0% found this document useful (0 votes)
24 views65 pages

HGM8110V 8120V 8110LT 8120LT 8110CAN 8120CAN en

Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
24 views65 pages

HGM8110V 8120V 8110LT 8120LT 8110CAN 8120CAN en

Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 65

HGM8100N SERIES

(HGM8110V_ 8120V_8110LT_8120LT_8110CAN_8120CAN)

GENSET CONTROLLER

USER MANUAL
Chinese trademark

English trademark

SmartGen — make your generator smart

SmartGen Technology Co., Ltd.


No.28 Jinsuo Road
Zhengzhou
Henan Province
P. R. China
Tel: +86-371-67988888/67981888/67992951
+86-371-67981000(overseas)
Fax: +86-371-67992952
Web: http://www.smartgen.com.cn/
http://www.smartgen.cn/
Email: [email protected]

All rights reserved. No part of this publication may be reproduced in any material form (including
photocopying or storing in any medium by electronic means or other) without the written permission
of the copyright holder.
Applications for the copyright holder’s written permission to reproduce any part of this publication
should be addressed to Smartgen Technology at the address above.
Any reference to trademarked product names used within this publication is owned by their
respective companies.
SmartGen Technology reserves the right to change the contents of this document without prior notice.

Table 1 Software Version

Date Version Note


2016-07-24 1.0 Original release.
2021-04-07 1.1 Modify the error in key function and other translation problems.
Add output port function: preheat output and key output;
Add Input port function: speed raise/drop input and battle mode;
2021-06-20 1.2
Add speed regulation rate setting and charging voltage selection;
Add new model HGM8110LT and HGM8120LT.
Add AIN8 Expansion Module function;
2021-08-10 1.3
Add torque instructions for fixing clips.
2022-06-16 1.4 Update manual format and company logo.

HGM8100N Series Genset Controller User Manual Page 2 of 65


This manual is suitable for HGM8110V, HGM8120V, HGM8110LT, HGM8120LT, HGM8110CAN,
HGM8120CAN controllers only.

Table 2 Notation Clarification

Sign Instruction

Highlights an essential element of a procedure to ensure correctness.


NOTE
Indicates a procedure or practice, which, if not strictly observed, could result in
CAUTION! damage or destruction of equipment.

Indicates a procedure or practice, which could result in injury to personnel or loss


WARNING! of life if not followed correctly.

HGM8100N Series Genset Controller User Manual Page 3 of 65


CONTENTS

1 OVERVIEW....................................................................................................................................................6
2 MODELS COMPARISON ..............................................................................................................................7
3 PERFORMANCE AND CHARACTERISTICS ................................................................................................8
4 SPECIFICATION ........................................................................................................................................ 11
5 OPERATION .............................................................................................................................................. 12
5.1 INDICATORS .................................................................................................................................... 12
5.2 KEY FUNCTION DESCRIPTION ....................................................................................................... 12
5.3 LCD DISPLAY................................................................................................................................... 14
5.3.1 MAIN DISPLAY ...................................................................................................................... 14
5.3.2 PARARMETERS SETTING MANUAL ..................................................................................... 16
5.3.3 PARAMETER SETTINGS ....................................................................................................... 16
5.4 AUTO START/STOP OPERATION .................................................................................................. 17
5.5 MANUAL START/STOP OPERATION ............................................................................................. 18
5.6 GENSET CONTROLLER ATS CONTROL PROCEDURES ................................................................ 19
5.6.1 HGM8120N ATS CONTROL PROCEDURES ......................................................................... 19
5.6.1.1 MANUAL TRANSFER PROCEDURES ............................................................................ 19
5.6.1.2 AUTO TRANSFER PROCEDURES.................................................................................. 19
5.6.2 HGM8110N ATS CONTROL PROCEDURES ......................................................................... 20
5.6.2.1 MANUAL CONTROL PROCEDURES ............................................................................. 20
5.6.2.2 AUTO CONTROL PROCEDURES ................................................................................... 20
6 PROTECTION ............................................................................................................................................ 21
6.1 WARNINGS ...................................................................................................................................... 21
6.2 SHUTDOWN ALARM ....................................................................................................................... 23
6.3 TRIP AND STOP ALARM ................................................................................................................. 24
6.4 TRIP ALARM .................................................................................................................................... 25
7 WIRINGS CONNECTION ........................................................................................................................... 26
8 SCOPES AND DEFINITIONS OF PROGRAMMABLE PARAMETERS....................................................... 29
8.1 CONTENTS AND SCOPES OF PARAMETERS ............................................................................... 29
8.2 ENABLE DEFINITION OF DIGITAL OUTPUT PORTS ...................................................................... 36
8.2.1 DEFINED CONTENTS OF DIGITAL OUTPUT PORTS............................................................ 36
8.2.2 CUSTOM PERIOD OUTPUT ................................................................................................... 40
8.2.3 CUSTOM COMBINED OUTPUT ............................................................................................. 41
8.3 DEFINED CONTENTS OF DIGITAL INPUT PORTS (ALL GND(B-) CONNECTED ACTIVE) ........... 41
8.4 SELECTION OF SENSORS............................................................................................................... 44
8.5 CONDITIONS OF CRANK DISCONNECT SELECTION ................................................................... 45
9 PARAMETERS SETTING........................................................................................................................... 46
10 SENSORS SETTING ................................................................................................................................ 47
11 COMMISSIONING ................................................................................................................................... 48
12 TYPICAL APPLICATION ......................................................................................................................... 49
13 INSTALLATION ....................................................................................................................................... 51
13.1 OVERALL DIMENSION .................................................................................................................. 51

HGM8100N Series Genset Controller User Manual Page 4 of 65


13.2 BATTERY VOLTAGE INPUT .......................................................................................................... 51
13.3 SPEED SENSOR INPUT ................................................................................................................. 51
13.4 OUTPUT AND EXPAND RELAYS .................................................................................................. 51
13.5 AC INPUT....................................................................................................................................... 52
13.6 WITHSTAND VOLTAGE TEST ...................................................................................................... 52
14 GSM SHORT MESSAGE ALARM AND REMOTE CONTROL ................................................................. 53
14.1 GSM SHORT MESSAGE ALARM .................................................................................................. 53
14.2 GSM SHORT MESSAGE REMOTE CONTROL .............................................................................. 53
15 CONNECTIONS OF CONTROLLER WITH ENGINE J1939 .................................................................... 55
15.1 CUMMINS ISB/ISBE ...................................................................................................................... 55
15.2 CUMMINS QSL9 ............................................................................................................................ 55
15.3 CUMMINS QSM11 (IMPORT) ....................................................................................................... 56
15.4 CUMMINS QSX15-CM570 ............................................................................................................ 56
15.5 CUMMINS GCS-MODBUS ............................................................................................................. 57
15.6 CUMMINS QSM11 ........................................................................................................................ 57
15.7 CUMMINS QSZ13 ......................................................................................................................... 58
15.8 DETROIT DIESEL DDEC III/IV ....................................................................................................... 58
15.9 DEUTZ EMR2 ................................................................................................................................. 59
15.10 JOHN DEERE................................................................................................................................ 59
15.11 MTU MDEC................................................................................................................................... 59
15.12 MTU ADEC (SMART MODULE) ................................................................................................... 60
15.13 MTU ADEC (SAM MODULE) ........................................................................................................ 60
15.14 PERKINS....................................................................................................................................... 61
15.15 SCANIA......................................................................................................................................... 61
15.16 VOLVO EDC3................................................................................................................................ 61
15.17 VOLVO EDC4................................................................................................................................ 62
15.18 VOLVO-EMS2 ............................................................................................................................... 62
15.19 YUCHAI ........................................................................................................................................ 63
15.20 WEICHAI ....................................................................................................................................... 63
16 ETHERNET INTERFACE ......................................................................................................................... 64
16.1 ETHERNET INTERFACE INTRODUCTION .................................................................................... 64
16.2 NETWORK CLIENT CONNECTION MODE .................................................................................... 64
16.3 CONTROLLER AND NETWORK CABLE CONNECTION ............................................................... 64
17 FAULT FINDING ...................................................................................................................................... 65

HGM8100N Series Genset Controller User Manual Page 5 of 65


1 OVERVIEW

HGM8100N series genset controllers are especially designed for extremely high/low temperature
environment (-40~+70)°C. The controllers can operate reliably in extreme temperature conditions
with the help of VFD display or LCD and the components that resist extreme temperature. Controller
has strong ability of anti-electromagnetic interference, can be used under complex electromagnetic
interference environment. It is easy to maintain and upgrade due to the plug-in terminal. All display
information is Chinese (also can be set as English or other languages).
HGM8100N series genset controllers integrate digitization, intelligentization and network
technology which are used for genset automation and monitor control system of single unit to
achieve automatic start/stop, data measurement, alarm protection and “three remote” functions
(remote control, remote measuring and remote communication).
HGM8100N series genset controllers adopt 32-bit micro-processor technology with precision
parameters measuring, fixed value adjustment, time setting and threshold setting and etc. Major
parameters can be configured from front panel, and all parameters can be configured by PC via
RS485 interface or ETHERNET to adjust and monitor. It can be widely used in all types of automatic
genset control system with compact structure, advanced circuits, simple connections and high
reliability.

HGM8100N Series Genset Controller User Manual Page 6 of 65


2 MODELS COMPARISON

HGM8100N series controllers include HGM8110V, HGM8120V, HGM8110LT, HGM8120LT,


HGM8110CAN and HGM8120CAN.
HGM8110N been collectively named of HGM8110V, HGM8110LT and HGM8110CAN.
HGM8120N been collectively named of HGM8120V, HGM8120LT and HGM8120CAN.

Table 3 Models Comparison

Item HGM8110V HGM8120V HGM8110CAN HGM8120CAN HGM8110LT HGM8120LT

Display VFD LCD (heated)


Mains
● ● ●
Monitoring
Input Number 8 8 8 8 8 8
Output Number 8 8 8 8 8 8
Sensor
5 5 5 5 5 5
Number
Earth Current ● ● ● ● ● ●
Schedule
● ● ● ● ● ●
Function
RS485 ● ● ● ● ● ●
ETHERNET ● ●
GSM ● ● ● ● ● ●
J1939 ● ● ● ●
USB ● ● ● ● ● ●
Real-time
● ● ● ● ● ●
Clock
Event Log ● ● ● ● ● ●
Input/Output
Expansion ● ● ● ●
Module
AIN24 Analog
Expansion ● ● ● ●
Module
AIN8 Analog
Expansion ● ● ● ●
Module

NOTE:
1) Two fixed output ports: start output and fuel output.
2) Analog sensor consists of three fixed sensors (temperature sensor, pressure sensor and fuel level sensor) and two
flexible sensors.

HGM8100N Series Genset Controller User Manual Page 7 of 65


3 PERFORMANCE AND CHARACTERISTICS

HGM8110N: used for single automation systems, can control genset start/stop through remote start
signals.
HGM8120N: AMF (Auto Mains Failure), updates based on HGM8110N, moreover, has mains
electricity monitoring and mains/generator automatic transfer function, especially for automatic
system composed by generator and mains.
Main characteristics are as below:
1) With ARM-based 32-bit SCM, highly integrated hardware, high reliability;
2) Vacuum fluorescent display (VFD) or LCD display (able to control heating according to the
environment temperature), selectable Chinese/English interface which can be chosen at the site,
making commissioning convenience for factory personnel;
3) LCD adopts hard screen acrylic material with good wear-resisting and scratch-resisting;
4) Silicone panel and pushbuttons can be used in extreme temperature environment;
5) RS485 communication interface enables “three remote” (remote control, remote measuring and
remote communication) according to MODBUS protocol;
6) Ethernet monitoring can be realized via ETHERNET communication interface (need controller
with Ethernet interface);
7) Equipped with SMS (Short Message Service) function. When genset has alarm, controller can
send short messages via SMS automatically to max. 5 telephone numbers. Besides, generator
status can be controlled and checked using SMS;
8) Equipped with CANBUS port and can communicate with J1939 genset. Not only can monitor
frequently-used data (such as water temperature, oil pressure, speed, fuel consumption and so
on) of ECU machine, but also control starting up, shutdown, raising speed and speed droop via
CANBUS port (need controller with CANBUS interface);
9) Suitable for 3-phase 4-wire, 3-phase 3-wire, single phase 2-wire, and 2-phase 3-wire systems
with voltage 120/240V and frequency 50/60Hz;
10) Collects and shows 3-phase voltage, current, power parameter and frequency of generator or
mains;
Mains Generator
Line voltage (Uab, Ubc, and Uca) Line voltage (Uab, Ubc, and Uca)
Phase voltage (Ua, Ub, and Uc) Phase voltage (Ua, Ub, and Uc)
Phase sequence Phase sequence
Frequency Hz Frequency Hz
Load
Current Ia, Ib, Ic A (unit)
Each phase and total active power P kW (unit)
Each phase and total reactive power Q Kvar (unit)
Each phase and total apparent power S kVA (unit)
Each phase and average power factor λ 1 (unit)

