Chiller Modbus Details

This document provides information on Bacnet object names and point list codes for a York Talk 2 chiller system. It lists 39 points including setpoints, temperatures, pressures, run times, frequencies and statuses. The points are mapped to Bacnet objects with references, types and addresses. Standard imperial and metric units are indicated for each point.

Uploaded by

ajithkumar95
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
301 views3 pages

Chiller Modbus Details

This document provides information on Bacnet object names and point list codes for a York Talk 2 chiller system. It lists 39 points including setpoints, temperatures, pressures, run times, frequencies and statuses. The points are mapped to Bacnet objects with references, types and addresses. Standard imperial and metric units are indicated for each point.

Uploaded by

ajithkumar95
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

10/7/2010

YVAA - Corsair / 1st, 2nd Systems SECTION 1 ELINK YORK TALK 2 Micro Board: 031-02478-xxx
Item Ref. Version Date YORK P N Checksum Baud COMMENTS
1 4800 Std. : See IOM FORM 101.21 -NM1 for all wiring instructions
2 4800 Opt
3
4
5
6  
7
8
9
10

ENG BACnet ENG


Bacnet Object LON Profile N2 MODBUS ENG UNITS
PAGE Object LON SNVT Type POINT LIST CODE: S = STANDARD O = OPTIONAL N = NOT AVAILABLE PAGE
Ref Name Name Metasys Ref
Typ/Ins Address Scale Imper SI POINT LIST DESCRIPTION 1 2 3 4 5 6 7 8 9 10
see notes 3
P03 AV1 YT2_ S01_ P03 nviYTS01p003 SNVT_count_f (51) ADF 1 0001 Div 10 °F °C Setpoint ( Start command must be active to take effect) S P03
P04 AV2 YT2_ S01_ P04 nviYTS01p004 SNVT_count_f (51) ADF 2 0002 Div 10 % % ISN Current Limit Start command must be active to take effect S P04
P05 AV3 YT2_ S01_ P05 nviYTS01p005 SNVT_count_f (51) ADF 3 0003 Div 10 % % ISN Sound Limit (RSL Option must be enabled or this point ignored) S P05
P06 AV4 YT2_ S01_ P06 nviYTS01p006 SNVT_count_f (51) ADF 4 0004 Div 10 P06
P07 BV1 YT2_ S01_ P07 nviYTS01p007 SNVT_switch (95) BD 1 0061 N/A 0/1 0/1 Start / Stop Command S P07
P08 BV2 YT2_ S01_ P08 nviYTS01p008 SNVT_switch (95) BD 2 0062 N/A P08
P09 BV3 YT2_ S01_ P09 nviYTS01p009 SNVT_switch (95) BD 3 0063 N/A P09
P10 BV4 YT2_ S01_ P10 nviYTS01p010 SNVT_switch (95) BD 4 0064 N/A 0/1 0/1 History Buffer 1 Request S P10
P11 AV5 YT2_ S01_ P11 nvoYTS01p011 SNVT_count_f (51) ADF 5 0005 X 10 °F °C Leaving Chilled Liquid Temp S P11
P12 AV6 YT2_ S01_ P12 nvoYTS01p012 SNVT_count_f (51) ADF 6 0006 X 10 °F °C Return Chilled Liquid Temp S P12
P13 AV7 YT2_ S01_ P13 nvoYTS01p013 SNVT_count_f (51) ADF 7 0007 X 10 °F °C VSD Internal Ambient Temp S P13
P14 AV8 YT2_ S01_ P14 nvoYTS01p014 SNVT_count_f (51) ADF 8 0008 X 10 °F °C Sys 1 Suction Temperature S P14
P15 AV9 YT2_ S01_ P15 nvoYTS01p015 SNVT_count_f (51) ADF 9 0009 X 10 °F °C Sys 1 Discharge Temperature S P15
