HDB en 13
HDB en 13
Name Art.-No.
IMPACT67 E DIO16 5P 55138
IMPACT67 E DIO14 DIO2/IOL2 5P 55139
IMPACT67 E DIO12 DIO4/IOL4 5P 55140
IMPACT67 E DIO16 4P 55142
IMPACT67 E DIO14 DIO2/IOL2 4P 55143
IMPACT67 E DIO12 DIO4/IOL4 4P 55144
Document status:
Murrelektronik GmbH
Falkenstraße 3
71570 Oppenweiler
GERMANY
Phone +49 7191 47-0
Fax +49 7191 47-491000
[email protected]
NOTE
Translation of the original instructions
Table of Contents
1 Introduction 6
1.1 Service and support 6
1.2 About this manual 7
1.3 Symbols 8
1.4 Trademarks 9
1.5 Specifications 9
1.6 Glossary 9
3 Description 14
3.1 Product Designation Code 14
3.2 Product properties 14
3.3 Ethernet/IP 15
3.3.1 Communication 15
3.3.2 RPI 16
3.3.3 QuickConnect™ 17
3.3.4 Device Level Ring (DLR) 17
3.4 IO-Link 18
3.5 Module 19
3.5.1 Module structure 19
3.5.2 Connections 21
3.5.3 Display elements 22
3.5.4 DIP switch settings 24
4 Technical Data 25
4.1 Electrical data 25
4.2 Environmental characteristics 27
5 Mounting 28
5.1 Requirements 28
5.2 Dimensions 28
5.3 Mounting distance 29
5.4 Installing the module 30
5.4.1 Functional ground 32
5.4.2 Addressing lid 32
6 Installation 33
6.1 Electrical Installation of the Module 33
6.1.1 Sensors and actuators 34
6.1.2 Connecting Ethernet bus 36
6.1.3 Connecting the power supply 37
7 Start-up 39
7.1 Loading the EDS files 40
7.2 Adding a module to the network 42
7.3 Commissioning without EDS 47
7.3.1 Connections, parameters and properties 47
7.3.2 Connection matrix 48
7.3.2.1 Art.-No. 55142 48
7.3.2.2 Art.-No. 55143 49
7.3.2.3 Art.-No. 55144 52
7.3.3 Assemblies 55
8 Configuration/setting 60
8.1 Module configuration 60
8.2 Setting parameters 63
8.3 RPI configuration 64
8.4 QuickConnect™-configuration 66
8.5 DLR configuration 67
8.6 IO-Link configuration 68
8.7 Configuration values 69
9 Operation 73
9.1 LED indication 73
9.1.1 LED indication for inputs and outputs 73
9.1.2 LED indication for state 74
9.1.3 LED display MS and NS 75
9.1.4 LED indication for LNK/ACT 76
9.1.5 LED indicator power US and UA 77
9.1.6 Extended LED indication 78
9.2 Diagnostics 81
9.2.1 Diagnostics structure in the control system 81
9.2.2 Diagnostics in the web server 81
9.2.3 Diagnostic value 82
9.2.3.1 Short-circuit diagnostic 82
9.2.3.2 Undervoltage diagnostic 82
9.2.3.3 Overvoltage diagnostic 82
9.2.3.4 General diagnostic 82
9.2.3.5 Buffer overflow diagnostic 82
9.2.3.6 IO-Link master diagnostic 83
9.2.3.7 IO-Link device diagnostic 84
9.3 Acyclic IO-Link device access 86
9.3.1 Reading an IO-Link device index 86
9.3.2 Writing an IO-Link device index 87
9.3.3 Read/Write ISDU Service 88
9.3.4 IO-Link master error codes 88
12 Appendix 97
12.1 Accessories 97
12.1.1 System components 97
12.1.2 Tools 97
12.2 Supported EtherNet / IP objects 98
12.3 Standards 98
12.3.1 Identity Object (Class Code: 0x01) 98
12.3.2 Message Router Object (Class Code: 0x02) 100
12.3.3 Assembly Object (Class Code: 0x04) 100
12.3.4 Connection Manager Object (Class Code: 0x06) 101
12.3.5 Discrete Input Point Object (Class Code: 0x08) 102
12.3.6 Discrete Output Point Object (Class Code: 0x09) 103
12.3.7 Device Level Ring (DLR) Object (Class Code: 0x47) 104
12.3.8 Quality of Service Object (Class Code: 0x48) 105
12.3.9 TCP/IP Interface Object (Class Code: 0xF5) 106
12.3.10 Ethernet Link Object (Class Code: 0xF6) 108
12.3.11 Vendor Specific Objects 110
12.3.11.1 IO-Link parameter object (class code: 0x80) 110
12.4 Explanation of the process data 113
12.4.1 Digital Input 113
12.4.2 DI Qualifier 113
12.4.3 DO Qualifier 114
12.4.4 System Status 114
12.4.5 IO-Link Port X Status 114
12.4.6 Diagnostic Buffer 115
12.4.7 Digital Output 115
12.5 Glossary 116
1 Introduction
Name Art.-No.
IMPACT67 E DIO16 5P 55138
IMPACT67 E DIO14 DIO2/IOL2 5P 55139
IMPACT67 E DIO12 DIO4/IOL4 5P 55140
IMPACT67 E DIO16 4P 55142
IMPACT67 E DIO14 DIO2/IOL2 4P 55143
IMPACT67 E DIO12 DIO4/IOL4 4P 55144
Information This document contains information on
1.3 Symbols
This document includes information and notes that have to be observed for
your own safety and to avoid injuries and material damage. They are marked
as follows:
DANGER!
Immediate danger
Failure to observe this warning involves an imminent risk of death or seri-
ous injuries.
WARNING!
Possible danger
Failure to observe this warning can lead to death or serious injuries.
CAUTION!
Low-risk danger
Failure to observe this warning can lead to mild to moderate injuries.
NOTICE
Possible material damage
Failure to observe the warning may cause damage to the device and/or
the system.
NOTE
Other technical information and notes of Murrelektronik GmbH.
RECOMMENDATION
Notes with this symbol are recommendations of Murrelektronik GmbH.
1.4 Trademarks
Trademarks of the following companies and institutions are used in this docu-
mentation:
1.5 Specifications
Specification Link
EtherNet/IP Specification http://www.odva.org
IO-Link Spezifikation http://www.io-link.com
1.6 Glossary
DANGER!
High electrical voltage in the machine/system.
Death or severe injuries resulting from electric shock.
When working on the machine/modules, comply with the five safety rules
of electrical engineering.
NOTE
Work on the hardware and software of the device may only be performed by
qualified personnel of Murrelektronik GmbH, with the exception of firmware
updates.
NOTE
Use only a power supply unit that allows max. 60 V DC or 25 V AC in case of
error. The power supply must comply with SELV or PELV.
CAUTION!
Hot surface!
Minor injuries caused by a contact with the surface and damage to devices.
Wear thermally suitable gloves.
Use thermally suitable connecting cables only.
Returns
Label the product and the packaging with
“For disposal”.
Package the product.
Send the package to:
Murrelektronik GmbH
Falkenstraße 3
71570 Oppenweiler | GERMANY
We will make sure that the items are disposed of in accordance with German
legislation. The most recent owner is responsible for transport to the return
point until items arrive at their destination.
3 Description
E Ethernet/IP
Property Description
Robust Versatile applications under very high
loads due to:
robust plastic case,
No formation of water of condensation
due to fully encapsulated case.
Vibration-proof Safety function also guaranteed when subjected to con-
tinuous vibration
Resistant Long life due to acid and alkali resistant plastic.
Tight Tight up to degree of protection IP67 (EN 60529)
3.3 Ethernet/IP
3.3.1 Communication
The maximum permissible cable length to the end point without any auxiliary
devices is 100 m.
A 2-port switch is integrated into the device (target). The switches send multi-
cast messages to all switch ports and behave in this case like a hub. When
EtherNet/IP Unmanaged Switches are used, this means that the more multi-
cast users (Ethernet/IP users) are added to the system, the higher the multi-
cast traffic for the users. Thus, a higher amount of bandwidth is used in the
system which results in longer response times. Each user must supply more
CPU power to view and reject messages that are not addressed to the user.
If the number of messages to be processed is too high, the user may be sub-
ject to an overload; missing responses may be at the incorrect RPI speed and,
ultimately, this may lead to an interruption in communication. This overload sit-
uation may influence both the PC/PLC scanner and the I/O user.
It is therefore recommended to split the entire network into several segments
by means of several switches. By choosing suitable RPI times and switches,
high-speed networks can be decoupled from non-time-critical systems.
