Fire Tender Load Calculation - R1

1. The document provides details on the load consideration for a fire tender dropping off at a hotel on Level_01. 2. It includes dimensions in millimeters for various points along the path of the fire tender, including widths of the path and heights of planters and walls. 3. The path allows a clearance of at least 4500 mm for the fire tender to maneuver.

Uploaded by

Dhana Sekaran
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
2K views8 pages

Fire Tender Load Calculation - R1

1. The document provides details on the load consideration for a fire tender dropping off at a hotel on Level_01. 2. It includes dimensions in millimeters for various points along the path of the fire tender, including widths of the path and heights of planters and walls. 3. The path allows a clearance of at least 4500 mm for the fire tender to maneuver.

Uploaded by

Dhana Sekaran
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 8

Fire Tender path: Load Consideration at Hotel Drop off : Level_01

15
3 4 BHE-XX-XX-DR-S-3002
BHE-XX-XX-DR-S-3001 BHE-XX-XX-DR-S-3001

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
1 2
wheel of fire tender
BHE-XX-XX-DR-S-3000 BHE-XX-XX-DR-S-3000

4500 4500 4500 4500 4500 4500 4500 4500 4500 4500 4500 4500 4500 4500 600

A
PLANTING REFER TO SOFTSCAPE PLAN
RAISED PLANTER
2
1575 14900

210
6600

L2-006A
1400

1100
PA
1350

C1 C2 C3 C4 C5 C6 C7
(400 x 800) (600 x 800) (600 x 800) (600 x 800) (600 x 800) (800 x 800) (450 x 800)

300
B
45
1500

PLANTING REFER TO
SOFTSCAP PLAN

70
2850 x 550 2850 x 650

00
10200
400 x 1300

11800

14075
9750

300 THK R.C. SLAB

dispersion distance
MOUNTABLE KERB 3 =210+270
3000 x 550 L5-003 3000 x 650
2
C8 C9 C10 C11 C12
1 3
C13 C14 C15
=480 mm
(400 x 800) (400 x 1000) (500 x 700) (500 x 700) L2-006B
(500 x 700) L2-006B L2-008B
(500 x 700) (500 x 700) (400 x 800)
C
HOTEL DROP-OFF 5870 3325 Typical section for the dispersion through slab

1200
PA FL +5.425 m
C16 C17 C18 C19 C20 C21 C22
PA PA C23

7500
(400 x 600) (400 x 600) (500 x 500) (450 x 450) 500 x 800 (500 x 500) 500 x 800 (500 x 500) 500 x 800 (500 x 500) 500 x 800
C15A (400 x 600)
HH
8250

(400 x 800)
250 THK R.C. SLAB
400 x 1300

300 x 800

1V

400 x 800
250 THK R.C. SLAB

400 x 700
300 x 600
C28 HOTEL DRO
6000 1200 (500 x 500)
D C25 WALL
300 x 800

(400 x 700) C26 C27 C29


(800 x 1200) C32 C33
(400 x 800) (450 x 450) (800 x 1200) (400 x 600)
RAMP DOWN TO GROUND LEVEL 300 x 800 JJ
C24
(400 x 800)
400 x 1500
9000

250 THK R.C. SLAB


300 x 800

300 x 800
0 x 1300

0 x 800

0 x 700

0 x 800
Fire Tender Load Consideration for slab Load intensity to consider by this method

1 2

Effective area diagram for the fire tender wheels


Fire Tender path: Load Consideration at Hotel Drop off : Level_01
15
3 4 BHE-XX-XX-DR-S-3002
BHE-XX-XX-DR-S-3001 BHE-XX-XX-DR-S-3001

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
1 2
wheel of fire tender
BHE-XX-XX-DR-S-3000 BHE-XX-XX-DR-S-3000

4500 4500 4500 4500 4500 4500 4500 4500 4500 4500 4500 4500 4500 4500 600

A
PLANTING REFER TO SOFTSCAPE PLAN
RAISED PLANTER
2
1575 14900

210
6600

L2-006A
1400

1100
PA
1350

C1 C2 C3 C4 C5 C6 C7
(400 x 800) (600 x 800) (600 x 800) (600 x 800) (600 x 800) (800 x 800) (450 x 800)

300
B
45
1500

PLANTING REFER TO
SOFTSCAP PLAN

70
2850 x 550 2850 x 650

00
10200
400 x 1300

11800

14075
9750

300 THK R.C. SLAB

dispersion distance
MOUNTABLE KERB 3 =210+270
3000 x 550 L5-003 3000 x 650
2
C8 C9 C10 C11 C12
1 3
C13 C14 C15
=480 mm
(400 x 800) (400 x 1000) (500 x 700) (500 x 700) L2-006B
(500 x 700) L2-006B L2-008B
(500 x 700) (500 x 700) (400 x 800)
C
HOTEL DROP-OFF 5870 3325 Typical section for the dispersion through slab

1200
PA FL +5.425 m
C16 C17 C18 C19 C20 C21 C22
PA PA C23

7500
(400 x 600) (400 x 600) (500 x 500) (450 x 450) 500 x 800 (500 x 500) 500 x 800 (500 x 500) 500 x 800 (500 x 500) 500 x 800
C15A (400 x 600)
HH
8250

