RINA LV Relay Settings-11062021

This document provides protection device settings for the electrical system of a material handling port in Ivory Coast. It lists 5 feeders/circuits and their overcurrent and earth fault relay settings, including the manufacturer, device function, and recommended primary current and time settings. The settings are provided to protect the incomers, bus section, and distribution transformers from overloads and ground faults.

Uploaded by

rahul patra
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
76 views4 pages

RINA LV Relay Settings-11062021

This document provides protection device settings for the electrical system of a material handling port in Ivory Coast. It lists 5 feeders/circuits and their overcurrent and earth fault relay settings, including the manufacturer, device function, and recommended primary current and time settings. The settings are provided to protect the incomers, bus section, and distribution transformers from overloads and ground faults.

Uploaded by

rahul patra
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 4

CUSTOMER RINA

PROJECT Material Handling System For Port of San Pedro, Ivory Coast
DOC NO. PP83/3133
REV NO. 0
PMCC 01 - Protective Device(Relay) Settings
For Incomers & Bus section
Phase Ground
OCR 51 (I>) OCR 50 (I>>) OCR 51 N OCR 50 N
Relay Manufacturer
S.No Feeder Number/Feeder Device Prim. Block Prim. Prim.
Panel FLA (A) & Phase CT Ratio Recomm Recomm Prim. Recomm Recomm Time
Description Function Selected Calculate Amps Calculate Time TOC by Calculate Amps Calculate Amps
Model ended Time Dial ended Amps Curve ended Time Dial ended Delay
Curve d Pickup Pickup d Pickup Delay (s) IOC d Pickup Pickup d Pickup Pickup
Pickup Pickup Pickup (A) Pickup Pickup (s)
(A) (A) (A)
IEC - IEC -
1 Schneider Electric Overcurrent &
4F3/Incomer-1 from TR-01 3608 4000 Extremly 0.99 1.00 4000 0.58 5.4 6 24000.00 0.65 Enabled Normal 0.18 0.2 800 0.23 0.90 1 4000 0.5
P5F30 Earth Fault
Inverse Inverse
IEC - IEC -
2 Schneider Electric Overcurrent &
5F3/Buscoupler 3608 4000 Extremly 0.99 1.00 4000 0.25 2.3 2.5 10000.00 0.25 Enabled Normal 0.18 0.2 800 0.14 0.90 0.9 3600 0.3
P5F30 Earth Fault
Inverse Inverse
IEC - IEC -
3 Schneider Electric Overcurrent &
PMCC 01 6F3/Incomer-2 from TR-02 3608 4000 Extremly 0.99 1.00 4000 0.58 5.4 6 24000.00 0.65 Enabled Normal 0.18 0.2 800 0.23 0.90 1 4000 0.5
P5F30 Earth Fault
Inverse Inverse
IEC -
4 15/0.4 kV , 2.5MVA , Schneider Electric Overcurrent &
3608 4000 - - - - - - - - - - Normal 0.18 0.2 800 0.32 N/A N/A N/A N/A
TR 01 LV SBEF(51G) P5F30 Earth Fault
Inverse
IEC -
5 15/0.4 kV , 2.5MVA , Schneider Electric Overcurrent &
3608 4000 - - - - - - - - - - Normal 0.18 0.2 800 0.32 N/A N/A N/A N/A
TR 02 LV SBEF(51G) P5F30 Earth Fault
Inverse

