Abb Cm-Efs.2s

The document provides information about voltage monitoring relays CM-EFS.2, including that they monitor single-phase AC and DC voltages, have adjustable thresholds for over and undervoltage, and can be configured for on or off delay with latching and non-latching options.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
28 views18 pages

Abb Cm-Efs.2s

The document provides information about voltage monitoring relays CM-EFS.2, including that they monitor single-phase AC and DC voltages, have adjustable thresholds for over and undervoltage, and can be configured for on or off delay with latching and non-latching options.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 18

Data sheet

Voltage monitoring relays CM-EFS.2


For single-phase AC/DC voltages

The CM-EFS.2 is an electronic voltage monitoring


relay that provides reliable monitoring of voltages
as well as detection of phase loss.
All devices are available with two different terminal
versions. You can choose between the proven
screw connection technology (double-chamber
cage connecting terminals) and the completely
tool-free Easy Connect Technology (push-in

2CDC 251 059 V0011


terminals).

Characteristics
–– Monitoring of DC and AC voltages (3-600 V)
–– TRMS measuring principle
–– One device includes 4 measuring ranges
–– Over- and undervoltage monitoring
–– ON- or OFF-delay configurable
–– Latching function configurable
–– Threshold values for >U and <U adjustable
–– Fixed hysteresis (5 %)
–– Precise adjustment by front-face operating controls Approvals
–– Screw connection technology or A UL 508, CAN/CSA C22.2 No.14
Easy Connect Technology available C GL
–– Housing material for highest fire protection classification
R EAC
UL 94 V-0
–– Tool-free mounting on DIN rail as well as demounting E CCC
–– Tripping delay TV adjustable (0 s; 0.1-30 s) L RMRS
–– 1x2 c/o (SPDT) contacts (common signal) or
2x1 c/o (SPDT) contact (separate signals for >U and <U)
Marks
configurable
a CE
–– 22.5 mm (0.89 in) width
–– 3 LEDs for status indication b RCM

Order data

Voltage monitoring relays


Type Rated control supply voltage Connection technology Measuring ranges Order code
CM-EFS.2P 24-240 V AC/DC Push-in terminals 3-30 V, 6-60 V, 30-300 V, 60-600 V 1SVR740750R0400
CM-EFS.2S 24-240 V AC/DC Screw type terminals 3-30 V, 6-60 V, 30-300 V, 60-600 V 1SVR730750R0400

Accessories
Type Description Order code
ADP.01 Adapter for screw mounting 1SVR430029R0100
MAR.12 Marker label for devices with DIP switches 1SVR730006R0000
COV.11 Sealable transparent cover 1SVR730005R0100
Connection technology
Maintenance free Easy Connect Technology with Approved screw connection technology with
push-in terminals double-chamber cage connecting terminals
Type designation CM-xxS.yyP Type designation CM-xxS.yyS
2CDC 253 026 F0011

2CDC 253 025 F0011


Push-in terminals Double-chamber cage connecting terminals

–– Tool-free connection of rigid and flexible wires with –– Terminal spaces for different wire sizes
wire end ferrule –– One screw for opening and closing of both cages
–– Easy connection of flexible wires without wire end –– Pozidrive screws for pan- or crosshead screwdrivers
ferrule by opening the terminals according to DIN ISO 2380-1 Form A 0.8 x 4 mm
–– No retightening necessary (0.0315 x 0.157 in), DIN ISO 8764-1 PZ1 ø 4.5 mm
–– One operation lever for opening both connecting (0.177 in)
terminals
–– For triggering the lever and disconnecting of wires
you can use the same tool (Screwdriver according to
DIN ISO 2380-1 Form A 0.8 x 4 mm (0.0315 x 0.157
in), DIN ISO 8764-1 PZ1 ø 4.5 mm (0.177 in))
–– Constant spring force on terminal point independent
of the applied wire type, wire size or ambient
conditions (e. g. vibrations or temperature changes)
–– Opening for testing the electrical contacting
–– Gas-tight

Both the Easy Connect Technology with push-in terminals and screw connection technology with double-chamber cage
connecting terminals have the same connection geometry as well as terminal position.

2 - Voltage monitoring relays CM-EFS.2 | Data sheet


Functions

Operating controls

1 Adjustment of the threshold value >U for overvoltage

2 Adjustment of the threshold value <U for undervoltage

3 Indication of operational states

U/T: green LED – control supply voltage/timing

R: yellow LED – relay status


1
U: red LED – over- / undervoltage
2
2CDC 251 059 V0011

4 Adjustment of the measuring range

5 Adjustment of the tripping delay TV


3
6 DIP switches (see DIP switch functions)
4

Application
The voltage monitoring relays CM-EFS.2 are designed for use in single-phase AC and/or DC systems for the simultaneous
monitoring of over- and undervoltages as well as detection of phase loss. Depending on the configuration, one c/o (SPDT)
contact each or both c/o (SPDT) contacts in parallel can be used for the over- and undervoltage monitoring. The devices
operate over an universal range of supply voltages, provide an adjustable tripping delay and work according to the open- or
closed-circuit principle.

