0% found this document useful (0 votes)
25 views

NMPSFA FPT AHU Sample

The document provides a functional test procedure for an air handling unit (AHU-00). It lists prerequisites that must be met before testing, required test equipment, control system setpoints and points that will be trended and tested. The test procedures will verify general system readiness, control of temperature, humidity, airflows, fans, dampers and valves operation as expected.

Uploaded by

ake
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
25 views

NMPSFA FPT AHU Sample

The document provides a functional test procedure for an air handling unit (AHU-00). It lists prerequisites that must be met before testing, required test equipment, control system setpoints and points that will be trended and tested. The test procedures will verify general system readiness, control of temperature, humidity, airflows, fans, dampers and valves operation as expected.

Uploaded by

ake
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 17

New Mexico Public School Facilities Authority

1312 Basehart Rd. SE, Suite 200


Albuquerque, NM 87106-4368
Functional Test Procedure
AIR HANDLING UNIT AHU-00

PROJECT: Project Name


PROJECT NUMBER: Project Number
REPORT ID: FPT-XXXX
SYSTEM DESCRIPTION: Air Handling Unit AHU-00
DATE OF TEST: ___________

Test Participant List:


Participant Company / Agency
PAC Authority
General Contractor
Mechanical Contractor
Controls Contractor
TAB Contractor
RFM / Owners Rep.

Functional Performance Test Prerequisites:


Prerequisite Yes No Comments
1. Chilled Water hydronic piping system has been cleaned,
flushed and pressure tested as required.
Test reports submitted to CxA for review.
2. Heating water hydronic piping system has been cleaned,
flushed and pressure tested as required.
Test reports submitted to CxA for review.
3. Test & Balance is complete.
TAB report submitted to CxA for review.
4. Electrical feed and disconnect are suitably sized for Air
Handler Unit – per AHU Manufacturer’s requirements (32
– 45 Amps).
5. Construction Checklists are complete and have been
submitted to CxA for review. AHU, VFD & BMS
6. All sensors have been calibrated with certified
instruments.
7. Operations & Maintenance Manuals submitted to CxA for
review.
8. Pre-FPT trend logs submitted to CxA for review. Refer to
test procedure #3 below for list of specific trend logs to be
submitted.
9. Control programming, interlocks, safeties, alarms, set
points, schedules and loop tuning are complete. Control
sequences have been tested and debugged.
10. Central plant is operating and providing both Chilled and
Heating Water. If the central boiler plant is not in
operation, then the circulation pumps should be turned on

Project Name Page 1 of 17 Functional Test Procedure


Air Handling Unit AHU-00
New Mexico Public School Facilities Authority
1312 Basehart Rd. SE, Suite 200
Albuquerque, NM 87106-4368
Functional Test Procedure
AIR HANDLING UNIT AHU-00

to provide pressure.
11. System is ready for Functional Performance Testing.
12. SA and RA Caps are ready for installation upon
completion of FPT, as required.

Test Equipment Required:


Equipment Responsible
Infrared Thermometer Mechanical Contractor
Digital Thermometer Mechanical Contractor
CO2 Sensor Mechanical Contractor
Laptop Computer Controls Contractor
Duct Airflow Instruments TAB Contractor
Magnahelic / Manometer (0” to 5”) TAB Contractor
Setpoints, Limits, and Schedules:
OCCUPANCY SCHEDULE
Monday-Friday Saturday Sunday Holiday

CONTROL SYSTEM POINTS


Yes/No Description Units Setpt or Value Comments
Supply Air Temp F
Supply Air Temp Setpoint F
Return Air Temp F
Outside Air Temp F
Mixed Air Temp F
Return Air Humidity %
Outside Air Humidity %
Supply Airflow CFM
Return Airflow CFM
Outside Airflow CFM
Supply Duct Static Pressure in. wg
Supply Duct Static Pressure SP in. wg
Supply Fan Status ON/OFF
Supply Fan Speed %
Supply Fan Speed Hz
Return Fan Status ON/OFF
Return Fan Speed %
Return Fan Speed Hz
Return Air CO2 PPM
Outside Air CO2 PPM

