The Electrical Load Management System (ELMS) uses a substation automation system to prevent generator overloading. The system includes intelligent electronic devices, a communication network, and a SCADA master station to control the substation. At the site, the main automation component is a Siemens SICAM AK 1703 ACP unit which processes field data, communicates via fiber optic networks, and supports redundant configurations to manage electrical loads.
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
29 views

Elms

The Electrical Load Management System (ELMS) uses a substation automation system to prevent generator overloading. The system includes intelligent electronic devices, a communication network, and a SCADA master station to control the substation. At the site, the main automation component is a Siemens SICAM AK 1703 ACP unit which processes field data, communicates via fiber optic networks, and supports redundant configurations to manage electrical loads.
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 37

Electrical

Load
Management
System (ELMS)
Contents
• Requirement of ELMS
• Substation Automation System Architecture
• ELMS Hardware
• Main Automation Unit AK 1703 ACP
Requirement of ELMS

• ELMS is used to prevent overloading of generators in


operation and to run plant at optimum load.

• ELMS philosophy is power based and load shedding is


done by comparison of power capacities of running
generators and running power load.
Substation Automation System
• The ELMS at FFC MM is a Substation Automation System.
• Substation Automation System is defined as a system
managing, controlling and protecting an electrical power
system.
• Substation Automation System consist of following main
components:
– Electrical Protection
– Control
– Measurement
– Monitoring
– Data Communications
Substation Automation System
• Architecture:

– Different architectures exist today to implement components of


power system automation.
– Modern Automation System consist of three main divisions:
• Object Division
• Communication Network
• SCADA Master
Substation Automation System
• Architecture:
- Object Division
• It consists of intelligent electronic devices (IEDs), microprocessor
based relays and/or Remote terminal units(RTU)
• They receive analog inputs from current transformers, voltage
transformers, transducers, digital inputs from auxiliary contacts or other
field devices.
• They perform logical or mathematical calculations on inputs and
provide an output either to the SCADA master, other field instruments
or IEDs or to switchgear such as command for opening a circuit
breaker.
Substation Automation System
• Architecture:
– The Communication Network
• Communication Network is nervous system of automation.

• It ensures that raw data, processed information and commands are


relayed quickly, effectively and error free among the various field
instruments, IEDs and SCADA system.

• In modern system the physical medium is predominantly fiber optic


cables.
Substation Automation System
• Architecture:
– SCADA Master
• The SCADA (supervisory control and data acquisition) master station is
brain of the substation automation system which controls complete
system.
• The SCADA master receives data and information from the field,
decides what to do with it, stores it (directly or after some form of
processing) and issues requests and/or commands to remote devices.
• SCADA master consists simply of an advanced, reliable PC or
workstation and a SCADA software.
Substation Automation System

Basic Architecture of Power System Automation


ELMS Hardware
• ELMS is based on Siemens SICAM 1703 Automation Units.
• Central Processing Unit is SICAM AK 1703 ACP automation
unit.
• TM-1703-MIC are used for Process Level data or field data
i.e. voltage and current signals from PTs and CTs, digital
inputs and outputs.
– Digital inputs are used for breaker on/off and rack-in/rack-out status.
– Digital outputs are used for tripping and interlocking feeders.
– Analog inputs are used for currents and voltage inputs.
ELMS Hardware
• There are two fiber optic rings in the system:
– Consisting of TM-MIC-1703 modules installed in Substation #
1, 2, 3 and 4.
– Consisting of Siprotec and SEPAM protection relays installed
on MV Feeders in Substation # 1.

• Two SCADA stations are installed:


– SCADA Server Workstation in CCR
– SCADA Client Workstation in Substation # 1
Main Automation Component
AK 1703 ACP
Applications of AK 1703 ACP
• Automation with integrated telecontrol
functionality
• Medium to large data volumes Configurations

• Tele control Peripherals and/or TOOLBOX II


process control peripherals
– inside of the rack, or
IEC 60870-5-104

Front End Front End, Control

– extended (redundant) Gateway applications,


Turbine
controller

IEC 60870-5-104
• Designed for multihierarchical

IEC 101
Dial up

networks
– almost any topology Subnode,
Station-

– combined use of different


controller.. SAT 200
(redundant) RTU

communication IEC 60870-5-104 / IEC 61850


IEC 60870-5-101 IEC 60870-5-103 IEC 60870-5-103

• Several redundant configurations


supported RTU Integrated Bay Control Unit + Protection
© Siemens AG 2008
Page 2 Feb-09 Energy Automation Energy Sector
Mechanical Design of AK 1703 ACP
• Backplane with
– Node bus
– Peripheral bus
– Power supply bus PS
PS