Operating mode
The CM-EFS.2 have 2 c/o (SPDT) contacts and include 4 measuring ranges: 3-30 V, 6-60 V, 30-300 V and 60-600 V.
The units are adjusted with front-face operating controls. The selection of: ON-delay A or OFF-delay B, open- h
or closed-circuit principle g, latching function ON f or OFF e and 2x1 c/o i or 1x2 c/o (SPDT) contacts j is
made with DIP switches. Potentiometers, with direct reading scale, allow the adjustment of the threshold valuemax (>U) for
overvoltage, the threshold valuemin (<U) for undervoltage and the tripping delay TV . The tripping delay TV is adjustable over
a range of instantaneous to a 30 s delay. The hysteresis is fixed at 5 %. Timing is displayed by a flashing green LED labelled
U/T.

Data sheet | Voltage monitoring relays CM-EFS.2 - 3


Function diagrams

Voltage window monitoring 1x2 c/o (SPDT) contacts j ON-delayed A without latching e
Open-circuit principle h
The voltage to be monitored (measured value) is applied to terminals B-C. The control supply voltage applied to terminals
A1-A2 is displayed by the glowing green LED.
If the measured value exceeds the threshold valuemax (>U) or drops below the threshold valuemin (<U), the tripping delay TV
starts and the red LED glows (overvoltage), or flashes W (undervoltage) respectively.
Timing of TV is displayed by the flashing W green LED.
When TV is complete and the measured value still exceeds the threshold valuemax minus the fixed hysteresis (5 %) or is still
below the threshold valuemin plus the fixed hysteresis (5 %), the output relays energize and the yellow LED (relay energized)
glows.
If the measured value decreases below the threshold valuemax minus the fixed hysteresis (5 %) or exceeds the threshold
valuemin plus the fixed hysteresis (5 %), the output relays de-energize and the red and yellow LEDs turn off.
If control supply voltage is interrupted, the green LED turns off.
Closed-circuit principle g
The voltage to be monitored (measured value) is applied to terminals B-C. When control supply voltage is applied to
terminals A1-A2, the output relays energize and the green and yellow LED (relays energized) glow.
If the measured value exceeds the threshold valuemax (>U) or drops below the threshold valuemin (<U), the tripping delay TV
starts and the red LED glows (overvoltage), or flashes W (undervoltage) respectively.
Timing of TV is displayed by the flashing W green LED.
When TV is complete and the measured value still exceeds the threshold valuemax minus the fixed hysteresis (5 %) or is
still below the threshold valuemin plus the fixed hysteresis (5 %), the output relays de-energize and the yellow LED (relays
energized) turns off.
If the measured value decreases below the threshold valuemax minus the fixed hysteresis (5 %) or exceeds the threshold
valuemin plus the fixed hysteresis (5 %), the output relays re-energize, the yellow LED glows and the red LED turns off.
If control supply voltage is interrupted, the output relays de-energize and the yellow and green LEDs turn off.

A1-A2

Thresholdmax
Hysteresis

Measured value
< TV TV < TV
Hysteresis
Thresholdmin

Open-circuit principle open

11-14 (15-18)
11-12 (15-16)
21-24 (25-28)
21-22 (25-26)
green LED
red LED
yellow LED
Closed-circuit principle closed

11-14 (15-18)
11-12 (15-16)
21-24 (25-28)
21-22 (25-26)
2CDC 252 232 F0205

green LED
red LED
yellow LED

4 - Voltage monitoring relays CM-EFS.2 | Data sheet


Voltage window monitoring 1x2 c/o (SPDT) contacts j OFF-delayed B without latching e
Open-circuit principle h
The voltage to be monitored (measured value) is applied to terminals B-C. The control supply voltage applied to terminals
A1-A2 is displayed by the glowing green LED.
If the measured value exceeds the threshold valuemax (>U) or drops below the threshold valuemin (<U), the output relays
energize, the yellow LED (relays energized) glows and the red LED glows (overvoltage), or flashes W (undervoltage)
respectively.
If the measured value decreases below the threshold valuemax minus the fixed hysteresis (5 %) or exceeds the threshold
valuemin plus the fixed hysteresis (5 %), the tripping delay TV starts and the red LED turns off.
Timing of TV is displayed by the flashing W green LED. When TV is complete, the output relays de-energize and the
yellow LED (relay energized) turns off.
If control supply voltage is interrupted, the green LED turns off.
Closed-circuit principle g
The voltage to be monitored (measured value) is applied to terminals B-C. When control supply voltage is applied to
terminals A1-A2, the output relays energize and the green and yellow LED (relays energized) glow.
If the measured value exceeds the threshold valuemax (>U) or drops below the threshold valuemin (<U), the output relays de-
energize, the yellow LED turns off and the red LED glows (overvoltage), or flashes W (undervoltage) respectively.
If the measured value decreases below the threshold valuemax minus the fixed hysteresis (5 %) or exceeds the threshold
valuemin plus the fixed hysteresis (5 %), the tripping delay TV starts and the red LED turns off.
Timing of TV is displayed by the flashing W green LED. When TV is complete, the output relays energize and the
yellow LED (relay energized) glows.
If control supply voltage is interrupted, the output relays de-energize and the yellow and green LEDs turn off.