Project Name Page 2 of 17 Functional Test Procedure


Air Handling Unit AHU-00
New Mexico Public School Facilities Authority
1312 Basehart Rd. SE, Suite 200
Albuquerque, NM 87106-4368
Functional Test Procedure
AIR HANDLING UNIT AHU-00

CONTROL SYSTEM POINTS


Yes/No Description Units Setpt or Value Comments
Outside Air Damper Position %
Mixed Air Damper Position %
Exhaust Air Damper Position %
Chilled Water Valve Position %
Heating Water Valve Position
Pre-Filter Differential Pressure in. wg
Final Filter Differential Pressure in. wg
Carbon Filter Differential Pressure in. wg
High Supply Duct Static Press in. wg

Functional Test Procedures:


Pass
No TEST PROCEDURE EXPECTED RESULTS
Y/N
GENERAL SYSTEM READINESS
1 Verify system has been operating at
stable, normal conditions. All test pre-
requisites have been satisfied.

Field Notes:

2 Verify adequate access is provided to all 1. Record any problems that interfere with
components that require periodic equipment access.
maintenance.

Field Notes:

Project Name Page 3 of 17 Functional Test Procedure


Air Handling Unit AHU-00
New Mexico Public School Facilities Authority
1312 Basehart Rd. SE, Suite 200
Albuquerque, NM 87106-4368
Functional Test Procedure
AIR HANDLING UNIT AHU-00

Pass
No TEST PROCEDURE EXPECTED RESULTS
Y/N
3 Review trends for each point listed below. 1 Controlled variables are stable and void of excess
Trend data is required for a minimum of 3 hunting.
consecutive business days sampled at 2 System appears to be ready for FPT
five minute intervals.
3 Note variables not under control in notes.

1. Supply Air Temp


2. Supply Air Temp Setpoint
3. Return Air Temp
4. Mixed Air Temp
5. Outside Air Temp
6. Return Air Humidity
7. Outside Air Humidity
8. SA Duct Static Pressure
9. SA Duct Static Pressure Setpoint
10. Supply Air Flow
11. Return Air Flow
12. Outside Airflow
13. Supply Fan Speed %
14. Return Fan Speed Hz
15. Chilled Water Valve Position
16. Heating Water Valve Position
17. Outside Air Damper Position
18. Mixed Air Damper Position
19. Exhaust Air Damper Position
20. Return Air CO2
21. Outside Air CO2
22. Filter Differential Pressure
Field Notes:

Project Name Page 4 of 17 Functional Test Procedure


Air Handling Unit AHU-00
New Mexico Public School Facilities Authority
1312 Basehart Rd. SE, Suite 200
Albuquerque, NM 87106-4368
Functional Test Procedure
AIR HANDLING UNIT AHU-00

SENSOR & ACTUATOR VERIFICATION


4 Verify the values shown at the BAS Sensor
BAS Measured
Workstation for all sensors in expected Value Value
results column are within the acceptable Supply Air Temp (°F)
tolerance of the temperature shown on Return Air Temp (°F)
the calibrated test instrument.
Mixed Air Temp (°F)
Verify sensors are accessible for future
maintenance. Outside Air Temp (°F) Existing Existing
Duct Static Press (in. wg)
Setting – 1.50
Supply Airflow (CFM)
Return Airflow (CFM)
Outside Airflow (CFM)
Return Air Humidity (%)
Outside Air Humidity (%) Existing Existing
Return CO2 (PPM)
Outside Air CO2 (PPM) Existing Existing

Field Notes:

