RINA LV Relay Settings-11062021
RINA LV Relay Settings-11062021
PROJECT Material Handling System For Port of San Pedro, Ivory Coast
DOC NO. PP83/3133
REV NO. 0
PMCC 01 - Protective Device(Relay) Settings
For Incomers & Bus section
Phase Ground
OCR 51 (I>) OCR 50 (I>>) OCR 51 N OCR 50 N
Relay Manufacturer
S.No Feeder Number/Feeder Device Prim. Block Prim. Prim.
Panel FLA (A) & Phase CT Ratio Recomm Recomm Prim. Recomm Recomm Time
Description Function Selected Calculate Amps Calculate Time TOC by Calculate Amps Calculate Amps
Model ended Time Dial ended Amps Curve ended Time Dial ended Delay
Curve d Pickup Pickup d Pickup Delay (s) IOC d Pickup Pickup d Pickup Pickup
Pickup Pickup Pickup (A) Pickup Pickup (s)
(A) (A) (A)
IEC - IEC -
1 Schneider Electric Overcurrent &
4F3/Incomer-1 from TR-01 3608 4000 Extremly 0.99 1.00 4000 0.58 5.4 6 24000.00 0.65 Enabled Normal 0.18 0.2 800 0.23 0.90 1 4000 0.5
P5F30 Earth Fault
Inverse Inverse
IEC - IEC -
2 Schneider Electric Overcurrent &
5F3/Buscoupler 3608 4000 Extremly 0.99 1.00 4000 0.25 2.3 2.5 10000.00 0.25 Enabled Normal 0.18 0.2 800 0.14 0.90 0.9 3600 0.3
P5F30 Earth Fault
Inverse Inverse
IEC - IEC -
3 Schneider Electric Overcurrent &
PMCC 01 6F3/Incomer-2 from TR-02 3608 4000 Extremly 0.99 1.00 4000 0.58 5.4 6 24000.00 0.65 Enabled Normal 0.18 0.2 800 0.23 0.90 1 4000 0.5
P5F30 Earth Fault
Inverse Inverse
IEC -
4 15/0.4 kV , 2.5MVA , Schneider Electric Overcurrent &
3608 4000 - - - - - - - - - - Normal 0.18 0.2 800 0.32 N/A N/A N/A N/A
TR 01 LV SBEF(51G) P5F30 Earth Fault
Inverse
IEC -
5 15/0.4 kV , 2.5MVA , Schneider Electric Overcurrent &
3608 4000 - - - - - - - - - - Normal 0.18 0.2 800 0.32 N/A N/A N/A N/A
TR 02 LV SBEF(51G) P5F30 Earth Fault
Inverse