A1-A2

Thresholdmax
Hysteresis

Measured value
TV TV
Hysteresis
Thresholdmin

Open-circuit principle open

11-14 (15-18)
11-12 (15-16)
21-24 (25-28)
21-22 (25-26)
green LED
red LED
yellow LED
Closed-circuit principle closed

11-14 (15-18)
11-12 (15-16)
21-24 (25-28)
21-22 (25-26)
2CDC 252 233 F0205

green LED
red LED
yellow LED

Data sheet | Voltage monitoring relays CM-EFS.2 - 5


Voltage window monitoring 1x2 c/o (SPDT) contacts j ON-delayed A with latching f
Open-circuit principle h
The voltage to be monitored (measured value) is applied to terminals B-C. The control supply voltage applied to terminals
A1-A2 is displayed by the glowing green LED.
If the measured value exceeds the threshold valuemax (>U) or drops below the threshold valuemin (<U), the tripping delay TV
starts and the red LED glows (overvoltage), or flashes W (undervoltage) respectively.
Timing of TV is displayed by the flashing W green LED.
When TV is complete and the measured value still exceeds the threshold valuemax minus the fixed hysteresis (5 %) or is still
below the threshold valuemin plus the fixed hysteresis (5 %), the output relays energize and the yellow LED (relay energized)
flashes Z .
If the measured value decreases below the threshold valuemax minus the fixed hysteresis (5 %) or exceeds the threshold
valuemin plus the fixed hysteresis (5 %), the red LED turns off. The output relays remain energized (latching function).
If control supply voltage is interrupted (reset), the output relays de-energize and the yellow and green LEDs turn off.
Closed-circuit principle g
The voltage to be monitored (measured value) is applied to terminals B-C. When control supply voltage is applied to
terminals A1-A2, the output relays energize and the green and yellow LED (relays energized) glow.
If the measured value exceeds the threshold valuemax (>U) or drops below the threshold valuemin (<U), the tripping delay TV
starts and the red LED glows (overvoltage), or flashes W (undervoltage) respectively.
Timing of TV is displayed by the flashing W green LED.
When TV is complete and the measured value still exceeds the threshold valuemax minus the fixed hysteresis (5 %) or is
still below the threshold valuemin plus the fixed hysteresis (5 %), the output relays de-energize and the yellow LED (relays
energized) flashes Y .
If the measured value decreases below the threshold valuemax minus the fixed hysteresis (5 %) or exceeds the threshold
valuemin plus the fixed hysteresis (5 %), the red LED turns off. The output relays remain de-energized (latching function).
If control supply voltage is interrupted (reset), the yellow and green LEDs turn off. The output relays energize again when
control supply voltage is re-applied.

A1-A2
Reset
Thresholdmax
Hysteresis

Measured value
< TV TV < TV
Hysteresis
Thresholdmin

Open-circuit principle open

11-14 (15-18)
11-12 (15-16)
21-24 (25-28)
21-22 (25-26)
green LED
red LED
yellow LED
Closed-circuit principle closed