HGM8100N Series Genset Controller User Manual Page 8 of 65


Accumulate total generator power W kWh, kVarh, kVAh (unit)
Earth current I A (unit)
11) For Mains, controller has over and under voltage, over and under frequency, loss of phase and
reverse phase sequence detection functions; for generator, controller has over and under
voltage, over and under frequency, loss of phase, reverse phase sequence, over and reverse
power functions;
12) 3 fixed analog sensors (temperature, oil pressure and liquid level);
13) 2 configurable analog sensors can be set as sensor of temperature, oil pressure or fuel level;
14) Precisely measure and display parameters about Engine;
Temp. (WT) °C/°F both be displayed
Oil pressure (OP) kPa/Psi/Bar all be displayed
Fuel level (FL) % (unit)
Speed (SPD) r/min (unit)
Voltage of Battery (VB) V (unit)
Voltage of Charger (VD) V (unit)
Hour count (HC) can accumulate to max. 65535 hours.
Start times can accumulate to max. 65535 times.
15) Control and protection functions: automatic start/stop of the genset, ATS (Auto Transfer Switch)
control with perfect fault indication and protection function;
16) All output ports are relay-out;
17) Parameter setting: parameters can be modified and stored in internal FLASH memory and
cannot be lost even in case of power outage; most of them can be adjusted using front panel of
the controller and all of them can be modified using PC via USB, RS485 or ETHERNET ports;
18) More kinds of curves of temperature, oil pressure, fuel level can be used directly and users can
define the sensor curves by themselves;
19) Multiple crank disconnect conditions (speed sensor, oil pressure, generator frequency) are
optional;
20) Widely power supply range DC(8~35)V, suitable to different starting battery voltage
environment;
21) Event log, real-time clock, scheduled start & stop generator (can be set as start genset once a
day/week/month whether with load or not);
22) PLC (Programmable Logic Controller) function. Users can use graphical programming to
achieve specific functions;
23) Can be used on pumping units or as an indicating instrument (indicate and alarm are enabled
only, relay is inhibited);
24) With maintenance function. Actions (warning, shutdown or trip and stop) can be set when
maintenance time out;
25) All parameters used digital adjustment, instead of conventional analog modulation with normal
potentiometer, with high reliability and stability;
26) Waterproof security level IP55 due to rubber seal installed between the controller enclosure and

HGM8100N Series Genset Controller User Manual Page 9 of 65


panel fascia;
27) Metal fixing clips enable perfect performance in high temperature environment;
28) Modular design, anti-flaming ABS plastic enclosure, pluggable connection terminals and
embedded installation way; compact structure with easy mounting;
29) With accumulative running A, B and accumulative power A, B function, users can eliminate log
event and re-accumulating, thus provide convenient for users’ statistic.

HGM8100N Series Genset Controller User Manual Page 10 of 65


4 SPECIFICATION

Table 4 Technical Parameters

Item Contents
Operating Voltage DC8.0V to DC35.0V, Continuous Power Supply.
Power Consumption <4W (standby ≤2W)
Alternator Input Range
3Phase 4Wire AC15V ~ AC 360V (ph-N)
3Phase 3Wire AC30V ~ AC620V (ph-ph)
Single Phase 2Wire AC15V ~ AC360V (ph-N)
2Phase 3Wire AC15V ~ AC360V (ph-N)
Alternator Frequency 50Hz/60Hz
Speed Sensor Voltage 1.0V to 24.0V (RMS)
Speed Sensor Frequency 10,000 Hz (max.)
Start Relay Output 16A DC28V at supply output
Fuel Relay Output 16A DC28V at supply output
Programmable Relay Output (1) 7A DC28V at supply output
Programmable Relay Output (2) 7A DC28V at supply output
Programmable Relay Output (3) 7A DC28V at supply output
Programmable Relay Output (4) 7A AC250V voltage free output
Programmable Relay Output (5) 8A AC250V voltage free output
Programmable Relay Output (6) 8A AC250V voltage free output
Case Dimension 242mm x 186mm x 53mm
Panel Cutout 214mm x 160mm
CT Secondary Current 5A rated
Working Temperature (-40~+70)°C
Working Humidity (20~93)%RH
When the temperature is -40°C, the controller can normally display
LCD Display within 25 seconds after power-on, and dynamically display that the
response speed is normal after 2 minutes.
Storage Temperature (-40~+70)°C
Protection Level IP55 Gasket
Apply AC2.2kV voltage between high voltage terminal and low
Insulating Intensity voltage terminal;
The leakage current is not more than 3mA within 1min.
Weight 0.85kg

HGM8100N Series Genset Controller User Manual Page 11 of 65


5 OPERATION

5.1 INDICATORS

Table 5 Alarm Indicators

Alarm Type Alarm Indicator


No Alarm Indicator off
Warning Slow flashing (1 time/s)
Trip Alarm Slow flashing (1 time/s)
Shutdown Alarm Fast flashing (5 times/s)
Trip and Stop Alarm Fast flashing (5 times/s)
Status Indicator: illuminated from crank disconnect to ETS while off during other periods.
Gens Normal Indicator: It is light on when generator is normal; flashing when generator state is
abnormal; off when there is no generator power.
Mains Normal Indicator: It is light on when mains is normal; flashing when mains state is abnormal;
off when there is no mains power.

5.2 KEY FUNCTION DESCRIPTION

Table 6 Key Function Descriptions

Icon Key Description


Stop running generator in Auto/Manual mode; Lamp test
(press at least 3 seconds); Reset alarm in stop mode;
Stop
During stopping process, press this button again to stop
generator immediately.

Start Start genset in Manual mode.

Manual Mode Press this key and controller enters in Manual mode.

Auto Mode Press this key and controller enters in Auto mode.

Alarming sound off; If there is trip alarm, pressing the


Mute/Reset Alarm
button at least 3 seconds can reset this alarm.

Can control generator to switch on or off in manual mode.


Gen Close/Open
(HGM8110N without)

Can control mains to switch on or off in manual mode.


Mains Close/Open
(HGM8110N without)

Close Can close breaker in manual mode (HGM8120N without)

HGM8100N Series Genset Controller User Manual Page 12 of 65


Icon Key Description

Open Can open breaker in manual mode (HGM8120N without)

Set Enter setting interface

1) Screen scroll;
Up/Increase
2) Up cursor and increase value in setting menu.
1) Screen scroll;
Down/Decrease
2) Down cursor and decrease value in setting menu.

1) Page scroll;
Left
2) Left move cursor in setting menu.

1) Page scroll;
Right
2) Right move cursor in setting menu.

Confirm In settings menu confirms the set value.

1. Returns to the previous screen;


Exit
2. In settings menu returns to the upper level menu.

NOTE: In manual mode, pressing and simultaneously will force generator to crank. Successful

start will not be judged according to crank disconnect conditions, operator will have to crank the starter motor

manually; when operator decides that the engine has fired, he/she should release the button and start output will be

deactivated, safety on delay will start.

CAUTION: Default password is “00318”, user can change it in case of others change the advanced parameters setting.

Please clearly remember the password after changing. If you forget it, please contact SmartGen services and send PD

information in the controller page of “ABOUT” to us.

HGM8100N Series Genset Controller User Manual Page 13 of 65


5.3 LCD DISPLAY

5.3.1 MAIN DISPLAY

Main screen show pages; use to scroll the pages and to scroll the screen.
★Main Screen, including as below,
Partial status display;
Gen: voltage, frequency;
Load: current, active power, reactive power, power factor;
Mains: voltage, frequency;
Engine: speed, temperature, oil pressure.
NOTE: HGM8110N has no mains correlative values; it will circularly scroll pages if no action after enter the main

interface.

★Status, including as below,


Status of genset, mains, and ATS.
NOTE: HGM8110N has no mains status screen.

★Engine, including as below,


Speed, temperature of engine, engine oil pressure, fuel level, flexible sensor 1, flexible sensor 2, battery
voltage, charger voltage, accumulated run time, accumulated start times, user A and user B accumulated
start times.
NOTE: If connected with J1939 engine via CANBUS port, this page also includes: coolant pressure, coolant level,

fuel temperature, fuel pressure, inlet temperature, exhaust temperature, turbo pressure, total fuel consumption and so

on. (Different engine with different parameters)

★Gen, including as below,


Phase voltage, Line voltage, frequency, phase sequence.
★Load, including as below,
Each phase current, each phase and total active power (positive and negative), each phase and total
reactive power (positive and negative), each phase and total apparent power, each phase and average
power factor (positive and negative), accumulated energy, earth current and user A and user B
accumulated energy.
NOTE: Power factor shows as following,

Remark:
P stands for active power
Q stands for reactive power

HGM8100N Series Genset Controller User Manual Page 14 of 65


Table 7 Power Factor Descriptions

Power Factor Conditions Active Power Reactive Power Remark


COS>0L P>0,Q>0 Input Input Load is inductive resistance.
COS>0C P>0,Q<0 Input Output Load is capacitance resistance.
Load equal to one under excitation
COS<0L P<0,Q>0 Output Input
generator.
Load equal to one over excitation
COS<0C P<0,Q<0 Output Output
generator.
Remark:
1. Input active power, generator or mains supplies electricity to load.
2. Output active power, load supplies electricity to generator or mains.
3. Input reactive power, generator or mains sends reactive power to load.
4. Output reactive power, load sends reactive power to generator or mains.
★Mains, including as below,
Phase voltage, Line voltage, frequency, phase sequence.
NOTE: HGM8100N without mains page.

★Alarm:
Display all alarm information, including warning, alarm shutdown, trip shutdown and trip without
shutdown.
NOTE: For ECU alarms and shutdown alarms, if the alarm information is displayed, check engine according to it,

otherwise, please check the engine manual according to SPN alarm code.

★Event log
Records all start/stop events (shutdown alarm, trip and shutdown alarm, manual/auto start or stop) and
the real time when alarm occurs.
★Others, including,
Time and date, countdown time for maintenance, input/output ports status, NET status etc.
★About, including,
Software and hardware version and PD number of controller.

HGM8100N Series Genset Controller User Manual Page 15 of 65


5.3.2 PARARMETERS SETTING MANUAL

Press to enter user menu;


Parameter: After entering the correct password (factory default password is 00318) you can enter
parameter settings screen.
Language: Selectable Simplified Chinese, English and others (default: Espanol).
Commissioning: On load, off load and custom commissioning are optional. Custom commissioning
can configure on load or not during commissioning, when to commissioning and select the mode
after commissioning (manual mode, auto mode and stop mode).
Clear users’ accumulation: Can clear total run time A and B, total electric energy A and B.

5.3.3 PARAMETER SETTINGS

 Mains setting
 Timer setting
 Engine setting
 Generator setting
 Load setting
 Switch setting
 Temperature sensor setting
 Oil pressure sensor setting
 Level sensor setting
 Flexible sensor1
 Flexible sensor2
 Digital input setting
 Output port setting
 Module setting
 Scheduling and maintenance setting
 GSM setting
 Expansion module setting
NOTE: Pressing can exit setting directly during setting.

HGM8100N Series Genset Controller User Manual Page 16 of 65


5.4 AUTO START/STOP OPERATION

Press , its indicator lights, and controller enters Auto mode.


Starting Sequence,
1) HGM8120N: When mains is abnormal (over and under voltage, over and under frequency, loss of
phase, reverse phase sequence), it enters into mains “abnormal delay” and LCD display countdown
time. When mains abnormal delay is over, it enters into “start delay”; it also enters into this mode
when “remote start (on load)” is active.
2) HGM8110N: Generator enters into “start delay” as soon as “remote start (on load)” is active.
3) Start Delay timer is shown on LCD.
4) When start delay is over, preheat relay outputs (if configured), “preheat start
delay XX s” is shown on LCD.
5) When preheat delay is over, fuel relay outputs 1s and then start relay output; if engine crank fails
during “cranking time”, the fuel relay and start relay deactivated and enter into “crank rest time” to
wait for next crank.
6) If engine crank fails within setting times, the controller sends Fail to Start signals and Fail to Start
message appears on LCD alarm page.
7) In case of successful crank attempt, “safety on timer” starts. During this period, low oil pressure,
high water temperature, under speed, charge failure alarms are disabled. As soon as this delay is
over, “start idle delay” is initiated (if configured).
8) During “start idle delay”, under speed, under frequency, under voltage alarms are inhibited. When this
delay is over, “warming up delay” starts (if configured).
9) When “warming up delay” is over, if generator state is normal, its indicator will be illuminated. If
voltage and frequency has reached on-load requirements, the closing relay will be energized,
generator will accept load, generator power indicator will turn on, and generator will enter Normal
Running state; if voltage and frequency are abnormal, the controller will initiate alarm (alarm type will
be displayed on LCD alarm page).
NOTE: In case of “Remote Start (off Load)”, the procedure is the same, except for step NO. 9: the closing relay will NOT

be energized, generator will NOT accept load.

Stopping Sequence:
1) HGM8120N: When mains returns normal during genset running, it enters into mains voltage “normal
delay”. When mains normal delay is over, it enters into “stop delay”; it also can enter into this mode
when “remote start” is inactive.
2) HGM8110N: Generator enters into “stop delay” as soon as “remote start (on load)” is inactive.
3) When stop delay is over, close generator relay is un-energized; generator enters into “cooling down
time”. After “transfer rest time”, close mains relay is energized. Generator indicator extinguish while
mains indicator lights.
4) Idle relay is energized as soon as entering “stop idle delay”.
5) If enter “ETS hold delay”, ETS relay is energized. Fuel relay is deactivated and decides whether
generator is stopped or not automatically.
6) Then enter gen-set “fail to stop time”, auto decides whether generator is stopped or not

HGM8100N Series Genset Controller User Manual Page 17 of 65


automatically.
7) Enter “after stop time” (if configured) as soon as generator stops. Otherwise, controller will send “fail
to stop” alarm. (If gen-set stopped successfully after warning of “fail to stop”, it will enter “after stop
time” and remove alarm.)
8) Enter “generator at rest” as soon as “after stop time” is over.

