This document provides specifications for a medium voltage switchboard including: - Rated voltage of 12kV, withstand voltage of 28kV and 75kV, and service voltage of 11kV. - Internal characteristics such as busbar ratings, cubicle details, circuit breaker information, and switch and transformer specifications. - External characteristics such as IP protection ratings, painting color, ceiling height, and cable gland information.
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
87 views

Mcset DML

This document provides specifications for a medium voltage switchboard including: - Rated voltage of 12kV, withstand voltage of 28kV and 75kV, and service voltage of 11kV. - Internal characteristics such as busbar ratings, cubicle details, circuit breaker information, and switch and transformer specifications. - External characteristics such as IP protection ratings, painting color, ceiling height, and cable gland information.
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

SET REU

DETAILED MATERIAL LIST

MCSET Range - Switchboard characteristics :


SWB TAG NUMBER/NAME MCSET SWB P1 VCB
Rated Voltage _12kV
Power frequency withstand voltage 28kV
Lightning Impulse withstand voltage 75kV
Service Voltage 11kV
Short-circuit withstand current 25kA/3s
Frequency 50 Hz
Installation type Indoor
Degree of protection for enclosure IP40
Degree of protection between MV-LV compartments IP2XC
Classes PM (partition class)
Service continuity LSC2B type - Metal-clad switchgear
Paint color RAL 9003 [Front face only]
Internal arc withstand IAC A-FLR 25kA / 1s
Installation With IA tunnel (Pressure relief duct.) Evacuation to the atmosphere is MANDATORY)
Ceiling Height 4000mm (recommended)
Anti-seismic option Without
Earthing system Unknown
Cable Type XLPE / STANDARD
Standard Cable cross section max./diameter 50-630mm² for single core, must be <70mm & 50-240mm² for three core / must be < 90mm
Gland Plates Drilled

Busbar characteristics
Main Busbar current rating _1250A @40°C
Busbar color coding L1-RED/L2-YELLOW/L3-BLUE (by stickers)
Main Horizontal Busbar coating/ material / insulation Bare / Copper / With insulation
Main Busbar Joints coating / material / insulation Bare / Copper / With insulation
Cables and CT's compartment connection busbar Bare / Copper / Without insulation
Earthing busbar Bare / Copper / Without insulation

Cubicle General Characteristics


CIRCUIT BREAKER :
Arc Quenching Technique Vacuum
Rated Breaking Capacity 25kA/3s
Close/Open Aux. Contact 4O+4C
Signaling contact drawn-in/out 4O+4C
Operating mechanism duty cycle O-0.3s - CO - 15s - CO
Push button O / C IEC: Red/Black
Mechanical position : O. / C. IEC: Black/White
OM position indicator IEC: White/Yellow

SHUTTERS:
Unpainted YES (IEC)
Padlocking feature YES

EARTHING SWITCH:
Signalling Contact 3O+3C
Making capacity 25kA/3s

Cubicle Name CAPACITOR FEEDER OUTGOING FEEDER


Cubicle Number **Please Indicate** **Please Indicate**

Product MCSET MCSET

Cubicle Type _AD1 _AD1


Qty 1 1 1
Depth / mm 1725 1725
Height / mm 2300 2300
Height with IA tunnel / mm 2730 2730
Width / mm 570 570

Vertical derivation Bars Current rating @40°C _1250A _1250A


(Vertical up to the switching device) Material Copper Copper
Coating Bare Bare
Insulation YES YES
Switchgear Compartment
Switching Device Device Withdrawable CB Withdrawable CB
Type EasyPact EXE EasyPact EXE
Rated Breaking Capacity 25kA/3s 25kA/3s
Rated current at (40°C degree) _1250A _1250A

Circuit Breaker Spring Charging Motor 110 Vdc 110 Vdc


Closing Coil 110 Vdc 110 Vdc
Opening Coil (1st) 110 Vdc 110 Vdc
Opening Coil (2nd) NO NO
Undervoltage coil NO NO
Electromagnet for Circuit Breaker NO NO
Spring discharge option NO NO
MV C.B. Mechanical closing option NO NO

Contactor MV Fuse --- ---


Shunt closing release --- ---
Shunt opening release --- ---

Earth Switch Switch YES [Cable] YES [Cable]


Electromagnet for Earthing Switch YES 110 Vdc YES 110 Vdc

Voltage Transformer Qty / Manufacturer --- ---


Location --- ---
Type --- ---
Primary / Secondary Voltage --- ---
1. Secondary --- ---
2. Secondary --- ---
MV Fuse --- ---
Blown Fuse Contact --- ---
Ferrodamp --- ---

Current Transformer 1st SET Qty / Manufacturer 3/ALCE 3/ALCE


Type AB12 AB12
Primary / Secondary Current 300-600 / 5-5 A 300-600 / 5-5 A
1. Secondary Cl:0.5 FS5 15-30VA Cl:0.5 FS5 15-30VA
2. Secondary 5P20 15-30VA 5P20 15-30VA
3. Secondary --- ---
Ith 25kA/3s 25kA/3s

Core Balance CT Qty / Manufacturer --- ---


Delivered separately Type --- ---
Internal diameter --- ---

Cable Compartment MV Cable Entry Bottom By Cable Bottom By Cable


Core No 1C 3C
Maximum number of cables per phase 3 3
Customer cable cross section 1x(3x1x150mm2) 1x(1x3x150mm2)

Maximum Customer cable cross section 50-630mm² for single core, must be <70mm 50-240mm² for three core / must be < 90mm

Cable Box No Yes


Gland Plates Drilled(Standard) Drilled(Standard)

Voltage Presence Indicators (VPIS) YES YES

Surge Arrester NO NO

Heater Cable Compartment YES/150W YES/150W


LV Compartment (Optional) --- ---
CB Compartment (Optional) --- ---
Busbar Compartment (Optional) --- ---

Mimic Diagram Static adhesive MIMIC (Standard) YES YES


LV Compartment
LV Equipment Energy Meter NO NO
Energy Analyzer PM5110 PM5110
Analogue ammeter 72x72mm/ Scala 2*In /90 degree YES/1 +Sel. Sw YES/1 +Sel. Sw
Analogue voltmeter 72x72mm /90 degree NO NO
Thermostat for heater YES YES
Hygrostat for heater NO NO
Local - Remote Switch YES YES
VARLOGIC VPL12N NO NO
CSH30 YES NO
Load Shedding with 6 positions NO YES
CT Test Box / Entrelec YES / 2 YES / 2
VT Test Box / Entrelec NO NO
IEC Type Socket YES/inside LV compartment YES/inside LV compartment
Transducer NO NO
Signal Lamp (Single Led type) YES YES
MCB As necessary As necessary
LV Compartment
Protection Relays Protection Relay C86 P3U30-5AAA1BCAA
Communication Interface ACE850TP/ ethernet 2XRJ45
Analog Output Module MSA141 ---
Synchro check module MCS025 ---
I/O Board for Sepam Relay MES120 x 2 ---

Backup Protection Relay P121A00Z312EC1 NO


Communication protocol MODBUS NO

ATS NO NO