For high-speed control systems of average size or any size, the use of Man-
aged Switches is recommended. To manage the multicast traffic, the switch
must support the IGMP Snooping function (Internet Group Management Pro-
tocol). For the connection of a control system to a large plant or company net-
work, a virtual LAN switch function of the use of routers is usually required.
Unicast connections.
The device has the possibility to establish data connections via so-called Uni-
cast connections. These connections allow a clear assignment of start and tar-
get addresses and this should result, in combination with the switches, in a
reduced data volume in the network. Please select the best type of connection
depending on your application.
3.3.2 RPI
Requested Packet Inter- When setting up an EtherNet/IP system, the RPI value must be carefully set
val (RPI) in the scanner.
According to the manufacturer's version, this value is in the range between 1
ms and several hundred ms.
The RPI value determines the speed at which the scanner sends Ethernet/IP
messages (packets).
It also determines the maximum speed at which the bus node sends
messages.
The value that is set in the scanner is transmitted to the device as soon as the
connection is established so that the system uses the same time base.
The RPI value can be used not only to set the speed but also to set the speed
at which the scanner expects timely reception.
If the selected RPI time is too short, a higher network load is automatically
generated.
Due to the higher network load, the system must spend more time to process
the queries accordingly.
This is also applicable to the messages which are not addressed directly to the
device since they must be accepted and rejected anyway.
This results in an overload situation in which the device is no longer able to
execute the internal processes and adhere to the required RPI time.
If the reception of the telegram exceeds the set RPI time by a factor of 4, the
control interrupts the I/O communication and switches into an error state.
Please observe:
a | Configurations which require RPI times shorter than 10 ms must be tested
in advance for correct operation.
b | The minimum supported RPI time is 1 ms!
3.3.3 QuickConnect™
Device Level Ring Device Level Ring (DLR) is a protocol which allows media redundancy in a
(DLR) ring topology, e.g. for Ethernet/IP™.
A ring network consists of at least one ring supervisor and any desired number
of users.
To build up the topology and to detect cable breaks inside the ring, there are
two different methods:
a | Beacon-based
b | Announce-based
Users which support DLR must have implemented the DLR object (0x47) that
provides the methods for configuration and diagnostic.
The modules described in this manual support the beacon-based DLR tech-
nology.
The described modules do not support the ring supervisor function and can
therefore not be used as ring supervisor.
3.4 IO-Link
IO-Link is a standardized link that enables connection of intelligent devices of
the sensor and actuator level to an automation system.
Communication takes place between a master and a device. A master module
has one or more ports. One device can be connected per port, which means
that the IO-Link is a point-to-point communication system and not a fieldbus.
The IO-Link master module builds the interface between the higher fieldbus
level and the IO-Link system.
The IO-Link device converts the data of the sensors/actuators into the IO-Link
format and passes the data on to the master. The device can be implemented
either directly into the sensor/actuator or as a separate device.
3.5 Module
Art.-No. 55138
X0 ... X7 Digital inputs and digital outputs
Art.-No. 55139
X0 ... X5 Digital inputs and digital outputs
X6, X7 Digital inputs and digital outputs or IO-Link
Art.-No. 55140
X0 ... X3 Digital inputs and digital outputs
X4 ... X7 Digital inputs and digital outputs or IO-Link
NOTICE
Material damage caused by male connectors and female connectors that
have not been sealed!
The degree of protection IP67 is only guaranteed if all connections are sealed
with connectors, screw plugs or sealing caps.
Seal unused male connectors and female connectors.
Art.-No. 55142
X0 ... X7 Digital inputs and digital outputs
Art.-No. 55143
X0 ... X5 Digital inputs and digital outputs
X6, X7 Digital inputs and digital outputs or IO-Link
Art.-No. 55144
X0 ... X3 Digital inputs and digital outputs
X4 ... X7 Digital inputs and digital outputs or IO-Link
NOTICE
Material damage caused by male connectors and female connectors that
have not been sealed!
The degree of protection IP67 is only guaranteed if all connections are sealed
with connectors, screw plugs or sealing caps.
Seal unused male connectors and female connectors.
3.5.2 Connections
Art.-No. 55138
X0 ... X7 LED digital inputs and digital outputs
Art.-No. 55139
X0 ... X5 LED digital inputs and digital outputs
X6, X7 LED digital inputs and digital outputs or IO-Link
Art.-No. 55140
X0 ... X3 LED digital inputs and digital outputs
X4 ... X7 LED digital inputs and digital outputs or IO-Link
1 LED MS
LED NS
LED LNK1/ACT1
LED Status (ST)
LED LNK2/ACT2
LED POWER UA
LED POWER US
NOTE
For further information on the behavior of the LEDs, please refer to chap. 9.1
"LED indication".
Art.-No. 55142
X0 ... X7 LED digital inputs and digital outputs
Art.-No. 55143
X0 ... X5 LED digital inputs and digital outputs
X6, X7 LED digital inputs and digital outputs or IO-Link
Art.-No. 55144
X0 ... X3 LED digitale Eingänge und digitale Ausgänge
X4 ... X7 LED digital inputs and digital outputs or IO-Link
1 LED MS
LED NS
LED LNK1/ACT1
LED Status (ST)
LED LNK2/ACT2
LED POWER UA
LED POWER US
NOTE
For further information on the behavior of the LEDs, please refer to chap. 9.1
"LED indication".
Set the DIP switch in such a way that the desired function of the module is
achieved.
DIP switch
10-bit DIP switch
NOTE
As-delivered: all switches are in the OFF position.
NOTICE
The saved default IP address is 192.168.1.6.
NOTICE
Switches 1 to 8 must be considered a binary number in which switch 1 rep-
resents 20 and switch 8 stands for 27 .
NOTICE
The IP address parameters are stored for all switch settings. This must be tak-
en into account in particular with the switch setting 0.
4 Technical Data
Module supply
Operating voltage US 24 V
Voltage range US 18 ... 30 V
Voltage range US 20.3 ... 30 V
(when using IO-Link)
Operating voltage UA 18 ... 30 V
Max. sensor current US 9A
Max. actuator current UA 9A
Current consumption ≤0.18 A
Cross-section of 7/8" connector ≤1.5 mm²
Reverse polarity protection for US and UA Yes
Reverse polarity protection Yes
Bus
Fieldbus protocol Ethernet/IP
Transfer rate 10/100 Mbit/s
EtherNet/IP addressing via DIP switches
RPI ≥1 ms
DLR Beacon-based Ring
Node
QuickConnect™ Class A
Inputs (DI)
Delay time 1 ms + t cycle
Input characteristic EN 61131-2, type 3
Sensor power supply port DIO ≤0.2 A load
Automatic start
Sensor power supply IO-Link port Art.-No. 55139, 55140, 55143, 55144 ≤1 A load
Automatic start
Short-circuit protection, sensor supply High-side switch with
overload protection
Connection M12
Conductor cross-section M12 ≤0.75 mm²
Outputs (DO)
Output current ≤1.6 A per channel
Frequency ≤50 Hz
Short-circuit protection actuator High-side switch with
overload protection
High-side switch with overload protection M12
Conductor cross-section M12 ≤0.75 mm²
Derating
actuator supply total
current
IO-Link
IO-Link devices operating voltage 24 V
IO-Link devices voltage range 20 ... 30 V
Specification V 1.1
Transfer rate Com 1 / Com 2 / Com 3
Input specification IO-Link specification
EN61131-2, type 1
Transfer rate recognition Automatic
Climatic
Operating temperature -25 °C ... +55 °C
Storage temperature -25 °C ... +70 °C
Degree of protection of the housing Acc. to EN 60529 IP67
Relative humidity ≤95 %
Installation height Above sea level ≤2000 m
Mechanical
Vibration test EN 60068 Part 2-6 10 ... 60 Hz,
amplitude
0,35 mm,
60 ... 150 Hz; 5 g
Shock test EN 60068 Part 2-27 15 g,
duration 11 ms
Electrical safety
Degree of protection EN 60529 IP67
Protection class When using an SELV or PELV power supply III
Degree of pollution 2
EMC immunity
Electrostatic discharge (ESD) EN 61000-4-2
High-frequency electrical fields EN 61000-4-3
Fast transient burst EN 61000-4-4
Voltage surges EN 61000-4-5
performed HF EN 61000-4-6
Magnetic field 50/60 Hz EN 61000-4-8
Power failures EN 61000-4-11
5 Mounting
5.1 Requirements
Conditions for mounting:
Even mounting surface to avoid mechanical tension
Provide suitable grounding
Suitable installation site in terms of vibration and shock load, temperature
and humidity (see chap. 4 "Technical Data" )
Protected to avoid tearing off the connecting cables by personnel or de-
vice
5.2 Dimensions
NOTE
For correct installation and improved heat dissipation, we recommend
keeping a minimum distance of 3 mm when mounting the IMPACT67.
