Alternator Data Sheet

The document provides technical parameters for a 6 MW 11 KV alternator. It lists 81 parameters including ratings, temperatures, voltages, currents, efficiencies and more. The alternator will be used indoors in a hot humid environment and meet relevant standards like IS-4722.
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
199 views

Alternator Data Sheet

The document provides technical parameters for a 6 MW 11 KV alternator. It lists 81 parameters including ratings, temperatures, voltages, currents, efficiencies and more. The alternator will be used indoors in a hot humid environment and meet relevant standards like IS-4722.
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 6

Project: MATRIX AGRO PVT LTD

Consultant: Synder Energo Pvt Ltd.


Rating: 6 MW-11 KV Alternator.
Doc No: TDC/ALTDATA/MAPL
Guranteed Technical Parameters Remarks
1 Temperature design reference 50 degC
2 Relative humidity 99% %
3 Atmosphere Hot & humid -
4 Location Indoor -
5 Generator terminal box Side of Alternator. -
6 Phase Side Side of Alternator. -
7 Neutral Side Side of Alternator. -
8 HT cable size 2R x 1C x 300 Sq.mm/Phase mm2
9 BBT location NA -
10 Alternator rotor type Cylindrical -
11 Mounting Horizontal -
12 Base plate NA -
13 Sole plates Required -
14 Foundation bolt and anchor bolts Required -
15 Alternator colour shade RAL-7032. -
16 Generator make TDPS -
17 Frame designation TC125 -
18 Applicable standard IS-4722, IEEE-519 -
19 Nominal output 7500 KVA
20 KW rating 6000 KW
21 Rated voltage 11000 V
22 Voltage variation +/- 10 %. %
23 Rated frequency 50 Hz.
24 Frequency variation +/- 5 %. %
25 Combined voltage and frequency variation +/- 10 %. %
26 Rated power factor 0.8 Lag
27 Full load current 394 Amps
28 Rated speed 1500 RPM
29 Number of poles Four -
30 Rotation of Alternator when viewed from DE Clockwise -
31 Number of phase terminals Three -
32 Number of neutral terminals Three -
33 Enclosure protection class, for Generator IP-54. -
34 Enclosure protection class, for Exciter IP-54. -
35 Short ckt ratio 0.50 -
36 Maximum permissible capacitive loading, kVAR 2959 kVAR
37 Maximum permissible inductive loading, kVAR 5699 kVAR
38 Steady state 3 ph, Peak SC current 0.30 kA
39 Symmetrical short duty and duration of short circuit - -
40 Sustained 2 ph SC current, kA (at NL excitation) 0.47 kA
41 Maximum initial SC current (peak at 110% Volts) 5.7 kA
42 3 ph SC withstand time 3.0 Sec
43 Ground fault withstand for lamination amp, time 100 Amps for 1.0 Secs. Sec
44 Saturation factor 0.88 -
45 Exciter field current at no load 2.6 Amps
46 Exciter field current at rated load 8.4 Amps
47 Exciter field current, maximum (50% OL @ 0.3PF) 16.9 Amps
48 Exciter field voltage at no load 31 Volts
49 Exciter field voltage at rated load 102 Volts
50 Exciter field voltage, maximum (50% OL @ 0.3PF) 199 Volts
51 Main field current at no load 100 Amps
Alternator Data Sheet page 1 of 6
Project: MATRIX AGRO PVT LTD
Consultant: Synder Energo Pvt Ltd.
Rating: 6 MW-11 KV Alternator.
Doc No: TDC/ALTDATA/MAPL
Guranteed Technical Parameters Remarks
52 Main field current at rated load 312 Amps
53 Main field current, maximum 526 Amps
54 Main field voltage at no load 75.6 Volts
55 Main field voltage at rated load 236 Volts
56 Main field voltage, maximum 399 Volts
57 Max continuous Neg. ph sequence current 15% of Rated Amps Amps
58 Neg seq withstand, I2 squre t 20 Sec
Refer Negative sequence
59 Max permissible short time unbalance load and time -
capability Curve
60 Max deviation from sine wave 5.0 (As per IS 4722) %