5.5 MANUAL START/STOP OPERATION

1) MANUAL START: Press , controller enters into Manual mode and its indicator lights. Press
to start generator, it can automatically detect crank disconnect, and generator accelerates to
high-speed running automatically. With high temperature, low oil pressure and abnormal voltage
during generator running, controller can protect genset to stop quickly. Press (HGM8120N) or
press and (HGM8110N) to open or close the switch. (Please refer to No.4~9 of Auto start
operation for detail procedures, which the difference is only the way of switch open and close).
2) MANUAL STOP: Press can stop the running generators. (Please refer to No.3~8 of Auto
stop operation for detail procedures).

NOTE: In “manual mode”, the procedures of ATS please refer to ATS procedure of generator in this manual.

HGM8100N Series Genset Controller User Manual Page 18 of 65


5.6 GENSET CONTROLLER ATS CONTROL PROCEDURES

5.6.1 HGM8120N ATS CONTROL PROCEDURES

5.6.1.1 MANUAL TRANSFER PROCEDURES

When controller is in Manual mode, the switch control procedures will start through manual transfer.
Users can control the loading transfer of ATS via pressing button to switch on or off.
A. If “Open breaker detect” is selected “Disable”
Press generator close/open key , if generator has taken load, it will send open signals; if load
disconnects, it will send gen close signals; if mains has taken load, mains will open breaker, and then
generator will close after open delay over.
Press mains close/open key , if mains has taken load, it will send open signals; if load
disconnects, it will send mains close signals; if generator has taken load, generator will open breaker,
and then mains will close after open delay over.
B. If “Open breaker detect” is selected “Enable”
To transfer load from mains to generator need to press mains close/open key firstly. After
open delay, press generator close/open key , and generator will close breaker. (there is no action
when pressing generator close/open key directly.)
The way to transfer load from generator to mains is as same as above.

5.6.1.2 AUTO TRANSFER PROCEDURES

When controller is in AUTO mode, switch control procedures will start through automatic transfer.
1) If input port is configured as Close Mains Auxiliary
A. If “Open breaker detect” is selected “Enable”
When transferring load from mains to generator, controller begins detecting “fail to transfer”, then
the open delay and transfer rest delay will begin. When detecting time out, if switch open failed, the
generator will not switch on, otherwise, generator switch on. Detecting transfer failure while
generator switch on. When detecting time out, if switch on fail, it needs to wait for generator to
switch on. If transfer failure warning is selected “Enable”, there is warning signals whatever switch on
or off failure.
The way to transfer load from generator to mains is as same as above.
B. If “Open breaker detect” is selected “Disable”
Mains load is transferred into generator load, after the delay of switch off and transfer interval,
generator switch on. Detecting transfer failure while generator switches on. After detecting time out,
if switch on fail, then wait for generator switch on. If transfer failure warning is selected “Enable”,
there is warning signals.
2) If input port is not configured as Close Mains Auxiliary
Mains load is transferred into generator load, after switch off and transfer interval delay, generator
switch on.
The way to transfer generator load to mains load is as same as above.

HGM8100N Series Genset Controller User Manual Page 19 of 65


5.6.2 HGM8110N ATS CONTROL PROCEDURES

5.6.2.1 MANUAL CONTROL PROCEDURES

When controller is in Manual mode, manual control will be executed.


Users can control switch on or off by pressing and key.
Press generator switch on key , generator will output load signals. Press generator switch off key
, generator will output unload signals.

5.6.2.2 AUTO CONTROL PROCEDURES

When controller is in Auto mode, switch control procedures will start auto transfer.

1) If input port is configured as Close Mains Auxiliary

A. If “Open breaker detect” is selected “Enable”


Generator load is transferred into generator un-load, after the delay of switch off, detecting transfer
failure while switch off output. When detecting time out, if switch off failed, it will wait for switch off.
Otherwise, switch off is completed.
Generator unload is transferred into generator load, after the delay of switch on, detecting transfer
failure while switch on outputting. When detecting time out, if switch on failed, it will wait for switch
on. Otherwise, switch on is completed.
If transfer failure warning is selected “Enable”, there is warning signals whatever switch on or off
failure.

B. If “Open breaker detect” is selected “Disable”


Generator load is transferred into generator unload, after the delay of switch off, switch off is
completed.
Generator unload is transferred into generator load, after the delay of switch on, detecting transfer
failure while switch on outputting. When detecting time out, if switch on failed, to wait for switch on.
Otherwise, switch on is completed.
If transfer failure warning is selected “Enable”, there is warning signal when “switch on fail”.

2) If input port is not configured as Close Mains Auxiliary


Generator un-load is transferred into generator load, close generator output.
Generator load is transferred into generator un-load, open generator output.
NOTE:

1) When using ATS of no interposition, switch off detecting should “Disable”;

2) When using ATS of having interposition, switch off “Disable” or “Enable” both are OK. If choose “Enable”, switch off

output should be configured;

3) When using AC contactor, switch off “Enable” is recommended.

HGM8100N Series Genset Controller User Manual Page 20 of 65


6 PROTECTION

6.1 WARNINGS

When controller detects the warning signals, alarm only and not stop the genset.

Table 8 Warning Alarms

No. Type Description


When controller detects the speed is higher than the set value, it will
1 Over Speed
send warn signals.
When controller detects the speed is lower than the set value, it will
2 Under Speed
send warn signals.
When controller detects the speed is 0 and the action selects “Warn”,
3 Loss of Speed Signal
it will send warn signals.
When controller detects the frequency is higher than the set value, it
4 Over Frequency
will send warn signals.
When controller detects the frequency is lower than the set value, it
5 Under Frequency
will send warn signals.
When controller detects the voltage is higher than the set value, it
6 Over Voltage
will send warn signals.
When controller detects the voltage is lower than the set value, it will
7 Under Voltage
send warn signals.
When controller detects the current is higher than the set value, it will
8 Over Current
send warn signals.
9 Fail to Stop When generator not stops after the “stop delay” is over.
When controller detects the charger voltage is lower than the set
10 Charging Failure
value, it will send warn signals.
When controller detects the battery voltage is higher than the set
11 Battery Over Voltage
value, it will send warn signals.
When controller detects the battery voltage is lower than the set
12 Battery Under Voltage
value, it will send warn signals.
When count down time is 0 and the action selects “Warn”, it will send
13 Maintenance Due
warn signals.
When controller detects the reverse power value (power is negative)
14 Reverse Power
is higher than the set value, it will send warn signals.
When controller detects the power value (power is positive) is higher
15 Over Power
than the set value, it will send warn signals.
When controller gets the alarm signals from engine via J1939, it will
16 ECU Warn
send warn signals.
When controller detects the generator loss phase, it will send warn
17 Gen Loss of Phase
signals.
Gen Reverse Phase When controller detects the reverse phase sequence, it will send
18
Sequence warn signals.
When controller detects the switch on and off fail, and the action
19 Switch Failure
selects enable, it will send warn signals.
20 Temp. Sensor Open When controller detects the sensor is open circuit, and the action

HGM8100N Series Genset Controller User Manual Page 21 of 65


No. Type Description
selects “warn”, it will send warn signals.
When controller detects the temperature is higher than the set value,
21 High Temp.
it will send warn signals.
When controller detects the temperature is lower than the set value,
22 Low Temp.
it will send warn signals.
Oil Pressure Sensor When controller detects the sensor is open circuit, and the action
23
Open selects “warn”, it will send warn signals.
When controller detects the oil pressure is lower than the set value, it
24 Low Oil Pressure
will send warn signals.
When controller detects the sensor is open circuit, and the action
25 Level Sensor Open
selects “warn”, it will send warn signals.
When controller detects the lever is lower than the set value, it will
26 Low Level
send warn signals.
When controller detects the sensor is open circuit, and the action
27 Flexible Sensor 1 Open
selects “warn”, it will send warn signals.
When controller detects the sensor value is higher than the max. set
28 Flexible Sensor 1 High
value, it will send warn signals.
When controller detects the sensor value is lower than the min. set
29 Flexible Sensor 1 Low
value, it will send warn signals.
When controller detects the sensor is open circuit, and the action
30 Flexible Sensor 2 Open
selects “warn”, it will send warn signals.
When controller detects the sensor value is higher than the max. set
31 Flexible Sensor 2 High
value, it will send warn signals.
When controller detects the sensor value is lower than the min. set
32 Flexible Sensor 2 Low
value, it will send warn signals.
When digital input port is set as warning and active, controller sends
33 Digital Input
corresponding warning signals.
When GSM is enabled but the controller couldn’t detect GSM module,
34 GSM Comm. Failure
controller sends corresponding warning signals.
When controller detects earth current is greater than value of setting,
35 Earth Fault
and the action selects “warn”, it will send warn signals.

HGM8100N Series Genset Controller User Manual Page 22 of 65


6.2 SHUTDOWN ALARM

When controller detects shutdown alarm, it will send gen close signals and stop the generator.

Table 9 Shutdown Alarms

No. Type Description


When controller detects emergency stop signals, it will send stop
1 Emergency Stop
signals.
When controller detects the speed value is higher than the set value,
2 Over Speed
it will send stop signals.
When controller detects the speed value is lower than the set value,
3 Under Speed
it will send stop signals.
When controller detects speed value equals to 0, and the action
4 Loss of Speed Signal
selects “shutdown”, it will send stop signals
When controller detects the frequency value is higher than the set
5 Over Frequency
value, it will send stop signals.
When controller detects the frequency value is lower than the set
6 Under Frequency
value, it will send stop signals.
When controller detects the voltage value is higher than the set
7 Over Voltage
value, it will send stop signals.
When controller detects the voltage value is lower than the set value,
8 Under Voltage
it will send stop signals.
If genset start failure within setting of start times, controller will send
9 Fail to Start
stop signals.
When controller detects the current value is higher than the set
10 Over Current
value, it will send stop signals.
When count down time is 0 and the action selects “Shutdown”, it will
11 Maintenance Due
send stop signals.
When controller receives engine shutdown signals via J1939,
12 ECU Shutdown
controller send stop signals.
After engine start, controller does not receive data signals via J1939,
13 ECU Comm. Failure
controller sends stop signals.
When controller detects reverse power value (power is negative) is
14 Reverse Power higher than the set value, and the reverse power action selects
“shutdown”, it will send stop signals.
When controller detects power value (power is positive) is higher
15 Over Power than the set value, and the reverse power action selects “shutdown”,
it will send stop signals.
When controller detects sensor is open circuit, and the action selects
16 Temp. Sensor Open
“shutdown”, it will send stop signals.
When controller detects temperature is higher than the set value, it
17 High Temp.
will send stop signals.
When controller detects sensor is open circuit, and the action selects
18 Pressure Sensor Open
“shutdown”, it will send stop signals.
19 Low Oil Pressure When controller detects oil pressure is lower than the set value, it will

HGM8100N Series Genset Controller User Manual Page 23 of 65


No. Type Description
send stop signals.
When controller detects sensor is open circuit, and the action selects
20 Level Sensor Open
“shutdown”, it will send stop signals.
When controller detects sensor is open circuit, and the action selects
21 Flexible Sensor 1 Open
“shutdown”, it will send stop signals.
When controller detects the sensor value is higher than the max. set
22 Flexible Sensor 1 High
value, it will send stop signals.
When controller detects the sensor value is lower than the min. set
23 Flexible Sensor 1 Low
value, it will send stop signals.
When controller detects sensor is open circuit, and the action selects
24 Flexible Sensor 2 Open
“shutdown”, it will send stop signals.
When controller detects the sensor value is higher than the max. set
25 Flexible Sensor 2 High
value, it will send stop signals.
When controller detects the sensor value is lower than the min. set
26 Flexible Sensor 2 Low
value, it will send stop signals.
When digital input port is set as shutdown, and the action is active, it
27 Digital Input
will send stop signals.
When controller detects the earth current of genset exceeds preset
28 Earth Fault earth fault threshold and the earth fault action selects “shutdown” it
will send stop signals.

6.3 TRIP AND STOP ALARM

When controller detects trip and stop alarm signals, it will shut down generator quickly and stop after
high speed cooling.

Table 10 Trip and Stop Alarms

No. Type Description


When controller detects the value is higher than the set value, and
1 Over Current
the action selects “trip and stop”, it will send trip and stop signals.
When count down time is 0 and the action selects “trip and stop”, it
2 Maintenance Due
will send trip and stop signals.
When controller detects reverse power value (power is negative) is
3 Reverse Power higher than the set value, and the action selects “trip and stop”, it
will send trip and stop signals.
When controller detects the power value (power is positive) is
4 Over Power higher than the set value, and the action selects “trip and stop”, it
will send trip and stop signals.
When digital input port is set as “trip and stop”, and the action is
5 Digital Input
active, it will send trip and stop signals.
When controller detects the earth current of genset exceeds preset
6 Earth Fault earth fault threshold and the earth fault action selects “trip and
stop”, it will send trip and stop signals.