NOTE
If angled male connectors are used, a minimum distance of 50 mm to the
wall, ceiling and between the modules must be adhered to.
NOTICE
Material damage due to incorrect installation
The fastening screws and tightening torques depend on the surface of the in-
stallation site.
Use fastening screws that are suitable for the
mounting surface structure!
Carefully tighten the screws! The indicated tightening
torques have to be adhered to.
NOTICE
Material damage through improper use
Do not use the modules as climbing aids. Improper use can cause the mod-
ules to break off or to be damaged otherwise.
Install the modules in such a way that they cannot be used as climbing aid!
NOTE
The screws and the grounding strap illustrated are not included in the scope
of delivery.
Module fastening
Art.-No.
M6 2 Nm 7000-98001-0000000
NOTE
Use a conductive screw to attach the grounding strap.
M4 1,2 Nm Art.-No.
7000-98001-0000000
Addressing lid
fastening
Art.-No.
M3 0,8 Nm
7000-98001-0000000
6 Installation
WARNING!
Danger due to electric voltage in the machine / system.
It may result in death or fatal injuries.
1. Observe the five safety rules.
2. Connect the device to the electrical system.
WARNING!
Risk of fire due to short circuit!
Supply lines and/or modules damaged due to short circuit
may overheat and cause fires!
Provide intelligent current monitoring or fuse.
The fuse must be designed for max. 9 A.
CAUTION!
Loss of function!
Only install cables and accessories that meet the requirements and
regulations for safety, electromagnetic compatibility and, if required, tele-
communication terminal equipment specifications as well as the
specification data.
CAUTION!
Hot surface!
Minor injuries caused by a contact with the surface and damage to devices.
Wear thermally suitable gloves.
Use thermally suitable connecting cables only.
NOTICE
Damage in the machine/plant caused by incorrect switching on of volt-
age sources
When the module is switched on with separate actuator and sensor voltage,
the function of the digital inputs and outputs cannot be guaranteed.
Always switch on voltage sources in the following order:
NOTE
Use only a power supply unit that allows max. 60 V DC or 25 V AC in case of
error. The power supply must comply with SELV or PELV.
NOTICE
Damage to and failure of the device due to ingress of liquids!
The degree of protection IP67 is only guaranteed if all connections are sealed
with plug connectors, screw plugs or sealing caps.
Seal unused male and female connectors.
Connection of
M12 female connector
Art.-No.
M12 0.6 Nm
7000-99102-0000000
NOTE
Feeding in an external mass via M12 female connectors can lead to faults.
Do not feed external mass to the module via M12 female connectors.
You will find a wide range of connecting wires in the catalog or in the online
shop of Murrelektronik GmbH at: http://shop.murrelektronik.com
NOTE
The cable length is limited to 20 m. The IMPACT67 automatically selects the
communication speed suitable for the IO-Link device.
Supported IO-Link The module supports the IO-Link communication using the following speeds:
communication 4,800 baud (COM 1)
38,400 baud (COM 2)
230,400 baud (COM 3)
Connecting the
M12 female connector
(bus)
Art.-No.
M12 0.6 Nm 7000-99102-0000000
You will find a wide range of connecting wires in the catalog or in the online
shop of Murrelektronik GmbH at: http://shop.murrelektronik.com
Connecting
7/8" male connector
POWER IN
XD1
Connecting
7/8" male connector
POWER OUT
XD2
Art.-No.
7/8" 1,5 Nm 7000-99104-0000000
You will find a wide range of connecting wires in the catalog or in the online
shop of Murrelektronik GmbH at: http://shop.murrelektronik.com
CAUTION!
Leaky housing!
Risk of personal injury and material damage due to failure caused by ingress
of
conductive liquids.
Seal unused male and female connectors.
You will find suitable sealing connectors/screw plugs for the ports in our
onlineshop. http://shop.murrelektronik.com
Cable
connection
You will find a wide range of connecting wires in the catalog or in the online
shop of Murrelektronik GmbH at: http://shop.murrelektronik.com
7 Start-up
CAUTION!
Uncontrolled processes
Personal injury and material damage due to incorrectly performed start-up
phases (e.g. first start-up, restart and
configuration changes).
Always perform the start-up in this sequence:
NOTICE
Functional errors in residential areas
Devices of EMC Class A may cause interferences in residential
areas.
The system operator has to take appropriate measures.
Loading the EDS files Installing the EDS files and/or the module description file.
The EDS file can be found in the online shop of Murrelektronik GmbH under
the article number of the module.
Alternative The dialog window can also be called via the menu line Files/New Compo-
module selection nent/Module.
Searching a module Use the input mask to search for the module that you want to add to the net-
work.
a | Use search terms which describe the desired module, e.g. product num-
ber, product name or manufacturer.
b | Use a filter from the dialog window.
General settings
Selecting the connec- In order to choose the best connection for every application, you can choose
tion from various connection options:
a | when adding the module to the network, select the right connection or
b | call the settings again by double-clicking the module.
In Module Definition
Click Change.
A new window appears.
Set the number or the type of connection
7.3.2 "Connection matrix" here.
Click the preset connection (Exclusive Owner).
Select the connection that meets the requirements.
The list of all connections that can be set is displayed.
NOTICE
The Murrelektronik modules support up to 3 connections at a time
(1 Exclusive Owner and 2 Non-Exclusive-Owner connections).
NOTICE
Listen Only connections can only be established to Multicast Non-Listen
Only connections of the over EDS category.
This selects the configuration instance to be used for the instance of the Non-
Listen Only connection used.
NOTICE
In order to use connections of the
Configuration via web server assembly instance 175 category, set the
Configuration parameter to over web server.
NOTICE
Expert connections are listed with the minimum length and do not consider
configurations of IO-Link data lengths.
The final length of an assembly instance is the minimum length plus the sum
of all all configured IO-Link data lengths.
Calculate separately for input and output data.
Minimum length + ∑ IO-Link port Z data length
7.3.3 Assemblies
Instance 101/104/107/110/113/116
101 104 107 110 113 116
Total length in 14 18 26 42 74 10 + ∑
bytes IO-Link input data
Digital inputs 0 ... 1 0 ... 1 0 ... 1 0 ... 1 0 ... 1 0 ... 1
DI Qualifier 2 ... 3 2 ... 3 2 ... 3 2 ... 3 2 ... 3 2 ... 3
DO Qualifier 4 ... 5 4 ... 5 4 ... 5 4 ... 5 4 ... 5 4 ... 5
System status 6 ... 9 6 ... 9 6 ... 9 6 ... 9 6 ... 9 6 ... 9
IO-Link port 1 10 ... 11 10 ... 13 10 ... 17 10 ... 25 10 ... 41 ...
input data (0 ... 32 bytes)
IO-Link port 2 12 ... 13 14 ... 17 18 ... 25 26 ... 41 42 ... 73 ...
input data (0 ... 32 bytes)
Tab. 7-16: Instance 101/104/107/110/113/116
Instance 102/105/108/111/114/117
102 105 108 111 114 117
Total length in 26 30 38 54 86 22 + ∑
bytes IO-Link input data
Digital input 0 ... 1 0 ... 1 0 ... 1 0 ... 1 0 ... 1 0 ... 1
DI Qualifier 2 ... 3 2 ... 3 2 ... 3 2 ... 3 2 ... 3 2 ... 3
DO Qualifier 4 ... 5 4 ... 5 4 ... 5 4 ... 5 4 ... 5 4 ... 5
System status 6 ... 9 6 ... 9 6 ... 9 6 ... 9 6 ... 9 6 ... 9
IO-Link port 1 10 ... 11 10 ... 13 10 ... 17 10 ... 25 10 ... 41 ...
input data (0 ... 32 bytes)
IO-Link port 1 12 ... 17 14 ... 19 18 ... 23 26 ... 41 42 ... 47 X ... X+5
status (6 bytes)
IO-Link port 2 18 ... 19 20 ... 23 24 ... 31 42 ... 47 48 ... 79 ...
input data (0 ... 32 bytes)
IO-Link port 2 20 ... 25 24 ... 29 32 ... 37 48 ... 53 80 ... 85 Y ... Y+5
status (6 bytes)
Tab. 7-17: Instance 102/105/108/111/114/117
Instance 103/106/109/112/115/118
103 106 109 112 115 118
Total length in 90 94 102 118 150 86 + ∑
bytes IO-Link input data
Digital input 0 ... 1 0 ... 1 0 ... 1 0 ... 1 0 ... 1
DI Qualifier 2 ... 3 2 ... 3 2 ... 3 2 ... 3 2 ... 3 2 ... 3
DO Qualifier 4 ... 5 4 ... 5 4 ... 5 4 ... 5 4 ... 5 4 ... 5
System status 6 ... 9 6 ... 9 6 ... 9 6 ... 9 6 ... 9 6 ... 9
IO-Link port 1 10 ... 11 10 ... 13 10 ... 17 10 ... 25 10 ... 41 ...
input data (0 ... 32 bytes)
IO-Link port 1 12 ...17 14 ... 19 18 ... 23 26 ... 31 42 ... 47 X ... X+5
status (6 bytes)
IO-Link port 2 18 ... 19 20 ... 23 24 ... 31 32 ... 47 48 ... 47 ...
input data (0 ... 32 bytes).