5 Verify the values shown at the BAS Valve/Actuator


BAS Observed Measured
Workstation for all actuators/control Value Position Value
valves in the expected results column are Chilled Water Valve (%) 0/100 % %
within the acceptable tolerance shown on Heating Water Valve (%) 0/100 % %
the calibrated test instrument.
Outside Air Damper (%) 0/100 % %
Verify actuators/control valves are
accessible for future maintenance. Return Air Damper (%) 0/100 % %
Exhaust Air Damper (%) 0/100 % %

Field Notes:

Project Name Page 5 of 17 Functional Test Procedure


Air Handling Unit AHU-00
New Mexico Public School Facilities Authority
1312 Basehart Rd. SE, Suite 200
Albuquerque, NM 87106-4368
Functional Test Procedure
AIR HANDLING UNIT AHU-00

TIME OF DAY SCHEDULING


6 Set the unit to be in the OFF mode. 1. The air handler is in the OFF mode.
2. The air handler is OFF.
a. The outside air damper is CLOSED.
b. The exhaust damper is CLOSED.
c. The mixed air damper is OPEN.
d. The supply fan is OFF.
e. The return fan is OFF
f. Chilled water control valve is CLOSED.
g. Heating water control valve is CLOSED.
Field Notes:

SUPPLY AIR TEMPERATURE CONTROL


7 Enable occupied mode via the BMS. 1. The air handling unit is in the occupied mode.
2. The air handling unit is ON.
Supply air temperature control is a. The outside air damper modulates to the
operating in fixed setpoint mode. MINIMUM.
b. The exhaust air damper modulates to maintain
NOTE: Lock out economizer mode for this equal airflow – SUPPLY= RETURN.
portion of the test. c. The mixed air damper remains OPEN.
d. The supply fan modulates to maintain the
supply duct static pressure setpoint.
e. The chilled water control valve modulates open
as needed to maintain the supply air
temperature setpoint. OR
f. The heating water control valve modulates
open as needed to maintain the supply air
temperature setpoint.
g. The Supply Fan VFD modulates to maintain the
Static Pressure setpoint.
h. The Return fan modulates to track the supply
fan with measured volume of Return = Supply.
Field Notes:

Project Name Page 6 of 17 Functional Test Procedure


Air Handling Unit AHU-00
New Mexico Public School Facilities Authority
1312 Basehart Rd. SE, Suite 200
Albuquerque, NM 87106-4368
Functional Test Procedure
AIR HANDLING UNIT AHU-00

8 Allow system to achieve equilibrium. 1. Unit is operating normally.

Supply Air Temp. Setpoint: ____°F


Chilled water valve Position: ______%
Heating water valve Position: ______%
Supply Fan VFD _______Hz ________%
Return Fan VFD _______Hz ________%
Field Notes:

9 Lower the supply air temperature set point 1. Chilled water valve modulates open to achieve
10°F below the current supply air supply air temperature set point.
temperature.
Programmed Setpoint: _____°F New Supply Air Temp. Setpoint: ____°F
Allow system to achieve equilibrium. Supply Air Temp.: _____°F
Chilled Water Valve Position: ______%
Heating Water Valve Position: ______%
Supply Fan VFD _______Hz ________%
Return Fan VFD _______Hz ________%
Field Notes:

10 Check for Heating Water Valve Leakage. 1. Heating water valve is closed.
Allow fan to run for at least five minutes
with heating water valve closed. Water ΔT: ____°F
Measure water temp drop across the coil
to check for heating water leak-by.
If water delta T is greater than 2°F, leakage may be
occurring.
Field Notes:

Project Name Page 7 of 17 Functional Test Procedure


Air Handling Unit AHU-00
New Mexico Public School Facilities Authority
1312 Basehart Rd. SE, Suite 200
Albuquerque, NM 87106-4368
Functional Test Procedure
AIR HANDLING UNIT AHU-00

