This document provides notes and details for the structural design of a building, including specifications for reinforced concrete beams, columns, foundations, and cantilever beams. It notes reference codes, construction procedures, reinforcement requirements, cover dimensions, load assumptions, and conditions of use. The designer assumes no responsibility for safety during demolition or construction or for accidents due to improper workmanship or premature loading.

Uploaded by

ROHIT PANDEY
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (1 vote)
1K views1 page

Cantilever Beam Drawing

This document provides notes and details for the structural design of a building, including specifications for reinforced concrete beams, columns, foundations, and cantilever beams. It notes reference codes, construction procedures, reinforcement requirements, cover dimensions, load assumptions, and conditions of use. The designer assumes no responsibility for safety during demolition or construction or for accidents due to improper workmanship or premature loading.

Uploaded by

ROHIT PANDEY
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

CivilConstruct - Civil Engineers & Construction Professionals Training Institute

"Civil Engineers &


Construction
Professionals
COLUMN Training Institute"
CANTILEVER BEAM SIGNATURE OF ARCHITECT SIGNATURE & STAMP OF RCC
ON RECORD:- Consultant:-
TOP BAR
(WHICHEVER IS GREATER)

DRAWING IS VALID FOR DESIGN ADECUACY,


PROVIDED IT IS SIGNED & STAMPED BY OUR OFFICE
NOTES:
1.Basic reference code IS456: 2000, IS1893(Part1): 2016, IS13920: 2016.
2.Due care shall be taken to ascertain that requisite strength of concrete is
gainedbefore commencement of deshuttering. It shall comply with

(DEPTH)
provisions of Clause No. 11.3 of IS 456: 2000.
LD OR 1.2 X L1

Nominal covers

`D'
3.For main reinf. up to 12mm dia. bar for mild exposure the nominalmay be reduced by 5mm for slabs & beams
only.
Cantilever Span (L1) 4. Beams with depth more than 750mm, provide side-face reinforcement.
5. Substratum shall be approved from our office before laying P.C.C.
LD
6. Minimum clear spacing between any two longitudinal bars in beam= 50mm.
7. Not more than 50% steel should be lapped at any section of Column / Shear wall
7. All laps (Ld) shall be staggered & not more than 50% bars to be lapped at any given section
For bundled bars, Ld shall be increased by 10% for 2 bars in contact,
20% for 3 bars in contact and 33% for 4 bars in contact.
8. All buildings shall have tie beams/plinth beams at ground/plinth level.
1000 MM STIRRUPS 9. If footings overlap with each other, necessary revision shall be obtained from our office.
10. Design is valid for number of floors as indicated in the drawing.
11. At any level where column size gets reduced in either dimension
tie beams/plinth beams are essential
12. For cantilevers, top bars to be anchored behind from external face of support for - Ld or span of cantilever - whichever is greater
13. Fire rating considered:- 2 Hour.
Use of this drawing for construction shall explicitly confirm acceptance of following conditions by Owner / Builder / Contractor
1. Our responsibility shall remain limited to safe and sound structural design as transmitted by this drawing.
2. This drawing shall not be used for any construction unless necessary statutory approvals are obtained by the
Owner / Builder / Architect from the Regulating Authorities. CivilConstruct-Civil Engineers & Construction Professionals TrainingInstitute are indemnified of any
legal consequences in case of unauthorised construction.
3. We shall not remain responsible for -
a.Safety of old structure during demolition.
b. Safety of any adjoining building /persons staying in
adjoining building/persons and properties on adjoining
roads.
c. Safety of construction worker/any personnel at work site during construction
d. Correctness/safety of any temporary structure, scaffolding, shuttering,
centering erected at site and any Injury to any personnel arising out of
any accidents.
DETAIL OF CANTILEVER BEAM(B10X)
e. Accidents occurring due to premature deshuttering, faulty / substandard construction material or workmanship / faulty construction Procedure
Plan
f. Any accident occurring due to construction of elements of buildings not designed by us.
4.Supervision if specifically asked for will be provided to the extent of
verification of reinforcement on site but responsibility regarding correct &
sound construction shall solely rest with contractor/ builder / owner.
5. All structural concrete should be weigh batched, machine mixed and mechanically vibrated.
6. Any discrepancy between our drawing & Architects drawing shall be brought to our notice before construction.
7. This drawing is property of CivilConstruct and shall not be reproduced or used without explicit permission of this office
DRAWING TO BE VALIDATED BY ARCHITECT ON RECORD AFTER CHECKING COMPLIANCE
WITH APPROVED PLANS FROM THE REGULATING LOCAL GOVERNMENT AUTHORITY
N0. Rev. Date Description No. Rev. Date Description
R0 20.05.2021 .
R1 .
.
.
.
Environmental
Exposure Condition Moderate Grade Of Concrete:
Design Live Load:
- Grade of Steel Fe500 TMT
(Unless Specified)
Superimposed
- SBC of Soil:
Dead load
Checked By Dealt By Drawn By Drg. No. Bldg: Job No.
Developer: DND Construction
Design Architect: DND Construction
Architect on DND Construction
Record:
Project: CANTILEVER BEAM by DND Construction
(Mumbai)
Title: CANTILEVER BEAM Layout