IO-Link port 2 20 ... 25 24 ... 29 32 ... 37 48 ... 53 80 ... 85 Y ... Y+5
status (6 bytes)
Diagnostic 26 ... 89 30 ... 93 38 ... 101 54 ... 117 86 ... 149 ...
buffer (64 bytes)
Tab. 7-18: Instance 103/106/109/112/115/118
Instance 119/122/125/128/131/134
119 122 125 128 131 134
Total length in 18 26 42 74 138 10 + ∑
bytes IO-Link input data
Digital input 0 ... 1 0 ... 1 0 ... 1 0 ... 1 0 ... 1 0 ... 1
DI Qualifier 2 ... 3 2 ... 3 2 ... 3 2 ... 3 2 ... 3 2 ... 3
DO Qualifier 4 ... 5 4 ... 5 4 ... 5 4 ... 5 4 ... 5 4 ... 5
System status 6 ... 9 6 ... 9 6 ... 9 6 ... 9 6 ... 9 6 ... 9
IO-Link port 1 10 ... 11 10 ... 13 10 .. 17 10 ... 25 10 ... 41 ...
input data (0 ... 32 bytes)
IO-Link port 2 12 ... 13 14 ... 17 18 ... 25 26 ... 41 42 ... 73 ...
input data (0 ... 32 bytes)
IO-Link port 3 14 ... 15 18 ... 21 26 ... 33 42 ... 57 74 ... 105 ...
input data (0 ... 32 bytes)
IO-Link port 4 16 ... 17 22 ... 25 34 ... 41 58 ... 73 106 ... 137 ...
input data (0 ... 32 bytes)
Tab. 7-19: Instance 119/122/125/128/131/134
Instance 120/123/126/129/132/135
120 123 126 129 132 135
Total length in 42 50 66 98 162 34 + ∑
bytes IO-Link input data
Digital input 0 ... 1 0 ... 1 0 ... 1 0 ... 1 0 ... 1 0 ... 1
DI Qualifier 2 ... 3 2 ... 3 2 ... 3 2 ... 3 2 ... 3 2 ... 3
DO Qualifier 4 ... 5 4 ... 5 4 ... 5 4 ... 5 4 ... 5 4 ... 5
System status 6 ... 9 6 ... 9 6 ... 9 6 ... 9 6 ... 9 6 ... 9
IO-Link port 1 10 ... 11 10 ... 13 10 ... 17 10 ... 25 10 ... 41 ...
input data (0 ... 32 bytes)
IO-Link port 1 12 ...17 14 ... 19 18 ... 23 26 ... 41 42 ... 47 W ... W+5
status (6 bytes)
IO-Link port 2 18 ... 19 19 ... 23 24 ... 31 32 ... 47 48 ... 79 ...
input data (0 ... 32 bytes)
IO-Link port 2 20 ... 25 24 ... 29 32 ... 37 48 ... 53 80 ... 85 X ... X+5
status (6 bytes)
IO-Link port 3 26 ... 27 30 ... 33 38 ... 45 54 ... 69 86 ... 117 ...
input data (0 ... 32 bytes)
IO-Link port 3 28 ... 33 34 ... 39 46 ... 51 70 ... 75 118 ... 123 Y ... Y+5
status (6 bytes)
IO-Link port 4 34 ... 35 40 ... 43 52 ... 59 76 ... 91 124 ... 155 ...
input data (0 ... 32 bytes)
IO-Link port 4 36 ... 41 44 ... 49 60 ... 65 92 ... 97 156 ... 161 Z ... Z+5
status (6 bytes)
Tab. 7-20: Instance 120/123/126/129/132/135
Instance 121/124/127/1230133/136
121 124 127 130 133 136
Total size in bytes 106 114 130 162 226 98 + ∑
IO-Link input data
Digital Input 0 ... 1 0 ... 1 0 ... 1 0 ... 1 0 ... 1 0 ... 1
DI Qualifier 2 ... 3 2 ... 3 2 ... 3 2 ... 3 2 ... 3 2 ... 3
DO Qualifier 4 ... 5 4 ... 5 4 ... 5 4 ... 5 4 ... 5 4 ... 5
System status 6 ... 9 6 ... 9 6 ... 9 6 ... 9 6 ... 9 6 ... 9
IO-Link port 1 in- 10 ... 11 10 ... 13 10 ... 17 10 ... 25 10 ... 41 (0 ... 32 bytes)
put data
IO-Link port 1 12 ...17 14 .. 19. 18 ... 23 26 ... 41 42 ... 47 W ... W+5 (6 bytes)
status
IO-Link port 2 in- 18 ... 19 19 ... 23 24 ... 31 42 ... 47 48 ... 79 (0 .. 32 bytes)
put data
IO-Link port 2 20 ... 25 24 ... 29 32 ... 37 48 ... 53 80 ... 85 X ... X+5 (6 bytes)
status
IO-Link port 3 in- 26 ... 27 30 ... 33 38 ... 45 54 ... 69 86 ... 117 (0 ... 32 bytes)
put data
IO-Link port 3 28 ... 33 34 ... 39 46 ... 51 70 ... 75 118 ... 123 Y ... Y+5 (6 bytes)
status
IO-Link port 4 in- 34 ... 35 40 ... 43 52 ... 59 76 ... 91 124 ... 155 (0 ... 32 bytes)
put data
IO-Link port 4 36 ... 41 44 ... 49 60 ... 65 92 ... 97 156 ... 161 Z ... Z+5 (6 bytes)
status
Diagnostic buffer 42 .. 105 50 ... 113 66 ... 129 98 ... 161 162 ... 225 (64 bytes)
Tab. 7-21: Instance 121/124/127/1230133/136
Instance 141/142/143/144/145/151
141 142 143 144 145 151
Total length in 6 10 18 34 66 2+∑
bytes IO-Link output data
Digital output 0 ... 1 0 ... 1 0 ... 1 0 ... 1 0 ... 1 0 ... 1
IO-Link port 1 2 ... 3 2 ... 5 2 ... 9 2 ... 17 2 ... 33 ...
output data (0 ... 32 bytes)
IO-Link port 2 4 ... 5 6 ... 9 10 ... 17 18 ... 33 34 ... 65 ...
output data (0 ... 32 bytes)
Tab. 7-23: Instance 141/142/143/144/145/151
Instance 146/147/148/149/150/152
146 147 148 149 150 152
Total length in 8 12 20 36 68 4+∑
bytes IO-Link output data
Digital output 0 ... 1 0 ... 1 0 ... 1 0 ... 1 0 ... 1 0 ... 1
IO-Link port 2 ... 3 2 ... 5 2 ... 9 2 ... 17 2 ... 33 ...
output data (0 ... 32 bytes)
IO-Link port 2 4 ... 5 6 ... 9 10 ... 17 18 ... 33 34 ... 65 ...
output data (0 ... 32 bytes)
Diagnostic 6 ... 7 10 ... 11 18 ... 19 34 ... 35 66 ... 67 ...
confirmation (2 bytes)
Tab. 7-24: Instance 146/147/148/149/150/152
Instance 153/154/155/156/157/163
153 154 155 156 157 163
Total length in 10 18 34 66 130 2+∑
bytes IO-Link output data
Digital output 0 ... 1 0 ... 1 0 ... 1 0 ... 1 0 ... 1 0 ... 1
IO-Link port 1 out- 2 ... 3 2 ... 5 2 ... 9 2 ... 17 2 ... 33 ...