HGM8100N Series Genset Controller User Manual Page 24 of 65


6.4 TRIP ALARM

When controller detects trip alarm, it will break close generator signals quickly, but genset not stop.

Table 11 Trip Alarms

No. Type Description


When controller detects the value is higher than the set value, and
1 Over Current
the action selects “trip”, it will send trip signals.
When controller detects reverse power value (power is negative) is
2 Reverse Power higher than the set value, and the action selects “trip”, it will send
trip signals.
When controller detects the power value (power is positive) is
3 Over Power higher than the set value, and the action selects “trip”, it will send a
trip signals.
When digital input port is set as “trip”, and the action is active, it will
4 Digital Input
send trip signals.
When controller detects the earth current of genset exceeds preset
5 Earth Fault earth fault threshold and the earth fault action select “trip” it will
send trip signals.

HGM8100N Series Genset Controller User Manual Page 25 of 65


7 WIRINGS CONNECTION

HGM8100N series controller’s back panel as following:

Fig.1 HGM8100N Back Panel

HGM8100N Series Genset Controller User Manual Page 26 of 65


Table 12 Terminal Wiring Connection

No. Function Cable Size Remarks


2
1 B- 2.5mm Connected with negative of starter battery.
Connected with positive of starter battery. If wire
2
2 B+ 2.5mm length is over 30m, better to double wires in parallel.
Max. 20A fuse is recommended.
3 Emergency stop 2.5mm2 Connected with B+ via emergency stop button.
2
4 Fuel relay output 1.5mm B+ is supplied by 3 terminal, rated 16A.
B+ is supplied by 3 terminal, Connected to
5 Start relay output 1.5mm2
rated 16A. starter coil.
B+ is supplied by 2 terminal,
6 Aux. Output 1 1.5mm2
rated 7A.
B+ is supplied by 2 terminal, Details see Table
7 Aux. Output 2 1.5mm2
rated 7A. 14.
B+ is supplied by 2 terminal,
8 Aux. Output 3 1.5mm2
rated 7A.
Connected with charger starter’s D+ (WL) terminals.
9 Charger(D+) 1.0mm2
Being hang up If there is no this terminal.
Ground connected is active
10 Aux. Input 1 1.0mm2
(B-).
Ground connected is active
11 Aux. Input 2 1.0mm2
(B-).
Ground connected is active
12 Aux. Input 3 1.0mm2
(B-). Details see Table
Ground connected is active 15.
13 Aux. Input 4 1.0mm2
(B-).
Ground connected is active
14 Aux. Input 5 1.0mm2
(B-).
Ground connected is active
15 Aux. Input 6 1.0mm2
(B-).
16 Magnetic Pickup Connected with Speed sensor, shielding line is
17 MP 2 0.5mm2 recommended. (B-) has already inside connected
18 MP 1 with speed sensor 2.
Ground connected is active Details see Table
19 Aux. Input 7 1.0mm2
(B-). 15.
Normally close output, rated
20
7A.
Details see Table
21 Aux. Output 4 1.5mm2 Public points of relay.
14.
Normally close output, rated
22
7A.
23 ECU CAN / Impedance-120Ω shielding wire is recommended, its
24 ECU CAN H 0.5mm2 single-end earthed. (HGM8110V, HGM8120V,
25 ECU CAN L 0.5mm2 HGM8110LT and HGM8120LT without this terminal)
26-32 RESERVE / Empty terminal.
33 RS485 / Impedance-120Ω shielding wire is recommended, its

HGM8100N Series Genset Controller User Manual Page 27 of 65


No. Function Cable Size Remarks
2
34 RS485A(+) 0.5mm single-end earthed.
2
35 RS485B(-) 0.5mm
Normally close output, rated
36 2.5mm2
8A.
Aux. Output 5 Normally close output, rated
37 2.5mm2
8A. Details see Table
2
38 2.5mm Public points of relay. 14
Normally close output, rated
39 2.5mm2
Aux. Output 6 8A.
40 2.5mm2 Public points of relay.
Connected to A-phase of mains (2A fuse is
41 Mains Voltage L1 1.0mm2
recommended) (HGM8110N without).
Connected to B-phase of mains (2A fuse is
42 Mains Voltage L2 1.0mm2
recommended) (HGM8110N without).
Connected to C-phase of mains (2A fuse is
43 Mains Voltage L3 1.0mm2
recommended) (HGM8110N without).
44 Mains Voltage N 1.0mm2 Connected to N-wire of mains (HGM8110N without).
Connected to A-phase of genset (2A fuse is
45 Genset Voltage L1 1.0mm2
recommended).
Connected to B-phase of genset (2A fuse is
46 Genset Voltage L2 1.0mm2
recommended).
Connected to C-phase of genset (2A fuse is
47 Genset Voltage L3 1.0mm2
recommended).
48 Genset Voltage N 1.0mm2 Connected to N-wire of gen-set.
Outside connected to secondary coil of current
49 Genset CT1 1.5mm2
transformer (rated 5A).
Outside connected to secondary coil of current
50 Genset CT2 1.5mm2
transformer (rated 5A).
Outside connected to secondary coil of current
51 Genset CT3 1.5mm2
transformer (rated 5A).
52 Genset Current COM 1.5mm2 See following installation instruction.
53 1.5mm2 Outside connected to secondary coil of current
Earth Current
54 1.5mm2 transformer (rated 5A).
Ground connected is active Details see Table
55 Aux. Input 8 1.0mm2
(B-). 15.
56 Aux. Sensor 1 1.0mm2 Connected to temperature, oil
57 Aux. Sensor 2 1.0mm2 pressure or fuel level sensors.
Connected to oil pressure
58 Oil Pressure Sensor 1.0mm2 Details see Table
sensor.
16.
Connected to temperature
59 Temperature Sensor 1.0mm2
sensor.
60 Fuel Level Sensor 1.0mm2 Connected to fuel level sensor.
61 Sensor COM / Public terminal of sensor, (B-) has already connected.
62 RS232 0.5mm2 Connected to GSM module.

HGM8100N Series Genset Controller User Manual Page 28 of 65


No. Function Cable Size Remarks
2
63 RS232 RX 0.5mm
64 RS232 TX 0.5mm2

NOTE: USB ports in controller rear panel are programmable parameter ports, user can directly configure controller
via PC.
NOTE: Ethernet ports in controller rear panel are website port, user can directly configure and monitor controller via
PC.
NOTE: Please refer to the Module Comparison in this manual for more details.

8 SCOPES AND DEFINITIONS OF PROGRAMMABLE PARAMETERS

8.1 CONTENTS AND SCOPES OF PARAMETERS

Table 13 Parameters Contents and Scopes

No. Items Parameters Defaults Description


Mains Setting
0: 3P4W; 1: 3P3W;
1 AC System (0~3) 0
2: 2P3W; 3: 1P2W.
Standard for checking mains over/under
2 Rated Voltage (30~30000)V 230 voltage. It is primary voltage when using
voltage transformer.
Standard for checking mains over/under
3 Rated Frequency (10.0~75.0) Hz 50.0
frequency.
4 Normal Delay (0~3600)s 10 The delay from mains abnormal to normal.
5 Abnormal Delay (0~3600)s 5 The delay from mains normal to abnormal.
6 Volt. Trans. (PT) (0~1) 0 0: Disable ; 1: Enable
7 Over Voltage (0~200)% 120 Setting value is mains rated voltage’s
percentage, and return value (default: over
8 Under Voltage (0~200)% 80 voltage: 116; under voltage: 84) and delay
value (default: 5s) can be set.
9 Over Frequency (0~200)% 114 Setting value is mains rated voltage’s
percentage, and return value (default: over
10 Under Frequency (0~200)% 90 voltage: 110; under voltage: 94) and delay
value (default: 5s) can be set.
11 Loss of Phase (0~1) 1
Reverse Phase 0: Disable; 1: Enable
12 (0~1) 1
Seq.
13 Mains Option (0~1) 0 0: AMF; 1: Display only.
Timer Setting
Time from mains abnormal or remote start
1 Start Delay (0~3600)s 1
signal is active to start genset.
Time from mains normal or remote start
2 Stop Delay (0~3600)s 1
signal is deactivated to stop genset.
Time of pre-powering heat plug before
3 Pre-heat Delay (0~3600)s 0
starter is powered up.

HGM8100N Series Genset Controller User Manual Page 29 of 65


No. Items Parameters Defaults Description
4 Cranking Time (3~60)s 8 Time of starter power up.
The waiting time before second power up
5 Crank Rest Time (3~60)s 10
when engine start fail.
Alarms for low oil pressure, high
6 Safety On Delay (0~3600)s 10 temperature, under speed, under
frequency/voltage, charge fail are inactive.
7 Start Idle Time (0~3600)s 0 Idle running time of genset when starting.
Warming Up Warming time between genset switch on
8 (0~3600)s 10
Time and normal running.
Radiating time before genset stop, after it
9 Cooling Time (0~3600)s 10
unloads.
10 Stop Idle Time (0~3600)s 0 Idle running time when genset stop.
ETS Solenoid The time of powering up the
11 (0~3600)s 20
Hold electromagnet during stop procedure.
Time between ending of genset idle delay
and stopped when “ETS output time” is set
as 0;
12 Fail to Stop Delay (0~3600)s 0
Time between ending of ETS hold delay
and stopped when “ETS output time” is not
0.
Time between genset stopped and
13 After Stop Time (0~3600)s 0
standby.
Engine Setting
Default: Conventional engine.
1 Engine Type (0~39) 0 When connected to J1939 engine, choose
the corresponding type.
Tooth number of the engine, for judging of
crank disconnect conditions and
2 Flywheel Teeth (10~300) 118
inspecting of engine speed. See the
installation instructions.
Offer standard to judge
3 Rated Speed (0~6000)r/min 1500
over/under/loading speed.
Setting value is percentage of rated speed.
Controller detects when it is ready to load.
4 Loading Speed (0~100)% 90
It won’t switch on when speed is under
loading speed.
Loss of Speed Time from detecting speed is 0 to confirm
5 (0~3600)s 5
Signal the action.
Loss of Speed
6 (0~1) 0 0: Warn; 1: Shutdown
Action
Over Speed Setting value is percentage of rated speed
7 (0~200)% 114
Shutdown and delay value (over speed default as 2s,
Under Speed under speed default as 3s) also can be
8 (0~200)% 80
Shutdown set.

HGM8100N Series Genset Controller User Manual Page 30 of 65


No. Items Parameters Defaults Description
9 Over Speed Warn (0~200)% 110 Setting value is percentage of rated speed
and delay value (default: 5s) and return
Under Speed
10 (0~200)% 86 value (default: over speed: 108; under
Warn
speed: 90) also can be set.
Battery Rated Standard for detecting over/under voltage
11 (0~60.0)V 24.0
Voltage of battery.
Battery Over Setting value is percentage of rated
12 (0~200)% 120
Volts voltage of battery. Delay value (default:
Battery Under 60s) & return value (default: over voltage:
13 (0~200)% 85
Volts 115; under voltage: 90) also can be set.
In normal running, when charger D+(WL)
14 Charge Alt Fail (0~60.0)V 8.0 voltage under this value, charge failure
alarms.
Max. Crank times of crank attempts. When
15 Start Attempts (1~10) times 3 reach this number, controller will send
start failure signal.
See Table 17.
There are 3 conditions of disconnecting
starter with engine. Each condition can be
16 Crank Disconnect (0~6) 2
used alone and simultaneously to
separating the start motor and genset as
soon as possible.
When generator frequency higher than the
Disconnect
17 (0~200)% 24 set value, starter will be disconnected. See
Generator Freq
the installation instruction.
When generator speed higher than the set
Disconnect
18 (0~200)% 24 value, starter will be disconnected. See the
Engine Speed
installation instruction.
When generator oil pressure higher than
Disconnect Oil
19 (0~1000)kPa 200 the set value, starter will be disconnected.
Pressure
See the installation instruction.
This function works with input speed
regulation function. The speed is adjusted
Speed Regulation
20 (1~50)r/min 20 at this rate for each input port speed
Rate
raise/drop active. (Conventional unit has
no this function.)
Charging Voltage
21 (0~1) 0 0: Charger D+; 1: Engine ECU
Selection
Generator Setting
0: 3P4W; 1: 3P3W;
1 AC System (0~3) 0
2: 2P3W; 3: 1P2W.
Numbers of generator pole, used for
2 Poles (2~64) 4 calculating starter rotate speed when
without speed sensor.

