Building Automation Systems
Building Automation Systems
The Building Automation system (BAS) shall consist of a centralized, PC-based operating station, for controlling, monitoring, and data
processing of major building systems and equipment. The centralized station is to be connected via its data network to de-centralized,
stand-alone programmable controllers. The network shall allow “Peer-to-Peer” communication. The BAS must have the ability to
control and interconnect components from different manufacturers. It must provide bi-directional data communication and coordinated
control via real-time data exchange through a common communications data exchange protocol. Integration shall extend to the
operator’s workstation software, which shall support user interaction with ALL control system components. Components from
manufacturers committed to working in an open protocol environment, such as BACnet per ASHRAE Standard 135, shall be utilized to
minimize the costs of providing integration and to allow interoperability between building systems and control vendors. Other open
protocol language systems, such as LonTalk, may also be used, provided there is compatibility with overall regional and/or central
monitoring and central strategies.
Fire alarm systems, security systems and elevator systems shall not be controlled by the BAS. These systems shall have independent
control panels and networks. The BAS system shall monitor the status of these systems only, in order to prompt emergency operating
modes of HVAC and lighting systems.
Please refer to the Sustainability section of the technical standards for additional information pertaining to sustainable design
requirements and their impact to the building automation system design and sequences of operation.
HVAC control algorithms shall include optimized start / stop for chillers, boilers, air handling units and all associated equipment and
feed forward controls based on predicted weather patterns. Lighting control shall be accomplished by use of separate control
equipment, which allows BAS monitoring and reporting and control settings. Optimal start / stop is to calculate the earliest time systems
can be shut down prior to the end of occupancy hours, and the latest time systems can start up in the morning with the aim of
minimizing equipment run time without letting space conditions drift outside comfort set points. A system that incorporates a Weather
Prediction Program, which stores historic weather data in memory and uses this information to anticipate peaks or part load conditions,
is highly desired. This information shall also be utilized to run economizer cycles and heat recovery equipment.
The BAS shall include control algorithms that switch pumps, compressors, boilers, etc. from “operating equipment” to “stand-by” on a
scheduled basis. Also, the BAS shall provide maintenance schedules for equipment in every identified building system, complete with
information on parts and tools needed to perform each task.
The BAS shall have the capability to allow building staff to measure energy consumption and monitor performance. Electrical values,
such as V, A, kW, KVAR, KVA, Power Factor (PF), kWh, KVARH, Frequency and Percent Total Harmonic Distortion (THD), shall be
measured.
Energy management measurements shall be totalized and trended in both instantaneous and time-based numbers for chillers, boilers,
air-handling units, pumps, etc. Energy monitoring data shall be automatically converted to standard database and spreadsheet format
and transmitted to a designated PC. Energy points are those points that are monitored to ensure compliance with ASHRAE Standard
90.1.
Hyatt Technical Standards and Guidance – Q1 2020 / Section last revised: Q1 2018 / Confidential and Proprietary Information 1
401
Building Automation Systems
The extent of automation, monitoring, and control will vary from project to project, but shall typically include the BAS points described in
the Sample BAS Points Schedule included in subsection 1.5 below
The consultant shall present a detailed report of the intended Scope of Coverage for the BAS and liaise with contracted suppliers and
manufacturers to ensure the system is fully functional in accordance with Design Services minimum standards.
Building Infrastructure / “Central Plant” – The BAS is primarily intended to interface with the major MEP components of the building
including, but not limited to:
• Cooling Towers and associated Pumps, Valves and Water Treatment Equipment
• Boilers / Water Heaters and associated Pumps, Valves and Water Treatment Equipment
Hyatt Technical Standards and Guidance – Q1 2020 / Section last revised: Q1 2018 / Confidential and Proprietary Information 2
402
Building Automation Systems
At minimum, a central host computer and control console shall be located in the Engineering Office area, with repeater workstations at
Communication Center and Security Command Center. The equipment must be located in a fully air-conditioned room with a direct
power feed from a UPS connection with either 15 minutes of power if also connected to the Emergency Generator, or a two hour,
battery back-up system if a Generator is not present. The repeater workstations can be realized via pop-up menus at a PC workstation
in those areas. The BAS host computer must be connected to the hotel Local Area Network via Ethernet based on TCP/IP protocol. If
the Hotel is part of a larger complex (e.g. one that contains residential, office and/or commercial components), an independent hotel
BAS workstation is required and may be linked to the Master Control Console for the entire complex only for monitoring and alarm
functions.