11 Raise the supply air temperature set point 1. Chilled and Heating water valves modulate to
15°F above the current supply air achieve supply air temperature set point.
temperature.
New Supply Air Temp. Setpoint: ____°F
Allow system to achieve equilibrium. Supply Air Temp.: _____°F
Chilled Water Valve Position: ______%
Heating Water Valve Position: ______%
Supply Fan VFD _______Hz ________%
Return Fan VFD _______Hz ________%
Field Notes:

12 Check for chilled water valve leakage. 1. Chilled water valve is closed.
Allow fan to run for at least five minutes
with chilled water valve closed. Water ΔT: ____°F
Measure water temp drop across the coil
to check for chilled water leak-by.
If water delta T is greater than 2°F, leakage may be
occurring.
Field Notes:

13 Return supply air temperature setpoint to Chilled and heating water valves modulate to maintain
original value. setpoint.

New Supply Air Temp. Setpoint: ____°F


Supply Air Temp.: _____°F
Chilled Water Valve Position: ______%
Heating Water Valve Position: ______%
Supply Fan VFD _______Hz ________%
Return Fan VFD _______Hz ________%
Field Notes:

Project Name Page 8 of 17 Functional Test Procedure


Air Handling Unit AHU-00
New Mexico Public School Facilities Authority
1312 Basehart Rd. SE, Suite 200
Albuquerque, NM 87106-4368
Functional Test Procedure
AIR HANDLING UNIT AHU-00

SUPPLY AIR TEMPERATURE RESET


14 Verify the supply air temperature setpoint 1. After an initial delay, the SA temp setpoint is reset
is at 53°F, from previous step. 0.2°F higher every 2 minutes.
2. The chilled and heating water valves modulate to
Globally change zone temperature set maintain the new SA temp setpoint.
points to 80°F, such that all the
associated VAVs are in heating mode. Initial SAT Setpoint.: _____°F
Final SAT Setpoint: _____°F
Allow system to run for 20 minutes. Low SAT Reset Temp: _____°F
Hi SAT Reset Temp: _____°F
Chilled Water Valve Position: ______%
Heating Water Valve Position: ______%
Field Notes:

15 Globally change zone temperature set 1. The supply air temperature setpoint is reset 0.5°F
points to 60°F, such that all the lower every 1 minute.
associated VAVs are in cooling mode. 2. The chilled water valves modulate to maintain the
new SA temp setpoint.
Allow system to run for 20 minutes.
Initial SAT Setpoint.: _____°F
Final SAT Setpoint: _____°F
Chilled Water Valve Position: ______%
Heating Water Valve Position: ______%
Field Notes:

16 Return all parameters to their initial 1. Unit resumes supply air setpoint mode operation.
values.
Field Notes:

Project Name Page 9 of 17 Functional Test Procedure


Air Handling Unit AHU-00
New Mexico Public School Facilities Authority
1312 Basehart Rd. SE, Suite 200
Albuquerque, NM 87106-4368
Functional Test Procedure
AIR HANDLING UNIT AHU-00

ECONOMIZER MODE
17 Place air handling unit into economizer 1. The air handling unit is in economizer mode.
mode by simulating a return air enthalpy a. The outside air damper modulates open to
reading above the OSA enthalpy reading. maintain the SA temp setpoint
b. Chilled and heating water control valves
Allow system to achieve equilibrium. modulate to closed.
2. Verify unit is meeting setpoints and is operating
normally.
Economizer Damper Position: _____%
Return Air Enthalpy: _____°F
Outside Air Enthalpy: _____°F
Chilled Water Valve Position: ______%
Heating Water Valve Position: ______%
Field Notes:

18 Disable economizer mode by simulating a 1. The air handling unit is not in economizer mode.
return air enthalpy reading below the OSA a. The outside air damper closes.
enthalpy reading.
b. Chilled and hot water valves modulate to
maintain the supply air temperature setpoint.
Allow system to achieve equilibrium. 2. Verify unit is meeting setpoints and is operating
normally.
Field Notes:

19 Return all setpoints and parameters to 1. The air handler returns to normal operation.
their original values.

Field Notes:

Project Name Page 10 of 17 Functional Test Procedure


Air Handling Unit AHU-00
New Mexico Public School Facilities Authority
1312 Basehart Rd. SE, Suite 200
Albuquerque, NM 87106-4368
Functional Test Procedure
AIR HANDLING UNIT AHU-00

RETURN CO2 CONTROL


20 Lower the Return CO2 setpoint 200 PPM 1. The outside air dampers modulate open to
below current Return CO2 level. maintain return CO2 below new setpoint.