P16 AV10 YT2_ S01_ P16 nvoYTS01p016 SNVT_count_f (51) ADF 10 0010 X10 °F °C Outside Ambient Air Temperature S P16
P17 AV11 YT2_ S01_ P17 nvoYTS01p017 SNVT_count_f (51) ADF 11 0011 X10 °F °C Sys 1 Oil Temperature S P17
P18 AV12 YT2_ S01_ P18 nvoYTS01p018 SNVT_count_f (51) ADF 12 0012 X10 PSI BAR Sys 1 Oil Pressure S P18
P19 AV13 YT2_ S01_ P19 nvoYTS01p019 SNVT_count_f (51) ADF 13 0013 X10 PSI BAR Sys 1 Suction Pressure S P19
P20 AV14 YT2_ S01_ P20 nvoYTS01p020 SNVT_count_f (51) ADF 14 0014 X10 PSI BAR Sys 1 Discharge Pressure S P20
P21 AV15 YT2_ S01_ P21 nvoYTS01p021 SNVT_count_f (51) ADF 15 0015 X10 % % Sys 1 Compressor % Full Load Amps S P21
P22 AV16 YT2_ S01_ P22 nvoYTS01p022 SNVT_count_f (51) ADF 16 0016 X1 * hrs hrs Sys 1 Total Run Hours S P22
P23 AV17 YT2_ S01_ P23 nvoYTS01p023 SNVT_count_f (51) ADF 17 0017 X1 * count count Sys 1 Total Number of Starts S P23
P24 AV18 YT2_ S01_ P24 nvoYTS01p024 SNVT_count_f (51) ADF 18 0018 X 10 °F °C Sys 1 Highest Motor Temp S P24
P25 AV19 YT2_ S01_ P25 nvoYTS01p025 SNVT_count_f (51) ADF 19 0019 X 10 °F °C Sys 2 Highest Motor Temp S P25
P26 AV20 YT2_ S01_ P26 nvoYTS01p026 SNVT_count_f (51) ADF 20 0020 X 10 °F °C Sys 2 Oil Temperature S P26
P27 AV21 YT2_ S01_ P27 nvoYTS01p027 SNVT_count_f (51) ADF 21 0021 X 10 PSI BAR Sys 2 Oil Pressure S P27
P28 AV22 YT2_ S01_ P28 nvoYTS01p028 SNVT_count_f (51) ADF 22 0022 X 10 PSI BAR Sys 2 Suction Pressure S P28
P29 AV23 YT2_ S01_ P29 nvoYTS01p029 SNVT_count_f (51) ADF 23 0023 X 10 PSI BAR Sys 2 Discharge Pressure S P29
P30 AV24 YT2_ S01_ P30 nvoYTS01p030 SNVT_count_f (51) ADF 24 0024 X1 % % Sys 2 Compressor % Full Load Amps S P30
P31 AV25 YT2_ S01_ P31 nvoYTS01p031 SNVT_count_f (51) ADF 25 0025 X1 * hrs hrs Sys 2 Total Run Hours S P31
P32 AV26 YT2_ S01_ P32 nvoYTS01p032 SNVT_count_f (51) ADF 26 0026 X1 * count count Sys 2 Total Number of Starts S P32
P33 AV27 YT2_ S01_ P33 nvoYTS01p033 SNVT_count_f (51) ADF 27 0027 X1 * hz hz VSD Output Frequency S P33
P34 AV28 YT2_ S01_ P34 nvoYTS01p034 SNVT_count_f (51) ADF 28 0028 X1 % % Sys 1 Flash Tank Feed Valve % Open O P34
P35 AV29 YT2_ S01_ P35 nvoYTS01p035 SNVT_count_f (51) ADF 29 0029 X 10 % % Sys 2 Flash Tank Feed Valve % Open O P35
P36 BV5 YT2_ S01_ P36 nvoYTS01p036 SNVT_switch (95) BD 5 0065 N/A 0/1 0/1 Chiller Run S P36
P37 BV6 YT2_ S01_ P37 nvoYTS01p037 SNVT_switch (95) BD 6 0066 N/A 0/1 0/1 Chiller Alarm ( 0 = alarm, 1= no alarm ) S P37
P38 BV7 YT2_ S01_ P38 nvoYTS01p038 SNVT_switch (95) BD 7 0067 N/A 0/1 0/1 Evaporator Heater Status S P38
P39 BV8 YT2_ S01_ P39 nvoYTS01p039 SNVT_switch (95) BD 8 0068 N/A 0/1 0/1 Evaporator Pump Status S P39
P40 BV9 YT2_ S01_ P40 nvoYTS01p040 SNVT_switch (95) BD 9 0069 N/A 0/1 0/1 Sys 1 Compressor Run Status S P40
P41 BV10 YT2_ S01_ P41 nvoYTS01p041 SNVT_switch (95) BD 10 0070 N/A 0/1 0/1 Sys 2 Compressor Run Status S P41
P42 BV11 YT2_ S01_ P42 nvoYTS01p042 SNVT_switch (95) BD 11 0071 N/A 0/1 0/1 Sys 1 Economizer Solenoid Valve Status S P42