For Motor Feeders


Phase Ground
OCR 51 (I>) OCR 50 (I>>) OCR 51 N OCR 50 N
Feeder Relay Manufacturer
S.No Phase CT CBCT Device Prim. Block Prim. Prim.
Panel Number/Feeder Load (kW) FLA (A) & Recomm Recomm Prim. Recomm Recomm Time
Ratio Ratio Function Selected Calculate Amps Calculate Time TOC by Calculate Amps Calculate Amps
Description Model ended Time Dial ended Amps Curve ended Time Dial ended Delay
Curve d Pickup Pickup d Pickup Delay (s) IOC d Pickup Pickup d Pickup Pickup
Pickup Pickup Pickup (A) Pickup Pickup (s)
(A) (A) (A)
IEC -
3F3/Dust
1 Schneider Electric Overcurrent & IEC - Long Long
PMCC 01 Suppression 75 75 150 150 150 1.10 1.10 165 0.27 N/A N/A N/A N/A N/A 0.10 0.1 15 0.1 1.00 1 150.35 0.1
P3F30 Earth Fault Time Inverse Time
kW Motor
Inverse
CUSTOMER RINA
PROJECT Material Handling System For Port of San Pedro, Ivory Coast
DOC NO. PP83/3133
REV NO. 0
PMCC 02- Protective Device(Relay) Settings
For Incomers & Bus section
Phase Neutral
Relay OCR 51 (I>) OCR 50 (I>>) OCR 51 N OCR 50 N
S.No Feeder Number/Feeder Manufacturer Device Prim. Block
Panel FLA (A) Phase CT Ratio Recomm Recomm Prim. Recomm Prim. Recomm Prim.
Description & Function Selected Calculate Amps Calculate Time TOC by Calculated Calculate Time
Model ended Time Dial ended Amps IOC Curve ended Amps Time Dial ended Amps
Curve d Pickup Pickup d Pickup Delay (s) Pickup d Pickup Delay (s)
Pickup Pickup Pickup (A) Pickup Pickup (A) Pickup Pickup (A)
(A)
Schneider IEC - IEC -
1 Overcurrent &
7F3/Incomer-1 from TR-03 3608 Electric 4000 Extremly 0.99 1.00 4000 0.58 5.41 6 24000.00 0.4 Enabled Normal 0.18 0.221 884 0.21 0.90 1.01 4040 0.4
Earth Fault
P5F30 Inverse Inverse
Schneider IEC - IEC -
2 Overcurrent &
8F3/Buscoupler 3608 Electric 4000 Extremly 0.99 1.00 4000 0.3 2.26 2.5 10000.00 0.2 Enabled Normal 0.18 0.2 800 0.11 0.90 0.9 3600 0.2
Earth Fault
P5F30 Inverse Inverse
Schneider IEC - IEC -
3 Overcurrent &
PMCC 02 9F3/Incomer-2 from TR-04 3608 Electric 4000 Extremly 0.99 1.00 4000 0.58 5.41 6 24000.00 0.4 Enabled Normal 0.18 0.221 884 0.21 0.90 1.01 4040 0.4
Earth Fault
P5F30 Inverse Inverse
Schneider IEC -
4 15/0.4 kV , 2.5MVA , Overcurrent &
3608 Electric 4000 - - - - - - - - - - Normal 0.18 0.221 884 0.29 N/A N/A N/A N/A
TR 03 LV SBEF(51G) Earth Fault
P5F30 Inverse
Schneider IEC -
5 15/0.4 kV , 2.5MVA , Overcurrent &
3608 Electric 4000 - - - - - - - - - - Normal 0.18 0.221 884 0.29 N/A N/A N/A N/A
TR 04 LV SBEF(51G) Earth Fault
P5F30 Inverse