Field Notes:

21 Raise the Return CO2 setpoint 200 PPM 1. The outside air dampers close to minimum
above current Return CO2 level. position.

Field Notes:

22 Return all setpoints and parameters to 1. The air handler returns to normal operation.
their original values.
Field Notes:

SUPPLY DUCT STATIC PRESSURE CONTROL


23 Allow system to achieve equilibrium. 1. Unit is meeting setpoints and is operating normally.
2. Supply fan is meeting the supply air static pressure
setpoint.
3. Return fan modulates to track the supply fan speed
with measured volume of Return = Supply.

Static Pressure SP: ____ in. wg


Static Pressure: ____ in. wg.
Supply Fan Speed: _____%
Return Fan Speed: _____%
Supply Fan Volume: _____ CFM
Return Fan Volume: ______ CFM
Field Notes:

Project Name Page 11 of 17 Functional Test Procedure


Air Handling Unit AHU-00
New Mexico Public School Facilities Authority
1312 Basehart Rd. SE, Suite 200
Albuquerque, NM 87106-4368
Functional Test Procedure
AIR HANDLING UNIT AHU-00

24 Partially block the Supply Air Discharge 1. The supply fan modulates to meet the new supply
approximately half way to introduce a air static pressure setpoint
higher than the current supply air static 2. Return fan modulates to track the supply fan speed
pressure. with measured volume of Return = Supply.

Allow system to achieve equilibrium. Static Pressure SP: ____ in. wg


Static Pressure: ____ in. wg.
Supply Fan Speed: _____%
Return Fan Speed: _____%
Supply Fan Volume: _____ CFM
Return Fan Volume: ______ CFM
Field Notes:

25 Remove the Supply Air Discharge 1. Unit resumes normal operation.


blockage.
Field Notes:

RETURN DUCT AIRFLOW CONTROL


26 Allow system to achieve equilibrium. 1. Unit is meeting setpoints and is operating normally.
2. Supply fan is meeting the supply air static pressure
setpoint.
3. Return fan modulates to track the supply fan speed
with measured volume of Return = Supply.

Static Pressure SP: ____ in. wg


Static Pressure: ____ in. wg.
Supply Fan Speed: _____%
Return Fan Speed: _____%
Supply Fan Volume: _____ CFM
Return Fan Volume: ______ CFM
Field Notes:

Project Name Page 12 of 17 Functional Test Procedure


Air Handling Unit AHU-00
New Mexico Public School Facilities Authority
1312 Basehart Rd. SE, Suite 200
Albuquerque, NM 87106-4368
Functional Test Procedure
AIR HANDLING UNIT AHU-00

27 Partially block the Return Air Intake 1. The supply fan modulates to meet the new supply
approximately half way to introduce a air static pressure setpoint
lower than the current return air flow. 2. Return fan modulates to track the supply fan speed
with measured volume of Return = Supply.
Allow system to achieve equilibrium.
Static Pressure SP: ____ in. wg
Static Pressure: ____ in. wg.
Supply Fan Speed: _____%
Return Fan Speed: _____%
Supply Fan Volume: _____ CFM
Return Fan Volume: ______ CFM
Field Notes:

28 Remove the Return Air Intake blockage. 1. Unit resumes normal operation.
Field Notes:

SUPPLY DUCT STATIC PRESSURE RESET – WILL BE COMPLETED WHEN SYSTEM IS BUILT OUT
29 Globally change damper positions such 1. Supply duct static pressure is increased 0.1 in. wg
that all the associated VAVs are at 90% increments
open. 2. Supply fan is meeting the new supply air static
pressure setpoint.
Allow system to run for 10 minutes. 3. Return fan modulates to track the supply fan speed
with measured volume of Return = Supply.