Revision: YCAV_YCIV_YVAA (Rev K_03a) Tab: YVAA Corsair (1 & Comps) Property of Johnson Controls, York, PA Page: 9
10/7/2010

ENG BACnet ENG


Bacnet Object LON Profile N2 MODBUS ENG UNITS
PAGE Object LON SNVT Type POINT LIST CODE: S = STANDARD O = OPTIONAL N = NOT AVAILABLE PAGE
Name Name Metasys
Ref Typ/Ins Address Scale Imper SI POINT LIST DESCRIPTION 1 2 3 4 5 6 7 8 9 10 REF
see note 3
P43 BV12 YT2_ S01_ P43 nvoYTS01p043 SNVT_switch (95) BD 12 0072 N/A 0/1 0/1 Sys 2 Economizer Solenoid Valve Status S P43
P44 BV13 YT2_ S01_ P44 nvoYTS01p044 SNVT_switch (95) BD 13 0073 N/A 0/1 0/1 Sys 1 VI Step Solenoid Valve 2 Status S P44
P45 BV14 YT2_ S01_ P45 nvoYTS01p045 SNVT_switch (95) BD 14 0074 N/A 0/1 0/1 Sys 2 VI Step Solenoid Valve 2 Status S P45
P46 BV15 YT2_ S01_ P46 nvoYTS01p046 SNVT_switch (95) BD 15 0075 N/A P46
P47 BV16 YT2_ S01_ P47 nvoYTS01p047 SNVT_switch (95) BD 16 0076 N/A P47
P48 BV17 YT2_ S01_ P48 nvoYTS01p048 SNVT_switch (95) BD 17 0077 N/A P48
P49 BV18 YT2_ S01_ P49 nvoYTS01p049 SNVT_switch (95) BD 18 0078 N/A P49
P50 BV19 YT2_ S01_ P50 nvoYTS01p050 SNVT_switch (95) BD 19 0079 N/A 0/1 0/1 S1-1 Cooling Type: 0=Water, 1=Glycol S P50
P51 BV20 YT2_ S01_ P51 nvoYTS01p051 SNVT_switch (95) BD 20 0080 N/A 0/1 0/1 Local/Remote Control Mode: 0 = Local, 1 = Remote S P51
P52 BV21 YT2_ S01_ P52 nvoYTS01p052 SNVT_switch (95) BD 21 0081 N/A 0/1 0/1 Display Units Mode: 0 = Imperial, 1 = SI S P52
P53 BV22 YT2_ S01_ P53 nvoYTS01p053 SNVT_switch (95) BD 22 0082 N/A P53
P54 BV23 YT2_ S01_ P54 nvoYTS01p054 SNVT_switch (95) BD 23 0083 N/A P54
P55 BV24 YT2_ S01_ P55 nvoYTS01p055 SNVT_switch (95) BD 24 0084 N/A P55
P56 MV1 YT2_ S01_ P56 nvoYTS01p056 SNVT_count_f (51) ADI 1 0030 X1 enum enum *Sys 1 Operational Code S P56
P57 MV2 YT2_ S01_ P57 nvoYTS01p057 SNVT_count_f (51) ADI 2 0031 X1 enum enum *Sys 1 Fault Code S P57
P58 MV3 YT2_ S01_ P58 nvoYTS01p058 SNVT_count_f (51) ADI 3 0032 X1 enum enum *Sys 2 Operational Code S P58
P59 MV4 YT2_ S01_ P59 nvoYTS01p059 SNVT_count_f (51) ADI 4 0033 X1 enum enum *Sys 2 Fault Code S P59
P60 MV5 YT2_ S01_ P60 nvoYTS01p060 SNVT_count_f (51) ADI 5 0034 X1 count count Sys 1 Condenser Fan Stage (0-14) S P60
P61 MV6 YT2_ S01_ P61 nvoYTS01p061 SNVT_count_f (51) ADI 6 0035 X1 count count Sys 1 Condenser Fan Speed (vsd) S P61
P62 MV7 YT2_ S01_ P62 nvoYTS01p062 SNVT_count_f (51) ADI 7 0036 X1 count count Sys 2 Condenser Fan Stage (0-14) S P62
P63 MV8 YT2_ S01_ P63 nvoYTS01p063 SNVT_count_f (51) ADI 8 0037 X1 count count Sys 2 Condenser Fan Speed (vsd) S P63
P64 MV9 YT2_ S01_ P64 nvoYTS01p064 SNVT_count_f (51) ADI 9 0038 X1 count count Lead System Number S P64
P65 MV10 YT2_ S01_ P65 nvoYTS01p065 SNVT_count_f (51) ADI 10 0039 X1 enum enum Spare N P65
P66 AV30 YT2_ S01_ P66 nvoYTS01p066 SNVT_count_f (51) ADF 30 0040 X1 °F °C Local Leaving Chilled Liquid Setpoint S P66
P67 AV31 YT2_ S01_ P67 nvoYTS01p067 SNVT_count_f (51) ADF 31 0041 X1 °F °C Low Leaving Chilled Liquid Temp Cutout S P67
P68 AV32 YT2_ S01_ P68 nvoYTS01p068 SNVT_count_f (51) ADF 32 0042 X1 % % Sys 1 Economizer Valve % Open S P68
P69 AV33 YT2_ S01_ P69 nvoYTS01p069 SNVT_count_f (51) ADF 33 0043 X1 % % Sys 2 Economizer Valve % Open S P69
P70 AV34 YT2_ S01_ P70 nvoYTS01p070 SNVT_count_f (51) ADF 34 0044 X 10 PSI BAR Low Suction Pressure Cutout S P70
P71 AV35 YT2_ S01_ P71 nvoYTS01p071 SNVT_count_f (51) ADF 35 0045 X1 * volts volts VSD DC Bus Voltage S P71
P72 AV36 YT2_ S01_ P72 nvoYTS01p072 SNVT_count_f (51) ADF 36 0046 X1 * °F °C Remote Leaving Chilled Liquid Setpoint N P72
P73 AV37 YT2_ S01_ P73 nvoYTS01p073 SNVT_count_f (51) ADF 37 0047 X1 * °F °C Sys 1 Subcooling S P73
P74 AV38 YT2_ S01_ P74 nvoYTS01p074 SNVT_count_f (51) ADF 38 0048 X1 * °F °C Cooling Range S P74
P75 AV39 YT2_ S01_ P75 nvoYTS01p075 SNVT_count_f (51) ADF 39 0049 X1 * °F °C Sys 1 Discharge Superheat S P75
P76 AV40 YT2_ S01_ P76 nvoYTS01p076 SNVT_count_f (51) ADF 40 0050 X1 °F °C Sys 2 Condenser Temperature S P76
P77 AV41 YT2_ S01_ P77 nvoYTS01p077 SNVT_count_f (51) ADF 41 0051 X1 °F °C Sys 2 Discharge Temperature S P77
P78 AV42 YT2_ S01_ P78 nvoYTS01p078 SNVT_count_f (51) ADF 42 0052 X1 °F °C Sys 2 Subcooling S P78
P79 AV 43 YT2_ S01_ P79 nvoYTS01p079 SNVT_count_f (51) ADF 43 0053 X1 °F °C Sys 2 Discharge Superheat S P79
P80 BV25 YT2_ S01_ P80 nvoYTS01p080 SNVT_switch (95) BD 25 0085 N/A 0/1 0/1 Sys 1 Lockout N P80
P81 BV26 YT2_ S01_ P81 nvoYTS01p081 SNVT_switch (95) BD 26 0086 N/A 0/1 0/1 Sys 2 Lockout N P81
P82 BV27 YT2_ S01_ P82 nvoYTS01p082 SNVT_switch (95) BD 27 0087 N/A P82
P83 BV28 YT2_ S01_ P83 nvoYTS01p083 SNVT_switch (95) BD 28 0088 N/A P83
P84 BV29 YT2_ S01_ P84 nvoYTS01p084 SNVT_switch (95) BD 29 0089 N/A P84