11-14 (15-18)
11-12 (15-16)
21-24 (25-28)
21-22 (25-26)
2CDC 252 234 F0205

green LED
red LED
yellow LED

6 - Voltage monitoring relays CM-EFS.2 | Data sheet


Voltage window monitoring 1x2 c/o (SPDT) contacts j OFF-delayed B with latching f
Open-circuit principle h
The voltage to be monitored (measured value) is applied to terminals B-C. The control supply voltage applied to terminals
A1-A2 is displayed by the glowing green LED.
If the measured value exceeds the threshold valuemax (>U) or drops below the threshold valuemin (<U), the output relays
energize, the yellow LED (relays energized) flashes Z and the red LED glows (overvoltage), or flashes W
(undervoltage) respectively.
If the measured value decreases below the threshold valuemax minus the fixed hysteresis (5 %) or exceeds the threshold
valuemin plus the fixed hysteresis (5 %), the red LED turns off. The output relays remain energized (latching function).
If control supply voltage is interrupted (reset), the output relays de-energize and the yellow and green LEDs turn off.
Closed-circuit principle g
The voltage to be monitored (measured value) is applied to terminals B-C. When control supply voltage is applied to
terminals A1-A2, the output relays energize and the green and yellow LED (relays energized) glow.
If the measured value exceeds the threshold valuemax (>U) or drops below the threshold valuemin (<U), the output relays
de-energize, the yellow LED (relays energized) flashes Y and the red LED glows (overvoltage), or flashes W
(undervoltage) respectively.
If the measured value decreases below the threshold valuemax minus the fixed hysteresis (5 %) or exceeds the threshold
valuemin plus the fixed hysteresis (5 %), the red LED turns off. The output relays remain de-energized (latching function).
If control supply voltage is interrupted (reset), the yellow and green LEDs turn off. The output relays energize again when
control supply voltage is re-applied.

A1-A2
Reset
Thresholdmax
Hysteresis

Measured value

Hysteresis
Thresholdmin

Open-circuit principle open

11-14 (15-18)
11-12 (15-16)
21-24 (25-28)
21-22 (25-26)
green LED
red LED
yellow LED
Closed-circuit principle closed

11-14 (15-18)
11-12 (15-16)
21-24 (25-28)
21-22 (25-26)
2CDC 252 235 F0205

green LED
red LED
yellow LED

Data sheet | Voltage monitoring relays CM-EFS.2 - 7


Voltage window monitoring 2x1 c/o (SPDT) contact i ON-delayed A without latching e
Open-circuit principle h
The voltage to be monitored (measured value) is applied to terminals B-C. The control supply voltage applied to terminals
A1-A2 is displayed by the glowing green LED.
If the measured value exceeds the threshold valuemax (>U) or drops below the threshold valuemin (<U), the tripping delay TV
starts and the red LED glows (overvoltage), or flashes W (undervoltage) respectively.
Timing of TV is displayed by the flashing W green LED.
When TV is complete and the measured value still exceeds the threshold valuemax minus the fixed hysteresis (5 %) or is still
below the threshold valuemin plus the fixed hysteresis (5 %), the output relay 1115-1216/1418 (>U), or 2125-2226/2428 (<U)
respectively, energizes and the yellow LED (relay energized) glows.
If the measured value decreases below the threshold valuemax minus the fixed hysteresis (5 %) or exceeds the threshold
valuemin plus the fixed hysteresis (5 %), the output relay 1115-1216/1418 (>U), or 2125-2226/2428 (<U) respectively, de-
energizes and the red and yellow LEDs turn off.
If control supply voltage is interrupted, the green LED turns off.
Closed-circuit principle g
The voltage to be monitored (measured value) is applied to terminals B-C. When control supply voltage is applied to
terminals A1-A2, the output relays energize and the green and yellow LED (relays energized) glow.
If the measured value exceeds the threshold valuemax (>U) or drops below the threshold valuemin (<U), the tripping delay TV
starts and the red LED glows (overvoltage), or flashes W (undervoltage) respectively.
Timing of TV is displayed by the flashing W green LED.
When TV is complete and the measured value still exceeds the threshold valuemax minus the fixed hysteresis (5 %) or is still
below the threshold valuemin plus the fixed hysteresis (5 %), the output relay 1115-1216/1418 (>U), or 2125-2226/2428 (<U)
respectively, de-energizes and the yellow LED (relays energized) turns off.
If the measured value decreases below the threshold valuemax minus the fixed hysteresis (5 %) or exceeds the threshold
valuemin plus the fixed hysteresis (5 %), the output relay 1115-1216/1418 (>U), or 2125-2226/2428 (<U) respectively, re-
energizes, the yellow LED glows and the red LED turns off.
If control supply voltage is interrupted, the output relays de-energize and the yellow and green LEDs turn off.

A1-A2

Thresholdmax
Hysteresis

Measured value
< TV TV < TV TV
Hysteresis
Thresholdmin

Open-circuit principle open

>U: 11-14 (15-18)


11-12 (15-16)

<U: 21-24 (25-28)


21-22 (25-26)
green LED
red LED
yellow LED
Closed-circuit principle closed

>U: 11-14 (15-18)


11-12 (15-16)

<U: 21-24 (25-28)


