K45 Dealer Manual 20110826
K45 Dealer Manual 20110826
DEALER MANUAL
K45-2 Engine Control Panel
FOR USE ON J1939 OR MECHANICAL
DIESEL ENGINES
Table of Contents
Table of Contents ...........................................................................................................2
1 General Warning ....................................................................................................4
2 Fly-back Diode Installation....................................................................................5
3 Considerations Prior to Operation .........................................................................5
4 Notes about this manual.........................................................................................6
5 Notes about the K45-2 ...........................................................................................6
6 Features of the K45-2 Control Panel .....................................................................6
7 Interface Panel .......................................................................................................7
7.1 Interface Button Layout .................................................................................7
7.1.1 The K45-2 Interface buttons / switches .................................................7
7.2 Interface LEDs and LCD Display..................................................................8
7.2.1 LCD display with back light ..................................................................8
7.2.2 Warning and Fault LEDs .......................................................................8
7.2.3 Manual mode LED.................................................................................8
8 Basic Operation......................................................................................................8
8.1 Starting the engine .........................................................................................8
8.1.1 Starting in manual start mode ................................................................8
8.1.2 Starting in automatic mode....................................................................9
8.1.3 Stopping the Engine ...............................................................................9
9 Menu Items and Setup .........................................................................................10
9.1 Main Display (RPM Screen)........................................................................10
9.2 Menu Screens...............................................................................................10
9.3 The Run Stop timer......................................................................................11
9.3.1 Setting the Stop timer...........................................................................11
9.3.2 Aborting the Stop timer .......................................................................11
9.4 Settings Menu ..............................................................................................13
9.4.1 Engine Parameters ...............................................................................14
9.4.2 Throttle Parameters (when Enabled) ...................................................18
9.4.3 4-20mA Sensor Parameters..................................................................22
9.4.3.1 Flow Parameters...............................................................................23
9.4.3.2 Pump Parameters .............................................................................24
9.4.4 Fuel Level Sender Parameters .............................................................26
9.4.5 Pump Oil Temperature Parameters ......................................................27
9.4.6 Pump Pressure #2.................................................................................28
9.4.7 Digital inputs........................................................................................30
9.4.8 Vacuum Priming ..................................................................................32
9.4.9 Flow Switch .........................................................................................34
9.4.10 Reset Fault History ..............................................................................36
9.4.11 Start Types ...........................................................................................37
9.4.12 MODBUS ............................................................................................38
9.4.12.1 MODBUS Communications ........................................................38
9.5 ECU Warnings and Faults ...........................................................................39
9.5.1 View Codes Present (No Fault Present)...............................................40
9.6 System Information......................................................................................41
9.7 Fault History ................................................................................................42
9.8 Engine Configuration...................................................................................42
10 Default Settings and Definitions......................................................................44
11 Troubleshooting (Fault Finding)......................................................................47
11.1 Serviceable Parts ..........................................................................................47
Contact Details:
1 General Warning
Prior to Installation
- Remove all electrical power from controller and engine
- Ensure machine is safely secured during installation
- Check and follow all safety warnings and read all instruction manuals carefully
- Only use the controller for its intended purpose.
Note:
If you have purchased this control panel with the engine, it is likely that the fly-
back diodes have been fitted to the engine wiring loom by the engine
manufacturer or panel installer. Ask your place or purchase to confirm that all
necessary diodes have been fitted.
7 Interface Panel
PANEL
7.1 Interface Button Layout ON/OFF
INC/DEC
TOGGLE
LIGHTS
ON/OFF
PANEL
FUSES
WARNING
/ FAULT
LEDs
7.1.1 The K45-2 Interface buttons / switches
Interface Button Purpose
MENU The MENU button allows access to the menu structure.
Pressing once while on the main screen enters the menu.
Further presses cycle back through the various menus.
DOWN The DOWN button allows for scrolling through menu
items and the decreasing of various values. This is
signified on the screen by ↓
UP The UP button allows for scrolling through menu items
and the increasing of various values. This is signified on
the screen by ↑
ENTER The ENTER button is used to alter values and confirm
changes. Pressing this button in the main menu will enter a
sub menu.
AUTO The AUTO button will place the K45-2 into Automatic
mode.
STOP The STOP button will stop the engine. The Engine
Cooldown Timer will commence. Pressing STOP a 2nd
time will bypass the cooldown timer.
MANUAL START The MANUAL START button will manually run the
engine by starting it immediately.
INC/DEC TOGGLE The INC/DEC toggle switch allows for a RPM trim
SWITCH adjustment between the Speed Select speed points.
8 Basic Operation
8.1 Starting the engine
As a general rule, auto-start functions and engine protection features are identical in
both manual start and automatic start modes, with the exception of the Stop Timer
function which will only operate in manual mode only. All bypass timers begin their
count down from engine start/running.
The moment the engine starts an automatic bypass timer on all sensors is active. The
duration of this time can vary depending on how the K45-2 or ECU has been set up. A
minimum engine sensor lock out time of 20 seconds applies to all sensors accept for
low oil pressure, this is typically less than 20 seconds.
On a successful start the LCD display will show the engine RPM, Battery Voltage and
Engine Hours.
1500RPM 12.5VDC
125.0HRS
23PSI 40’C
Status: Running@Load
Main Display
When the engine has started, the engine speed can be quickly adjusted by toggling the
increment/decrement switch. The idle and load speeds can be set and adjusted in the
controller software which can be accessed by pressing the MENU button, however
they may not be accessed whilst the engine is running.
To use the unit in Remote Auto-start mode the controller must be set in Auto Mode.
This is achieved by pressing the AUTO button. Once in auto mode the Manual mode
LED will be off and the display will show “Status:Auto:”.
To initiate a start in auto mode the Remote Start Input must be triggered. These are
two wires, usually brown and black, provided at the base of the controller.
The start input is either a maintained or momentary input. Please refer to the
schematic for your particular setup. The default setup is a maintained input. This is
user definable in User Settings Menu under Start Types.