NOTES
LON SNVTS Used: SNVT_count (8), SNVT_lev_percent (81), SNVT_temp_p (105), SNVT_switch (95) , SNVT_time_minute (123) , SNVT_freq_hz (76) , SNVT_amp (01) , SNVT_elec_kwh (13) , SNVT_power_kilo (83) ,
1
SNVT_volt (44) , SNVT_volt_ac (138), SNVT_press_p (87)
2
MODBUS scaling factors indicated in BOLD with an (*) asterisk are User Configurable, by a field technician if necessary. All Modbus values are of the type SIGNED with the exception of the User Configurabale values that are all
3
UNSIGNED. Modbus Function Types Supported (ENG P03-P06 = Types 03, 06, 16) , ( ENG P07- P10 = 01, 03, 05, 15, 06, 16), (ENG P11-P35, P56-P79) = 03, 04) , (ENG P36-P55, P80 -P84 = 01, 02, 03)
4 BACnet Engineering Units shown with an (*) Asterisk will be assigned a BACnet Eng Unit type of (95) ie NO UNITS.
5 Status Codes: Special Display characters such as (, ), [, ], {, },/,\,%,< and > are not compatible with Elink N2 formats. Substitute text strings , "-", PCT, GTN will be used .
6 Status Codes: Status Code Text string lengths are limited to 60 total characters (including spaces)
7 Codes are available only in Firmware versions C.A21.14.03 or later. Contact your JCI FSC for assistance on upgrading your firmware
8
9
10
NOTE: The Appropriate Product Code Listing Summary Should Accompany Document