-
Integrated interfaces for: -
56
CCC C CD AC D
56
D D D C 2x
2x
• power supply (2x) PPP
- - -
P P I I PO
- - - - - -
I I OP
- - - -
222 222222 2222

• external peripheral bus (Ax-Bus) 000


PS 1 1 1
- 077
001302
110011
1120
1 1 1 1 PS
770070 0007 -

• redundancy control 56
2x
56
2x

• Configuration of
– 2 / 4 Power supply boards PS-56xx
– 9 /17 AK 1703
Double euro format boards
Mechanical Design – Small Rack (CM-2832)
•44 units width
•Suitable for
– rear panel installation
•Room / interfaces for:
– 9 Double euro format boards
– 2 Power supplies PS 562x
(2 interfaces integrated )
– 9 Interfaces for external
Ax 1703 peripheral bus (integrated)
– 1 Interface for redundancy control
(integrated)
– 2 Interfaces for redundancy synchronization
(High Speed Link interfaces, integrated)
Mechanical Design – Large Rack (CM-2835)
• 19“ width (84 units)
• Suitable for
– rear panel installation (optional)
– (swing) frame installation

• Room / interfaces for:


– 17 Double euroformat boards
– 4 Power supplies PS 562x
(2 interfaces integrated )
– 17 Interfaces for external
Ax 1703 peripheral bus (integrated)
– 1 Interface for redundancy control
(integrated)
– 6 Interfaces for redundancy synchronization
(High Speed Link interfaces, integrated)
Basic Architecture of AK 1703 ACP
1 Master control element (CP-2010)

PS
Up to 16 processing and PS
-
-
communication elements (CP-2017) 56
56
CC C D D C 2x
2x
PP P I I P
- - - - - -
22 2 22 2
Up to 2 SIM (serial interface modul) 00
PS 1 1
0 11 0
1 1 1 PS
1
on each CP-2017, - 07 7 00 7 -
56 56
1 SIM on CP-2010 2x 2x
1 SIM has
- 2 serial communication interfaces, or
- 1 ethernet interface, or
- 1 ethernet and 1 serial interface, or
- 1 Profibus interface (DP-Master)

=> up to 66 serial communication /


Fieldbus / LAN / WAN possible

Up to 16 peripheral elements inside of the rack


Master Control Element CP-2010
System Functions, Communication & Process Peripherals
• Central element, coordinating all system services
• Central hub function for all connected basic system elements
• Time management & central clock of the automation unit
• Setting and keeping the own clock's time with a resolution of 10ms
• Synchronization via serial communication
• Redundancy
• Voting and change-over for redundant processing and communication elements of the own
automation unit by an external SCA-RS redundancy switch
• Storing firmware and parameters on a Flash Card for Plug&Play module exchange
• Automatic data flow routing & priority based data transmission (priority control)
• Open-/closed-loop control function for the execution of freely definable user programs which are
created with CAEX plus according to IEC 61131-3, for example using function diagram technology
• Engineering is done using SAT TOOLBOX II, including OPM II.
• Function and failure indication via LEDs
Processing and Communication Element CP-2012
• Time management: keeping the time with a resolution of 10ms
• Communication via installable protocol elements to any superior or subordinate automation unit
• Own circular buffer and process image for each connected station (data keeping)
• Redundant communication routes
• Transmission of spontaneous information objects from and to
peripheral elements, via the serial Ax 1703 peripheral bus
• Redundant open-/closed-loop control functions
• Loadable without service interruption
• Autonomy: function maintained even in case of master control element failure
• Automatic data flow routing & priority based data transmission (priority control)
Component List of AK 1703 ACP
Racks
CM-2835 AK 1703 ACP Board Rack 17 Board Slot (19" width)
CM-2832 AK 1703 ACP Board Rack 9 Board Slots
Power Supply
PS-5620 Power Supply 24-60VDC/80W
PS-5622 Power Supply 110-220VDC, 230VAC/80W
Master Control Element plus Accessories
CP-2010 Central Processor (Master Control Element)
1 SIM can be equipped optionally
CM-2837 Connector for Communication & System I/O
Processing and Communication elements + Accessories
CP-2012 Communication and Processing
Up to 2 SIMs can be equipped optionally
CM-2838 Connector for Communication & System I/O
Serial Interface modules (SIM)
SM-2551 Serial Interface Processor 2 Serial Interfaces
SM-2556 Network-Interf.Ethernet 10/100TX
SM-2556+ SM-0551 Network-Interf.Ethernet 10/100TX and 1 Serial Interface
Peripheral Elements AK 1703 internal
Binary I/Os
DI-2100 Binary Input 8x8, 24-60VDC, resolution 10ms
DI-2110 Binary Input 8x8, 24-60VDC, resolution 1ms
DI-2111 Binary Input 8x8, 110/220VDC, resolution 1ms
DO-2201 Binary Output Transistor 40x, 24-60VDC
DO-2210 Checked Command Ouptut ,
64x1- or 1,5- pole, 32x2-pole 24-60VDC
DO-2211 Checked Command Ouptut ,
64x1- or 1,5- pole, 32x2-pole 24-125VDC
Analog I/Os, Combinations
AI-2300 Analog Input 16x ±20mA,
and 4x 2 optional analog Inputs/Outputs*)
MX-2400 Binary Input 4x8, 24-60VDC, resolution 1ms
Command output 16x 24-60VDC
Binary Output 2x 24-60VDC
Analog Input 2x ±20mA,
and 1x 2 optional analog Inputs/Outputs*) Process interface
with
*) SM-0570 Analog Input (2x±20mA,±10V),
pre manufactured
SM-0571 Analog Input (2x Pt100),
SM-0572 Analog Output (2x ±20 mA), cables CM-2890
SM-0574 Counter Input, buffered (2x24-60VDC)
Peripheral Elements AK 1703 external
Binary I/Os
DI-2100 Binary Input 8x8, 24-60VDC, resolution 10ms
DI-2110 Binary Input 8x8, 24-60VDC, resolution 1ms
DI-2111 Binary Input 8x8, 110/220VDC, resolution 1ms
DO-2201 Binary Output Transistor 40x, 24-60VDC
DO-2210 Checked Command Ouptut ,
64x1- or 1,5- pole, 32x2-pole 24-60VDC
DO-2211 Checked Command Ouptut ,
TP Patch cable
64x1- or 1,5- pole, 32x2-pole 24-125VDC max. 3 m