Maintained operation is usually a “close to start / open to stop” setup. i.e.
while the contacts are closed the engine will be running. When the contacts are open
the engine will stop.
Momentary operation uses two (active ground) inputs in the controller to start
and stop the engine. The same Remote Start Input starts the engine and Remote Stop
Input stops the engine.
To avoid false starts the Remote Start Input must be closed for at least 4 seconds
before are crank to start will occur. If the Remote Start Input has been triggered the
display will show “Status:StartActive” and a countdown timer.
If the contactor opens before the elapsed timer the controller will wait for another start
signal. The slush timer on this input is useful when using single or two floats to start
and stop the engine.
If the timer reaches 0 the normal start procedure will occur as per in manual mode.
1500RPM 12.5VDC
125.0HRS
Pls WAIT or hit STOP
Status: Cooldown 10
On any stop the shutdown screen above will appear. In the case of a mechanical style
engine the screen will appear until the engine RPM drops to zero and/or the
stabilization counter has elapsed. In the case of an electronic engine with an onboard
ECU, the shutdown period will last for the entire Stabilization timer. No other
operations can be down during this time. The Stabilize period is a safeguard to the
ECU ignition input.
Sleep Mode
When the controller is waiting for a start and no buttons have been pressed for
approximately 10mins the K45-2 will go into sleep mode to conserve battery power.
The unit is still active but the backlight will be turned off.
RPM, Battery voltage and engine hours are displayed at all times on the main display.
Depending on usage, extra engine data may be displayed on alternative screens that
can be displayed by pressing the buttons.
** Please Note: it is always good practice to return to the main RPM display
screen before starting as other information is displayed at various times.
MENU
4. View Active Codes
5. System Info
6. Fault History
MENU
7. Engine Config.
• Press the buttons to alter the hours. Press ENTER to save the changes.
• The screen will now show:
• Press buttons to alter the minutes. Press ENTER to save the changes.
• The screen will now return to the main menu.
• Press MENU to return to the RPM screen.
• The screen will now show:
1500RPM 12.5VDC
125.0HRS
Stop in - 05:30:29
Status: OK
The timer will commence when the engine has started and the K45-2 has detected
engine RPMs. The hourglass will be animated when the stop timer is active. Upon
completion, the engine will be stopped and the screen will show:
Normal : Shutdown
Timer Complete!
Press ENTER to
Cancel Stop Timer
Enter Password
01: 01:01:01
• Use the buttons to enter the required value and press ENTER to proceed to
the next. Once all 4 have been set press ENTER
A correct password will allow access to the Setup Menu. For an incorrect password,
“Wrong password Please Re-enter” will momentarily appear and the screen will
return to the Settings Menu.
• Press to cycle through all available menu headings as per below
SETUP
>1. Engine
2. Throttle
3. 4-20mA Sensor
SETUP
4. Fuel Level
5. Pump Oil Temp.
6. Pump Pressure #2
SETUP
7. Vacuum Priming
8. Reset History
9. Start Types
SETUP
10. MODBUS
Each of these items is associated with different parameters described in detail below.
Please note, that at any time the MENU button can be pressed to exit any screen and
to return to the RPM screen. Refer to section 7.1.1 for the K45-2 Interface buttons /
switches functionality.
• Press ENTER then to alter the engine Underspeed set point. Then press
ENTER once again to save the value. If the engine speed falls below this value
for a minimum of 4 seconds an engine shutdown will occur.
• Press the button to move to the next item. The screen will show:
Engine Parameters
6. Overspeed
1950 rpm
Enter=Edit =Select
• Press ENTER then to alter the engine Overspeed set point. Then press
ENTER once again to save the value. If the engine speed rises above this value
for a minimum of 4 seconds an engine shutdown will occur.
Engine Parameters
7. Start Speed
650 rpm
Enter=Edit =Select
• Press ENTER then to alter the engine Start Speed setpoint. Then press
ENTER once again to save the value. On a start of the engine when the engine
speed rises above this value a crank disconnect will occur.
• Press the button to move to the next item. The screen will show:
Engine Parameters
8. Lockout Delay
30 secs
Enter=Edit =Select
• Press ENTER then to alter the Engine Sensor Lockout Delay timer then
ENTER to save the value. When the engine starts and engine speed is
detected, the K45-2 will display sensor readings and will only enable engine
shutdowns after the sensor lockout time has expired.
• Press the button to move to the next item. The screen will show:
Engine Parameters
9. Crank Time
10 secs
Enter=Edit =Select
• Press ENTER then to alter the Engine Crank Time then ENTER to save
the value. This value represents the maximum time that the K45-2 will crank
the engine on each start attempt. The engine will only crank for the full length
of time if it has not successfully started.
• Press the button to move to the next item. The screen will show:
Engine Parameters
10. Crank Rest Time
10 secs
Enter=Edit =Select
• Press ENTER then to alter the Crank Rest Time then ENTER to save the
value. The timer will begin once the K45-2 ceases to crank the engine after an
unsuccessful start attempt. After this time has elapsed, the K45-2 may attempt
another crank attempt.
• Press the button to move to the next item. The screen will show:
Engine Parameters
K45-2 – Dealer Manual Dealer Manual-20110826
YJ_2.0VP.doc
Page 15 of 57
.
• Press the button to move to the next item. The screen will show:
Engine Parameters
12. Glow Time
3 secs
Enter=Edit =Select
• Press ENTER then to alter the period of time the Glow plugs are energized
before engine cranking, then ENTER to save the value. This is used to aid
engine starting in colder temperatures.
• Press the button to move to the next item. The screen will show:
Engine Parameters
13. Warm Up Time
0 mins
Enter=Edit =Select
• Press ENTER then to alter the Engine Warm Up timer then ENTER to
save the value. The timer will begin when the K45-2 detects the engine has
started. The engine speed will be set to idle and cannot be adjusted until the
Warm Up time has expired.