61 Effective winding capacitance to earth
62 a. per phase, micro farad. 0.0695 micro Farad
63 b. all phases connected, together, micro farad. 0.2086 micro Farad
64 Surge impedance, ohms. 302.0 Ohms
65 Synchronous impedance, ohms. 32.62 Ohms
66 Maximum noise level <=85 + 3dB(A) dB(A)
67 Stator winding test voltage, KV 23.0 kV
68 Field winding test voltage, KV 1.5 kV
69 Maximum permissible impact load 11.3 MVA for 30 Secs MVA
70 Insulation class
71 Stator Class F -
72 Rotor Class F -
73 Exciter armature F -
74 Exciter field F -
75 Max temp rise over specified ambient
76 Stator Class B -
77 Rotor Class B -
78 Type of winding treatment for Stator and rotor VPI for Stator and Rotor -
Ref rotor assembly clause for
79 Max permissible vibration limit
details, As per IS-12075.
80 Max harmonic content in output 1.50% %
Tooth < 1.7 T
81 Flux densities in various parts at no load and full load Tesla
Core < 1.5 T
82 Over load capability, 50%, minutes 150% for 30 Secs -
83 Over load capability, 10%, hours 110% for One Hr in every 12 Hrs -
84 Efficiency at 25% load, at rated PF. 94.00 %
85 At unitiy PF 94.10 %
86 Efficiency at 50% load, at rated PF. 96.20 %
87 At unitiy PF 96.70 %
88 Efficiency at 75% load, at rated PF. 96.60 %
89 At unitiy PF 97.50 %
90 Efficiency at 100% load, at rated PF. 96.70 %
91 At unitiy PF 97.60 %
92 Critical speed of Generator rotor > 2160RPM, Ref. Outline Drg RPM
93 Ratio of short circuit torque to full load torque 6.04 -
94 Range of adjustment of voltage +10 %
95 Earth fault current limited to 100 Amps for 1.0 Secs. -
With NGR Current limited to
96 Earthing mode -
100Amps.
97 Auxiliary AC supply 230 VAC, 50 Hz. -
Alternator Data Sheet page 2 of 6
Project: MATRIX AGRO PVT LTD
Consultant: Synder Energo Pvt Ltd.
Rating: 6 MW-11 KV Alternator.
Doc No: TDC/ALTDATA/MAPL
Guranteed Technical Parameters Remarks
Suitable for parallel operation with
98 Duty -
grid and other Generators
99 Conneciton Star. -
100 Alternator rotor break away torque 114 kg-m
101 Min barring speed 12.00 RPM
102 Stator shell
Whether designed for carrying its lifting tackle attached for
103 Yes -
transportation
104 Stator shell material of construction MS -
105 Overall dimensions diameter length Refer Outline Drawings -
106 Stator laminations
107 Materials Silicon Steel -
108 Thickness of laminations 0.5 mm
109 Inter laminaiton insulation type Varnish -
Tooth < 1.7 T
110 Flux density Tesla
Core < 1.5 T
111 Type of winding Lap Winding -
112 Armature conductors
113 Conductor material Copper -
114 Current density at max machine capability < 7.5 Amps/sq. mm
115 Insulaton, (Stator winding)
116 Type of insulaiton Mica based, suitable for VPI -
117 Class of insulation Class 'F' -
118 End coil insulation Class 'F' -
119 Min insulaiton resistance required before energize >12 Meg Ohms
Min polarisation index required before energising (considering
120 2.0 -
1min/10 min or 1 min/15 min values)
121 Is insulation as per IEC standard. Class F with Yes -
Temp rise (by resistance), considering 41deg C as cooling air
122 79 Deg C
inlet temperature
123 Temp rise by RTD 84 Deg C
124 Cooling media
125 Max outlet temperature of cooling medium (air) 67 Deg C
126 Insulation (Rotor winding)
127 Type of insulaiton Nomex based, suitable for VPI -
128 Class of insulation F -
129 Min insulaiton resistance required before energize >2.0 Meg Ohms
Min polarisation index required before energising (considering
130 NA -
1min/10 min or 1 min/15 min values)
Temp rise (by resistance), considering 41deg C as cooling air