HGM8100N Series Genset Controller User Manual Page 31 of 65


No. Items Parameters Defaults Description
To offer standards for detecting of
generator’ over/under voltage and loading
3 Rated Voltage (30~30000)V 230
voltage. It is primary voltage when using
voltage transformer.
Setting value is percentage of generator
rated voltage. Detect when controller
4 Loading Voltage (0~200)% 85 ready to loading. If generator voltage
under load voltage, won’t enter into
normally running.
To offer standards for detecting of
5 Rated Frequency (10.0~75.0) Hz 50.0
over/under/load frequency.
Setting value is percentage of generator
Loading rated frequency. When generator
6 (0~200)% 85
Frequency frequency under load frequency, it won’t
enter into normal running.
7 Volt. Trans. (PT) (0~1) 0 0: Disable; 1: Enable
Over Volt.
8 (0~200)% 120 Setting value is percentage of generator
Shutdown
rated volt. Delay value (default: 3s) also
Under Volt.
9 (0~200)% 80 can be set.
Shutdown
Over Freq. Setting value is percentage of generator
10 (0~200)% 114
Shutdown rated freq. Delay value (default: over
Under Freq. frequency: 2s; under frequency: 3s) also
11 (0~200)% 80
Shutdown can be set
12 Over Volt. Warn (0~200)% 110 Setting value is percentage of generator
rated volt. Delay value (default: 5s) and
Under Volt.
13 (0~200)% 84 return value(default: over voltage: 108;
Warn
under voltage: 86) also can be set.
14 Over Freq. Warn (0~200)% 110 Setting value is percentage of generator
rated freq. Delay value (default: 5s) and
15 Under Freq. Warn (0~200)% 84 return value (default: over frequency: 108;
under frequency: 86) also can be set.
16 Loss of Phase (0~1) 1 0: Disable 1: Enable.
Reverse Phase When it is enabled, controller begins to
17 (0~1) 1
Sequence monitor alarms.
Load Setting
1 CT Ratio (5~6000)/5 500 The ratio of external current transformer.
Generator’s rated current, standard of load
2 Rated Current (5~6000)A 500
current.
Generator’s rated power, standard of load
3 Rated Power (0~6000)kW 276
power.
Setting value is percentage of generator
4 Over Current (0~200)% 120 rated volt. Delay value also can be set as
DMT or IDMT.

HGM8100N Series Genset Controller User Manual Page 32 of 65


No. Items Parameters Defaults Description
5 Over Power (0~1) 0 0: Disable 1: Enable
6 Reverse Power (0~1) 0 0: Disable 1: Enable
7 Earth Fault (0~1) 0 0: Disable 1: Enable
ATS Setting
Interval time from mains switch off to
1 Transfer Time (0~7200)s 5 generator switch on; or from generator
switch off to mains switch on.
Pulse width of mains/generator switch on.
2 Close Time (0~20.0)s 5.0
When it is 0, means output constantly.
3 Open Time (0~20.0)s 3.0 Pulse width of mains/generator switch off.
Time of detecting ATS auxiliary contacts
4 Check Time (0~20.0)s 5.0
after transferred.
5 Check Fail Warn (0~1) 0 0: Disable 1: Enable
6 Open Check (0~1) 0 0: Disable 1: Enable
Instant. Mains
7 (0~1) 1 0: Disable 1: Enable
Dropout
Module Setting
0: Stop mode 1: Manual mode
1 Power On Mode (0~2) 0
2: Auto mode
Controller’s address during remote
2 Module Address (1~254) 1
sensing.
3 Stop Bits (0~1) 0 0: 2 stop bits; 1: 1 stop bit
0: Simplified Chinese 1: English 2:
4 Language (0~2) 0
Others.
5 Password (0~65535) 00318 For entering advanced parameters setting.
6 Temperature Unit (0~1) 0 0: ºC 1: ºF
7 Press Unit (0~2) 0 0: kPa; 1: Psi; 2: Bar
8 Time and Date Current time and date can be set by users.
0: Disable 1: Enable
All the settings about Ethernet (IP address,
9 Ethernet (0~1) 1
subnet mask) will active after the next
time power on.
GSM Setting
1 GSM Enable (0~1) 0 0: Disable; 1: Enable
0: Disable; 1: Enable
2 Phone Number Max.20 digits Its national and area’s cods must be
added. e.g. China: 8613666666666.
Scheduling and Maintenance Setting
1 Scheduled Run (0~1) 0 0: Disable; 1: Enable
Scheduled Not
2 (0~1) 0 0: Disable; 1: Enable
Run
3 Maintenance (0~1) 0 0: Disable; 1: Enable
Analog Sensor Setting
Temperature Sensor

HGM8100N Series Genset Controller User Manual Page 33 of 65


No. Items Parameters Defaults Description
1 Curve Type (0~15) 7 SGX. See Table 16.
Open Circuit
2 (0~2) 0 0: Warn; 1: Shutdown; 2: No action
Action
Shutdown when sensor temperature
High Temp. higher than this value. Detecting only after
3 (0~300)ºC 98
Shutdown safety delay is over. The delay value
(default: 3s) also can be set.
Warn when sensor temperature higher
than this value. Detecting only after
4 High Temp. Warn (0~300)ºC 95 safety delay is over. The delay value
(default: 5s) and return value (default: 93)
also can be set.
Low Temp.
5 (0~1) 0 0: Disable; 1: Enable
Warn
Oil Pressure Sensor
1 Curve Type (0~15) 7 SGX. See Table 16.
Open Circuit
2 (0~2) 0 0: Warn; 1: Shutdown; 2: No action
Action
Shutdown when oil pressure lower than
Low Oil Pressure this value. Detecting only after safety delay
3 (0~1000)kPa 103
Shutdown is over. The delay value (default: 3s) also
can be set.
Warn when oil pressure higher than this
Low Oil Pressure value. Detecting only after safety delay is
4 (0~1000)kPa 124
Warn over. The delay value (default: 5s) and
return value (default: 138) also can be set.
Level Sensor
1 Curve Type (0~15) 4 SGH. See Table 16.
2 Open Circuit Action (0~2) 0 0: Warn; 1: Shutdown; 2: No action
Warn when level lower than this value. It is
detecting all the time. The delay value
3 Low Level Warn (0~300)% 10
(default: 5s) and return value (default: 15)
also can be set.
Flexible Sensor 1
Flexible Sensor 1 0: Disable 1: Enable; (can be set as
1 (0~1) 0
Setting temperature/pressure/level sensor).
Flexible Sensor 2
Flexible Sensor 2 0: Disable; 1: Enable; (can be set as
1 (0~1) 0
Setting temperature/pressure/level sensor).
Digital Inputs Setting
Digital Input Port 1
1 Contents Setting (0~55) 28 Remote start (on load). See Table 15.
2 Active Type (0~1) 0 0: Closed to active; 1: Open to active
Digital Input Port 2

HGM8100N Series Genset Controller User Manual Page 34 of 65


No. Items Parameters Defaults Description
1 Contents Setting (0~55) 26 High temperature shutdown. See Table 15.
2 Active Type (0~1) 0 0: Closed to active; 1: Open to active
Digital Input Port 3
1 Contents Setting (0~55) 27 Low oil pressure shutdown. See Table 15.
2 Active Type (0~1) 0 0: Closed to active; 1: Open to active
Digital Input Port 4
1 Contents Setting (0~55) 0 User defined. See Table 15.
2 Active Type (0~1) 0 0: Closed to active; 1: Open to active
0: From safety on 1: From starting
3 Arming (0~3) 2
2: Always 3: Never
0: Warn; 1: Shutdown; 2: Trip and stop;
4 Active Actions (0~4) 0
3: Trip; 4: Indication
5 Active Delay (0~20.0)s 2.0 Time from detecting active to confirm
LCD display detailed contents when the
6 Description
input is active.
Digital Input Port 5
1 Contents Setting (0~55) 0 User defined. See Table 15.
2 Active Type (0~1) 0 0: Closed to active; 1: Open to active
0: From safety on 1: From starting
3 Arming (0~3) 2
2: Always 3: Never
0: Warn; 1: Shutdown; 2: Trip and stop;
4 Active Actions (0~4) 1
3: Trip; 4: Indication
5 Active Delay (0~20.0)s 2.0 Time from detecting active to confirm
LCD display detailed contents when the
6 Description
input is active.
Digital Input Port 6
1 Contents Setting (0~55) 0 User defined .See Table 15.
2 Active Type (0~1) 0 0: Closed to active; 1: Open to active
0: From safety on 1: From starting
3 Arming (0~3) 2
2: Always 3: Never
0: Warn; 1: Shutdown; 2: Trip and stop;
4 Active Actions (0~4) 2
3: Trip; 4: Indication
5 Active Delay (0~20.0)s 2.0 Time from detecting active to confirm
LCD display detailed contents when the
6 Description
input is active.
Digital Input Port 7
1 Contents Setting (0~55) 5 Lamp test. See Table 15.
2 Active Type (0~1) 0 0: Closed to active; 1: Open to active
Digital Input Port 8
1 Contents Setting (0~55) 0 User defined. See Table 15.
2 Active Type (0~1) 0 0: Closed to active; 1: Open to active
0: From safety on 1: From starting
3 Arming (0~3) 2
2: Always 3: Never
4 Active Actions (0~4) 0 0: Warn; 1: Shutdown; 2: Trip and stop;

HGM8100N Series Genset Controller User Manual Page 35 of 65


No. Items Parameters Defaults Description
3: Trip; 4: Indication
5 Active Delay (0~20.0)s 2.0 Time from detecting active to confirm
LCD display detailed contents when the
6 Description
input is active.
Relay Outputs Setting
Relay Output Port 1
User defined period output 1 (default as in
1 Contents Setting (0~299) 1
preheat output). See Table 14.
2 Active Type (0~1) 0 0: Normally open; 1: Normally close.
Relay Output Port 2
1 Contents Setting (0~299) 35 Idle control. See Table 14.
2 Active Type (0~1) 0 0: Normally open; 1: Normally close.
Relay Output Port 3
1 Contents Setting (0~299) 29 Generator closed output. See Table 14.
2 Active Type (0~1) 0 0: Normally open; 1: Normally close.
Relay Output Port 4
1 Contents Setting (0~299) 31 Mains closed output. See Table 14.
2 Active Type (0~1) 0 0: Normally open; 1: Normally close.
Relay Output Port 5
1 Contents Setting (0~299) 38 ETS. See Table 14.
2 Active Type (0~1) 0 0: Normally open; 1: Normally close.
Relay Output Port 6
1 Contents Setting (0~299) 48 Common alarm. See Table 14.
2 Active Type (0~1) 0 0: Normally open; 1: Normally close.

8.2 ENABLE DEFINITION OF DIGITAL OUTPUT PORTS

8.2.1 DEFINED CONTENTS OF DIGITAL OUTPUT PORTS

Table 14 Defined Contents of Digital Output Ports

No. Type Description


0 Not Used
1 Custom Period 1
2 Custom Period 2
3 Custom Period 3
4 Custom Period 4
5 Custom Period 5
6 Custom Period 6
Details of function description please see the following.
7 Custom Combined 1
8 Custom Combined 2
9 Custom Combined 3
10 Custom Combined 4
11 Custom Combined 5
12 Custom Combined 6
13 Preheat Output When the controller starting engine is in preheating, and

HGM8100N Series Genset Controller User Manual Page 36 of 65


No. Type Description
preheat is enabled (PC sensor 4 configuration interface),
it outputs when lower the threshold, not output when
over the threshold.
14 Reserved
15 Reserved
16 Reserved
Action when over speed shutdown and emergency stop.
17 Air Flap Control
It also can close the air in flow.
Action when warning, shutdown, trips. Can be connected
18 Audible Alarm annunciator externally. When “Alarm Mute” configurable
input port is active, it can remove the alarm.
Action in genset starting and disconnect when genset
19 Louver Control
stopping completely.
It is controlled by fuel pump of level sensor’s limited
20 Fuel Pump Control
threshold.
It is controlled by heating of temperature sensor’s
21 Heater Control
setting bound.
It is controlled by cooler of temperature sensor’s setting
22 Cooler Control
bound.
23 Fuel Pre-Supply Output Action when start and running safety period.
Output in start period. If there is no generator frequency
24 Generator Excite
during high-speed running, output for 2 seconds again.
25 Pre-Lubricate Actions in period of pre-heating to safety run.
26 Remote Control Output This port is controlled by communication (PC).
Supply power for GSM module (GSM module is reset
27 GSM Power
when GSM communication failed).
When the unit type is SINOTRUK Or SINOTRUK3000, it
28 Key Output
constantly outputs after preheating.
29 Close Gen Output Control generator to take load.
30 Open Output Control generator to off load.
31 Close Mains Output Control mains to take load.
32 Reserved
33 Start Relay
Action when genset is cranking and disconnect when
34 Fuel Relay
stopped completely.
Used for engine which has idles. Close before starting
35 Idle Control and open in warming up delay; Close during stopping
idle mode and open when stop is completed.
36 Speed Raise Output Action in warming up delay.
Action between the period from “stop idle” to “wait for
37 Speed Drop Output
stop”.
Used for engines with ETS electromagnet. Close when
38 Energize to Stop
stop idle is over and open when pre-set “ETS delay” is over.
39 Speed Drop Pulse Active 0.1s when controller enters into stop idle, used