• Press the button to move to the next item. The screen will show:
Engine Parameters
14. Cool Down Time
0 mins
Enter=Edit =Select
• Press ENTER then to alter the Cool Down timer then ENTER to save the
value. The timer will begin when the K45-2 detects either an engine fault, a
request to switch the engine off, or the ignition switch is turned off. The
engine speed will be returned to idle for the Cool Down and a shutdown will
occur.
• Press the button to move to the next item. The screen will show:
Engine Parameters
15. Shutdown Timer
1 mins
Enter=Edit =Select
• Press ENTER then to alter the Shut Down timer then ENTER to save the
value. The shutdown timer is used in applications when it is a requirement to
return a pump, compressor or generator to normal operating conditions prior to
the engine shutting down. The engine speed will be returned to idle and cannot
be adjusted until the timer is complete.
K45-2 – Dealer Manual Dealer Manual-20110826
YJ_2.0VP.doc
Page 16 of 57
.
• Press the button to move to the next item. The screen will show:
Engine Parameters
16. Eng. Temp. Alarm
105’c
Enter=Edit =Select
• Press ENTER then to alter the Engine Temperature Alarm then ENTER to
save the value. This is used as a secondary failsafe means for shutting the
engine down in the event of high engine temperature.
• Press the button to move to the next item. The screen will show:
Engine Parameters
17. Read Eng. Temp.
Mechanical Sender
Enter=Edit =Select
• Press ENTER then to alter the Read Eng. Temp. value then ENTER to
save the value. This is used to choose where the engine temperature is read
from either a resistive temperature sender or from the J1939 CAN BUS.
• Press the button to move to the next item. The screen will show:
Engine Parameters
18.Eng OilPrs.Alarm
20PSI
Enter=Edit =Select
• Press ENTER then to alter the Low Oil Pressure Alarm then ENTER to
save the value. This is used as a secondary failsafe means for shutting the
engine down in the event of low engine oil pressure.
• Press the button to move to the next item. The screen will show:
Engine Parameters
19. Read Oil Prs.
Mechanical Sender
Enter=Edit =Select
• Press ENTER then to alter the Read Oil Prs. value then ENTER to save the
value. This is used to choose where the engine oil pressure is read from either
a resistive oil pressure sender or from the J1939 CAN BUS.
• Press the button to move to the next item. The screen will show:
Engine Parameters
20.Coolant Level
Disabled
Enter=Edit =Select
• Press ENTER then to alter the Enable/Disable the Water Coolant Level
input, then ENTER to save the value. Where fitted, low Coolant Level
detection is used to shutdown the engine in the event of an inadequate level of
engine coolant.
• Press the button to move to the next item. The screen will show:
Engine Parameters
21. Crank Assist
10 counts
Enter=Edit =Select
• Press ENTER then to alter the value of Crank Assistance, then ENTER to
save the value. A slight increase of the Crank Assist value may assist with
certain engine configurations that exhibit an inability to crank.
• Press the MENU button to move to the SETUP screen.
1. Engine
>2. Throttle
3. 4-20mA Sensor
• Press ENTER and the screen will show:
Throttle Parameters
1. Throttle Type
Goto Fixed RPM
Enter=Edit =Select
• Press ENTER then to Goto Fixed RPM (automatic throttling) then ENTER
to save the value. When automatic throttling is enabled, the engine can be
started and allowed to automatically reach a set RPM point. Manual RPM
adjustment is allowed when the engine has reached this set speed.
Alternatively, the Toggle Switch option may be used where automatic
throttling is not available.
• Press the button to move to the next item. The screen will show:
Throttle Parameters
2. Engine Idle
800 rpm
Enter=Edit =Select
• Press ENTER then to alter the Engine Idle on engine startup, then ENTER
to save the value. An Autodetect option is available for J1939 ECU engines.
• Press the button to move to the next item. The screen will show:
Throttle Parameters
3. Line Fill Speed
1200 rpm
Enter=Edit =Select
• Press ENTER then to alter the Line Fill Speed, then ENTER to save the
value. This function becomes active once the engine warm up period has
completed. Press the button to move to the next item. The screen will show:
Throttle Parameters
4. Line Fill Time
2 mins
Enter=Edit =Select
• Press ENTER then to alter the Line Fill Time, then ENTER to save the
value. The Line Fill time period will commence once the engine warm up
period has completed.
• Press the button to move to the next item. The screen will show:
Throttle Parameters
5. MaxRPM@Variable
1800 rpm
Enter=Edit =Select
• Press ENTER then to alter the MaxRPM @Variable, then ENTER to save
the value. The MaxRPM@ Variable indicates how high the engine will throttle
to if Pump Pressure is not being achieved, when throttling with respect to
pressure i.e GO Variable.
• Press the button to move to the next item. The screen will show:
Throttle Parameters
5. MinRPM@Variable
1000 rpm
Enter=Edit =Select
• Press ENTER then to alter the MinRPM @Variable, then ENTER to save
the value. The MinRPM@ Variable indicates how low the engine will throttle
to if a Pump Pressure above the target is being achieved, when throttling with
respect to pressure i.e GO Variable.
• Press the button to move to the next item. The screen will show:
Throttle Parameters
7.RPM Dead Zone
20 rpm
Enter=Edit =Select
• Press ENTER then to alter the RPM Dead Zone, then ENTER to save the
value. The RPM Dead Zone indicates how close the desired and actual engine
rpm must be to be considered satisfactory.
• Press the button to move to the next item. The screen will show:
Throttle Parameters
8.Target Pressure
500KPA
Enter=Edit =Select
Enter=Edit =Select
• Press ENTER then to alter the RPM Decrement Speed, then ENTER to
save the value. This is the rate at which the engine speed decreases with each
decrement.
• Press the button to move to the next item. The screen will show:
Throttle Parameters
12. Feedback Delay
0.5 secs
Enter=Edit =Select
• Press ENTER then to alter the RPM Feedback Delay, then ENTER to save
the value. The Feedback Delay is used to adjust the RPM sensitivity when
altering engine speed.
