Ref 601
Ref 601
Technical Reference
ABB REF 601 IEC
F2020
Contents
1 Model information 1
2 General description 1
3 Supported features 1
3.1.2 Functionality . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
3.2.2 Functionality . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
3.3.2 Functionality . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
5 References 5
1 Model information
Manufacturer ABB
Variants This model covers the features present in the ABB REF 601 IEC relay belonging to
the ABB Relion 605 series. To model the ABB REJ 603 please use the PowerFactory ABBREJ
603 relay model.
2 General description
The ABB REF 601 IEC relay has been modeled using two PowerFactory relay models:
The PowerFactory ABB REF 601 IEC relay models simulate most of the protective elements
available in the relay.
The model implementation has been based on the information available in the relay manual [1].
3 Supported features
It represents the interface between the power system and the relay protective elements. The
currents flowing in the power system are converted by a block simulating the 3 phase CT and by
a block simulating a single phase CT measuring the earth current; the secondary currents are
then measured by an element modeling the digital sampling of the relay.
3.1.2 Functionality
The ”Ct-3p” and the ”Ct-E/N” block represent ideal CTs. Using the CT default configuration the
current at the primary side are converted to the secondary side using the CT ratio. The CT
saturation and/or its magnetizing characteristic are not considered. Please set the ”Detailed
Model” check box in the ”Detailed Data” tab page of the CT dialog and insert the data regarding
the CT burden, the CT secondary resistance and the CT excitation parameter if more accurate
simulation results are required.
The ”Measure” block simulates a DFT (”Discrete Fourier Transform) using 20 samples per cycle.
The CT secondary rated current (1 or 5 A) value must be set in the ”Measure” block.
If no core CT is available please select the 3 phases CT also in the ”Ct-E/N” slot: the earth
current will be calculated assuming that an Holmgreen’s connection of the phases is used.
A set of inverse time and definite time overcurrent elements is modeling the relay protective
functions. All the inverse characteristics available in the relay are available in the inverse time
model blocks.
3.2.2 Functionality
The inverse time overcurrent elements support the following trip characteristics:
The relationship between current and time for normal inverse, very inverse, extremely inverse
and long time inverse complies with the BS 142.1966 and IEC 60255-3 standards. The RI-type
characteristic is a special characteristic used mainly in combination with existing mechanical
relays.
The relationships between the relay settings and the model parameters can be found in the
following table:
It represents the output stage of the relay; it’s the interface between the relay and the power
breaker.
3.3.2 Functionality
The ”Trip Logic” block is collecting the trip signals coming from the protective elements and
operating the relay output contacts. The output contact is ”yout”.
To disable the relay model ability to open the power circuit breaker simply disable the ”Trip Logic”
block.
5 References
[1] ABB Ltd. Distribution Automation, Maneja Works, Vadodara - 390 013, India. User’s manual
and Technical description Feeder Protection Relay REF601 IEC Document ID: 1MDU07204-
YN Issued: 30.09.2010 Revision: C Product version:1.0 SP1, 2009.