Initial Static Pressure SP: ____ in. wg


Final Static Pressure SP: ____ in. wg
High Reset Static Pressure: ____ in. wg
Low Reset Static Pressure: ____ in. wg
Field Notes:

Project Name Page 13 of 17 Functional Test Procedure


Air Handling Unit AHU-00
New Mexico Public School Facilities Authority
1312 Basehart Rd. SE, Suite 200
Albuquerque, NM 87106-4368
Functional Test Procedure
AIR HANDLING UNIT AHU-00

30 Globally change damper positions such 1. Supply duct static pressure is decreased 0.1 in. wg
that all the associated VAVs are at 40% increments
open. 2. Supply fan is meeting the new supply air static
pressure setpoint.
Allow system to run for 10 minutes. 3. Return fan modulates to track the supply fan speed
with measured volume of Return = Supply.

Initial Static Pressure SP: ____ in. wg


Final Static Pressure SP: ____ in. wg
Field Notes:

31 Return all parameters to their initial 1. Unit resumes normal operation.


values.
Field Notes:

VERIFICATION OF SAFETIES & ALARMS


32 Supply Fan Fault: 1. Supply fan fault alarm received at BAS
Move the H-O-A switch into the HAND workstation.
position – at VFD, set drive to Start and
2. System shut down is enabled.
Run at 55 Hz or more.
3. Supply and Return fans are de-energized.
With supply fan running, remove electrical
power at local disconnect or breaker. 4. Outside Air and Relief Dampers close.
Confirm system shutdown and alarm 5. Return Air Damper Opens.
notification at BAS workstation. 6. Chilled Water Valve closes.
Repeat test with H-O-A switch in the 7. BAS workstation graphics show correct status
AUTO position by removing the forced and/or value of field devices.
setting

Field Notes:
Alarm Notification at BAS: PASS / FAIL
System Shut Down – Hand Mode: PASS / FAIL
System Shut Down – Auto Mode: PASS / FAIL

33 Restore electrical power to supply fan. 1. BAS acknowledges alarm condition is cleared.
Acknowledge and clear alarm at BAS 2. System re-start is enabled
workstation.
3. Fans, valves and dampers resume normal
Confirm system re-starts. operation.
Allow system to achieve equilibrium. 4. BAS workstation graphics show correct status
and/or value of field devices.

Project Name Page 14 of 17 Functional Test Procedure


Air Handling Unit AHU-00
New Mexico Public School Facilities Authority
1312 Basehart Rd. SE, Suite 200
Albuquerque, NM 87106-4368
Functional Test Procedure
AIR HANDLING UNIT AHU-00

Field Notes:
Alarm Acknowledged and Cleared at BAS: PASS / FAIL
Air Handling Unit Restarts and resumes normal operation: PASS / FAIL

34 Return Fan Fault: 1. Return fan fault alarm received at BAS


Move the H-O-A switch into the HAND workstation.
position – at VFD, set drive to Start and
2. System shut down is enabled.
Run at 55 Hz or more.
3. Return fan is de-energized.
With supply fan running, remove electrical
power at local disconnect or breaker. 4. Supply fan remains running.
Confirm system shutdown and alarm 5. Outside Air and Relief Dampers close.
notification at BAS workstation. 6. Return Air Damper Opens.
Repeat test with H-O-A switch in the 7. Chilled Water Valve closes.
AUTO position by removing the forced
setting 8. BAS workstation graphics show correct status
and/or value of field devices.