• Press the button to move to the next item. The screen will show:
Throttle Parameters
13. Ramp Rate RPM/sec
100
Enter=Edit =Select
• Press ENTER then to alter the RPM Ramp Rate, then ENTER to save the
value. This is the rate at which the engine speed will increase once the engine
has started and the warm up timer has expired.
• Press the button to move to the next item. The screen will show if GO
Variable has been selected in Throttle Type :
Throttle Parameters
14. Stagnant Time
1mins
Enter=Edit =Select
• Press ENTER then to alter the Stagnant Time, then ENTER to save the
value. If Pressure or Flow is not achieved and the RPM is either at the
MaxRPM or MinRPM@Variable limit this timer will begin indicating the
pressure or flow value is not moving toward the target. This timer indicates
how long this state is acceptable. Once this timer has expired the engine will
perform a shutdown. This feature can de disabled by setting the time to
0mins.
• Press the button to move to the next item. The screen will show if GO
Variable has been selected in Throttle Type :
Throttle Parameters
15. System Retries
3
Enter=Edit =Select
• Press ENTER then to alter the System Retries value, then ENTER to save
the value. If the Stagnant Time has expired and the engine has shutdown and
restarted to achieve water pressure or flow, System Retries defines the amount
of times a restart will occur before a fault or latched shutdown is performed.
2. Throttle
>3. 4-20mA Sensor
Flow Parameters
1. Sender Function
Enabled
Enter=Edit =Select
• Press ENTER then to Enable or Disable the Flow sensing function, then
ENTER to save the value.
• Press the button to move to the next item. The screen will show:
Flow Parameters
2. SenderRange 4-20mA
200 L/S
Enter=Edit =Select
• Press ENTER then to alter the Range of the 4-20mA Sender in use, then
ENTER to save the value.
• Press the button to move to the next item. The screen will show:
Flow Parameters
3. Set Min. Flow
75 L/S
Enter=Edit =Select
• Press ENTER then to alter the Minimum Flow Rate Alarm, then ENTER
to save the value. A lower rate of flow than this value will trigger an engine
shutdown.
• Press the button to move to the next item. The screen will show:
Flow Parameters
4. Set Max. Flow
150 L/S
Enter=Edit =Select
• Press ENTER then to alter the Maximum Flow Rate Alarm, then ENTER
to save the value. A flow rate in excess of this value will trigger an engine
shutdown.
• Press the button to move to the next item. The screen will show:
Flow Parameters
5. Flow Bypass Time
3 mins
K45-2 – Dealer Manual Dealer Manual-20110826
YJ_2.0VP.doc
Page 23 of 57
.
Enter=Edit =Select
• Press ENTER then to alter the Flow Rate Alarm Bypass Timer, then
ENTER to save the value. Upon engine startup, the K45-2 will display the
flow rate and the Flow Bypass Timer will commence. Engine shutdown due to
maximum or minimum flow rates will only be enabled after the bypass time
has expired.
• Press the button to move to the next item. The screen will show:
Flow Parameters
6. Flow Slush Time
10 secs
Enter=Edit =Select
• Press ENTER then to alter the Flow Slush Time period, then ENTER to
save the value. This value allows for a timer to commence upon detection of a
flow rate outside of the minimum or maximum permissible values before the
engine will be shutdown.
Pump Parameters
1. Sender Function
Enabled
Enter=Edit =Select
• Press ENTER then to Disable, Enable or “Enable w. Start_Stop” the Pump
Pressure sensing function, then ENTER to save the value.
”Enable with Start Stop” when in Auto will enable the engine start and stop to
be controlled by Line Pressure start and stop points.
• Press the button to move to the next item. The screen will show:
Pump Parameters
2. SenderRange 4-20mA
1000 KPA
Enter=Edit =Select
• Press ENTER then to alter the Range of the 4-20mA Sender in use, then
ENTER to save the value.
• Press the button to move to the next item. The screen will show:
Pump Parameters
3. Set Min Press.
200 KPA
Enter=Edit =Select
• Press ENTER then to alter the Minimum Pump Pressure Alarm, then
ENTER to save the value. The low pump pressure or Loss of Prime
alarm/engine shutdown is set in this screen.
• Press the button to move to the next item. The screen will show:
Pump Parameters
4. Set Max Press.
600 KPa
Enter=Edit =Select
• Press ENTER then to alter the Maximum Pump Pressure Alarm, then
ENTER to save the value. A pump pressure in excess of this value will trigger
an engine shutdown. Press the button to move to the next item. The screen
will show:
Pump Parameters
5. Pump Prs. Bypass
3min
Enter=Edit =Select
• Press ENTER then to alter the Pump Pressure Alarm Bypass Timer, then
ENTER to save the value. Upon engine startup, the K45-2 will display the
pump pressure and the Pump Pressure Bypass Timer will commence. Engine
shutdown due to maximum or minimum pressure pump will only be enabled
after the bypass time has expired. Press the button to move to the next item.
The screen will show:
Pump Parameters
6. Pump Prs. Slush
3 secs
Enter=Edit =Select
• Press ENTER then to alter the Pump Pressure Slush Timer, then ENTER
to save the value. This value allows for a timer to commence upon detection of
a pump pressure outside of the minimum or maximum permissible values
before the engine will be shutdown. Press the button to move to the next
item. The screen will show:
Pump Parameters
7. Calibration
50counts 0KPA
Enter=Edit =Select
• Press ENTER then to alter the Calibration Counts then ENTER to save the
value. This value allows the operator to Zero the transducer and remove any
offset that may occur. Press the button to move to the next item. The screen
will show:
Pump Parameters
8. Start Option
Start Low Stop High
Enter=Edit =Select
• Press ENTER then to alter the Start Option then ENTER to save the value.
The controller can set set to Start on a Low pressure and Stop on a High
Pressure OR Start on a High Pressure and Stop on a Low Pressure.