For Motor Feeders


Phase Ground
Relay OCR 51 (I>) OCR 50 (I>>) OCR 51 N OCR 50 N
Feeder
S.No Manufacturer Phase CT CBCT Device Prim. Block Prim.
Panel Number/Feeder Load (kW) FLA (A) Recomm Recomm Prim. Recomm Prim. Recomm
& Ratio Ratio Function Selected Calculate Amps Calculate Time TOC by Calculated Calculate Amps Time
Description ended Time Dial ended Amps Curve ended Amps Time Dial ended
Model Curve d Pickup Pickup d Pickup Delay (s) IOC Pickup d Pickup Pickup Delay (s)
Pickup Pickup Pickup (A) Pickup Pickup (A) Pickup
(A) (A)
IEC - IEC -
Schneider
1 1F1/Quay Belt Overcurrent & Long Long
PMCC 02 160 273 Electric 400 400 0.75 0.76 304 0.27 N/A N/A N/A N/A N/A 0.0682 0.068 27.2 0.1 0.68 0.68 272.85 0.1
Conveyor (TT1) Earth Fault Time Time
P3F30
Inverse Inverse
IEC - IEC -
Schneider
2 2F1/Quay Belt Overcurrent & Long Long
PMCC 02 160 273 Electric 400 400 0.75 0.76 304 0.27 N/A N/A N/A N/A N/A 0.0682 0.068 27.2 0.1 0.68 0.68 272.85 0.1
Conveyor (TT2) Earth Fault Time Time
P3F30
Inverse Inverse
IEC - IEC -
Schneider
3 3F1/Mobile Hopper Overcurrent & Long Long
PMCC 02 75 150 Electric 150 150 1.10 1.10 165 0.28 N/A N/A N/A N/A N/A 0.1002 0.1 15 0.1 1.00 1 150.35 0.1
2 Earth Fault Time Time
P3F30
Inverse Inverse
IEC - IEC -
2R1/Quay Belt Schneider
4 Overcurrent & Long Long
PMCC 02 Conveyor IC2 160 273 Electric 400 400 0.75 0.76 304 0.27 N/A N/A N/A N/A N/A 0.0682 0.068 27.2 0.1 0.68 0.68 272.85 0.1
Earth Fault Time Time
(TT2) P3F30
Inverse Inverse
IEC - IEC -
11F1/Quay Belt Schneider
5 Overcurrent & Long Long
PMCC 02 Conveyor IC3 160 273 Electric 400 400 0.75 0.76 304 0.27 N/A N/A N/A N/A N/A 0.0682 0.068 27.2 0.1 0.68 0.68 272.85 0.1
Earth Fault Time Time
(TT3) P3F30
Inverse Inverse
IEC - IEC -
Schneider
6 12F1/Mobile Overcurrent & Long Long
PMCC 02 75 150 Electric 150 150 1.10 1.10 165 0.28 N/A N/A N/A N/A N/A 0.1002 0.1 15 0.1 1.00 1 150.35 0.1
Hopper 1 Earth Fault Time Time
P3F30
Inverse Inverse
CUSTOMER RINA
PROJECT Material Handling System For Port of San Pedro, Ivory Coast
DOC NO. PP83/3133
REV NO. 0
DG SYNCH PANEL AT MRSS S/S - Protective Device(Relay) Settings
Phase Neutral
Relay OCR 51 (I>) OCR 50 (I>>) OCR 51 N OCR 50 N
Feeder
S.No Rating Manufacturer Phase CT Device Block
Panel Number/Feeder FLA (A) Calculate Recomm Prim. Calculated Recomm Prim. Calculate Recomm Prim. Calculate Recomm Prim.
(kVA) & Ratio Function Time TOC by Time
Description Curve d Pickup ended Amps Time Dial Pickup ended Amps Curve d Pickup ended Amps Time Dial d Pickup ended Amps
Model Delay (s) IOC Delay (s)
Value Pickup (A) Value Pickup (A) Value Pickup (A) Value Pickup (A)

Schneider IEC - IEC -


1 1F1/Incomer-1 Overcurrent &
1050 1461 Electric 1600 Very 1.00 1.00 1600 0.55 7.3 8.73 13968 0.51 Enabled Normal 0.18 0.3 480 0.25 0.91 1 1600 0.5
DG SYNCH from EDG 01 Earth Fault
P3G30 Inverse Inverse
PANEL @ MRSS
S/S Schneider IEC - IEC -
2 1F2/Incomer-2 Overcurrent &
1050 1461 Electric 1600 Very 1.00 1.00 1600 0.55 7.3 8.73 13968 0.51 Enabled Normal 0.18 0.3 480 0.25 0.91 1 1600 0.5
from EDG 02 Earth Fault
P3G30 Inverse Inverse
CUSTOMER RINA
PROJECT Material Handling System For Port of San Pedro, Ivory Coast
DOC NO. PP83/3133
REV NO. 0
DG SYNCH PANEL AT MRSS S/S - Protective Device(Relay) Settings
Phase Neutral
Relay OCR 51 (I>) OCR 50 (I>>) OCR 51 N OCR 50 N
Feeder
S.No Rating Manufacturer Phase CT Device Block
Panel Number/Feeder FLA (A) Calculate Recomm Prim. Calculated Recomm Prim. Calculate Recomm Prim. Calculate Recomm Prim.
(kVA) & Ratio Function Time TOC by Time
Description Curve d Pickup ended Amps Time Dial Pickup ended Amps Curve d Pickup ended Amps Time Dial d Pickup ended Amps
Model Delay (s) IOC Delay (s)
Value Pickup (A) Value Pickup (A) Value Pickup (A) Value Pickup (A)

Schneider IEC - IEC -


1 1F1/Incomer-1 Overcurrent &
500 696 Electric 800 Very 0.96 1.00 800 0.82 7.0 8 6400 0.41 Enabled Normal 0.17 0.217 173.6 0.18 0.87 1 800 0.4
DG SYNCH from EDG 03 Earth Fault
P3G30 Inverse Inverse
PANEL @ DSS
S/S Schneider IEC - IEC -
2 1F2/Incomer-2 Overcurrent &
500 696 Electric 800 Very 0.96 1.00 800 0.82 7.0 8 6400 0.41 Enabled Normal 0.17 0.217 173.6 0.18 0.87 1 800 0.4
from EDG 04 Earth Fault
P3G30 Inverse Inverse