put data (0 ... 32 bytes)
IO-Link port 2 out- 4 ... 5 6 ... 9 10 ... 17 18 ... 33 34 ... 65 ...
put data (0 ... 32 bytes)
IO-Link port 3 out- 6 ... 7 10 ... 13 18 ... 25 34 ... 49 66 ... 97 ...
put data (0 ... 32 bytes)
IO-Link port 4 8 ... 9 14 ... 17 26 ... 33 50 ... 65 98 ... 129 ...
output data (0 ... 32 bytes)
Tab. 7-25: Instance 153/154/155/156/157/163
Instance 158/159/160/161/162/164
158 159 160 161 162 164
Total length in 12 20 36 68 132 4+∑
bytes IO-Link output data
Digital output 0 ... 1 0 ... 1 0 ... 1 0 ... 1 0 ... 1 0 ... 1
IO-Link port 1 out- 2 ... 3 2 ... 5 2 ... 9 2 ... 17 2 ... 33 ...
put data (0 ... 32 bytes)
IO-Link port 2 out- 4 ... 5 6 ... 9 10 ... 17 18 ... 33 34 ... 65 ...
put data (0 ... 32 bytes)
IO-Link port 3 out- 6 ... 7 10 ... 13 18 ... 25 34 ... 49 66 ... 97 ...
put data (0 ... 32 bytes)
IO-Link port 4 out- 8 ... 9 14 .. 17 26 ... 33 50 ... 65 98 ... 129 ...
put data (0 ... 32 bytes)
Diagnostic 10 ... 11 18 ... 19 34 ... 35 66 ... 67 130 ... 131 ...
confirmation (2 bytes)
Tab. 7-26: Instance 158/159/160/161/162/164
8 Configuration/setting
WARNING!
Protection function may be impaired if the module configuration is
changed.
The person who makes the changes is responsible for maintaining the
protective function of the device.
Make sure that only authorized persons change the configuration.
If you change the configuration, use the password hierarchy provided by
your engineering software.
After every change to the configuration, test the protection equipment for
efficiency.
Configuration via EDS After the import of the EDS in the programming software and the selection of
a connection suitable for the application, the configuration files can be found
in the controller tags.
The input and output tags associated with the device can be found next to it.
All configuration tags have a specific name that describes the function of the
areas.
Enter the appropriate values for your application.
Each time when a connection with the control system is established, the
device is correctly configured
For more information on the adjustable values, please refer to chap. 8.7 "Con-
figuration values"
Configuration via web The device can also be configured via web server if this is necessary. Howev-
server er, this requires some settings beforehand.
Call up the web server of the device in your browser by entering the IP ad-
dress of the device in the address line.
Navigate to the device parameters and change the
Configuration parameter to Over Web Server.
NOTICE
Parameter are transmitted in Forward Open Telegram (power reset or separa-
tion of the connection is required).
NOTICE
The minimum RPI is 1 ms.
8.4 QuickConnect™-configuration
Use of Quickconnect™ QuickConnect™ is usually used on applications which require a fast integra-
tion of users, e.g. of an IO module, in an EtherNet/IP network in order to guar-
antee a correct functioning.
A typical application is, for example, a robot application during which the tool
to be used is often changed.
Prerequisites for Quick- To use QuickConnect™ the control system requires an electrical lock signal
Connect™ that signals the startup and the correct power supply to the device.
This signal is the trigger to start the QuickConnect™ sequence of the control
system.
This sequence and the directly wired signal to a digital input of the control sys-
tem must be implemented by the system builder.
NOTICE
Further information regarding the integration of QuickConnect can be found in
the manual of the control manufacturer.
The use of modules which are not DLR-compliant in an EtherNet/IP ring net-
work is not excluded but results in a higher ring recovery time when the ring
topology is interrupted.
NOTICE
The modules described in this manual support the beacon-based DLR tech-
nology.
IO-Link device configu- It is possible to parameterize the connected IO-Link devices through EtherNet/
ration through IP Explicit Messages.
EtherNet/IP Explicit
Messages
For further information, please refer to chap. 9.3 "Acyclic IO-Link device ac-
cess"
NOTICE
Unexpected behavior of the device.
Use only the values listed here.
Diagnostic parameters
General parameters
9 Operation
Yellow
Continuously lit - 0
Red
0V 0
Off
Tab. 9-1: LED indication digital input
Red 0V 1
continuously lit
Off 0V 0
Error at input or output In the event of an error (short circuit, overload or feedback) at the digital output
or the sensor power supply, the relevant LEDs light up in red at the M12 port.
Off
Tab. 9-3: LED indication IO-Link
Green
Continuously lit An error is active on the module
Red
Tab. 9-4: LED indication ST
LED-Indication
Overview
Green
Flashing At least one connection timed out
Red
Continuously lit The module has detected that another
device is using its IP address
Red
Flashing Self-test
Green
Red
Device is switched off.
Device does not have a configured IP
Off address. Device has no link
Tab. 9-5: LED indication NS
Grün
Flashing Self-test
Grün
Rot
Flashing The module has detected that another
device is already using its IP address
Rot
Device is off
Off
Tab. 9-6: LED indication MS
LED-Indication
Overview
LED-Indication
Overview
NOTE
At US <18 V, an error-free operation is no longer guaranteed.
LED-Indication
Overview
Off
Tab. 9-12: Extended LED indication, update
Off
POWER UA Off
POWER US
Tab. 9-14: Extended LED Indication, recovery firmware: system startup
Yellow
POWER UA
POWER US
Off
Tab. 9-15: Extended LED states, recovery firmware: system initialization
POWER US
Off
Tab. 9-16: Extended LED Indication, recovery firmware: system run
ST Flash, flash,
pause Firmware update: initialization of trans-
(double flash) mission
Yellow
Flashing 1 Hz
POWER US
Yellow
Tab. 9-17: Extended LED Indication, firmware update: initialization of transmission
9.2 Diagnostics
Diagnostic monitoring Another possibility to monitor the diagnostics of the module is the diagnostic
page of the integrated web server.
a) Information
b) Warning
c) Defect
4| Type: this shows whether the diagnostic has just occurred or the fault has
already been eliminated.
Active
Inactive
Description Value
Parameter Error 0x6320
Parameter Missing 0x6321
Parameter Not Initialized 0x6330
Parameter Not Specific 0x6340
Parameter Changed 0x6350
Wire Break Of A Subordinate Device 0x7700
Wire Break Of Subordinate Device 1 0x7701
Wire Break Of Subordinate Device 2 0x7702
Wire Break Of Subordinate Device 3 0x7703
Wire Break Of Subordinate Device 4 0x7704
Wire Break Of Subordinate Device 5 0x7705
Wire Break Of Subordinate Device 6 0x7706
Wire Break Of Subordinate Device 7 0x7707
Wire Break Of Subordinate Device 8 0x7708
Wire Break Of Subordinate Device 9 0x7709
Wire Break Of Subordinate Device 10 0x770A
Wire Break Of Subordinate Device 11 0x770B
Wire Break Of Subordinate Device 12 0x770C
Wire Break Of Subordinate Device 13 0x770D
Wire Break Of Subordinate Device 14 0x770E
Wire Break Of Subordinate Device 15 0x770F
Short Circuit 0x7710
Ground Fault 0x7711
Communication Monitoring: General Error 0x8100
Process Data Monitoring: General Error 0x8110
Technology Specific Application Fault 0x8C00
Simulation Active 0x8C01
Process Variable Range Over-Run 0x8C10
Measurement Range Over-Run 0x8C20
Process Variable Range Under-Run 0x8C30
Maintenance Required - Cleaning 0x8C40
Maintenance Required - Refill 0x8C41
Maintenance Required - Wear And Tear 0x8C42
Tab. 9-25: IO-Link device diagnostic (IO-Link identification 0x41)
Name Value
No Master Error 0
Service Not Available 1
Port Blocked 2
Timeout 3
Invalid Index 4
Invalid Sub-Index 5
Wrong Port 6
Wrong Port Function 7
Invalid Length 8
ISDU Not Supported 9
Tab. 9-29: IO-Link master error codes
10 Web server
The Murrelektronik web server is a graphic tool that can be used to obtain in-
formation on the device quickly and intuitively and to configure or parameter-
ize it according to your needs.
Prerequisites Prerequisite for a correct graphic display of the web server:
Install a current web browser on your PC.
Mozilla Firefox from version 57 or
Internet Explorer from version 11
Google Chrome from version 64
Operating areas
The web server is divided into 3 operating areas:
1 | System tree
• Shows the device and the available sub-functions.