Press the button to move to the next item. The screen will show:
Pump Parameters
9. Start Pressure
300KPA
Enter=Edit =Select
• Press ENTER then to alter the Start Pressure then ENTER to save the
value. This is the trigger pressure to Start the engine.
Press the button to move to the next item. The screen will show:
Pump Parameters
10. Stop Pressure
700KPA
Enter=Edit =Select
• Press ENTER then to alter the Start Pressure then ENTER to save the
value. This is the trigger pressure to Stop the engine.
Please Note: The Start and Stop Pressures are usually set between the limits set in
SET MIN PRESS. & SET MAX PRESS.
Press the MENU button to exit the Pump Parameters.
6. Flow Switch
• Press ENTER and the screen will show:
Fuel Level Setup
1. Fuel Alarm Point
Disabled
Enter=Edit =Select
• Press ENTER then to alter the Low Fuel Level Alarm percentage (%), then
ENTER to save the value. This is the percentage of fuel remaining in the fuel
tank which will trigger a warning or engine shutdown. Press the button to
move to the next item.
Press ENTER then to alter the Pump Discharge Pressure Slush Timer, then
ENTER to save the value. This value allows for a timer to commence upon detection
of a pump pressure outside of the minimum or maximum permissible values before
the engine will be shutdown. Press the MENU button to move to the SETUP screen
• Press the button to move to the next item. The screen will show:
Digital Inputs
6.Water Loss Input
Normally Closed
Enter=Edit =Select
• Press ENTER then to alter the Water Loss Input type to Normally Closed
or Normally Open, then ENTER to save the value.
Disabled
Enter=Edit =Select
• Press ENTER then to alter the Vacuum Priming Function to Enable or
Disabled, then ENTER to save the value.
• Press the button to move to the next item. The screen will show:
Vacuum Priming
2. Slush Time
4 secs
Enter=Edit =Select
• Press ENTER then to alter the Vacuum Priming Slush Time, then ENTER
to save the value. The Slush Time affects the “ Vac. Water Loss” and the ”
Accum Pump Clutch” Digital Inputs which in there normal state are Normally
Closed. These inputs must see the alternate state (OPEN) for the set slush
time before the “Bypass Time” begins to count down and Clutch Relay R9
will be engaged.
• Press the button to move to the next item. The screen will show:
Vacuum Priming
3. Bypass Time
6 mins
Enter=Edit =Select
• Press ENTER then to alter the Vacuum Priming Bypass Time. , then
ENTER to save the value. The Bypass Time will begin countdown when the
“Vac. Water Loss” input and the “Accum Pump Clutch Inputs” are triggered.
If water pressure/flow has not been sensed and the Bypass time has elapsed the
engine will commence a controlled shutdown.
If the “Vac. Water Loss” input is LOW and the Accum. Pump Clutch Inputs is
triggered the clutch will be engaged and the status will Show PUMP: ON.
Once water has returned the clutch will turn OFF and the Pump status will also
show Pump OFF.
The Timer, when counting down, is indicating that the water is low and the
pump is on. If the timer reaches 00:00 the engine will shutdown.
If water returns, the timer will reset to the set time Timer: 06:00
Please note: The displayed timer does not indicate the flow switch timer only
the Vacuum Timing Function.
Disabled
Enter=Edit =Select
• Press ENTER then to alter the Flow Switch Bypass Timer, then ENTER to
save the value. Upon engine startup, the panel will bypass the Flow Switch
until the Bypass Timer has expired. If the Bypass Timer is set, engine
shutdown due to a flow switch fault will only be enabled after the bypass time
has expired.
• Press the button to move to the next item. The screen will show:
Flow Switch Param.
2. Flow Slush Timer
10 secs
Enter=Edit =Select
• Press ENTER then to alter the Flow Switch Slush Timer, then ENTER to
save the value. This value allows for a timer to commence upon detection of a
flow switch fault before the engine will be shutdown.
• Press the button to move to the next item. The screen will show:
Flow Switch Param.
3. Flow Switch Type
Normally Closed
Enter=Edit =Select
• Press ENTER then to alter the Flow Switch Type, then ENTER to save the
value. A Normally Open or Normally Closed Flow Switch type may be used.
• Press the button to move to the next item. The screen will show:
Flow Switch Param.
4. Shutdown Type
Controlled
Enter=Edit =Select
• Press ENTER then to alter the Flow Switch Shutdown Type, then ENTER
to save the value. This value allows for either an Immediate or Controlled
engine shutdown to occur upon Flow Switch fault. A Controlled shutdown
will allow a cooldown period to expire, an Immediate shutdown type will not.
• Press the button to move to the next item. The screen will show:
Flow Switch Param.
5. Input Type
Passive
Enter=Edit =Select
• Press ENTER then to alter the Flow Switch Input Type, then ENTER to
save the value. The settings available are Active, allowing a powered Flow
Switch to be used, and Passive, allowing an un-powered switch-type Flow
Switch to be used.
• Press the button to move to the next item. The screen will show:
Flow Switch Param.
6. Latched Shutdown
Shutdown Latched
Enter=Edit =Select
• Pressure ENTER then to alter the Latched shutdown enable, then ENTER
to save the value. This value allows for either a latched shutdown or non-
latched shutdown to occur upon Flow Switch fault.
• Press the MENU button to move to the SETUP screen.
12. Modbus
• Press ENTER and the screen will show:
Press Enter to Reset
the Fault History
or Menu to Exit
9.4.12 MODBUS
• Press ENTER then to alter the Slave Address. The controller has a unique
address in the MODBUS chain which can be configured between 0 and 250.
Press ENTER to save the value.
Press to move to the next item or MENU to Exit
The amber LED will illuminate when a warning message is generated. The message
will not be cleared until the engine problem is rectified. The K45-2 will not shutdown
on an “ECU Warning!”, however, the ECU will shut the engine down itself if an
“ECU Stop!” occurs. The ECU is permitted to self-protect and the “ECU Stop!” will
be logged in the K45-2. The red LED will illuminate when an engine shutdown
message is generated. If a warning or stop is present, the faults can be viewed in the
“View Active Codes” menu.
