FEWA-Water Meter For HDPE
FEWA-Water Meter For HDPE
D.I. CIRCULAR MANHOLE TOP 1. UNLESS OTHERWISE SPECIFIED ALL DIMENSIONS ARE IN
D.I. CIRCULAR MANHOLE TOP 600 LOCKING & HINGED TYPE MILIMETER.
600 LOCKING & HINGED TYPE 200 WIDE MS P.V.C COATED STEPS WITH GRP SEALING PLATE
PLACED STAGGERED & BONDED IN 2. FOR TAPPING POINTS, REFER TO TECHNICAL SPECIFICATION.
WITH GRP SEALING PLATE
CONCRETE 3. CABLE FOR F.T. SHALL BE NEATLY DRESSED THROUGH
PERFORATED CABLE TRAY.
300x300x300 GRAB BAR 4. FLOW INDICATOR SHALL BE INSTALLED NEAR THE PIT
DEEP DRAIN SUMP 5. EARTHING SHALL BE DONE AS PER F.T. MANUFACTURER'S
RECOMMENDATION.
6. REFER TO GENERAL NOTES, FEWA-WS-PL-TD-001
VENT PIPE (TYP.) 7. THESE DIMENSIONS ARE ONLY FOR GUIDE LINE.CONTRACTOR
SHALL DESIGN AND SUBMIT SHOP DRAWINGS.
100mm P.V.C SLEEVE 100mm P.V.C SLEEVE
DI SPOOL WITH 1/2" 8. PROVIDE DRAIN PIPE WITH GRAVEL SURROUND FROM SUMP
TAPPING POINTS AND IN CASE WATER TABLE IS BELOW SUMP LEVEL.
WITH SADDLE,STOP COCK 9. SPOOL IS OPTIONAL & REQUIREMENT, REFER BOQ.
VALVES
STRAINER
JOINT PANEL
FEWA
INDICATION PLATE
WITH FEWA LOGO
STEEL SUPPORT
VENT PIPE
GRAB BAR
HEAVY DUTY BITUTHENE
SHEET SEATING 100mm P.V.C SLEEVE
(AS REQUIRED)
STONE PITCHING IN C.M.
OVER COMPACTED ROAD
BASE (TYPICAL) DETAIL-A STEEL &
CONCRETE SUPPORT
DI SPOOL WITH 1/2"
(STEEL PLATE SHALL BE 10mm THICK
200 WIDE MS P.V.C COATED STEPS
TAPPING POINTS AND WITH FOR VALVES UPTO DN500 & 12mm
100mm P.V.C SLEEVE PLACED STAGGERED 300 c/c &
(AS REQUIRED)
SADDLE,STOP COCK VALVES BONDED IN CONCRETE THICK FOR VALVES OVER DN500)
WATER/FLOW DI FLANGE ADAPTOR (RESTRAINT) STANDARD DRAWING
STRAINER METER ONE SIDE FLANGE TO SUIT FLANGED
WATER PROOFING SYSTEM
OTHER SIDE TO SUIT HDPE PIPE DN 100 TO 200 - Z SHALL BE 250mm
HDPE SHORT PIPE WITH SPIGOT (d)
PUDDLE FLANGE
DN 250 TO 500 - Z SHALL BE 300mm REV DATE CADD CHECK DESCRIPTION
PUDDLE FLANGE
DN 600 TO 800 - Z SHALL BE 400mm
DN 900 & ABOVE - Z SHALL BE 450mm
d160 1m 1m -
GRAVEL -
d200 1m 1m
CONCRETE C35 TITLE
BITUTHENE SHEET SEE DETAIL-A FOR COMBINED CHAMBER
FOUNDATION DRAIN PIPE A SUITABLE SIZE SHALL BE
100 GAUGE POLYTHENE SHEET WITH REBAR
BLINDING CONCRETE PROPOSED BY THE CONTRACTOR
SECTION A-A C 20 FOR FEWA'S APPROVAL
APPROVED AREF BARHAMA DRAWING NO. REV.
GEO TEXTILE FOR MWA_PRO_05
SANDY AREA CHECKED THOMAS VERGIS FEWA - WD - PL - SD - 31
DESIGNED MERAJ MOHSIN DATE SHEET SCALE
D:\FEWA\WATER\TENDER\STANDARD DRAWINGS (30-6-2014)\3-HDPE PIPELINE DRAWINGS\FEWA-WD-PL-SD-31.dwg, 1/11/2015 12:05:34 PM, DWG To PDF.pc3