Revision: YCAV_YCIV_YVAA (Rev K_03a) Tab: YVAA Corsair (1 & Comps) Property of Johnson Controls, York, PA Page: 10
10/7/2010

ENG Operational Code ENG Fault/Inhibit Code ENG Fault/Inhibit Code (cont)
PAGE PAGE PAGE
P56,58 C_OPER.CODE P57,59 C_FAULT.CODE P57,59 C_FAULT.CODE
63 Manual Override 1 Low Ambient Temperature 52 Reserved 52
64 Daily Schedule Shutdown 2 High Ambient Temperature 53 Reserved 53
65 Unit Switch OFF 3 Low Chilled Liquid Temperature 54 Reserved 54
66 Remote Controlled Shutdown 4 Reserved 4 55 Reserved 55
67 Loss of External Communications 5 Low RTC Battery Voltage 56 Reserved 56
68 Flow Switch Shutdown 6 Invalid Number of Comp ressors Selected 57 Reserved 57
69 VSD Cooling Shutdown 7 VSD Communications Failure 58 Reserved 58
70 Serial Number Shutdown 8 Pre-charge Low DC Bus Voltage 59 Reserved 59
71 Reserved 71 9 Pre-charge DC Bus Voltage Imbalance 60 Reserved 60
72 Reserved 72 10 Bus Voltage High DC 61 Reserved 61
73 Reserved 73 11 Bus Voltage Low DC 62 Reserved 62
74 No Run Permissive 12 Voltage Imbalance DC Bus
75 Anti-Recycle Timer Active 13 High VSD Ambient Temperature
76 System Switch OFF 14 Phase Input Single
77 System Not Running 15 VSD Power Supply Fault
78 System Running 16 VSD Logic Board Fault
79 Discharge Pressure Limiting 17 Motor Current Overload (Hardware)
80 Suction Pressure Limiting 18 CT Plug Fault
81 Motor Current Limiting 19 Reserved 19
82 Reserved 82 20 Reserved 20
83 ISN Motor Current Limiting 21 Reserved 21
84 Remote Motor Current Limiting 22 Reserved 22
85 System Pumping Down 23 Reserved 23
86 VSD PreCharging 24 Reserved 24
87 VSD Baseplate Temp Limiting 25 Reserved 25
88 VSD Internal Ambient Temp Limiting 26 Reserved 26
89 Sound Limiting 27 High Discharge Pressure (Software)
90 ISN Sound Limiting 28 High Differential Oil Pressure
91 Remote Sound Limiting 29 Low Differential Oil Pressure
92 Pulldown Motor Current Limiting 30 Low Suction Pressure
93 Cooling Demand Shutdown 31 High Discharge Temperature
94 Reserved 94 32 Reserved 32
95 Reserved 95 33 Eductor Clog Fault
96 Reserved 96 34 Sensor Failure
35 Low Motor Current
36 High Motor Temperature
37 Pre-charge Low DC Bus Voltage
38 Pre-charge DC Bus Voltage Imbalance
39 High DC Bus Voltage
40 Low DC Bus Voltage
41 DC Bus Voltage Imbalance
42 High Motor Current
43 Motor Current Overload (Software)
44 IGBT Gate Driver Fault
45 High Baseplate Temperature
46 Single Phase Input
47 VSD Run Signal Fault
48 High Discharge Press (Hardware – HPCO)
49 Reserved 49
50 Control Voltage Fault
51 Low Discharge Superheat

Revision: YCAV_YCIV_YVAA (Rev K_03a) Tab: YVAA Corsair (1 & Comps) Property of Johnson Controls, York, PA Page: 11