If there are more than one code present, pressing the ENTER button will go to the
next code available. If there is more than one code present you may have to go out of
this screen and return to it to view current information.
MENU
1. Set Stop Timer
2. User Settings
>3. View Active Codes
No Active
Fault Codes
• If there are no active codes broadcasted from the engine’s ECU, the screen
will show NO ACTIVE FAULT CODES.
• View Active Codes (Fault(s) Present)
• Any fault codes and messages generated by the engine’s ECU will be
displayed by the K45-2 Control Module.
• Press ENTER and the screen will show: For example:
SPN:110 FMI: 3
OC: 1 1/1
Eng Coolant Temp. High
• If active codes are present the screen will show the SPN (Suspect Parameter
Number), FMI (Failure Mode Identifier), OC (Occurrence Count) and a
description of the fault.
• If multiple messages exist then the 1 of 1 (1/1) will be altered to 1 of 2 or 1 of
3 etc. To view multiple messages press ENTER to view each message.Press
the MENU button to move to the SETUP screen.
Note:
An active code can only be cleared by the ECU once the problem has been rectified.
The K45-2 Control Module treats ECU warnings for oil pressure and engine
temperature as shutdowns. The K45-2 will not permit an engine start if the oil and
engine temperature sensors are faulty or disabled.
Serial Number
373
Build Date
20110401
Firmware Version
V1.98VP
• Press ENTER and the screen will return to the MENU screen.
Occurrence: 1
• Continue to press ENTER until all faults are shown and the screen returns to
the MENU screen.
This screen shows the Engine Speed Setpoint 1 value for Idle.
• Press ENTER and the Screen will now show:
Torque @ Idle
Pt1 131%
This screen shows the Engines Torque output at Engine Speed Setpoint 1 for idle.
• Press ENTER and the Screen will now show:
Engine Speed Pt2
0 rpm
This screen shows the Engines Torque output at Engine Speed Setpoint 1 for idle.
• Press ENTER repeatedly to view Setpoint 3, Setpoint 4, and Setpoint 5 values.
Following these, the Screen will show:
Engine Speed @High
Idle Pt6 0 rpm
This screen shows the Gain in KPa. Press ENTER and the Screen will now show:
Reference Engine
Torque 0 Nm
Override 0 secs
This screen shows the Requested Speed Control Lower Limit value.
• Press ENTER and the Screen will now show:
Req. Spd. Control
High Lim. 0 rpm
This screen shows the Requested Speed Control High Limit value.
• Press ENTER and the Screen will now show:
Req. Torque Cntrl
Low Limit 131%
This screen shows the Requested Torque Control Lower Limit value.
• Press ENTER and the Screen will now show:
Req. Torque Cntrl
High Limit 131%
This screen shows the Requested Torque Control High Limit value.
5 Under speed 650RPM 550 to 2000RPM 25 RPM Engine overload slow speed protection with
slush delay of 5secs.
6 Over speed 1950RPM 1000 to 25 RPM Engine high speed protection with slush delay
4000RPM of 5secs
7 Start Speed 600rpm 400 to 2000RPM 25RPM Digital and analogue sensor shutdown bypass
timer on engine startup.
8 Lockout delay 30secs 20 to 60secs 1 sec Digital and analogue sensor shutdown bypass
timer on engine startup.
9 Crank Timer 10secs 5 to 20secs 1sec Maximum time engine will crank on a start
attempt.
10 Crank Rest Timer 10secs 5 to 60secs 1sec Allows engine to rest after an unsuccessful
start attempt before retry.
11 Crank Attempts 3 attempts 3 to 10 attempts 1 Allows engine to retry after a failed start
attempt.
12 Glow Timer 3sec 0 to 20secs 1 Time to energize Glow plug(s) when starting
engine as an aid in cold temperatures.
13 Warm Up Timer 0 mins 0 to 20 mins 10 min Allows engine to warm up at idle prior to
throttling at full load.
14 Cool Down Timer 0 mins 0 to 20 mins 1 min Allows engine to cool down to idle after
operating at full load.
15 Shutdown Timer 1mins 0 to 20mins 1 min Allows engine to cool down to idle after a
Pump fault has occurred.
16 Engine Temp Alarm 105’C 0 to 200’C 1 'C If the Engine Coolant temperature rises above
this value the engine will be immediately
shutdown.
17 Read Eng. Temp Mechanical Mechanical -- Source of Engine Coolant Temperature --
Sender Sender or J1939 Resistive sender or J1939 CAN BUS value.
ECU
18 Engine Oil Pressure 20PSI 0 to 144PSI 1 PSI If the Engine Oil Pressure falls below this
Alarm value the engine will be immediately
shutdown.
19 Read Oil. Prs. Mechanical Mechanical -- Source of Engine Oil Pressure -- Resistive
Sender Sender or J1939 Sender or J1939 CAN BUS value.
ECU
20 Engine Coolant Level Disabled Disabled to - Allows Low Engine Water Coolant Level
Enabled detection with 5sec slush before Engine
Shutdown.
21 Crank Assist 10counts 0 to 150counts 1 count Allows engines that exhibit rpm faults to
extend their initial crank time.
5 MaxRPM@ Variable 1800RPM 900 to 4000RPM 25 RPM When in Variable and pump pressure is not
achieved this is the maximum RPM the engine
will throttle to.
6 MinRPM@ Variable 1000RPM 900 to 4000RPM 25 RPM When in Variable and pump pressure is
achieved this is the minimum RPM the engine
will throttle to.
7 RPM Dead Zone 20RPM 10 to 200RPM 10 RPM When the engine speed is changing the
throttle will cease to alter once the real time
speed is within +/- the RPM dead zone of the
target RPM
8 Target Pressure 500KPA 0 to 3200KPA 10KPA When in Variable the Target Pressure the
system is trying to achieve
9 Pressure Deadband 20KPA 10 to 300KPA 5KPA When the engine speed is changing the
throttle will cease to alter once the real time
pressure is within +/- the pressure dead zone
of the target Pressure
10a J1939 INC Speed 20RPM/SEC 10 to 10 RPM When throttling to idle, line fill speed, fixed
(ECU electronic 250RPM/Sec speed or max/min RPM this defines the
engines) incremental rate at which the throttle will
increase.