131 89 Deg C
inlet temperature
132 Temp rise by RTD NA -
133 Cooling media
134 Max outlet temperature of cooling medium (air) 67 Deg C
135 Test voltages
136 Stator winding 50 Hz 1 min. test voltage 23KV kV
137 Generator field winding test voltage 1.5KV kV
Pull out power at rated voltage with infinite bus and field set for
138 9633 kW per Sec at 0.8 PF -
rated MVA for rated and unity pf
139 Reactances, ( ± 15% Tolerance on reactance as per IEC: 60034-3)
140 Base MVA 7.5 MVA
Alternator Data Sheet page 3 of 6
Project: MATRIX AGRO PVT LTD
Consultant: Synder Energo Pvt Ltd.
Rating: 6 MW-11 KV Alternator.
Doc No: TDC/ALTDATA/MAPL
Guranteed Technical Parameters Remarks
141 Xd (sat) 1.99 P.U.
142 Xd (unsat) 2.17 P.U.
143 Xq (sat) 1.92 P.U.
144 Xq (unsat) 2.18 P.U.
145 Xd' (sat) 0.27 P.U.
146 Xd' (unsat) 0.31 P.U.
147 Xq' (sat) 1.92 P.U.
148 Xq' (unsat) 2.18 P.U.
149 Xd'' (sat) 0.213 P.U.
150 Xd'' (unsat) 0.213 P.U.
151 Xq'' (sat) 0.36 P.U.
152 Xq'' (unsat) 0.36 P.U.
153 X2 (sat) 0.287 P.U.
154 X0 (sat) 0.167 P.U.
155 X2 (unsat) 0.287 P.U.
156 X0 (unsat) 0.190 P.U.
157 Armature leakage resistance (sat) 0.157 P.U.
158 Armature leakage resistance (unsat) 0.178 P.U.
159 Maximum fault contribution, MVA 38.74 MVA (rms)
160 Resistances and time constants
161 Armature resistances, 25 degC, ohm/phase 0.0969 Ohms
162 Armature resistances, 75 degC, ohm/phase 0.1156 Ohms
163 Armature resistances, 100 degC, ohm/phase 0.1249 Ohms
164 Field resistances, 25 degC, ohm 0.5930 Ohms
165 Field resistances, 75 degC, ohm 0.7071 Ohms
166 Field resistances, 100 degC, ohm 0.7641 Ohms
167 Effective negative seq resistance ohms 0.1203 Ohms
168 Td" secs 0.035 Secs
169 Tdo" secs 0.44 Secs
170 Td' secs 0.34 Secs
171 Tdo' secs 2.57 Secs
172 Ta secs 0.13 Secs
173 Intertia Constant:
174 Moment of intertia of Generator -- -
175 Inertia constant "H" at base MVA 0.42 -
176 Moment of intertia of rotor 1065 kg.Sq.M
177 Excitation System Details:
178 Excitation system type Brushless -
179 Exciter enclosure IP54 -
180 Field breaker / contactor rating Not in TDPS Scope -
181 Discharge resistor rating Not in TDPS Scope -
182 Redundant thyrister circuit, yes/no NO -
183 Exciter rating, KW 86 kW approx kW
184 Exciter nominal response <50 m Secs.
185 Exciter ceiling voltage at 150% rated load with 0.3 PF 199 Volts
186 Exciter air gap 2.5 mm
187 Exciter field resistance at 75'C temperature 12.1 Ohms
188 Cooling system:
189 Cooling method CACW -
190 Type of cooler Water to Air -
191 No. of coolers (or section) 2 x 60% -
Alternator Data Sheet page 4 of 6
Project: MATRIX AGRO PVT LTD
Consultant: Synder Energo Pvt Ltd.
Rating: 6 MW-11 KV Alternator.
Doc No: TDC/ALTDATA/MAPL
Guranteed Technical Parameters Remarks
192 Cooler location Top of Alternator. -
193 Loading of Generator with one cooler out 67% output with one section out -
194 Capacity of cooler / section, Kcals / Hr. 105286 kCals/Hr
195 Cooling water inlet temp 32 degC (Delta T: 5 Deg C) Deg C
196 Cooling water requirement 700 LPM
197 Cooling water required pressure approx 1 to 2 kg/Sq.Cm(g)
198 Cooling air inlet temp 41 approx Deg C
199 Cooling air outlet temp 67 approx Deg C
200 Cooler tube type and material Ad Brass -
201 Cooler tube design pressure approx 5 kg/cm2 kg/Sq.Cm(g)
202 Water pressure drop across coolers < 1kg / Sq. Cm kg/Sq.Cm(g)
Alternator cooler shall be designed with 10% tube plugging
203 OK -
margin
204 Bearings:
205 Bearing type Sleeve bearings, force lubricated
206 Make Dum Dum -
207 Size EF22 - 225 -
208 Mounting End Shield Mounted -
209 Type of lubrication Forced Oil Lubricated -
