MSC90 Modbus Protocol Manual
MSC90 Modbus Protocol Manual
Manual (V1.0)
Our Protocol is standard MODBUS protocol with RTU (hexadecimal number) transmission mode. Modbus protocol is a
Master -slave protocol. There is only one device communication at any time. The information exchange is managed by the
master, only which can initiate it and query the slave in turn. When the address is same between the master and slave, the
slave can response to the order message. Direct communication among slaves are impossible. Any order’s header and
terminator are not included in the protocol frame. The start and end of the order message will be identified by the interval
time. When the interval time is equal and longer than 3.5 character, that is to say finishing frame detected. If there is no
slave in the network or CRC check error, there is no return frame received by the master. At this time, the Master confirm
whether it is timed out according timeout setting. If it is timeout, retransmission or an abnormal error window will be made.
1
Write Register Frame
Slave Function Starting Register Register Code Byte Number Register Data CRC16
Address Code Address Number (N)
1byte 1byte 2bytes 2 bytes 1 byte N*2byte 2byte
0---247 10H AddrH, AddrL NH, NL 1---24 N*2 DataH, DataL CrcL, CrcH
2
4. Register Code List Table 4(1st Menu Register Codes)
No Parameter Parameter Name Address Type Range Remark
11 LOC Parameters Password 12 Read 0-9999 Default:0(Table 9)
12 ALM1 OUT1 Alarming mode 14 Write 0-4 Default:0(Table 8)
13 ALA1 OUT1 Alarming value 15 -1999-9999 50
14 ALH1 OUT1 Alarming hysteresis value 16 -1999-9999 5
15 ALM2 OUT2 Alarming mode 17 0-4 Default:0 ( Table 8)
16 ALA2 OUT2 Alarming value 18 -1999-9999 50
17 ALH2 OUT2 Alarming hysteresis value 19 -1999-9999 5
12 OUt1 OUT1 output signal type 20 0-4 Default:0(Table 10)
13 OUL1 OUT1 low limit of range 21 -1999-9999 0
14 OUH1 OUT1 high limit of range 22 -1999-9999 1000
15 Out2 OUT2 output signal type 23 0-4 Default:0(Table 10)
16 OUL2 OUT2 low limit of output Range 24 -1999-9999 0
17 OUH2 OUT2 high limit of output Range 25 -1999-9999 1000
Addr Address 26 1-200 1
bAUd Baudrate 27 0-3 Default:2(Table 11)
SUF Math mode 28 0-3 Default:0(Table 12)
KVL1 1 Channel Math coefficient 29 -19.99-99.99 1.00
KVL2 2 Channels Math coefficient 30 -19.99-99.99 1.00
PdIS P V screen display mode 31 0-1 Default:0(Table 13)
18 SdIS SV screen display mode 32 0-3 Default:0(Table 14)
OUtS Output selection 33 0-4 Default:0(Table 15)
Input 2 Measurement
Bit3 Bit2
xxxx xxxx xxxx 00xxB Input 2 is working ok, normal
xxxx xxxx xxxx 01xxB Channel is in disconnection
4
9. LOC : Password Setting Table 9
Setting Value Password Setting
132 1st, 2nd menu
1024 Calibration password
3003 Isolator unction setting
5
3 OUT1 for Math value output
OUT2 for Input 2 measurement value output
4 OUT1 for Input 1 measurement value output
OUT2 for Math value output
20 0-20mV
21 0-40mV
22 0-100mV
23 -20mV-20mV
24 -100mV-100mV
25 0-20mA
26 0-10mA
27 4-20mA
28 0-5V
29 1-5V
30 -5-5V
31 0-10V
36 -10V-10V
37 0-75mV
42 -40mV-40mV
46 -75mV-75mV
20 0-20mV