11a J1939 DEC Speed 20RPM/SEC 10 to 10 RPM When throttling to idle, line fill speed, fixed
(ECU electronic 250RPM/Sec speed or max/min RPM this defines the
engines) decremented rate at which the throttle will
decrease.
10b Linear INC Speed 20% 10 to 100% 1% When throttling to idle, line fill speed, fixed
speed or max/min RPM this defines the
incremental rate at which the throttle will
increase.
11b Linear Dec Speed 20% 10 to 100% 1% When throttling to idle, line fill speed, fixed
speed or max/min RPM this defines the
decremented rate at which the throttle will
decrease.
12 Feedback Delay 0.2sec. 0.5 to 4.0secs 0.1 sec When throttling to idle, line fill speed, fixed
speed or max/min RPM this defines the delay
between throttling steps to allow the pump or
genset system to respond.
13 Throttle Ramp Rate 100RPM/SEC 10 to 10 RPM Engine speed rate of increase at engine
600RPM/Sec startup, normally after warm up and line fill
timer.
14 Stagnant Time 1min 0 to 20mins 1min When in Variable, if the target is not achieved
and the RPM is at MIN or MAXRPM for the
stagnant time, the system has become
stagnant and the engine will shutdown.
Set to 0mins to Disable.
15 System Retries 3 0 to 20 1 The amount of times the engine will restart
when the system becomes stagnant before a
latched shutdown occurs.
4-20A Flow Sensor
1 Fuel Level Alarm Point Disabled Disabled to 99% 1% Enabling low fuel level monitoring using VDO
sender as a percentage of 100.
2 Fuel Level Alarm Warning Warning to - Enabling low fuel level warning or engine
Action Shutdown shutdown.
3 Fuel Level Sender Tubular Tubular Sender - Select type of fuel level sender to be used
Type Sender to Float or Arm from VDO range.
Type
4 Fuel Level Sender 82 Counts 10 to 254 1 count Allows K45-2 calibration for fuel level sender
Calibration from VDO range.
Pump Oil
Temperature
1 Pump Temperature Disabled Disable to Enable - Enabling Pump Temperature shutdown.
Alarm
2 Pump Temperature 40°C 10 to 145°C 1°C Maximum allowable operating Pump
Setpoint Temperature.
System Control
1 Remote Start Type Maintained Maintained to - Trigger type for a remote start input.
Momentary Maintained type will remain activated,
Momentary will activate and deactivate.
2 Remote Start Input Start NO Close to Rise/ - Start Trigger may be Close to Rise or Close to
Type Stop NO Close to Fall Fall. Stop Trigger may be Close to Rise or
Close to Fall.
3 Fuel Relay Control Energize to Energize to - Engine Fuel Solenoid may remain energized or
Run Run/Energize to de-energized during engine running.
Stop
11.2 General
When troubleshooting problems, these general causes should be kept in mind:
1. Incorrect wiring of the unit.
2. Poor battery condition, battery not charged or poor battery connections.
3. Incorrectly connected or missing fly-back diodes on the engine electrics
which have inductive loads (starter motor, solenoids etc), which can cause
problems when they are switched off. These can cause resetting problems
for electronic components.
4. The RPM is used for a variety of purposes by the microprocessor program
apart from just displaying the engine speed. If the RPM is measured using
a signal from the alternator rather than a magnetic pickup then a faulty
alternator may be the likely cause, rather than a flat battery, in the event of
RPM read errors.
When an alarm or warning occurs during the operation of the engine, the engine will
be shutdown and a fault will be shown on the screen. The faults are shown in English,
though the following is a more detailed table of descriptions:
On Power Up, the display Program not installed Contact authorized dealer
backlight is on with black correctly
bar across top line
Clock will not keep time RTC Battery requires Contact authorized dealer
once controller turned off replacement for replacement battery.
Startup power glitch Do a power reset. Remove
power for 3 or more
seconds then reconnect
Engine fault indicates over Reduction in engine load Check conditions of load
speed
Check throttle settings
Tachometer incorrectly set Contact authorized dealer
Engine fault indicates zero Fuel level low Ensure adequate fuel level
rpm
Alternator failure Alternator replacement
may be required
Alternator wiring incorrect Ensure wiring adheres to
wiring diagram
Engine cranks but does not Fuel solenoid not Ensure "Energize to Stop"
start operating correctly / "Energize to Run"
operation is set correctly
Ensure wiring adheres to
wiring diagram
Ensure adequate fuel level
in tank
Fuel solenoid does not Fuel solenoid wiring Ensure wiring adheres to
operate incorrect wiring diagram
Fuel solenoid is incorrect Contact authorized dealer
type – ‘Energize to Stop’/
‘Energize to Run’
may be required
Sensor # fault is indicated The applicable sensor has Check condition for which
indicated a fault sensor provides protection
Pressure is not displayed The controller does not Contact authorized dealer
measure pressure
Engine shutdown due to Blocked pump and/or Check pump and pipes for
Max Pressure pipes blockage
Max pressure is incorrectly Adjust Max pressure
set setting in Set Pump
Pressure Sender Menu
Limited Warranty
Intention … This policy is written with the consumer in mind, therefore, the language is intended to be
simple and hopefully may assist consumers and companies in fully understanding the terms, their
obligations and the conditions of contract outlined within this warranty policy.
Names … Kensho P/L for the purposes of this warranty is the Original Equipment Manufacturer
(OEM) or ‘the manufacturer’. The ‘consumer’ means the end user, persons, company or group using
the Kensho product. The ‘original retail purchaser’ or ORP means (but not limited to) the
aftermarket re-seller, supplier or dealer of a particular brand of product/s. The ‘ORP’ also includes
Original Equipment Manufacturers and assemblers that have purchased any product from Kensho P/L.