21-22 (25-26)
2CDC 252 236 F0205

green LED
red LED
yellow LED

8 - Voltage monitoring relays CM-EFS.2 | Data sheet


Voltage window monitoring 2x1 c/o (SPDT) contact i OFF-delayed B without latching e
Open-circuit principle h
The voltage to be monitored (measured value) is applied to terminals B-C. The control supply voltage applied to terminals
A1-A2 is displayed by the glowing green LED.
If the measured value exceeds the threshold valuemax (>U) or drops below the threshold valuemin (<U), the output relay
11 15-1216/1418 (>U), or 2125-22 26/2428 (<U) respectively, energizes, the yellow LED (relays energized) glows and the red LED
glows (overvoltage), or flashes W (undervoltage) respectively.
If the measured value decreases below the threshold valuemax minus the fixed hysteresis (5 %) or exceeds the threshold
valuemin plus the fixed hysteresis (5 %), the tripping delay TV starts and the red LED turns off.
Timing of TV is displayed by the flashing W green LED. When TV is complete, the output relay 1115-1216/1418 (>U), or
2125-2226/2428 (<U) respectively, de-energizes and the yellow LED (relay energized) turns off.
If control supply voltage is interrupted, the green LED turns off.
Closed-circuit principle g
The voltage to be monitored (measured value) is applied to terminals B-C. When control supply voltage is applied to
terminals A1-A2, the output relays energize and the green and yellow LED (relays energized) glow.
If the measured value exceeds the threshold valuemax (>U) or drops below the threshold valuemin (<U), the output relay
1115-1216/1418 (>U), or 2125-22 26/2428 (<U) respectively, de-energizes, the yellow LED turns off and the red LED glows
(overvoltage), or flashes W (undervoltage) respectively.
If the measured value decreases below the threshold valuemax minus the fixed hysteresis (5 %) or exceeds the threshold
valuemin plus the fixed hysteresis (5 %), the tripping delay TV starts and the red LED turns off.
Timing of TV is displayed by the flashing W green LED. When TV is complete, the output relay 1115-1216/1418 (>U), or
2125-2226/2428 (<U) respectively, energizes and the yellow LED (relay energized) glows.
If control supply voltage is interrupted, the output relays de-energize and the yellow and green LEDs turn off.

A1-A2

Thresholdmax
Hysteresis

Measured value
TV TV
Hysteresis
Thresholdmin

Open-circuit principle open

>U: 11-14 (15-18)


11-12 (15-16)

<U: 21-24 (25-28)


21-22 (25-26)
green LED
red LED
yellow LED
Closed-circuit principle closed

>U: 11-14 (15-18)


11-12 (15-16)

<U: 21-24 (25-28)


21-22 (25-26)
2CDC 252 237 F0205

green LED
red LED
yellow LED

Data sheet | Voltage monitoring relays CM-EFS.2 - 9


Voltage window monitoring 2x1 c/o (SPDT) contact i ON-delayed A with latching f
Open-circuit principle h
The voltage to be monitored (measured value) is applied to terminals B-C. The control supply voltage applied to terminals
A1-A2 is displayed by the glowing green LED.
If the measured value exceeds the threshold valuemax (>U) or drops below the threshold valuemin (<U), the tripping delay TV
starts and the red LED glows (overvoltage), or flashes W (undervoltage) respectively.
Timing of TV is displayed by the flashing W green LED.
When TV is complete and the measured value still exceeds the threshold valuemax minus the fixed hysteresis (5 %) or is still
below the threshold valuemin plus the fixed hysteresis (5 %), the output relay 1115-1216/1418 (>U), or 2125-2226/2428 (<U)
respectively, energizes and the yellow LED (relay energized) flashes Z .
If the measured value decreases below the threshold valuemax minus the fixed hysteresis (5 %) or exceeds the threshold
valuemin plus the fixed hysteresis (5 %), the red LED turns off. The output relay 1115-1216/1418 (>U), or 2125-2226/2428 (<U)
respectively, remains energized (latching function).
If control supply voltage is interrupted (reset), the output relay 1115-1216/1418 (>U), or 2125-2226/2428 (<U) respectively, de-
energizes and the yellow and green LEDs turn off.
Closed-circuit principle g
The voltage to be monitored (measured value) is applied to terminals B-C. When control supply voltage is applied to
terminals A1-A2, the output relays energize and the green and yellow LED (relays energized) glow.
If the measured value exceeds the threshold valuemax (>U) or drops below the threshold valuemin (<U), the tripping delay TV
starts and the red LED glows (overvoltage), or flashes W (undervoltage) respectively.
Timing of TV is displayed by the flashing W green LED.
When TV is complete and the measured value still exceeds the threshold valuemax minus the fixed hysteresis (5 %) or is still
below the threshold valuemin plus the fixed hysteresis (5 %), the output relay 1115-1216/1418 (>U), or 2125-2226/2428 (<U)
respectively, de-energizes and the yellow LED (relays energized) flashes Y .
If the measured value decreases below the threshold valuemax minus the fixed hysteresis (5 %) or exceeds the threshold
valuemin plus the fixed hysteresis (5 %), the red LED turns off. The output relay 1115-1216/1418 (>U), or 2125-2226/2428 (<U)
respectively, remains de-energized (latching function).
If control supply voltage is interrupted (reset), the yellow and green LEDs turn off. The output relays energize again when
control supply voltage is re-applied.

