0% found this document useful (0 votes)
47 views7 pages

Relay Test - Pulkit

The document contains technical specifications for overcurrent relays protecting four feeders (302-305) and a transformer at the Pulkit station. It lists the relay type, serial number, function, CT ratios, and pickup values for phase and ground overcurrent elements for each relay. The relays are configured to trip the circuit breakers upon reaching the specified current and time thresholds.

Uploaded by

Kareem Olawale
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
47 views7 pages

Relay Test - Pulkit

The document contains technical specifications for overcurrent relays protecting four feeders (302-305) and a transformer at the Pulkit station. It lists the relay type, serial number, function, CT ratios, and pickup values for phase and ground overcurrent elements for each relay. The relays are configured to trip the circuit breakers upon reaching the specified current and time thresholds.

Uploaded by

Kareem Olawale
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 7

Date: 30th December, 2021

Station: Pulkit

Feeder : Feeder-1 (302)

Relay Type: REJ 601

Serial No: IVYV91383327

Relay Function: O/C and E/F

CT Ratio: 150/1

t@ 2x I>>> Remar
Phase I> I> tms Curve I>> I>> t(s)
P.U P.U(s) I>>> t(s) k
Flags &
R-B 1.0 In 0.5 NI 1.15 - 2 0.1 5.0 0.03 Trips
CB
Flags &
Y-B 1.0 In 0.5 NI 1.13 - 2 0.1 5.0 0.03 Trips
CB
Flags &
R-Y 1.0 In 0.5 NI 1.17 - 2 0.1 5.0 0.03 Trips
CB
Flags &
R-N 0.1In 0.1 NI 0.099 - 0.15 0.3 na - Trips
CB
0.1 Flags &
Y-N 0.1In 0.1 NI 01 - 0.15 0.3 na - Trips
CB
0.10 Flags &
B-N 0.1In 0.1 NI 0 - 0.15 0.3 na - Trips
CB
Date: 30th December, 2021

Station: Pulkit

Feeder : Feeder-2 (303)

Relay Type: REJ 601

Serial No: IVYV91343152

Relay Function: O/C and E/F

CT Ratio: 150/1

t@ 2x I>>> Remar
Phase I> I> tms Curve I>> I>> t(s)
P.U P.U(s) I>>> t(s) k
Flags &
R-B 1.0 In 0.5 NI 1.13 - 2 0.1 5.0 0.03 Trips
CB
Flags &
Y-B 1.0 In 0.5 NI 1.15 - 2 0.1 5.0 0.03 Trips
CB
Flags &
R-Y 1.0 In 0.5 NI 1.14 - 2 0.1 5.0 0.03 Trips
CB
Flags &
R-N 0.1In 0.1 NI 0.11 - 0.15 0.3 na - Trips
CB
0.1 Flags &
Y-N 0.1In 0.1 NI 0 - 0.15 0.3 na - Trips
CB
Flags &
B-N 0.1In 0.1 NI 0.12 - 0.15 0.3 na - Trips
CB
Date: 30th December, 2021

Station: Pulkit

Feeder : Feeder-3 (304)

Relay Type: REJ 601

Serial No: IVYV91383329

Relay Function: O/C and E/F

CT Ratio: 150/1

t@ 2x I>>> Remar
Phase I> I> tms Curve I>> I>> t(s)
P.U P.U(s) I>>> t(s) k
Flags &
R-B 1.0 In 0.5 NI 1.14 - 2 0.1 5.0 0.03 Trips
CB
Flags &
Y-B 1.0 In 0.5 NI 1.10 - 2 0.1 5.0 0.03 Trips
CB
Flags &
R-Y 1.0 In 0.5 NI 1.09 - 2 0.1 5.0 0.03 Trips
CB
Flags &
R-N 0.2In 0.1 NI 0.11 - 0.5 0.3 na - Trips
CB
0.1 Flags &
Y-N 0.2In 0.1 NI 0 - 0.15 0.3 na - Trips
CB
Flags &
B-N 0.2In 0.1 NI 0.10 - 0.15 0.3 na - Trips
CB
Date: 30th December, 2021

Station: Pulkit

Feeder : Feeder-4 (305)