The system must have the following features:
• Color, graphical floor plan and schematics display for mechanical systems as specified in the approved Data Reporting Point
schedule.
• Ability to monitor indoor air quality in accordance with Design Services HVAC minimum standards
• Alarm management to monitor, buffer, and direct alarm reports to operator devices and memory files. Each decentralized
controller panel shall perform distributed, independent alarm analysis, prioritizing and filtering.
• Auto-dial alarm shall be included (critical alarms shall initiate a call to a remote operator device).
• Web Based Operator Interface to allow access to BAS data retrieval via the Internet or Intranet. This interface shall use HTML-
based pages to send and receive data from the BAS system to a web browser. The interface shall provide several levels of
user access, from read only access to modify data.
• Compatible with other systems, which may require interfaces, or become part of the BAS include:
§ Security Systems
§ Fire Alarm Systems to the extent permitted by code
§ Lighting Control System
§ Lift Status Indication
§ Property Management System
§ Kitchen Refrigeration System
§ Sustainable Systems
• (Optional) Interface to the Property Management System (Oracle Opera) to manage and control MEP systems and energy
consumption in Guestrooms at the Front Desk.
• Provide standard communication protocol for transfer of meter reading data from the Building Automation System into the
hotel's Web-based Energy Reporting system.
• Energy Management features to provide efficient control of all MEP systems minimally including:
§ Non-essential load shedding
§ Scheduling of lighting and fan operation
§ Temperature offset for all hotel areas when unoccupied
o Graphical and tabular reporting
§ Recording of data from all sub-metering devices. See section 1.6 below for sub-metering requirements.
• Provide interface to the hotel supplied Computerized Maintenance Management System (CMMS) that provides a more
extensive scheduling, control and escalation of periodical preventative maintenance, inventory control, tracking, escalation of
unresolved problems, etc.
Hyatt Technical Standards and Guidance – Q1 2020 / Section last revised: Q1 2018 / Confidential and Proprietary Information 3
403
Building Automation Systems
Please see section Guestroom Power, Data, Lighting and Controls in Building Systems for additional information on technology and
controls required for the guestrooms.
Guestrooms – Typical: Controlled by “Stand Alone” Digital Thermostat and local Lighting Controls. Thermostat is interfaced with
Property Management System (PMS) to achieve temperature offset when Guestroom is either “Unsold” or “Unoccupied”. May also
utilize a local “Room Control Unit” (RCU) to de-energize additional, specified power connections when Guestroom is either “Unsold” or
“Unoccupied”.
Guestrooms – Optional: Provide Digital Controls connected to the BAS network to monitor operating conditions and functions of:
Guestroom Fan Coil Unit, Thermostat and Lighting Controls. May also utilize a local Room Control Unit (RCU) that interfaces with the
Property Management System to de-energize additional, specified power connections when Guestroom is either “Unsold” or
“Unoccupied”.
As required for above, additional controls are to be provided on Exterior Doors and (operable) Exterior Windows to control Fan Coil Unit
operation when either are “open” for an extended period of time.