HGM8100N Series Genset Controller User Manual Page 37 of 65


No. Type Description
for control part of ECU dropping to idle speed.
40 ECU Stop Used for ECU engine and control its stop.
41 ECU Power Used for ECU engine and control its power.
Active 0.1s when controller enters into warming up
42 Speed Raise Pulse delay; used for control part of ECU raising to normal
speed.
43 Crank Success Close when detects a successful start signal.
44 Generator OK Action when generator is normal.
45 Generator Available Action in period of generator ok to high-speed cooling.
46 Mains OK Action when mains normal.
47 Reserved
Action when genset common warning, common
48 Common Alarm
shutdown, common trips alarm.
49 Common Trip and Stop Action when common trip and stop alarm.
50 Common Shutdown Action when common shutdown alarm.
51 Common Trip Action when common trips alarm.
52 Common Warning Action when common warning alarm.
53 Reserved
54 Battery Over Voltage Action when battery’s over voltage warning alarm.
55 Battery Under Voltage Action when battery’s low voltage warning alarm.
56 Charging Failure Action when charge failure warning alarms.
57 Reserved
58 Reserved
59 Reserved
60 ECU Warning Indicate ECU sends a warning signal.
61 ECU Shutdown Indicate ECU sends a shutdown signal.
62 ECU Comm. Failure Indicate controller not communicate with ECU.
63 Reserved
64 Reserved
65 Reserved
66 Reserved
67 Reserved
68 Reserved
69 Digital Input 1 Active Action when input port 1 is active.
70 Digital Input 2 Active Action when input port 2 is active.
71 Digital Input 3 Active Action when input port 3 is active.
72 Digital Input 4 Active Action when input port 4 is active.
73 Digital Input 5 Active Action when input port 5 is active.
74 Digital Input 6 Active Action when input port 6 is active.
75 Digital Input 7 Active Action when input port 7 is active.
76 Digital Input 8 Active Action when input port 8 is active.
77~80 Reserved
81~96 Expand Digital Input 1~16 Active Action when expand digital input port is active.
97~98 Reserved

HGM8100N Series Genset Controller User Manual Page 38 of 65


No. Type Description
99 Emergency Stop Action when emergency stop alarm.
100 Fail to Start Action when failed start alarm.
101 Fail to Stop Action when failed stop alarm.
102 Under Speed Warning Action when under speed warning.
103 Under Speed Shutdown Action when under speed shuts down.
104 Over Speed Warning Action when over speed warn.
105 Over Speed Shutdown Action when over speed shutdown alarm.
106 Reserved
107 Reserved
108 Reserved
109 Gen Over Freq. Warning Action when generator over frequency warning.
110 Gen Over Freq. Shutdown Action when generator over frequency shutdown alarm.
111 Gen Over Volt. Warn Action when generator over voltage warning.
112 Gen Over Volt. Shut Action when generator over voltage shutdown.
113 Gen Under Freq. Warning Action when generator low frequency warning.
114 Gen Under Freq. Shut Action when generator low frequency shutdown.
115 Gen Under Volt. Warning Action when generator low voltage warning.
116 Gen Under Volt. Shut Action when generator low voltage shutdown.
117 Gen Loss of Phase Action when generator loss phase.
118 Gen Reverse Phase Seq. Action when generator reverse phase sequence.
119 Reserved
120 Over Power Alarm Action when controller detects generator has over power.
121 Reserved
Action when controller detects generator has reverse
122 Reverse Power Alarm
power.
123 Over Current Alarm Action when over current alarm.
124 Reserved
125 Mains Inactive
126 Mains Over Freq.
127 Mains Over Volt.
128 Mains Under Freq.
129 Mains Under Volt.
130 Mains Phase Seq. Wrong
131 Mains Loss of Phase
132~138 Reserved
139 High Temp Warning Action when high-temperature warning.
140 Low Temp Warning Action when low temperature warning.
141 High Temp Shutdown Action when high-temperature shutdown alarm.
142 Reserved
143 Low Oil Pressure Warning Action when low oil pressure warning.
144 Low Oil Pressure Shutdown Action when low oil pressure shutdown.
145 Oil Pressure Sensor Open Action when oil pressure sensor is open circuit.
146 Reserved
147 Low Fuel Level Action when controller has low fuel level alarm.

HGM8100N Series Genset Controller User Manual Page 39 of 65


No. Type Description
148 Reserved
149 Reserved
150 Flexible Sensor 1 High Warn
151 Flexible Sensor 1 Low Warn
152 Flexible Sensor 1 High Shut
153 Flexible Sensor 1 Low Shut
154 Flexible Sensor 2 High Warn
155 Flexible Sensor 2 Low Warn
156 Flexible Sensor 2 High Shut
157 Flexible Sensor 2 Low Shut
158~161 Reserved
162 Expand 1 Sensor 15 High Shut.
163 Expand 1 Sensor 15 High Alarm
164 Expand 1 Sensor 15 Low Shut.
165 Expand 1 Sensor 15 Low Alarm
166~201 Expand 1 Sensor 16~24
202~229 Reserved
230 Stop Mode Action in Stop mode.
231 Manual Mode Action in Manual mode.
232 Reserved
233 Auto Mode Action in Auto mode.
234 Generator On Load
235 Mains On Load
236~239 Reserved
240~279 PLC Flag 1~40 Action when PLC flag is 1.
280~299 Reserved

8.2.2 CUSTOM PERIOD OUTPUT

Defined period output is composed by 2 parts, period output S1 and condition output S2.

While S1 and S2 are TRUE synchronously, OUTPUT;


While S1 or S2 is FALSE, NOT OUTPUT.
Period output S1, can set generator’s one or more period output freely, can set the delay time and output
time after entering into period.
Condition output S2; can set as any conditions in output ports.
NOTE: When delay time and output time both are 0 in period output S1, it is TRUE in this period.
Example,
Output period: start
Delay output time: 2s
Output time: 3s
Condition output contents: input port 1 is active
Close when condition output active/inactive: close when active (disconnect when inactive);

HGM8100N Series Genset Controller User Manual Page 40 of 65


Input port 1 active, after enter “start time” and delay 2s, this defined period output is outputting, after 3s, stop outputting;
Input port 1 inactive, defined output period is not outputting.

8.2.3 CUSTOM COMBINED OUTPUT

Defined combination output is composed by 3 parts, or condition output S1, or condition output S2, and
condition output S3.

S1 or S2 is TRUE, and S3 is TRUE, defined combination output is outputting;


S1 and S2 are FALSE, or S3 is FALSE, defined combination output is not outputting.
NOTE: S1, S2, S3 can be set as any contents except for “defined combination output” in the output setting.
NOTE: 3 parts of defined combination output (S1, S2, S3) couldn’t include or recursively include themselves.
Example,
Contents of or condition output S1: input port 1 is active;
Close when or condition output S1 is active /inactive: close when active (disconnect when inactive);
Contents of or condition output S2, input port 2 is active;
Close when or condition output S2 is active /inactive: close when active (disconnect when inactive);
Contents of and condition output S3: input port 3 is active;
Close when and condition output S3 is active /inactive: close when active (disconnect when inactive);
When input port 1 active or input port 2 active, if input port 3 is active, defined combination output is outputting; If input port
3 inactive, defined combination output is not outputting;
When input port 1 inactive and input port 2 inactive, whatever input port 3 is active or not, defined combination output is not
outputting.

8.3 DEFINED CONTENTS OF DIGITAL INPUT PORTS (ALL GND(B-) CONNECTED ACTIVE)

Table 15 Defined Contents of Digital Input Ports

No. Type Description


Including following functions,
Indication: indicate only, not warning or shutdown.
Warning: warn only, not shutdown.
Shutdown: alarm and shutdown immediately
Trip and stop: alarm, generator unloads and shuts down
0 Users Defined after high-speed cooling
Trip: alarm, generator unloads but not shutdown.
Never: input inactive.
Always: input is active all the time.
From crank: detecting as soon as start.
From safety on: detecting after safety on run delay.
1 Reserved
2 Alarm Mute Can prohibit “Audible Alarm” output when input is active.

HGM8100N Series Genset Controller User Manual Page 41 of 65


No. Type Description
Can reset shutdown alarm and trip alarm when input is
3 Reset Alarm
active.
Use for CANBUS engine and it is 60Hz when input is
4 60Hz Active
active.
5 Lamp Test All LED indicators are illuminating when input is active.
All buttons in panel is inactive except direction buttons
6 Panel Lock and there is in the right of first row in LCD when input
is active.
7 Reserved
8 Idle Speed Active Under voltage/frequency/speed protection is inactive.
In Auto mode, during generator normal running, when
9 Auto Stop Inhibit
input is active, inhibit generator shutdown automatically.
In Auto mode, inhibit generator start automatically when
10 Auto Start Inhibit
input is active.
In Auto mode, inhibit scheduled run genset when input is
11 Scheduled Run Inhibit
active.
12 Reserved
13 Gen Closed Auxiliary Connect generator loading switch’s Aux. Point.
14 Gen Load Inhibit Prohibit genset switch on when input is active.
15 Mains Closed Auxiliary Connect mains loading switch’s Aux. Point.
16 Mains Load Inhibit Prohibit mains switch on when input is active.
When input is active, controller enters into Auto mode;
17 Auto Mode Lock
mode selection buttons are inactive.
When input is active, controller won’t work under Auto
18 Auto Mode Inhibit mode. Auto mode key and simulate auto key input does
not work.
19 Reserved
20 Reserved
All shutdown alarms are prohibited except emergency
21 Alarm Stop Inhibit
stop.
22 Instrument Mode All outputs are prohibited in this mode.
23 Reserved
Controller will set maintenance time and date as default
24 Reset Maintenance Time
when input is active.
25 Reserved
26 High Temperature Shutdown Connected sensor digital input.
27 Low Oil Pressure Shutdown Connected sensor digital input.
In Auto mode, when input is active, genset can start
28 Remote Start On Load automatically and take load after genset normal running;
when input is inactive, genset will stop automatically.
In Auto mode, when input is active, genset can start
automatically and NOT take load after genset normal
29 Remote Start Off Load
running; when input is inactive, genset will stop
automatically.

HGM8100N Series Genset Controller User Manual Page 42 of 65


No. Type Description
In Manual mode, when input is active, genset will start
30 Manual Start automatically; when input is inactive, genset will stop
automatically.
31 Reserved
32 Reserved
33 Simulate Stop Key An external button can be connected and pressed as
34 Simulate Manual Key simulate panel.
35 Reserved
36 Simulate Auto Key An external button can be connected and pressed as
37 Simulate Start Key simulate panel.
This is simulate G-close key when HGM8110N controller
38 Simulate Generator Load Key
is applied.
This is simulate G-open key when HGM8110N controller
39 Simulate Mains Load Key
is applied.
40 Reserved
41 Reserved
42 Reserved
43 Reserved
44 Reserved
45 Aux. Mains OK In Auto mode, mains normal when input is active.
46 Aux. Mains Failure In Auto mode, mains abnormal when input is active.
47 Alternative Config. 1 Alternative configuration is active when input is active.
48 Alternative Config. 2 Users can set different parameters to make it easy to
49 Alternative Config. 3 select current configuration via input port.
50 Reserved
When it is active, speed value of speed regulation rate is
51 Speed Raise Input increased. (Only active for 34 item GTSC1 of ECU unit
type.)
When it is active, speed value of speed regulation rate is
52 Speed Drop Input decreased. (Only active for 34 item GTSC1 of ECU unit
type.)
53~55 Reserved

HGM8100N Series Genset Controller User Manual Page 43 of 65


8.4 SELECTION OF SENSORS

Table 16 Sensors Selection

No. Description Remark


0 Not used
1 Custom Res Curve
2 Custom 4-20mA curve
3 VDO
4 CURTIS
5 VOLVO-EC
Defined resistance’s range is
6 DATCON
1 Temperature Sensor 0~6KΩ, default is SGX
7 SGX
sensor.
8 SGD
9 SGH
10 PT100
11 SUSUKI
12 PRO
13~15 Reserved
0 Not used
1 Custom Res Curve
2 Custom 4-20mA curve
3 VDO 10Bar
4 CURTIS
5 VOLVO-EC
6 DATCON 10Bar
Defined resistance’s range is
7 SGX
2 Pressure Sensor 0~6KΩ, default is SGX
8 SGD
sensor.
9 SGH
10 VDO 5Bar
11 DATCON 5Bar
12 DATCON 7Bar
13 SUSUKI
14 PRO
15 Reserved
0 Not used
1 Custom Res Curve
Defined resistance’s range is
2 Custom 4-20mA curve
3 Fuel Level Sensor 0~6KΩ, default is SGH
3 SGD
sensor.
4 SGH
5~15 Reserved

NOTE: User should make special declare when order controller if your genset is equipped with sensor of 4~20mA.

HGM8100N Series Genset Controller User Manual Page 44 of 65


8.5 CONDITIONS OF CRANK DISCONNECT SELECTION

Table 17 Crank Disconnect Conditions Selection

No. Setting Description


0 Gen frequency
1 Speed sensor
2 Speed sensor + Gen frequency
3 Oil pressure
4 Oil pressure + Gen frequency
5 Oil pressure + Speed sensor
6 Oil pressure + Speed sensor + Gen frequency

NOTE:

1. There are 3 conditions to make starter disconnected with engine, that is, speed sensor, generator frequency and

engine oil pressure. They all can be used separately. We recommend that engine oil pressure should be using with

speed sensor and generator frequency together, in order to make the starter motor is separated with engine

immediately and can check crank disconnect exactly.

2. Speed sensor is the magnetic equipment which be installed in starter for detecting flywheel teeth.

3. When set as speed sensor, must ensure that the number of flywheel teeth is as same as setting, otherwise, “over

speed shutdown” or “under speed shutdown” may be caused.