210 Oil flow rate, (liters / Hr / Bearing) 12 LPM
211 Oil pressure Approx 1 to 2 Kg/Sq.Cm(g)
Inlet = 45 degC, Outlet = 60 degC
212 Oil in and oil out temperature -
approx
213 Oil flow indicators Flow glasses provided -
Flow control is by orifice of
214 Oil flow regulator, with min flow control various sizes, usually 3.2, 4 and 5 -
mm dia orifice is supplied
215 Oil pressure indicator, pressure gauge Provided -
216 Bearing temp indicator, RTD Provided -
217 Bearing clearances 0.303-0.378 mm
218 Axial float +/-10 mm
219 Bearing oil type ISO-VG 46 -
220 Oil flow visible glass tubes and flow control valves shall be provided for both the bearings
221 Anti Condensation Heaters:
222 Type and numbers Flat / tubilar type -
223 Rating 500 W, 1 ph, 230V (2 nos.) -
Bottom foot of main AC
224 Location -
Generator
225 Embedded temp detector, (RTD type)
226 Type Duplex RTDs -
227 Winding 12 nos. -
228 Bearing One number per bearing. -
229 Hot air 2 nos. -
230 Cold air 2 nos. -
231 Dial type spot mounted temperature gauges
232 Coolers Two nos. -
233 Bearings: One number / bearing. -
234 Water Leakage Detector:
235 Quantity 2 nos -
Alternator Data Sheet page 5 of 6
Project: MATRIX AGRO PVT LTD
Consultant: Synder Energo Pvt Ltd.
Rating: 6 MW-11 KV Alternator.
Doc No: TDC/ALTDATA/MAPL
Guranteed Technical Parameters Remarks
236 Location Cooler tray -
237 Humidity sensors
238 Quantity Not Required -
239 Location NA -
240 Rotating Diodes:
241 Normal polarity 6 nos -
242 Reverse polarity 6 nos -
243 PIV 1600 Volts
244 Current rating 312 Amps
245 Range 240-500 Amps -
246 Miscellaneous data
247 Air gap, a. Main machine 11 approx mm
248 b. Exciter 2.5 approx mm
249 Stator lamination withstand for 100A, secs. 1 Sec -
250 Total weight of Generator, MT Refer Outline Drawings MT
251 Stator weight, MT Refer Outline Drawings MT
252 Rotor weight, MT Refer Outline Drawings MT
253 Exciter weight, MT Refer Outline Drawings MT
254 Overall length of stator, mm Refer Outline Drawings mm
255 Overall dia of stator, mm Refer Outline Drawings mm
256 Overall dia of rotor, mm Refer Outline Drawings mm
257 Heaviest lift, MT Refer Outline Drawings MT
258 Weight of cooler, MT Refer Outline Drawings MT
259 Stator shipping dimension mm Refer Outline Drawings mm
260 Rotor shipping dimension mm Refer Outline Drawings mm
261 Exciter shipping dimension mm Refer Outline Drawings mm
Clear space required for Alternaotr rotor removal, from ND end
262 Refer Outline Drawings meters
of Alternator, mm
263 Other accessories, (shall be included in scope of supply)
264 Dowel pins, cable gland plates OK, provided.
265 Mating flanges for all the water and oil inlet and outlet lines OK, provided.
Provision shall be made for measurement of shaft vibration on
the Generator DE and NDE end bearings. At least 15 mm of
Generator shaft shall be burnished (mirror like finish) at the
266 OK, provided.
target area of the vibration probe at both ends for measurement
of shaft vibration. Provision shall be made for mounting the
vibration probes inside the bearing housing
Brush gear arrangement, carbon brushes and 2 nos. sliprings
alongwith rotor Earthing brush (for rotor earth fault relays by
TEIL) shall be provided on the Alternator. Two nos slip-rings
267 OK, provided.
with carbon brushes shall be provided for +ve and –ve of
Alternator field and one carbon brush shall be provided for
earthing of Alternator rotor
268 PMG for AVR Excitation Input Not Required
269 Spare items, (to be supplied with Alternator)

Alternator Data Sheet page 6 of 6