The ÖLFLEX CLASSIC 110 cable is a VDE approved power and control cable for occasional flexible use and fixed installation in medium mechanical load conditions. It can be used in dry, damp, or wet indoor areas, as well as outdoors if UV protection is used. The cable is resistant to acids, alkalis and certain oils at room temperature and is suitable for torsion applications in wind turbines.

Uploaded by

Ardi Pratama
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
46 views

DB1119752EN

The ÖLFLEX CLASSIC 110 cable is a VDE approved power and control cable for occasional flexible use and fixed installation in medium mechanical load conditions. It can be used in dry, damp, or wet indoor areas, as well as outdoors if UV protection is used. The cable is resistant to acids, alkalis and certain oils at room temperature and is suitable for torsion applications in wind turbines.

Uploaded by

Ardi Pratama
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

1119752 DATA SHEET

valid from:
03.03.2023 ÖLFLEX CLASSIC 110

Application
ÖLFLEX CLASSIC 110 cables are VDE approved power and control cables for occasional flexible use and fixed installation for medium
mechanical load conditions. They are also suitable for use in dry, damp or wet areas. If using outdoors, observe the indicated temperature
range and use with UV protection. They are largely resistant to acids, alkalis and certain oils at room temperature.
ÖLFLEX CLASSIC 110 cables are limited suitable for free and continuously recurring movements. The maximum tensile load is 15 N/mm²
of conductor cross-section during installation and operation. Compulsory guidance is not permitted.

Application range:
As power- and connecting cable for control systems in machine tools, plant engineering and construction, industrial machinery, conveyor
systems, production and assembly lines as well as in measuring and control technology and data processing systems. This cable is suitable
for torsion application in wind turbines. The torsional load is limited to applications, which are typical for the loop in wind turbine generators
(WTG).

Design
Design based on
EN 50525-2-51
Certification ⊲ VDE-REG 7030 ⊳
limited to following dimension range:
0.5 mm² - 2.5 mm² 2 - 65 cores
4 mm² - 16 mm² 2 - 7 cores
25 mm² - 120 mm² 2 - 5 cores
EN 13501-6 and EN 50575
Classification of fire behaviour
(article/dimension range see www.lappkabel.com/cpr)
Conductor fine wire strands of bare copper, acc. to IEC 60228 resp. EN 60228, Class 5
Insulation LAPP special PVC compound P8/1
TI2 acc. to EN 50363-3 rwith increased requirements acc. to LAPP specification
Core identification code acc. to VDE 0293-1, with or without GN/YE ground conductor
black cores with white numbers acc. to EN 50334
Stranding cores are stranded in layers
Outer sheath PVC compound TM2 acc. to EN 50363-4-1
with increased requirements acc. to LAPP specification
colour: Silver Grey, similar RAL 7001
dlsafjl öjf

Electrical properties at 20 °C
Nominal voltage U₀ / U: 300 / 500 V
Test voltage core / core: 4000 V AC

Mechanical and thermal properties


Minimum bending radius occasional flexing: 10 x outer diameter
fixed installation: 4 x outer diameter
Temperature range occasional flexing: - 15˚C up to +70˚C max. conductor temp.
Fixed installation: - 40˚C up to +80˚C max. conductor temp.
Bending cycles and power chain Power chain
operation parameters limited to 2-7 cores and 0.5 – 2.5 mm²
Min. bending radius: 15 x outer diameter
temperature range: -5 °C up to +70 °C max. conductor temp.
Travelling distance up to 5 m: 0.2 … 1 million bending cycles
Torsional stress in WTG:
TW-0 (5000 cycles at ≥ +5˚C)
TW-1 (2000 cycles at ≥ -20˚C)
± 150˚/m at 1 revolution per minute
Flammability flame retardant acc. to IEC 60332-1-2 resp. EN 60332-1-2
Oil resistance acc. to EN 50290-2-22 TM54
.
Tests acc. to IEC 60811 resp. EN 60811, EN 50395, EN 50396

Creator: MAIH / PDC Document: DB1119752EN


Page 1 of 2
Released: ALTE / PDC Version: 12
We reserve all rights according to DIN ISO 16016.
PD 0019/05_04.18EN
1119752 DATA SHEET
valid from:
03.03.2023 ÖLFLEX CLASSIC 110

General requirements These cables are conform to the EU-Directive 2014/35/EU (Low Voltage Directive).

A part of these cables (see www.lappkabel.com/cpr) are classified


in accordance with the EU-Regulation no. 305/2011 (CPR).
Environmental information These cables meet the substance-specific requirements of the EU Directive 2011/65/EU (RoHS).
.

Creator: MAIH / PDC Document: DB1119752EN


Page 2 of 2
Released: ALTE / PDC Version: 12
We reserve all rights according to DIN ISO 16016.