A1-A2
Reset
Thresholdmax
Hysteresis

Measured value
< TV TV < TV TV
Hysteresis
Thresholdmin

Open-circuit principle open

>U: 11-14 (15-18)


11-12 (15-16)

<U: 21-24 (25-28)


21-22 (25-26)
green LED
red LED
yellow LED
Closed-circuit principle closed

>U: 11-14 (15-18)


11-12 (15-16)

<U: 21-24 (25-28)


21-22 (25-26)
2CDC 252 239 F0205

green LED
red LED
yellow LED

10 - Voltage monitoring relays CM-EFS.2 | Data sheet


Voltage window monitoring 2x1 c/o (SPDT) contact i OFF-delayed B with latching f
Open-circuit principle h
The voltage to be monitored (measured value) is applied to terminals B-C. The control supply voltage applied to terminals
A1-A2 is displayed by the glowing green LED.
If the measured value exceeds the threshold valuemax (>U) or drops below the threshold valuemin (<U), the output relay 1115-
12 16/1418 (>U), or 21 25-22 26/2428 (<U) respectively, energizes, the yellow LED (relays energized) flashes Z and the red
LED glows (overvoltage), or flashes W (undervoltage) respectively.
If the measured value decreases below the threshold valuemax minus the fixed hysteresis (5 %) or exceeds the threshold
valuemin plus the fixed hysteresis (5 %), the red LED turns off. The output relay 1115-1216/1418 (>U), or 2125-2226/2428 (<U)
respectively, remains energized (latching function).
If control supply voltage is interrupted (reset), the output relays de-energize and the yellow and green LEDs turn off.
Closed-circuit principle g
The voltage to be monitored (measured value) is applied to terminals B-C. When control supply voltage is applied to
terminals A1-A2, the output relays energize and the green and yellow LED (relays energized) glow.
If the measured value exceeds the threshold valuemax (>U) or drops below the threshold valuemin (<U), the output relay 1115-
12 16/1418 (>U), or 2125-22 26/2428 (<U) respectively, de-energizes, the yellow LED (relays energized) flashes Y and the
red LED glows (overvoltage), or flashes W (undervoltage) respectively.
If the measured value decreases below the threshold valuemax minus the fixed hysteresis (5 %) or exceeds the threshold
valuemin plus the fixed hysteresis (5 %), the red LED turns off. The output relay 1115-1216/1418 (>U), or 2125-2226/2428 (<U)
respectively, remains de-energized (latching function).
If control supply voltage is interrupted (reset), the yellow and green LEDs turn off. The output relays energize again when
control supply voltage is re-applied.

A1-A2
Reset
Thresholdmax
Hysteresis

Measured value

Hysteresis
Thresholdmin

Open-circuit principle open

>U: 11-14 (15-18)


11-12 (15-16)

<U: 21-24 (25-28)


21-22 (25-26)
green LED
red LED
yellow LED
Closed-circuit principle closed

>U: 11-14 (15-18)


11-12 (15-16)

<U: 21-24 (25-28)


21-22 (25-26)
2CDC 252 239 F0205

green LED
red LED
yellow LED

Data sheet | Voltage monitoring relays CM-EFS.2 - 11


Electrical connection

A1 1115 2125 A1-A2 Rated control supply voltage


B B-C Measuring ranges: 3-30 V, 6-60 V, 30-300 V, 60-600 V
B 1115 2125 11 15-1216/1418 Output contacts - open- or closed-circuit principle
21 25-2226/2428

2CDC 252 207 F0005


A1 A2 1216 1418 2226 2428
1418 1216 C
2428 2226 A2

Connection diagram

MÓNG SẾN: 1 2 3 4
DIP switches OFF OFF OFF ON

Position 4 3 2 1 1 ON OFF-delay
2CDC 252 274 F0005

ON 2x1 c/o
closed OFF ON-delay
2 ON Closed-circuit principle
OFF 1x2 c/o
open OFF Open-circuit principle
3 ON Latching function activated
OFF Latching function not activated
4 ON 2x1 c/o (SPDT) contact
OFF 1x2 c/o (SPDT) contacts
OFF = Default

12 - Voltage monitoring relays CM-EFS.2 | Data sheet


Technical data
Data at Ta = 25 °C and rated values, unless otherwise indicated

Input circuits
Supply circuit A1-A2
Rated control supply voltage Us 24-240 V AC/DC
Rated control supply voltage Us tolerance -15...+10 %
Rated frequency 50/60 Hz
Typical current / power consumption 24 V DC 30 mA / 0.75 W
115 V AC 17 mA / 1.9 VA
230 V AC 11 mA / 2.6 VA
Power failure buffering time 20 ms
Transient overvoltage protection varistors