The term ‘Stand-Alone Product’ means a Kensho product sold separately by the ORP and the ORP
has not fitted the Kensho product to their equipment or engines as a complete package.
Who is covered … This warranty and period of warranty strictly applies to the “original retail
purchaser”, that means the OEM, re-seller, supplier or dealer that “directly” bought the product from
the manufacturer.
How Long Coverage Lasts … This warranty runs for 24 months or 2000 engine operating hours
(whichever occurs first) from the day you purchase the product/s. Warranty periods in general may be
subject to change in future without notice. Please refer to the Manufacturer or Dealer in which the
product/s was purchased for any changes periodically.
What Kensho Will Do … KENSHO P/L at its discretion will repair any product proven to be
defective in materials or workmanship. In the event repair is not possible, replacement of the product
with a new or similar product/s and price, or refund of the full purchase price of the product, whichever
is deemed by the manufacturer appropriate to the original retail purchaser on a case by case basis.
ORP Obligations … Your obligations as the original retail purchaser are simple. The original retail
purchaser must consult Kensho from the suitability of the product to the environment and its intended
use. Fly-back diodes are a warranty requirement and correct wiring and installation of the product must
be followed as per the manufacturer’s requirements. Please also be aware that product was intended to
be installed by authorized agents with expert and technical knowledge and not for the average
consumer. You must therefore inform Kensho of each product sold as a ‘stand-alone product’ but not
fitted by you or your company as this warranty will not cover such claims. Also in the event of
complete product failure and on-site repairs are necessary Kensho must have the ‘first-right’ of call, in
other words, you must notify us prior to attempting repairs.
Consumer Obligations … The consumer must take care not to abuse, misuse, tamper with or damage
the product. Doing so will likely void this warranty but more importantly may cause loss of life or
limb. Please follow the instruction manuals on all your equipment and products carefully. Do not
modify, alter or repair this product under any circumstances. Please consult your approved and
authorized dealer or seller for technical issues. You are also obligated to be diligent during the
operation of your machinery.
What is not covered … This warranty does not cover equipment, components or engines supplied by
manufacturers’ other than Kensho P/L. Misused, Abused, Neglected, Damaged or Tampered with
product/s (whether accidental, intentional or incidental) are not eligible for any kind of warranty claim.
The product/s being used for a purpose or application not specifically designed for or intended by the
manufacturer. The product/s are not covered if electrically installed or wired incorrectly, contrary to the
manufacturer’s schematic and instructions or any unauthorized product/s modifications or alterations
not intended by the manufacturer. This warranty does not cover circumstances whereby the
manufacturer’s product is used in conjunction with or coupled to another manufacturer’s product
(whether electronic or otherwise) thus causing conflicts in operation, electrical interference or damage
to person and property. Excessive or incorrect power (voltages & amperages) to the product/s, contrary
to the manufacturer’s specifications, will void this warranty. The absence of FLY-BACK diodes in the
K45-2 – Dealer Manual Dealer Manual-20110826
YJ_2.0VP.doc
Page 56 of 57
.
controllers’ electrical system will void warranty. This warranty will not cover damage to components
and circuit boards caused by excessive physical force applied by the user or original retail purchaser
when removing ‘replaceable relays’ or ‘pressing buttons’. This warranty does not cover disruption
caused by the manufacturer’s product/s to other electronic devices normal operation due to unshielded
radio/microwave frequencies or EMF interference. This warranty does not cover miscellaneous
expenses for removal, installation, service, towing or any down time, nor does it cover material, labor,
or additional parts required for replacement or repair of damages caused by abuse (including fire or
wreckage), misuse, neglect, if the product is defective by way of manufacturer, failure to follow
manufacturer’s operating, wiring and /or installation instructions. This warranty does not cover peeling,
fading or discoloration of decal/stickers, protective enclosure/s and the product in general caused by
extreme climates and temperatures, ‘Acts of God’, prolonged exposure to direct sunlight or frost,
chemicals or abrasives. Please consult your manual to determine the products acceptable operating
range, warning and recommendations. THE MANUFACTURER SHALL NOT BE LIABLE FOR
ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES INCLUDING WITHOUT LIMITATION,
INDIRECT AND SPECIAL DAMAGES CAUSED BY AND RESULTING FROM DEFECTS IN
THE PRODUCT/S WHETHER CAUSED BY THE MANUFACTURER OR NOT. The replacement,
repair, time taken for repair or any other equitable remedy to the original retail purchaser will be solely
at the discretion of KENSHO P/L, including the cost for transit of faulty product/s from the
manufacturer to the original retail purchaser if the product is deemed to be a manufacturing fault. The
manufacturer will not be liable for loss or damage to product/s in transit between the original retail
purchaser and customer. Warranty claims are limited to the retail price paid for the product and may
not include the cost of labor or transport. The warranty period does not extend if the defective product/s
is repaired or replaced with new or is re-sold as second-hand goods by the consumer. This warranty
will not cover controllers sold as stand-alone units (in other words, sold without being fitted to a
specific engine) for reason that the product was intended to be installed by authorized agents with
expert knowledge. Repairs for product failure undertaken without the knowledge or consent of the
manufacturer will void warranty whether the repairs were undertaken by consumer or authorized agent.
How to get Service … The consumer may contact the OEM or dealer in the State or Country in which
the product was purchased. The dealer, reseller or OEM may proceed in making claim to the
manufacturer of the product. Warranty claims are for defect and manufacturing faults only and any
claims are only valid if;
• The warranty claim is made within the warranty period and before the allowable engine
operating hours,
• The customer makes a claim within 30 days of discovering the failure or fault,
• The “original retail purchaser” makes the warranty claim,
• Proof of purchase is supplied by way of serial number and company order/record,
• The product is not re-sold as second-hand good,
• The product fault is deemed by the manufacturer to be a manufacturing fault and not caused
by the customer.