4. If genset without speed sensor, please don’t select corresponding items, otherwise, “start fail” or “loss speed signal”

maybe caused.

5. If genset without oil pressure sensor, please don’t select corresponding items.

6. If not select generator frequency in crank disconnect setting, controller will not collect and display the relative power

quantity (can be used in water pump set); if not select speed sensor in crank disconnect setting, the rotating speed

displayed in controller is calculated by generator frequency and number of poles.

HGM8100N Series Genset Controller User Manual Page 45 of 65


9 PARAMETERS SETTING

In HGM8110N controller, there are no items of mains in setting and also no mains items in configurable
ports of input/output.
CAUTION: Please change the controller parameters when generator is in standby mode only (e. g. Crank disconnect

conditions selection, configurable input, configurable output, various delay), otherwise, shutdown and other abnormal

conditions may happen.

NOTE: Maximum set value must over minimum set value in case that the condition of too high as well as too low will

happen.

NOTE: When setting the warning alarm, please set the correct return value; otherwise, maybe there is abnormal alarm.

When setting the maximum value, the return value must less than set value; when setting the minimum value, the return

value must over set value.

NOTE: Please set the generator frequency value as low as possible when cranking, in order to make the starter be

separated quickly as soon as crank disconnect.

NOTE: Configurable input could not be set as same items; otherwise, there are abnormal functions. However, the
configurable output can be set as same items.

HGM8100N Series Genset Controller User Manual Page 46 of 65


10 SENSORS SETTING

1. When reselect sensors, the sensor curve will be transferred into the standard value. For example, if
temperature sensor is SGX (120°C resistor type), its sensor curve is SGX (120°C resistor type); if
select the SGD (120°C resistor type), the temperature sensor curve is SGD curve.
2. When there is difference between standard sensor curves and using sensor, user can adjust it in
“curve type”.
3. When input the sensor curve, X value (resistor) must be input from small to large, otherwise, mistake
occurs.
4. If select sensor type as “None”, sensor curve is not working.
5. If corresponding sensor has alarm switch only, user must set this sensor as “None”, otherwise,
maybe there is shutdown or warning.
6. The headmost or backmost values in the vertical coordinates can be set as same as below,

Fig.2 Sensor Curve Setting

Table 18 Normal Pressure Unit Conversion Form

N/m2 (pa) kgf/cm2 bar psi


-5 -5 -4
1Pa 1 1.02x10 1x10 1.45x10
1kgf/cm2 9.8x104 1 0.98 14.2
1bar 1x105 1.02 1 14.5
-2 -2
1psi 6.89x103 7.03x10 6.89x10 1

HGM8100N Series Genset Controller User Manual Page 47 of 65


11 COMMISSIONING

Please make the under procedures checking before commissioning,


1) Ensure all the connections are correct and wires diameter is suitable.
2) Ensure that the controller DC power has fuse, controller’s positive and negative correctly connected
to starting battery.
3) Emergency stop must be connected with positive of starting battery via scram button’s normal close
point and fuse.
4) Take proper action to prevent engine to crank disconnect (e. g. Remove the connection wire of fuel
valve). If checking is OK, make the starting battery power on; choose manual mode and controller will
execute routine.
5) Set controller under manual mode, press “start” button, genset will start. After the setting times as
setting, controller will send signal of Start Fail; then press “stop” to reset controller.
6) Recover the action of stop engine start (e. g. Connect wire of fuel valve), press start button again,
genset will start. If everything goes well, genset will normal run after idle running (if idle run be set).
During this time, please watch for engine’s running situations and AC generator’s voltage and
frequency. If abnormal, stop genset running and check all wires connection according to this manual.
7) Select the AUTO mode from controller’s panel, connect mains signal. After the mains normal delay,
controller will transfer ATS (if fitted) into mains load. After cooling time, controller will stop genset
and make it into “at rest” mode until there is abnormal of mains.
8) When mains is abnormal again, genset will be started automatically and into normal running, then
controller send signal to making generator switch on, and control the ATS as generator load. If not
like this, please check ATS’ wires connection of control part according to this manual.
9) If there is any other question, please contact SmartGen’s service personnel.

HGM8100N Series Genset Controller User Manual Page 48 of 65


12 TYPICAL APPLICATION

Fig.3 HGM8110N Typical Application Diagram

Fig.4 HGM8120N typical application diagram

NOTE: Fuse F1: min. 2A; max. 20A. Fuse F2: max. 32A. Users should select suitable fuse depend on practical

application.

HGM8100N Series Genset Controller User Manual Page 49 of 65


Fig.5 HGM8100N Expansion Module Typical Application Diagram

HGM8100N Series Genset Controller User Manual Page 50 of 65


13 INSTALLATION

13.1 OVERALL DIMENSION

Controller is panel built-in design; it is fixed by clips when installed. The controller’s overall dimensions
and cutout dimensions for panel, please refers to as following,

Fig.6 Overall Dimensions and Panel Cutout

NOTE: The torque of 0.27N·m (2.75kgf·cm) is recommended.

13.2 BATTERY VOLTAGE INPUT

HGM8100N series controller can suit for widely range of battery voltage DC(8~35)V. Negative of battery
must be connected with the engine shell. Diameter of wire that connects from power supply to battery
must be over 2.5mm2. If floating charger configured, please firstly connect output wires of charger to
battery’s positive and negative directly, then, connect wires from battery’s positive and negative to
controller’s positive and negative input ports in order to prevent charger disturbing the controller’s normal
working.

13.3 SPEED SENSOR INPUT

Speed sensor is the magnetic equipment which be installed in starter and for detecting flywheel teeth. Its
connection wires to controller should apply for 2 cores shielding line. The shielding layer should connect
to No.16 terminal in controller while another side is hanging in air. The else two signal wires are
connected to No.17 and No.18 terminals in controller. The output voltage of speed sensor should be
within AC(1~24)V (effective value) during the full speed. AC12V is recommended (in rated speed). When
install the speed sensor, let the sensor is spun to contacting flywheel first, then, port out 1/3 lap, and lock
the nuts of sensor at last.

13.4 OUTPUT AND EXPAND RELAYS

CAUTION: All outputs of controller are relay contact output type. If need to expand the relays, please add freewheel
diode to both ends of expand relay’s coils (when coils of relay have DC current) or, increase resistance-capacitance return

circuit (when coils of relay have AC current), in order to prevent disturbance to controller or others equipment.

HGM8100N Series Genset Controller User Manual Page 51 of 65


13.5 AC INPUT

Current input of controller must be connected to outside current transformer. And the current
transformer’s secondary side current must be 5A. At the same time, the phases of current transformer
and input voltage must correct. Otherwise, the current of collecting and active power maybe not correct.
NOTE: ICOM port must be connected to negative pole of battery.

WARNING! When there is load current, transformer’s secondary side prohibits open circuit.

13.6 WITHSTAND VOLTAGE TEST

CAUTION: When controller has been installed in control panel, if need the high voltage test, please disconnect

controller’s all terminal connections, in order to prevent high voltage into controller and damage it.

HGM8100N Series Genset Controller User Manual Page 52 of 65


14 GSM SHORT MESSAGE ALARM AND REMOTE CONTROL

14.1 GSM SHORT MESSAGE ALARM

When controller detects alarm, it will send short message to phone automatically.
NOTE: All alarms about shutdown, trip and stop and trip will be sent to the pre-set phone. Warnings are sent to the

phone according to the pre-set.

14.2 GSM SHORT MESSAGE REMOTE CONTROL

Users send order message to GSM module, then controller will make actions according to this SMS order
and pass back corresponding operations information. Controllers only execute the orders by pre-set.

Table 19 SMS Orders List

No. SMS Orders Pass back Information Description


GENSET ALARM Genset stop alarm.
SYSTEM IN STOP MODE At rest status in stop
GENSET AT REST mode.
SYSTEM IN MANUAL MODE At rest status in manual
GENSET AT REST mode.
SYSTEM IN AUTO MODE At rest status in Auto
Get status of
1 SMS GENSET GENSET AT REST mode.
genset.
SYSTEM IN STOP MODE Running status in stop
GENSET IS RUNNING mode.
SYSTEM IN MANUAL MODE Running status in manual
GENSET IS RUNNING mode.
SYSTEM IN AUTO MODE Running status in stop
GENSET AT RUNNING mode.
Generator shutdown alarm
GENSET ALARM
or trip alarm.
Cannot start in stop
2 SMS START STOP MODE NOT START Start genset.
mode.
SMS START OK Start in manual mode.
AUTO MODE NOT START Cannot start in auto mode
3 SMS STOP MODE SMS STOP OK Set as stop mode.
SMS MANUAL
4 SMS MANUAL MODE OK Set as manual mode.
MODE
5 SMS AUTO MODE SMS AUTO MODE OK Set as auto mode.
Pass back information can
6 SMS DETAIL be set via controller Gets details information of genset.
software.
SMS INHIBIT
7 INHIBIT START OK Set as inhibit start.
START
SMS PERMIT
8 PERMIT START OK Remove inhibit boot.
START

NOTE: Its national and area’s codes must be added. e.g. China: 8613666666666.

HGM8100N Series Genset Controller User Manual Page 53 of 65


NOTE: When sending orders, users need to follow SMS orders in above form and all the letters must be capital.

NOTE: Pass back information from SMS DETAIL include: working mode, mains voltage, generator voltage, load current,

mains frequency, generator frequency, active power, apparent power, power factor, battery voltage, D+ voltage, water

temperature, oil pressure, oil level, engine speed, total running time, genset status, and alarm status.

HGM8100N Series Genset Controller User Manual Page 54 of 65


15 CONNECTIONS OF CONTROLLER WITH ENGINE J1939

15.1 CUMMINS ISB/ISBE

Table 20 Connector B

Terminals of controller Connector B Remark


Fuel relay output 39
Starting relay output - Connect with starter coil directly.
Expand 30A relay, battery
ECU power;
Auxiliary output 1 voltage of 01, 07, 12, 13 is
Set auxiliary output 1 as “ECU power”.
supplied by relay.

Table 21 9-Pin Connector

Terminals of controller 9 pins connector Remark


CAN communication shielding line
CAN GND SAE J1939 shield
(connect with ECU terminal only).
Impedance 120Ω connecting line is
CAN(H) SAE J1939 signal
recommended.
Impedance 120Ω connecting line is
CAN(L) SAE J1939 return
recommended.
Engine type: Cummins ISB.

15.2 CUMMINS QSL9

Suitable for CM850 engine control module.

Table 22 50-Pin Connector

Terminals of controller 50 pins connector Remark


Fuel relay output 39
Starting relay output - Connect to starter coil directly.

Table 23 9-Pin Connector

Terminals of controller 9 pins connector Remark


CAN communication shielding line
CAN GND SAE J1939 shield-E
(connect with ECU terminal only).
Using impedance 120Ω connecting
CAN(H) SAE J1939 signal-C
line.
Using impedance 120Ω connecting
CAN(L) SAE J1939 return-D
line.
Engine type: Cummins-CM850.

HGM8100N Series Genset Controller User Manual Page 55 of 65


15.3 CUMMINS QSM11 (IMPORT)

It is suitable for CM570 engine control module. Engine type is QSM11 G1, QSM11 G2.

Table 24 C1 Connector

Terminals of controller C1 connector Remark


Outside expand relay, when fuel output,
Fuel relay output 5&8 making port 5 and port 8 of C1 be
connected.
Starting relay output - Connect to starter coil directly.

Table 25 3-Pin Data Link Connector

Terminals of controller 3 pins data link connector Remark


CAN communication shielding line
CAN GND C
(connect with ECU terminal only).
CAN(H) A Using impedance 120Ω connecting line.
CAN(L) B Using impedance 120Ω connecting line.
Engine type: Cummins ISB.

15.4 CUMMINS QSX15-CM570

It is suitable for CM570 engine control module. Engine type is QSX15.

Table 26 50-Pin Connector

Terminals of controller 50 pins connector Remark


Fuel relay output 38 Oil spout switch.
Starting relay output - Connect to starter coil directly.

Table 27 9-Pin Connector

Terminals of controller 9 pins connector Remark


CAN communication shielding line
CAN GND SAE J1939 shield-E
(connect with ECU terminal only).
CAN(H) SAE J1939 signal-C Using impedance 120Ω connecting line.
CAN(L) SAE J1939 return-D Using impedance 120Ω connecting line.
Engine type: Cummins QSX15-CM570.

HGM8100N Series Genset Controller User Manual Page 56 of 65


15.5 CUMMINS GCS-MODBUS

It is suitable for GCS engine control module. RS485-MODBUS used to read information of engine. Engine
types are QSX15, QST30, SK23/45/60/78 and so on.

Table 28 D-SUB Connector 06

Terminals of controller D-SUB connector 06 Remark


Outside expand relay, when fuel output,
Fuel relay output 5&8 making port 05 and 08 of the connector 06
be connected.
Starting relay output - Connect to starter coil directly.

Table 29 D-SUB Connector 06

Terminals of controller D-SUB connector 06 Remark


CAN communication shielding line
RS485 GND 20
(connect with ECU terminal only).
RS485+ 21 Using impedance 120Ω connecting line.
RS485- 18 Using impedance 120Ω connecting line.
Engine type: Cummins QSK-MODBUS, Cummins QST-MODBUS, Cummins QSX-MODBUS.