Measuring circuit B-C


Monitoring function Over- and undervoltage monitoring
Measuring method TRMS measuring principle
Measuring inputs terminal connection B-C
measuring range 3-30 V, 6-60 V, 30-300 V, 60-600 V
input resistance 600 kΩ
pulse overload capacity t < 1 s 800 V
continuous capacity 660 V
Threshold value >U and <U adjustable within the indicated
measuring range
Tolerance of the adjusted threshold value 10 % of the range end value
Hysteresis related to the threshold value 5 % fixed
Measuring signal frequency range DC / 15 Hz - 2 kHz
Rated measuring signal frequency range DC / 50-60 Hz
Maximum response time AC 80 ms
DC 120 ms
Accuracy within the rated control supply voltage tolerance ΔU ≤ 0.5 %
Accuracy within the temperature range ΔU ≤ 0.06 % / °C
Transient overvoltage protection varistors

Timing circuit
Time delay TV 0 s or 0.1-30 s adjustable
Repeat accuracy (constant parameters) ±0.07 % of full scale
Tolerance of the adjusted time delay -
Accuracy within the rated control supply voltage tolerance Δt ≤ 0.5 %
Accuracy within temperature range Δt ≤ 0.06 % / °C

User interface
Indication of operational states
Control supply voltage U/T: green LED V: control supply voltage applied

W: tripping delay TV active


Measured value U: red LED V: overvoltage
W: undervoltage
Relay status R: yellow LED V: output relay energized, no latching function
Z: output relay energized, active latching function
Y: output relay de-energized, active latching function

Data sheet | Voltage monitoring relays CM-EFS.2 - 13


Output circuits
Kind of output 11-12/14 relay, 1st c/o (SPDT) contact
21-22/24 relay, 2nd c/o (SPDT) contact
1 x 2 c/o (SPDT) contacts (common signal) or
2 x 1 c/o (SPDT) contact (separate signal for >U and
<U) configurable
Operating principle open- or closed-circuit principle configurable (open-
circuit principle: output relays energize if the measured
value exceeds d / falls below c the adjusted
threshold value, closed-circuit principle: output relays
de-energize if measured value exceedsd / falls
below c the adjusted threshold value)
Contact material AgNi
Rated operational voltage Ue 250 V
Minimum switching voltage / Minimum switching current 24 V / 10 mA
Maximum switching voltage / Maximum switching current 250 V AC / 4 A AC
Rated operational current Ie AC-12 (resistive) at 230 V 4A
AC-15 (inductive) at 230 V 3A
DC-12 (resistive) at 24 V 4A
DC-13 (inductive) at 24 V 2A
AC rating (UL 508) utilization category (Control Circuit Rating Code) B 300
max. rated operational voltage 300 V AC
max. continuous thermal current at B 300 5A
max. making/breaking 3600/360 VA
apparent power at B 300
Mechanical lifetime 30 x 106 switching cycles
Electrical lifetime AC-12, 230 V, 4 A 0.1 x 106 switching cycles
Maximum fuse rating to achieve n/c contact 6 A fast-acting
short-circuit protection n/o contact 10 A fast-acting

General data
MTBF on request
Duty time 100 %
Dimensions (W x H x D) product dimensions 22.5 x 85.6 x 103.7 mm (0.89 x 3.37 x 4.08 in)
packaging dimensions 97 x 109 x 30 mm (3.82 x 4.29 x 1.18 in)
Weight Screw connection Easy Connect Technology
technology (Push-in)
Net weight 0.157 kg (0.346 lb) 0.146 kg (0.322 lb)
Gross weight 0.179 kg (0.395 lb) 0.168 kg (0.370 lb)
Mounting DIN rail (IEC/EN 60715),
snap-on mounting without any tool
Mounting position any
Material of housing UL 94 V-0
Degree of protection housing IP50
terminals IP20

14 - Voltage monitoring relays CM-EFS.2 | Data sheet


Electrical connection
Screw connection Easy Connect
technology Technology (Push-in)
Connecting capacity fine‑strand with(out) 1 x 0.5-2.5 mm² 2 x 0.5-1.5 mm²
wire end ferrule (1 x 18-14 AWG) (2 x 18-16 AWG)
2 x 0.5-1.5 mm²
(2 x 18-16 AWG)
rigid 1 x 0.5-4 mm² 2 x 0.5-1.5 mm²
(1 x 20-12 AWG) (2 x 20-16 AWG)
2 x 0.5-2.5 mm²
(2 x 20-14 AWG)
Stripping length 8 mm (0.32 in)
Tightening torque 0.6 - 0.8 Nm -
(7.08 lb.in)