2 | Navigation bar
• The navigation bar enables you to switch between the different pages
of the device or the sub-function. In addition, the white highlighting
shows which page is currently displayed.
3 | Page contents
• This area shows the contents of the page (selected in the navigation
bar).
NOTICE
The settings are only applied after the device is restarted.
NOTICE
If there are more than 8 diagnostics, a diagnostic overflow is displayed.
Restarting the device will reset the diagnostics.
The menu contains information on how to select the different functions of the
device (e.g. restart).
Download System File Load the configuration file from the online shop to the device.
To Device (.ZIP archive) The ZIP archive contains the latest description file (Lic file).
Language files for the web server and possibly required pictures.
Enter the article number of the device in the Murrelektronik online shop.
Download the configuration file with the extension “.zip”.
Save the file without unpacking it.
In the web server, navigate to the Maintenance menu item.
In the web server of the bus node, click the menu item
Download System File To Device.
Click the “...” button. button.
Select the .ZIP archive downloaded from the online shop in the file dialog.
Click Download System File To Device.
NOTICE
The loaded configuration (all parameters) is only applied after the device is re-
started.
Malfunctions
Murrelektronik assumes no liability for malfunctions resulting from a manually
edited file.
The configuration file must not be edited!
NOTICE
Damage caused by defective or damaged devices!
The functioning of the modules is not guaranteed.
Replace defective or damaged devices.
Device cleaning:
Use only oil-free compressed air or spirit
Only use lint-free materials (e.g. leather cloth)
Do not use contact spray
12 Appendix
12.1 Accessories
Designation Art.-No.
Connection adapter, 3-pin 333138
Screw Plug M12 Metal 996049
Plastic M12 screw plug, VE10 58627
7/8" Plastic screw plug 55385
Ground strap 4 mm2 100 mm for M4 4000-71001-0410004
Grounding strap screw-down set M4 4000-71003-0101604
Designation label 20x8 in a set (20 pcs) 55318
12.1.2 Tools
Designation Art.-No.
6-part screwdriver set 7000-98001-0000000
M12 Torque wrench set AF 13 7000-99102-0000000
7/8'' installation wrench set, wrench size 22 7000-99104-0000000
12.3 Standards
Class Attribute
Attribute Access Name Data Type Description of Attribute Semantics of Values
ID Rule
1 Get Revision UINT Revision of this object The current value assigned to
this attribute is one (01). If up-
dates that require an increase
in this value are made, then
the value of this attribute in-
creases by 1.
2 Get Max UINT Maximum instance number of The largest instance number of
Instance an object currently created in a created object at this class
this class level of the device. hierarchy level. This attribute
will show one (01).
6 Get Max ID UINT The attribute ID number of the The value of this attribute will
Class last class attribute of the class be seven (07).
Attribute definition implemented in the
device.
7 Get Max ID UINT The attribute ID number of the The value of this attribute will
Instance last instance attribute of the differ by product variant. This
Attributes class definition implemented in attribute will show nine (09).
the device.
Tab. 12-1: Identity Object Class Attribute
Instance Attribute
Attribute Access Name Data Type Description of Attribute Value
ID Rule
1 Get Vendor ID UINT Identification of each vendor 640
by number
2 Get Devise UINT Indication of general type of 7
Type product
3 Get Prodict UINT Identification of a particular Example: 55142
Code product of an individual vendor
4 Get Revision STRUCT Revision of the item the Identi-
of: ty Object represents
Major USINT 1
Revision
Minor USINT 6
Revision
5 Get State WORD Summary status of device
6 Get Serial UDINT Serial number of device
Number
7 Get Prodict SHORT_ Human readable identification Example:
Name STRING IMPACT67 E DIO16 4P
8 Get State USINT Present state of the device as
represented by the state tran-
sition diagram
Tab. 12-2: Identity Object Instance Attribute
Common Services
Service Code Implemented for Service Name Description of Service
Class Instance
0x01 No Yes Get_Attribute_All Returns a predefined listing of
this objects attributes.
0x05 No Yes Reset Invokes the Reset service for
the device. Option 0 restarts
the device. Option 1 invokes a
factory reset of the device.
0x0E Yes Yes Get_Attribute_Single Returns the contents of the
specified attribute.
Tab. 12-3: Common Services of Identity Object
Class Attribute
Attribute Access Name Data Type Description of Attribute Semantics of Values
ID Rule
1 Get Revision UINT Revision of this object The current value assigned to
this attribute is two (02). If up-
dates that require an increase
in this value are made, then
the value of this attribute in-
creases by 1.
Tab. 12-4: Assembly Object Class Attribute
Instance Attribute
Attribute Access Name Data Type Description of Attribute
ID Rule
3 Set,Get Data ARRAY of BYTE
4 Get Size UINT Number of bytes in Attribute 3
Tab. 12-5: Assembly Object Instance Attribute
Common Services
Service Code Implemented for Service Name Description of Service
Class Instance
0x0E Yes Yes Get_Attribute_Single Returns the contents of the
specified attribute.
0x10 No Yes Set_Attribute_Single Modifies an attribute value.
Tab. 12-6: Common Services of Assembly Object
Instance Attribute: There are no Instance Attributes implemented for this object.
Common Services: Common Services of Ethernet Link Object.
Service Code Implemented for Service Name Description of Service
Class Instance
0x0E Yes No Get_Attribute_Single Returns the contents of the
specified attribute.
Tab. 12-8: Common Services of Ethernet Link Object
Class Attribute
Attribute Access Name Data Type Description of Attribute Semantics of Values
ID Rule
1 Get Revision UINT Revision of this object. The current value assigned to
this attribute is two (02). If up-
dates that require an increase
in this value are made, then
the value of this attribute in-
creases by 1.
2 Get Max UINT Maximum instance number of The largest instance number of
Instance an object currently created in a created object at this class
this class level of the device. hierarchy level. This attribute
will show sixteen (16).
Tab. 12-9: Discrete Input Point Object Class Attribute
Instance Attribute
Attribute Access Name Data Type Description of Attribute
ID Rule
3 Get Value BOOL Input point value
Tab. 12-10: Discrete Input Point Object Instance Attribute
Common Services
Service Code Implemented for Service Name Description of Service
Class Instance
0x0E Yes Yes Get_Attribute_Single Returns the contents of the
specified attribute.
Tab. 12-12: Common Services of Discrete Input Point Object
Class Attribute
Attribute Access Name Data Type Description of Attribute Semantics of Values
ID Rule
1 Get Revision UINT Revision of this object The current value assigned to
this attribute is one (01). If up-
dates that require an increase
in this value are made, then
the value of this attribute in-
creases by 1.
2 Get Max UINT Maximum instance number of The largest instance number of
Instance an object currently created in a created object at this class
this class level of the device. hierarchy level. This attribute
will show sixteen (16).
Tab. 12-13: Discrete Output Point Object Class Attribute
Instance Attribute
Attribute Access Name Data Type Description of Attribute
ID Rule
3 Get Value BOOL Output point value
Tab. 12-14: Discrete Output Point Object Instance Attribute
Common Services
Service Code Implemented for Service Name Description of Service
Class Instance
0x0E Yes Yes Get_Attribute_Single Returns the contents of the
specified attribute.
0x10 No Yes Set_Attribute_Single Modifies the contents of the at-
tributes of the class or object.
Tab. 12-16: Common Services of Discrete Output Point Object
Class Attribute
Attribute Access Name Data Type Description of Attribute Semantics of Values
ID Rule
1 Get Revision UINT Revision of this object The current value assigned to
this attribute is three (03). If up-
dates that require an increase
in this value are made, then
the value of this attribute in-
creases by 1.
Tab. 12-17: Device Level Ring Object Class Attribute
Instance Attribute
Attribute Access Name Data Type Description of Attribute
ID Rule
1 Get Network Topolo- USINT Current network topology mode.
gy
2 Get Network State USINT Current status of network.
10 Get Active Supervisor STRUCT of: IP and/or MAC address of the active ring
Address supervisor.
UDINT Supervisor IP Address
ARRAY of 6 Supervisor MAC Address
USINTs
12 Get Capability Flags USINT Describes the DLR capabilities of the de-
vice
Tab. 12-18: Device Level Ring Object Instance Attribute
Common Services
Service Code Implemented for Service Name Description of Service
Class Instance
0x01 No Yes Get_Attribute_All Returns a predefined listing of
this objects attributes.
0x0E Yes Yes Set_Attribute_Single Returns the contents of the
specified attribute.