Field Notes:
Alarm Notification at BAS: PASS / FAIL
System Shut Down – Hand Mode: PASS / FAIL
System Shut Down – Auto Mode: PASS / FAIL

35 Restore electrical power to return fan. 1. BAS acknowledges alarm condition is cleared.
Acknowledge and clear alarm at BAS 2. System re-start is enabled
workstation.
3. Fans, valves and dampers resume normal
Confirm system re-starts. operation.
Allow system to achieve equilibrium. 4. BAS workstation graphics show correct status
and/or value of field devices.

Field Notes:
Alarm Acknowledged and Cleared at BAS: PASS / FAIL
Air Handling Unit Restarts and resumes normal operation: PASS / FAIL

36 High Supply Air Static Pressure Alarm: 1. High Pressure alarm received at BAS workstation.
Move the H-O-A switch into the HAND 2. System shut down is enabled.
position– at VFD, set drive to Start and
Run at 60 Hz. 3. Supply and Return fans are de-energized.
With supply fan running, manually trip 4. Outside Air and Relief Dampers close.
High Pressure cut-out switch using hand 5. Return Air Damper Opens.
help pump with gage.
6. Chilled Water Valve closes.
Confirm system shutdown and alarm
notification at BAS workstation. 7. Hot water valve closes.
Repeat test with H-O-A switch in the 8. BAS workstation graphics show correct status
AUTO position. and/or value of field devices.

Project Name Page 15 of 17 Functional Test Procedure


Air Handling Unit AHU-00
New Mexico Public School Facilities Authority
1312 Basehart Rd. SE, Suite 200
Albuquerque, NM 87106-4368
Functional Test Procedure
AIR HANDLING UNIT AHU-00

Field Notes:
Alarm Notification at BAS: PASS / FAIL
System Shut Down – Hand Mode: PASS / FAIL
System Shut Down – Auto Mode: PASS / FAIL

37 Reset High Pressure cut-out switch back 1. BAS acknowledges alarm condition is cleared.
to normal operation.
2. System re-start is enabled
Acknowledge and clear alarm at BAS
3. Fans, valves and dampers resume normal
workstation.
operation.
Confirm system re-starts.
4. BAS workstation graphics show correct status
Allow system to achieve equilibrium. and/or value of field devices.

Field Notes:
Alarm Acknowledged and Cleared at BAS: PASS / FAIL
Air Handling Unit Restarts and resumes normal operation: PASS / FAIL

38 Dirty Pre-Filter Alarm: 1. Dirty pre-filter alarm is generated at the BAS


Simulate a dirty filter alarm at the pre- Workstation.
filter.
Field Notes:

39 Dirty Final Filter Alarm: 1. Dirty final filter alarm is generated at the BAS
Simulate a dirty filter alarm at the final Workstation.
filter.
Field Notes:

40 Dirty Carbon Filter Alarm: 2. Dirty carbon filter alarm is generated at the BAS
Simulate a dirty filter alarm at the final Workstation.
filter.
Field Notes:

41 Return all parameters to their initial 1. Unit resumes normal operation.


values.
Field Notes:

Note: Duct Detector and Sequence will be tested as part of the Fire Detection System by the
LAHJ. Jacobs will receive and review their report.

END OF TEST
DATE:
Project Name Page 16 of 17 Functional Test Procedure
Air Handling Unit AHU-00
New Mexico Public School Facilities Authority
1312 Basehart Rd. SE, Suite 200
Albuquerque, NM 87106-4368
Functional Test Procedure
AIR HANDLING UNIT AHU-00

SUMMARY OF RESULTS:

LESSONS LEARNED:


CORRECTIVE ISSUES:


Acceptance of Test:

This test cannot be accepted at this time due to the Corrective Issues noted above.
This test is accepted by the Performance Assurance Authority identified below. Any
Corrective Issues noted above do not adversely impact the overall performance of the
system.

Witnessed Date
Performance Assurance Authority

Project Name Page 17 of 17 Functional Test Procedure


Air Handling Unit AHU-00

You might also like