Environmental data
Ambient temperature ranges operation -25...+60 °C (-13...+140 °F)
storage -40...+85 °C (-40...+185 °F)
Damp heat, cyclic (IEC/EN 60068-2-30) 55 °C, 6 cycles
Vibration, sinusoidal Class 2
Shock Class 2

Isolation data
Rated insulation voltage Ui supply / measuring circuit / output 600 V
output 1 / output 2 250 V
Rated impulse withstand voltage Uimp supply / measuring circuit / output 6 kV 1.2/50 μs
output 1 / output 2 4 kV 1.2/50 μs
Pollution degree 3
Overvoltage category III

Standards / Directives
Standards IEC/EN 60947-5-1, IEC/EN 60255-27, EN 50178
Low Voltage Directive 2014/35/EU
EMC Directive 2014/30/EU
RoHS Directive 2011/65/EU

Electromagnetic compatibility
Interference immunity to IEC/EN 61000-6-2
electrostatic discharge IEC/EN 61000-4-2 Level 3
radiated, radio-frequency, electromagnetic field IEC/EN 61000-4-3 Level 3
electrical fast transient / burst IEC/EN 61000-4-4 Level 3
surge IEC/EN 61000-4-5 Level 3
conducted disturbances, induced by IEC/EN 61000-4-6 Level 3
radio-frequency fields
Interference emission IEC/EN 61000-6-3
high-frequency radiated IEC/CISPR 22, EN 55022 Class B
high-frequency conducted IEC/CISPR 22, EN 55022 Class B

Data sheet | Voltage monitoring relays CM-EFS.2 - 15


Technical diagrams

Load limit curves

V V
300 300
V 200 V 200
resistive load
resistive load
100 100
80 80
60 60
50 50
40 40
30 30
20 20

2CDC 252 194 F0205

2CDC 252 193 F0205


10 10
0.1 0.2 0.5 1 2 4 6 10 0.1 0.2 0.5 1 2 4 6 10
I A I A

AC load (resistive) DC load (resistive)

1.0
Switching cycles

0.9

0.8
F
0.7 250 V
resistive load
0.6

0.5
2CDC 252 192 F0205

0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
cos ϕ

2CDC 252 148 F0206


Derating factor F for inductive AC load
Switching current [A]

Contact lifetime

16 - Voltage monitoring relays CM-EFS.2 | Data sheet


Dimensions
in mm and inches

113.4 4.47”
105.9 4.17” 22.5 0.89”

85.6 3.37”

2CDC 252 009 F0011


103.7 4.08”

Accessories
in mm and inches

8 0.32”
22.5 0.89” 4.8 0.19”

68 2.68”
0.453”
11.5
0.256”

62.5 2.461”
6.5

22.2
2CDC 252 008 F0010

2CDC 252 020 F0011

2CDC 252 010 F0011


0.874”
0.394”

0.787”
10

20

4T22
0.309”
7.85

front to back
60 2.362” 19.9 110.5 4.31”
70 2.756” 0.783”
ADP.01 ‑ Adapter for screw mounting MAR.12 ‑ Marker label for devices COV.11 ‑ Sealable transparent cover
with DIP switches

Further documentation
Document title Document type Document number
Electronic products and relays Technical catalogue 2CDC 110 004 C02xx
CM-EFS.2 Instruction manual 1SVC 730 570 M0000

You can find the documentation on the internet at www.abb.com/lowvoltage


-> Automation, control and protection -> Electronic relays and controls -> Measuring and monitoring relays.

CAD system files


You can find the CAD files for CAD systems at http://abb-control-products.partcommunity.com
-> Low Voltage Products & Systems -> Control Products -> Electronic Relays and Controls.

Data sheet | Voltage monitoring relays CM-EFS.2 - 17


Contact us

ABB STOTZ-KONTAKT GmbH

Document number 2CDC 112 174 D0201 (07.2016)


P. O. Box 10 16 80
69006 Heidelberg, Germany
Phone: +49 (0) 6221 7 01-0
Fax: +49 (0) 6221 7 01-13 25
E-mail: [email protected]

You can find the address of your


local sales organisation on the
ABB home page
http://www.abb.com/contacts
-> Low Voltage Products and Systems

Note:
We reserve the right to make technical changes
or modify the contents of this document without
prior notice. With regard to purchase orders, the
agreed particulars shall prevail. ABB AG does
not accept any responsibility whatsoever for
potential errors or possible lack of information in
this document.

We reserve all rights in this document and in


the subject matter and illustrations contained
therein. Any reproduction, disclosure to third
parties or utilization of its contents – in whole
or in parts – is forbidden without prior written
consent of ABB AG.

Copyright© 2016 ABB


All rights reserved