Tab. 12-19: Common Services of Device Level Ring Object
Class Attribute
Attribute Access Name Data Type Description of Attribute Semantics of Values
ID Rule
1 Get Revision UINT Revision of this object The current value assigned to
this attribute is one (01). If up-
dates that require an increase
in this value are made, then
the value of this attribute in-
creases by 1.
2 Get Max In- UINT Maximum instance number of The largest instance number of
stance an object currently created in a created object at this class
this class level of the device. hierarchy level. This attribute
will show one (01).
Tab. 12-20: Quality of Service Object Class Attribute
Instance Attribute
Attribute Access Name Data Type Description of Attribute
ID Rule
1 Set, Get 802.1Q Tag Enable USINT Enables or disables sending 802.1Q
frames on CIP and IEEE 1588 messages.
4 Set, Get DSCP Urgent USINT DSCP value for CIP transport class 0/1 Ur-
gent priority messages.
5 Set, Get DSCP Scheduled USINT DSCP value for CIP transport class 0/1
Scheduled priority messages.
6 Set, Get DSCP High USINT DSCP value for CIP transport class 0/1
High priority messages.
7 Set, Get DSCP Low USINT DSCP value for CIP transport class 0/1 low
priority messages.
8 Set, Get DSCP Explicit USINT DSCP value for CIP explicit messages
(transport class 2/3 and UCMM) and all
other EtherNet/IP encapsulation messag-
es.
Tab. 12-21: Quality of Service Object Instance Attribute
Common Services
Service Code Implemented for Service Name Description of Service
Class Instance
0x0E Yes Yes Get_Attribute_Single Returns the contents of the
specified attribute.
0x10 No Yes Set_Attribute_Single Modifies the contents of the at-
tributes of the class or object.
Tab. 12-22: Common Services of Quality of Service
Class Attribute
Attribute Access Name Data Type Description of Attribute Semantics of Values
ID Rule
1 Get Revision UINT Revision of this object The current value assigned to
this attribute is four (04). If up-
dates that require an increase
in this value are made, then
the value of this attribute in-
creases by 1.
2 Get Max In- UINT Maximum instance number of The largest instance number of
stance an object currently created in a created object at this class
this class level of the device, hierarchy level. This attribute
will show one (01).
Tab. 12-23: TCP/IP Interface Object Class Attribute
Instance Attribute
Attribute Access Name Data Type Description of Attribute
ID Rule
1 Get Status USINT Interface status
2 Get Configuration USINT Interface capability flags.
Capability
3 Set, Get Configuration USINT Interface control flags.
Capability
4 Get Physical Link Object STRUCT of Path to physical link object.
Path size UINT Size of Path
Path Padded Logical segments identifying the physi-
EPATH cal link object.
5 Set, Get Interface STRUCT of TCP/IP network interface configuration.
Configuration
IP Address UDINT The device’s IP address.
Network Mask UDINT The device’s network mask.
Gateway UDINT Default gateway address.
Address
Name Server UDINT Primary name server
Name Server 2 UDINT Secondary name server.
Domain Name STRING Default domain name.
6 Set, Get Host Name STRING Host name
10 Set, Get SelectAcd BOOL Activates the use of ACD.
11 Set, Get LastConflictDetected STRUCT of Structure containing information related
to the last conflict detected.
AcdActivity USINT State of ACD activity when last conflict
detected.
RemoteMAC Array of 6 USINT MAC address of remote node from the
ARP PDU in which a conflict was detect-
ed.
ArpPdu ARRAY of 28 Copy of the raw ARP PDU in which a
USINT conflict was detected.
12 Set, Get EtherNet/IP Quick- BOOL Enable/Disable of QuickConnect fea-
Connect ture.
13 Get Encapsulation Inac- UINT Number of seconds of inactivity before
tivity Timeout TCP connection or DTLS session is
closed.
Tab. 12-24: TCP/IP Interface Object Instance Attribute
Common Services
Service Code Implemented for Service Name Description of Service
Class Instance
0x01 No Yes Get_Attribute_All Returns a predefined listing of
this objects attributes.
0x0E Yes Yes Get_Attribute_Single Returns the contents of the spec-
ified attribute.
0x10 NO Yes Set_Attribute_Single Modifies a single attribute.
Tab. 12-25: Common Services of TCP/IP Interface Object
Class Attribute
Attribute Access Name Data Type Description of Attribute Semantics of Values
ID Rule
1 Get Revision UINT Revision of this object. The current value assigned to
this attribute is four (04). If up-
dates that require an increase
in this value are made, then
the value of this attribute in-
creases by 1.
2 Get Max UINT Maximum instance number of The largest instance number of
Instance an object currently created in a created object at this class
this class level of the device. hierarchy level. This attribute
will show two (02).
3 Get Number of UINT Number of object instances The number of object instanc-
Instances currently created at this class es at this class hierarchy level.
level of the device. This attribute will show two
(02).
Tab. 12-26: Ethernet Link Object Class Attribute
Instance Attribute
Attribute Access Name Data Type Description of Attribute
ID Rule
1 Get Interface Speed USINT Interface speed currently in use.
2 Get Interface Flags USINT Interface status flags.
3 Get Physical Address USINT MAC layer address.
4 Get Interface Counters STRUCT of
In Octets UDINT Octets received on the interface.
In Ucast Packets UDINT Unicast packets received on the inter-
face.
In NUcast Packets UDINT Non-unicast packets received on the in-
terface.
In Discards UDINT Inbound packets received on the inter-
face but discarded.
In Errors UDINT Inbound packets that contain errors
(does not include In Discards).
In Unknown Protos UDINT Inbound packets with unknown proto-
col.
Out Octets UDINT Octets sent on the interface.
Out Ucast Packets UDINT Unicast packets sent on the interface.
Out NUcast Packets UDINT Non-unicast packets sent on the inter-
face.
Out Discards UDINT Outbound packets discarded.
Out Errors UDINT Outbound packets that contain errors.
5 Get Media Counters STRUCT of Media-specific counters
Alignment Errors UDINT Frames received that are not an inte-
gral number of octets in length.
FCS Errors UDINT Frames received that do not pass the
FCS check.
Single Collisions UDINT Successfully transmitted frames which
experienced exactly one collision.
Multiple Kollisionen UDINT Successfully transmitted frames which
experienced more than one collision.
SQE Test Errors UDINT Number of times SQE test error mes-
sage is generated.
Deferred Transmis- UDINT Frames for which first transmission at-
sions tempt is delayed because the medium
is busy.
Late Collisions UDINT Number of times a collision is detected
later than 512 bit-times into the trans-
mission of a packet.
Common Services
Service Code Implemented for Service Name Description of Service
Class Instance
0x01 No Yes Get_Attribute_All Returns a predefined listing of
this objects attributes.
0x0E Yes Yes Get_Attribute_Single Returns the contents of the spec-
ified attribute.
0x4C No Yes1 Set_Attribute_Single Gets then clears the specified at-
tribute.
1
The Get_and_Clear sevice is only implemented for the attributes 4 and 5.
Tab. 12-28: Common Services of Ethernet Link Object
This Object is only implemented in the devices with part number 55143
and 55144.
Class Attribute
Attribute Access Name Data Type Description of Attribute Semantics of Values
ID Rule
1 Get Revision UINT Revision of this object The current value assigned to
this attribute is one (01). If up-
dates that require an increase
in this value are made, then
the value of this attribute in-
creases by 1.
2 Get Max UINT Maximum instance number of The largest instance number of
Instance an object currently created in a created object at this class
this class level of the device. hierarchy level. This attribute
will show one (01).
6 Get Max ID UINT The attribute ID number of the The value of this attribute will
Class Attri- last class attribute of the class be seven (07).
bute definition implemented in the
device.
7 Get Max ID In- UINT The attribute ID number of the The value of this attribute will
stance Attri- last instance attribute of the differ by product variant. Part
butes class definition implemented in number 55143 will show 2 and
the device. 55144 will show 4.
Tab. 12-29: IO-Link Device Parameter Object Class Attribute
Instance Attribute
Attribute Access Name Data Type Description of Attribute
ID Rule
11 Get IO-Link Port 1 USINT State of IO-Link Port 1
21 Get IO-Link Port 2 USINT State of IO-Link Port 2
32 Get IO-Link Port 3 USINT State of IO-Link Port 3
42 Get IO-Link Port 4 USINT State of IO-Link Port 4
1 Only available in 55143 or 55144
2
Only available in 55144
Tab. 12-30: IO-Link Device Parameter Object Instance Attribute
Common Services The IO-Link Device Parameter Object provides the following common
services.