(400 x 800)
250 THK R.C. SLAB
400 x 1300

300 x 800

1V

400 x 800
250 THK R.C. SLAB

400 x 700
300 x 600
C28 HOTEL DRO
6000 1200 (500 x 500)
D C25 WALL
300 x 800

(400 x 700) C26 C27 C29


(800 x 1200) C32 C33
(400 x 800) (450 x 450) (800 x 1200) (400 x 600)
RAMP DOWN TO GROUND LEVEL 300 x 800 JJ
C24
(400 x 800)
400 x 1500
9000

250 THK R.C. SLAB


300 x 800

300 x 800
0 x 1300

0 x 800

0 x 700

0 x 800
Load intensity to consider by this method
Fire Tender Load Consideration for slab
Effective area of the the
region under fire tender
wheels

Effective area diagram for the fire tender wheels


Fire Tender path: Load Consideration at Hotel Drop off : Level_01
15
3 4 BHE-XX-XX-DR-S-3002
BHE-XX-XX-DR-S-3001 BHE-XX-XX-DR-S-3001

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
1 2
wheel of fire tender
BHE-XX-XX-DR-S-3000 BHE-XX-XX-DR-S-3000

4500 4500 4500 4500 4500 4500 4500 4500 4500 4500 4500 4500 4500 4500 600

Length is 11.4 m.
Maximum two fire
A Maximum 527 kN load tender, partly can
on each column PLANTING REFER TO SOFTSCAPE PLAN stay in a bay of
because of one fire 9mX9m. RAISED PLANTER
tender in a bay 2
1575 14900

210
6600

L2-006A
1400

1100
PA
1350

C1 C2 C3 C4 C5 C6 C7
(400 x 800) (600 x 800) (600 x 800) (600 x 800) (600 x 800) (800 x 800) (450 x 800)

300
B
45
1500

PLANTING REFER TO
SOFTSCAP PLAN

70
2850 x 550 2850 x 650

00
10200
400 x 1300

11800

14075
9750

300 THK R.C. SLAB

dispersion distance
MOUNTABLE KERB 3 =210+270
3000 x 550 L5-003 3000 x 650
2
C8 C9 C10 C11 C12
1 3
C13 C14 C15
=480 mm
(400 x 800) (400 x 1000) (500 x 700) (500 x 700) L2-006B
(500 x 700) L2-006B L2-008B
(500 x 700) (500 x 700) (400 x 800)
C
HOTEL DROP-OFF 5870 3325 Typical section for the dispersion through slab

1200
PA FL +5.425 m
C16 C17 C18 C19 C20 C21 C22
PA PA C23

7500
(400 x 600) (400 x 600) (500 x 500) (450 x 450) 500 x 800 (500 x 500) 500 x 800 (500 x 500) 500 x 800 (500 x 500) 500 x 800
C15A (400 x 600)
HH
8250

(400 x 800)
250 THK R.C. SLAB
400 x 1300

300 x 800

1V

400 x 800
250 THK R.C. SLAB

400 x 700
300 x 600
C28 HOTEL DRO
6000 1200 (500 x 500)
D C25 WALL
300 x 800

(400 x 700) C26 C27 C29


(800 x 1200) C32 C33
(400 x 800) (450 x 450) (800 x 1200) (400 x 600)
RAMP DOWN TO GROUND LEVEL 300 x 800 JJ
C24
(400 x 800)
400 x 1500
9000

250 THK R.C. SLAB


300 x 800

300 x 800
0 x 1300

0 x 800

0 x 700

0 x 800
Fire Tender Load Consideration for Punching in Column

Load of one fire tender = 45 Tonn = 450 kN

Total length of one fire fighting vehicle is 11.4 m so assuming worst case of two fire tender in a bay of (9mX9m).

-Total Load of two fire tenders = 450X2


= 900 kN

Load Intensity of two fire tenders in 9X9 m grid= Total load of two fire tenders
Total effective area of 1 bay

= 900
9X9
=11.11 kN/m2
Fire Tender path: Load Consideration at Function drop off: Ground level

wheel of fire tender

285
350
45

dispersion distance
=285+320
=605 mm

Typical section for the dispersion through slab

Load intensity of fire tender for the slab design


Load intensity to consider by this method

1 2

Effective area diagram for the fire tender wheels


Fire Tender path: Load Consideration at Function drop off: Ground level

wheel of fire tender

285
350
45

dispersion distance
=285+320
=605 mm

Typical section for the dispersion through slab

Load intensity of fire tender for the slab design


Load intensity to consider by this method
Effective area of the the
region under fire tender
wheels

Effective area diagram for the fire tender wheels


Fire Tender path: Load Consideration at Ramp: Ground level to Level-1

wheel of fire tender


310 mm filling in this zone.

310
350
45

dispersion distance
=310+320
=630 mm

Typical section for the dispersion through slab

Load intensity of fire tender for the slab design


Load intensity to consider by this method
1 2
Effective area of the the
region under fire tender
wheels

Effective area diagram for the fire tender wheels


Fire Tender path: Load Consideration at Ramp: Ground level to Level-1

wheel of fire tender


310 mm filling in this zone.

310
350
45

dispersion distance
=310+320
=630 mm

Typical section for the dispersion through slab

Load intensity of fire tender for the slab design


Load intensity to consider by this method
Effective area of the the
region under fire tender
wheels

Effective area diagram for the fire tender wheels