15.6 CUMMINS QSM11

Table 30 Engine OEM Connector

Terminals of controller OEM connector of engine Remark


Fuel relay output 38
Starting relay output - Connect with starter coil directly.
CAN communication shielding line
CAN GND - (connect with controller’s this terminal
only).
CAN(H) 46 Using impedance 120Ω connecting line.
CAN(L) 37 Using impedance 120Ω connecting line.
Engine type: common J1939.

HGM8100N Series Genset Controller User Manual Page 57 of 65


15.7 CUMMINS QSZ13

Table 31 Engine OEM Connector

Terminals of controller OEM connector of engine Remark


Fuel relay output 45
Starting relay output - Connect to starter coil directly.
Setting to idle speed control, normally
close output. Making 16 connect to 41
Auxiliary output 1 16&41
during high-speed running of controller via
external expansion relay.
Setting to pulse raise speed control,
normally open output. Making 19 connect
Auxiliary output 2 19&41 with 41 for 0.1s during high-speed
warming of controller via external
expansion relay.
CAN communication shielding line
CAN GND - (connect with controller’s this terminal
only).
CAN(H) 1 Using impedance 120Ω connecting line.
CAN(L) 21 Using impedance 120Ω connecting line.
Engine type: Common J1939.

15.8 DETROIT DIESEL DDEC III/IV

Table 32 Engine CAN Port

Terminals of controller CAN port of engine Remark


Expand 30A relay, battery
Fuel relay output voltage of ECU is supplied
by relay.
Starting relay output - Connect to starter coil directly.
CAN communication shielding line
CAN GND -
(connect with controller’s terminal only).
CAN(H) CAN(H) Using impedance 120Ω connecting line.
CAN(L) CAN(L) Using impedance 120Ω connecting line.
Engine type: Common J1939.

HGM8100N Series Genset Controller User Manual Page 58 of 65


15.9 DEUTZ EMR2

Table 33 F Connector

Terminals of controller F connector Remark


Expand 30A relay, battery
Fuel relay output voltage of 14 is supplied
by relay. Fuse is 16A.
Starting relay output - Connect to starter coil directly.
- 1 Connect to battery negative pole.
CAN communication shielding line
CAN GND -
(connect with controller’s terminal only).
Impedance 120Ω connecting line is
CAN(H) 12
recommended.
Impedance 120Ω connecting line is
CAN(L) 13
recommended.
Engine type: VolvoEDC4.

15.10 JOHN DEERE

Table 34 21-Pin Connector

Terminals of controller 21 pins connector Remark


Fuel relay output G, J
Starting relay output D
CAN communication shielding line
CAN GND -
(connect with controller’s terminal only).
CAN(H) V Using impedance 120Ω connecting line.
CAN(L) U Using impedance 120Ω connecting line.
Engine type: John Deere.

15.11 MTU MDEC

Suitable for MTU engines, 2000 series, 4000 series.

Table 35 X1 Connector

Terminals of controller X1 connector Remark


Fuel relay output BE1
Starting relay output BE9
CAN communication shielding line
CAN GND E
(connect with one terminal only).
CAN(H) G Using impedance 120Ω connecting line.
CAN(L) F Using impedance 120Ω connecting line.
Engine type: MTU-MDEC-303.

HGM8100N Series Genset Controller User Manual Page 59 of 65


15.12 MTU ADEC (SMART MODULE)

It is suitable for MTU engine with ADEC (ECU8) and SMART module.

Table 36 ADEC (X1 Port)

Terminals of controller ADEC (X1 port) Remark


X1 Terminal 9 Connected to negative of
Fuel relay output X1 10
battery.
X1 Terminal 33 Connected to negative of
Starting relay output X1 34
battery.

Table 37 ADEC (X4 Port)

Terminals of controller SMART (X4 port) Remark


CAN communication shielding line
CAN GND X4 3 (connect to controller’s this terminal
only).
CAN(H) X4 1 Using impedance 120Ω connecting line.
CAN(L) X4 2 Using impedance 120Ω connecting line.
Engine type: MTU-ADEC.

15.13 MTU ADEC (SAM MODULE)

It is suitable for MTU engine with ADEC (ECU7) and SAM module.

Table 38 ADEC (X1 Port)

Terminals of controller ADEC (X1 port) Remark


X1 Terminal 28 Connected to negative of
Fuel relay output X1 43
battery.
X1 Terminal 22 Connected to negative of
Starting relay output X1 37
battery.

Table 39 SAM (X23 Port)

Terminals of controller SAM (X23 port) Remark


CAN communication shielding line
CAN GND X23 3 (connect with controller’s this terminal
only).
CAN(H) X23 2 Using impedance 120Ω connecting line.
CAN(L) X23 1 Using impedance 120Ω connecting line.
Engine type: Common J1939.

HGM8100N Series Genset Controller User Manual Page 60 of 65


15.14 PERKINS

It is suitable for ADEM3/ ADEM4 engine control module. Engine type is 2306, 2506, 1106, and 2806.

Table 40 Connector

Terminals of controller Connector Remark


Fuel relay output 1, 10, 15, 33, 34
Starting relay output - Connect to starter coil directly.
CAN communication shielding line
CAN GND -
(connect with controller’s terminal only).
CAN(H) 31 Using impedance 120Ω connecting line.
CAN(L) 32 Using impedance 120Ω connecting line.
Engine type: Perkins.

15.15 SCANIA

It is suitable for S6 engine control module. Engine model is DC9, DC12, and DC16.

Table 41 B1 Connector

Terminals of controller B1 connector Remark


Fuel relay output 3
Starting relay output - Connect to starter coil directly.
CAN communication shielding line
CAN GND -
(connect with controller’s terminal only).
CAN(H) 9 Using impedance 120Ω connecting line.
CAN(L) 10 Using impedance 120Ω connecting line.
Engine type: Scania.

15.16 VOLVO EDC3

Suitable engine control model is TAD1240, TAD1241, and TAD1242.

Table 42 “Stand alone” Connector

Terminals of controller “Stand alone” Connector Remark


Fuel relay output H
Starting relay output E
ECU power;
Auxiliary output 1 P
Set auxiliary output 1 as “ECU power”.

Table 43 “Data bus” Connector

Terminals of controller “Data bus” connector Remark


CAN communication shielding line
CAN GND -
(connect with controller’s terminal only).
CAN(H) 1 Using impedance 120Ω connecting line.
CAN(L) 2 Using impedance 120Ω connecting line.
Engine type: Volvo.
NOTE: When this engine type is selected, preheating time should be set to at least 3 seconds.

HGM8100N Series Genset Controller User Manual Page 61 of 65


15.17 VOLVO EDC4

Suitable engine types: TD520, TAD520 (optional), TD720, TAD720 (optional), TAD721, TAD722, and
TAD732.

Table 44 Connector

Terminals of controller Connector Remark


Expanded 30A relay, and
Fuel relay output relay offers battery voltage
for terminal14. Fuse is 16A.
Starting relay output - Connect to starter coil directly.
1 Connected to negative of battery.
CAN communication shielding line
CAN GND -
(connect with controller’s terminal only).
CAN(H) 12 Using impedance 120Ω connecting line.
CAN(L) 13 Using impedance 120Ω connecting line.
Engine type: VolvoEDC4.

15.18 VOLVO-EMS2

Volvo Engine types are TAD734, TAD940, TAD941, TAD1640, TAD1641, and TAD1642.

Table 45 Engine CAN Port

Terminals of controller Engine’s CAN port Remark


ECU stop;
Auxiliary output 1 6
Set auxiliary output 1 as “ECU stop”.
ECU power;
Auxiliary output 2 5
Set auxiliary output 2 as “ECU power”.
3 Negative power.
4 Positive power.
CAN communication shielding line
CAN GND -
(connect with controller’s terminal only).
CAN(H) 1(Hi) Using impedance 120Ω connecting line.
CAN(L) 2(Lo) Using impedance 120Ω connecting line.
Engine type: Volvo-EMS2.
NOTE: When this engine type is selected, preheating time should be set to at least 3 seconds.

HGM8100N Series Genset Controller User Manual Page 62 of 65


15.19 YUCHAI

It is suitable for Yuchai BOSCH common rail electronic-controlled engine.

Table 46 Engine 42-Pin Port

Terminals of controller Engine 42 pins port Remark


Fuel relay output 1.40 Connect to engine ignition lock.
Starting relay output - Connect to starter coil directly.
CAN communication shielding line (connect
CAN GND -
with controller’s this terminal only).
CAN(H) 1.35 Using impedance 120Ω connecting line.
CAN(L) 1.34 Using impedance 120Ω connecting line.

Table 47 Engine 2-Pin Port

Battery Engine 2 pins port Remark


Battery negative 1 Wire diameter 2.5mm2.
Battery positive 2 Wire diameter 2.5mm2.
Engine type: BOSCH.

15.20 WEICHAI

It is suitable for Weichai BOSCH common rail electronic-controlled engine.

Table 48 Engine Port

Terminals of controller Engine port Remark


Fuel relay output 1.40 Connect to engine ignition lock.
Starting relay output 1.61
CAN communication shielding line (connect
CAN GND -
with controller’s this terminal only).
CAN(H) 1.35 Using impedance 120Ω connecting line.
CAN(L) 1.34 Using impedance 120Ω connecting line.
Engine type: GTSC1.
NOTE: If there is any question of connection between controller and ECU communication, please feel free to

contact SmartGen’s service personnel.

HGM8100N Series Genset Controller User Manual Page 63 of 65


16 ETHERNET INTERFACE

16.1 ETHERNET INTERFACE INTRODUCTION

ETHERNET port, used for controller monitoring, can realize network client connection mode.
NOTE: After changing controller network parameters (e.g. IP address, subnet mask etc.) new settings will take effect
only after the controller is restarted.

16.2 NETWORK CLIENT CONNECTION MODE

When the controller is used as network client, it can be monitored via network port using TCP ModBus
protocol.
The procedure is the following:
1) Set IP address and subnet mask of the controller. The IP address should be in the same network
segment and different from the IP address used by the monitoring equipment (e.g. PC). e.g.: if
monitoring equipment IP address is 192.168.0.16, controller IP can be 192.168.0.18, subnet mask
is 255.255.255.0.
2) Connect the controller. It can be connected to the monitoring equipment directly using network
cable or via switchboard.
3) The communication between the controller and monitoring equipment is carried out using TCP
ModBus protocol.
NOTE: Controller parameters can be set in this connection mode. SmartGen provides testing software for this

connection mode. Communication protocol can be obtained from the SmartGen service.

16.3 CONTROLLER AND NETWORK CABLE CONNECTION

Table 49 Controller Internet Access

No. Name Description


1 TX+ Tranceive Data+
2 TX- Tranceive Data-
3 RX+ Receive Data+
4 NC Not connected
5 NC Not connected
6 RX- Receive Data-
7 NC Not connected
8 NC Not connected
1) Controller and PC connection via a line of cable
For this connection crossover cable must be used.
Crossover cable: EIA/TIA 568A standard on one end and EIA/TIA 568B on the other end.
NOTE: If PC network port has Auto MDI/MDIX function, parallel cable can also be used.

2) Controller and PC connection via switchboard (or router).


Parallel lines must be used.
Parallel cable: EIA/TIA 568A standard on both ends or EIA/TIA 568B standard on both ends.
NOTE: If switchboard (or router) network port has Auto MDI/MDIX function, crossover cable can also be used.

HGM8100N Series Genset Controller User Manual Page 64 of 65


17 FAULT FINDING

Table 50 Fault Finding

Symptoms Possible Solutions


Check starting batteries;
Controller no response with power. Check controller connection wirings;
Check DC fuse.
Check the water/cylinder temperature is too high or not;
Genset shutdown Check the genset AC voltage;
Check DC fuse.
Check emergency stop button is correct or not;
Check whether the starting battery positive be connected with
Controller emergency stop
the emergency stop input;
Check whether the circuit is open.
Low oil pressure alarm after crank
Check the oil pressure sensor and its connections.
disconnect
High water temp. alarm after crank
Check the water temperature sensor and its connections.
disconnect
Check related switch and its connections according to the
Shutdown alarm in running information on LCD;
Check digital inputs.
Check fuel oil circuit and its connections;
Check starting batteries;
Crank not disconnect
Check speed sensor and its connections;
Refer to engine manual.
Check starter connections;
Starter no response
Check starting batteries.
Genset running while ATS not Check ATS;
transfer Check the connections between ATS and controllers.
Check connections;
Check setting of COM port is correct or not;
RS485 communication is abnormal Check RS485’s connections of A and B is reverse connect or not;
Check RS485 transfer module whether damaged or not;
Check communication port of PC whether damage.
Check connections of CAN high and low polarity;
Check if correctly connected of 120Ω resister;
ECU communication failed Check if type of engine correct;
Check if connections from controller to engine and setting of
outputs correct.
Get information from LCD of alarm page;
If there is detailed alarm, check engine according to description.
ECU warning or stop
If not, please refer to engine manual according to SPN alarm
code.

_________________________________

HGM8100N Series Genset Controller User Manual Page 65 of 65

You might also like