Command On/Off 2 2
Status On/Off 2 2
Status (low/high) 2 2
Burner Lockout 2 2
Burner Status 2 2
Burner Trip 2 2
Gas Meter 2 2
Pressure 2 2
Hyatt Technical Standards and Guidance – Q1 2020 / Section last revised: Q1 2018 / Confidential and Proprietary Information 4
404
Building Automation Systems
Command On/Off 6
Pump Status 6
Pump Trip 6
Pump Status 1 1
Pump Trip 1 1
Supply Temperature 5
TOTAL 17 11 37 8
2. FANS
Fan Status 6
Fan Trip 6
Fan On/Off 6
Hyatt Technical Standards and Guidance – Q1 2020 / Section last revised: Q1 2018 / Confidential and Proprietary Information 5
405
Building Automation Systems
Fan Status 6
Fan Trip 6
Fan On/Off 6
TOTAL 0 0 24 12
Incoming Meter 1
TOTAL 1 0 8 0
Trip 1 1
Pump Status 3 3
TOTAL 0 0 5
TOTAL 1 0 3 0
6. LIFTS 12
TOTAL 12 0 12 0
Pumps 20
Hyatt Technical Standards and Guidance – Q1 2020 / Section last revised: Q1 2018 / Confidential and Proprietary Information 6
406
Building Automation Systems
Pump Status 20
Pump Trip 20
MCC 11
Power Consumption 11
Water Consumption 11
TOTAL 13 0 52 0
Chiller Status 6
Chiller Tripping 6
Chiller On/Off 6
Compressor Run/Trip 24
Secondary Pumps 8
Hyatt Technical Standards and Guidance – Q1 2020 / Section last revised: Q1 2018 / Confidential and Proprietary Information 7
407
Building Automation Systems
Butterfly Valves 6
TOTAL 10 12 106 26
Flow Switch 1 1
TOTAL 0 0 12 2
TOTAL 0 0 12 0
TOTAL 5 0 0 0
Hyatt Technical Standards and Guidance – Q1 2020 / Section last revised: Q1 2018 / Confidential and Proprietary Information 8
408
Building Automation Systems
Filter DPS 20
Chilled Water VM 20
Hot Water VM 20
Fresh Air DM 20
Return Air DM 20
Exhaust Air DM 20
Water Humidifier 20
Filter DPS 5
Chilled Water VM 5
Hot Water VM 5
Fresh Air DM 5
Hyatt Technical Standards and Guidance – Q1 2020 / Section last revised: Q1 2018 / Confidential and Proprietary Information 9
409
Building Automation Systems
TOTAL 10 10 25 10
14.1 Feeder 2
Status 1
Trip 1
14.4 Transformer 1
TOTAL 8 0 6 0
Status 5
Trip 5
Hyatt Technical Standards and Guidance – Q1 2020 / Section last revised: Q1 2018 / Confidential and Proprietary Information 10
410
Building Automation Systems
15.3 Transformer 5
Status 5
Consumption (KwH) 5
Consumption (fuel) 5
TOTAL 10 0 65 0
Hyatt Technical Standards and Guidance – Q1 2020 / Section last revised: Q1 2018 / Confidential and Proprietary Information 11
411
Building Automation Systems
AREA GAS DIESEL OIL STEAM HOT WATER COLD WATER ELECTRICITY
Main Laundry X X X X X
Emergency Generator X X
Water Heaters X X X
Steam Boilers X X X
Chillers X* X X
Commissary Kitchens X X* X X X
Banquet Kitchens X X* X X X
Serviced Apartments X X* X X X
* = As applicable
Additional sub-meters may be required for Sustainable Systems including, but not limited to, total lighting power, plug load power, on-
site power generation, condensate collection, etc.
All meters to be compatible with the Building Automation System and permit automatic recording, storage, retreival and analysis of
data. Meters shall provided accurate measurement within +/- 1% over the anticipated range of flows, pressures, temperatures and
power consumption to be measured.
Hyatt Technical Standards and Guidance – Q1 2020 / Section last revised: Q1 2018 / Confidential and Proprietary Information 12
412
Building Automation Systems
A. Experience Record
The manufacturer and installer shall have no less than 5 years of documented experience in the manufacture or
installation of the work in this field, and shall be able to provide professional commissioning of the system. The BAS
manufacturer shall provide a list of 5 comparable projects with a similar scope of work that are successfully in operation
utilizing the products planned for the Hyatt property. The BAS manufacturer shall employ specialists in the field for
Engineering, Programming, Installation, Field Supervision, Start-up, Testing, Commissioning and Training. The
specialists shall have a minimum of 5 years experience in their respective fields and roles.
B. Future Expansion
The BAS system shall be designed to allow future expansion utilizing open protocol system programming. The elements
of the system shall be modular in design with provision for increased capacity.
C. Installation, Commissioning and Training
The BAS manufacturer shall be responsible for providing a project-specific installation, commissioning and training
program to Hyatt Design Services for review and approval.
D. Spare Parts and Maintenance
An extended maintenance agreement and spare parts list shall be submitted to Hyatt Design Services for review and
approval, together with a schedule of anticipated costs for a 5-year period after the standard warranty period has
expired.
E. Emergency Service
Emergency service shall be available on a 24-hour, 7 day per week basis.
Hyatt Technical Standards and Guidance – Q1 2020 / Section last revised: Q1 2018 / Confidential and Proprietary Information 13
413