Service Code Implemented for Service Name Description of Service
Class Instance
0x01 No Yes Get_Attribute_All Returns a predefined listing of
this objects attributes.
0x0E Yes Yes Get_Attribute_Single Returns the contents of the spec-
ified attribute.
Tab. 12-32: Common Services of IO-Link Parameter Object
Object-Specific Ser- The following class-specific services are defined for the IO-Link Device
vices Parameter Object.
Service Code Implemented for Service Name Description of Service
Class Instance
0x4B No Yes Read_ISDU Read the parameter in the IO-
Link Device in raw format. i.e. Big
Endian
0x4C No Yes Write_ISDU Write the parameter in the IO-
Link Device in raw format i.e. Big
Endian
Tab. 12-33: Common services of Object-Specific Services
The order of the digital input data depends on the configuration parameter
"Pin_Port_based_IO_Layout". This is explained in the following tables:
Port Based
Byte 1 0
Bit 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0
Port X7 X7 X6 X6 X5 X5 X4 X4 X3 X3 X2 X2 X1 X1 X0 X0
Pin 2 4 2 4 2 4 2 4 2 4 2 4 2 4 2 4
Chan- 17 07 16 06 15 05 14 04 13 03 12 02 11 01 10 00
nel
Tab. 12-38: Port Based
Pin Based
Byte 1 0
Bit 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0
Port X7 X6 X5 X4 X3 X2 X1 X0 X7 X6 X5 X4 X3 X2 X1 X0
Pin 2 2 2 2 2 2 2 2 4 4 4 4 4 4 4 4
Chan- 17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00
nel
Tab. 12-39: Pin Based
NOTICE
The tables for Port and Pin Based are also applicable to Digital Input Qualifier,
Digital Output Qualifier and Digital Output.
12.4.2 DI Qualifier
The Digital Input Qualifiers inform you quickly about the integrity of the input
signal.
NOTICE
The bit order depends on the configuration parameter
“Pin_Port_based_IO_Layout”. See chap. 12.4.1 "Digital Input"
12.4.3 DO Qualifier
The Digital Output Qualifiers inform you quickly about the integrity of the out-
put signal.
NOTICE
The bit order depends on the configuration parameter
“Pin_Port_based_IO_Layout”. See chap. 12.4 "Explanation of the process da-
ta"
The system state bit string gives information about the entire device.
Byte Description
0 ... 3 Bit 0: Undervoltage bus/sensor supply
Bit 1: Undervoltage actuator supply
Bit 3: External error
Bit 4: At least one channel has a sensor short circuit
Bit 5: At least one channel has an actuator short circuit
Bit 6: At least one channel has an actuator warning
Bit 7: At least one analog channel has an error
Bit 8: Internal communication error
Bit 9: At least one IO-Link channel has an error (except wire-
break)
Bit 10: Overvoltage bus/sensor supply
Bit 11: Overvoltage actuator supply
Bit 12: At least one IO-Link channel has a wirebreak
Bit 13 ... 31: reserved, set to 0
Byte Description
0 ... 3 Reserved
NOTICE
For further information on a diagnostic structure, please refer to chap. 9.2.1
"Diagnostics structure in the control system"
NOTICE
The order of the digital output data depends on the configuration parameter
“Pin_Port_based_IO_Layout”. See chap. 12.4.1 "Digital Input"
12.5 Glossary
Term Meaning
Ethernet/IP Ethernet Industrial Protocol
Open standard for industrial networks that supports both cyclic and acyclic transfer of
messages and uses standard Ethernet communication chips and physical media.
10Base-T - Transfer rate: 10 Mbits/s
- Physical structure: star topology
- Maximum cable length: 100 m
- Network cable: twisted-pair cable of category 5
Address mapping Address mapping is mapping one address on another address system. Address map-
ping translates addresses of a protocol into addresses of another protocol. This al-
lows systems using two different protocols to work with each other.
BASP BASP (= Befehlsausgabesperre, i.e. command output block) enabled means that all
module outputs will be disabled and inputs will not be read.
Broadcast Broadcast in a computer network is a message by means of which data packages are
transferred from one point to all network devices.
CIP Common Industrial Protocol
The Common Industrial Protocol is an application protocol used in automation tech-
nology. It supports the transition between fieldbuses and industrial Ethernet and IP
networks. This industrial protocol uses Ethernet/IP in the application layer as inter-
face between fieldbus and control, I/O, etc.
Term Meaning
Ethernet frame In each Ethernet frame (data package), there are addresses of transmitter (source)
and receiver (target). When a frame is received, the receiving unit of a receiving sta-
tion compares the MAC target address with its own MAC address. When the address-
es match, the receiving unit forwards the contents of the frame to a superior layer. If
they do not match, the frame is discarded.
Ethernet scanner A scanner (master) exchanges realtime I/O data with expansion modules and scan-
ners. It can answer connection requests and initialize connections.
IP Internet Protocol
Protocol used for transferring data within a network, e.g. internet or intranet, from one
computer to another. Each computer in the network can be clearly identified by
means of its IP address. If data is sent from one computer to another, it is subdivided
into small information packages containing each transmitter and receiver addresses.
These packages can be sent over the network using different routes and arrive at
their destination in a different order than the sequence of sending. Another protocol,
the transmission control protocol [TCP], then restores the original order.
ODVA ODVA is an international association for open and compatible information and com-
munication technologies in automation systems.
e.g. EtherNet/IP, DeviceNet, CompoNet and ControlNet,....
Term Meaning
IO-Link Standardized communication system to connect
intelligent sensors and actuators to an automation system
13 Legal notes
Disclaimer
Murrelektronik GmbH has reviewed the contents of this technical documenta-
tion for conformity with the described hardware and software. It is possible that
certain details may not be correct. For this reason, we make no warranty re-
garding the accuracy of this technical documentation, and assume no liability
for any errors, in particular full conformity. This exclusion of liability shall not
apply if the damage was caused deliberately and/or due to gross negligence,
nor does it cover any claims based on the German Product Liability Act.
Should a major contractual obligation have been violated negligently, the lia-
bility of Murrelektronik GmbH shall be limited to typically occurring damage.
We reserve the right to make technical alterations and amend the content of
this documentation. We recommend to regularly check whether this documen-
tation has been updated because corrections that might be required due to
technical modifications will be included by Murrelektronik GmbH at regular in-
tervals. Please contact us if you would like to suggest any improvements.
Copyright
It is prohibited to transfer or photocopy the documentation either in paper or in
digital form, reuse or divulge its contents unless otherwise expressly permitted
by Murrelektronik GmbH or in conjunction with the production of documenta-
tion for third-party products that contain products made by Murrelektronik Gm-
bH. Compensation will be claimed if our copyright is violated. All rights
reserved, particularly in the event of a patent being granted or a utility model
being registered.
Usage rights
Murrelektronik GmbH grants its customers a non-exclusive right revocable at
any time and for an indefinite period of time to use this technical documenta-
tion to create their own technical documentation. For this purpose, the docu-
mentation produced by Murrelektronik GmbH may be changed in parts, or
amended, or copied, and transferred to the customer's users as part of the
customer's own technical documentation on paper or on electronic media. In
this case, the customers shall bear sole responsibility for the correctness of
the contents of the technical documentation produced by them.
If the technical documentation is integrated in part, or in full in the customer's
technical documentation, the customer shall refer to the copyright of Murrelek-
tronik GmbH. All safety instructions must be included.
Although the customer is obliged to make reference to the copyright of Mur-
relektronik GmbH, provided the technical documentation of Murrelektronik
GmbH is used, the customers shall market and/or use the technical documen-
tation on their sole responsibility. The reason is that we have no influence on
changes or applications of the technical documentation and even minor
changes to the initial product or deviations in the intended applications may
render incorrect the specifications contained in the technical documentation.
For this reason, the customer is obliged to label the technical documentation
provided by Murrelektronik GmbH if and the extent to which the documenta-
tion is amended by the customer. The customers shall undertake to exempt
Murrelektronik from claims for damages of third parties if the latter are attrib-
utable to any defects in the documentation. This shall not apply to damage to
the rights of third parties caused deliberately or by gross negligence.
The customers shall be entitled to use the company brands of Murrelektronik
GmbH exclusively for their product advertising, but only inasmuch as the prod-
ucts of Murrelektronik GmbH are integrated into the products marketed by the
customers. When using Murrelektronik GmbH brands, the customers shall so
state in an adequate manner.
The information in the manual has been compiled with utmost care. Liability for the correctness,
completeness and topicality of the information is restricted to gross negligence.