Relay Type: REJ 601

Serial No: IVYV91383328

Relay Function: O/C and E/F

CT Ratio: 150/1

t@ 2x I>>> Remar
Phase I> I> tms Curve I>> I>> t(s)
P.U P.U(s) I>>> t(s) k
Flags &
R-B 1.0 In 1.0 NI 1.05 - 4 0.1 5.0 0.03 Trips
CB
Flags &
Y-B 1.0 In 1.0 NI 1.08 - 4 0.1 5.0 0.03 Trips
CB
Flags &
R-Y 1.0 In 1.0 NI 1.04 - 4 0.1 5.0 0.03 Trips
CB
Flags &
R-N 0.1In 0.1 NI 0.1 - 0.5 0.3 na - Trips
CB
0.0 Flags &
Y-N 0.1In 0.1 NI 9 - 0.5 0.3 na - Trips
CB
Flags &
B-N 0.1In 0.1 NI 0.11 - 0.5 0.3 na - Trips
CB
Date: 30th December, 2021

Station: Pulkit

Feeder : Transformer Sec (301)

Relay Type: REJ 601

Serial No: IVYV91343151

Relay Function: O/C and E/F

CT Ratio: 1250/1

t@ 2x I>>> Remar
Phase I> I> tms Curve I>> I>> t(s)
P.U P.U(s) I>>> t(s) k
Flags &
R-B 1.0 In 0.5 NI 1.07 - 2 0.1 5.0 0.03 Trips
CB
Flags &
Y-B 1.0 In 0.5 NI 1.08 - 2 0.1 5.0 0.03 Trips
CB
Flags &
R-Y 1.0 In 0.5 NI 1.08 - 2 0.1 5.0 0.03 Trips
CB
Flags &
R-N 0.05In 0.1 NI 0.052 - 0.1 0.03 na - Trips
CB
0.0 Flags &
Y-N 0.05In 0.1 NI 51 - 0.1 0.03 na - Trips
CB
0.05 Flags &
B-N 0.05In 0.1 NI 1 - 0.1 0.03 na - Trips
CB
Date: 23rd December, 2021

Station: Pulkit

Feeder : Transformer Primary (101)

Relay Type: REF 615

Serial No: IVYV91358085

Relay Function: O/C and E/F

CT Ratio: 300/1

Phase I> I> tms Curve t@ 2x I>> I>> t(s) Remark


P.U P.U(s)
Flags &
R-B 1.0 In 1.0 NI 1.07 - 2 0.1 Trips
CB
Flags &
Y-B 1.0 In 1.0 NI 1.08 - 2 0.1 Trips
CB
Flags &
R-Y 1.0 In 1.0 NI 1.08 - 2 0.1 Trips
CB
Flags &
R-N 0.1In 0.1 NI 0.19 - 0.2 0.05 Trips
CB
0.1 Flags &
Y-N 0.1In 0.1 NI 5 - 0.2 0.05 Trips
CB
Flags &
B-N 0.1In 0.1 NI 0.20 - 0.2 0.05 Trips
CB
Date: 23rd December, 2021

Station: Pulkit

Feeder : Transformer Bay (101)

Relay Type: RET 650

Serial No: I2032008

Relay Function: Differential

CT Ratio: Primary - 300/1, Secondary – 1250/1

Phase Id p.u Remark

Flags, and Trips both


R-B 0.2 0.22
132kV and 33kV side

Flags, and Trips both


Y-B 0.2 0.21
132kV and 33kV side
Flags, and Trips both
R-Y 0.2 0.17
132kV and 33kV side
Flags, and Trips both
R-N 0.1 0.12
132kV and 33kV side
Flags, and Trips both
Y-N 0.1 0.11
132kV and 33kV side
Flags, and Trips both
B-n 0.1 0.12
132kV and 33kV side
Flags, and Trips both
r-n 0.1 0.267
132kV and 33kV side
Flags, and Trips both
y-n 0.1 0.286
132kV and 33kV side
Flags, and Trips both
b-n 0.1 0.276
132kV and 33kV side
Flags, and Trips both
r-y 0.2 0.18
132kV and 33kV side

Flags, and Trips both


y-b 0.2 0.182
132kV and 33kV side

Flags, and Trips both


r-b 0.2 0.182
132kV and 33kV side