction according to the number of
Throw data are based on 1200mm active of 10dB, re 10 -12 watts, for a 1200mm slots aimed in that direction, with the total
airflow apportioned between slots.
section. For a 600mm section the throw section. (See Table A for other lengths.)
11
PERFORMANCE DATA TECNALCO
12
PERFORMANCE DATA TECNALCO
13
PERFORMANCE DATA TECNALCO
Pressures are given in Pascal (Pa) The tests were conducted with the Plenums not provided by Air Diffusion
FlowBar and plenums as a composite may demonstrate performance variations
Isothermal throw values are given for assembly. from the published data and therefore
terminal velocities of 0.8, 0.5 and Air Diffusion would not be able to
0.3m/sec respectively. Throws listed are for the 1-way air pattern. subsequently guarantee that performance
For divided air flow, select the airflow in matches our data.
Each NC value represents the noise criteria each direction according to the number of
curve which will not be exceeded by the slots aimed in that direction, with the total
sound pressure in any of the octave bands, airflow apportioned between slots.
2nd through 7th, with a room absorption
of 10dB, re 10 -12 watts.
14
PERFORMANCE DATA TECNALCO
Pressures are given in Pascal (Pa) The tests were conducted with the Plenums not provided by Air Diffusion
FlowBar and plenums as a composite may demonstrate performance variations
Isothermal throw values are given for assembly. from the published data and therefore
terminal velocities of 0.8, 0.5 and Air Diffusion would not be able to
0.3m/sec respectively. Throws listed are for the 1-way air pattern. subsequently guarantee that performance
For divided air flow, select the airflow in matches our data.
Each NC value represents the noise criteria each direction according to the number of
curve which will not be exceeded by the slots aimed in that direction, with the total
sound pressure in any of the octave bands, airflow apportioned between slots.
2nd through 7th, with a room absorption
of 10dB, re 10 -12 watts.
15
DIMENSIONS - DIFFUSERS TECNALCO
TFB-10/15/20/25/30 - HT
F S W H
1 Slot (25mm) 40 25 70 43
1 Slot (38mm) 45 38 95 43
1 Slot (51mm) 55 51 121 43
1 Slot (63mm) 55 63 146 59
1 Slot (76mm) 60 76 171 59
TFB-10/15/20/25/30 - JT
F S W H
1 Slot (25mm) 40 25 70 43
1 Slot (38mm) 45 38 95 43
1 Slot (51mm) 55 51 121 43
1 Slot (63mm) 55 63 146 61
1 Slot (76mm) 60 76 171 61
16
INSTALLATION TECNALCO
The H3 hard ceiling clip can be used to mount the FlowBar assembly when a standard plasterboard ceiling
is required.
The SS1 spline clip is also used to adjoin multiple sections of FlowBar when continuous lengths are desired.
17
INSTALLATION TECNALCO
18