Analog I/Os, Combinations


AI-2300 Analog Input 16x ±20mA,
and 4x 2 optional analog Inputs/Outputs*)
MX-2400 Binary Input 4x8, 24-60VDC, resolution 1ms
Command output 16x 24-60VDC
Binary Output 2x 24-60VDC
Analog Input 2x ±20mA,
and 1x 2 optional analog Inputs/Outputs*)

*) SM-0570 Analog Input (2x±20mA,±10V), Board Rack Extension: CM-2833


SM-0571 Analog Input (2x Pt100), Same mechanical design, power supply,
SM-0572 Analog Output (2x ±20 mA),
process connection like AK 1703 ACP board rack
SM-0574 Counter Input, buffered (2x24-60VDC)
Peripheral Element TM 1703 ACP Available I/O Modules
Power supply
PS-6630 24-60VDC EMC+
1-2
PS-6632 110-220VDC EMC+
Peripheral Control Modules
PE-6400 Ax-PE Bus coupler (electrical, USB, 3m) 1
PE-6411 Ax-PE Bus coupler (1x optical PCF, 200m)
Binary I/O-modules
DI-6100 Binary Input 2x8, 24-60VDC, resolution 10ms
DI-6101 Binary Input 2x8, 110/220VDC, resolution 10ms
DI-6102 Binary Input 2x8, 24-60VDC, resolution 1ms
DI-6103 Binary Input 2x8, 110/220VDC, resolution 1ms
DI-6104 Binary Input 2x8, 220VDC, resolution 10ms
DO-6200 Binary Output Transistor 2x8, 24-60VDC
DO-6212 Binary Output Relays 8x 24-220VDC/230VAC
DO-6220 Command Output Basic Module 24-125VDC 1-8
DO-6221 Command Output Basic Module with measure 24-125VDC
DO-6230 Command Output Relay Module Relays 2x8 24-125VDC
Analog I/O-modules
AI-6300 Analog Input 2x2 ±20mA/±10V
AI-6307 Analog Input 2x2 ± 5mA
AI-6310 Analog Input 2x2 Pt100/Ni100
AO-6380 Analog Output 4x ±20mA/±10mA/±10V
TE-6420 Speed Measurement 2x2 24VDC/5VDC/NAMUR
TE-6450 Position Acquisition 2x2 SSI/RS422
Peripheral Element TM 1703 ACP
Power Supply
PS-6632 + AI-6300
4 VT-Inputs

Output Relay for


Synchrocheck/ 3 CT-Inputs
Synchronizing

Ax-Bus interface (optical & electrical)


no additional Ax Bus coupler necessary
Peripheral Elements TM 1703 external
Electrical

TP patch cable
max. 3 m
Ax 1703-businterface
electrical
CM-0843

USB cable,
max. 3m
Peripheral Elements TM 1703 external
Electrical & Optical

TP patch cable
max. 3 m

Ax 1703-bus interface
optical CM-0843

CM-0842

fiber optic, PCF,


max. 200m

USB cable,
max. 3m
ELMS System Inputs
• Digital Inputs:
1. Circuit Breaker Open/Close
2. Rack In/Out
3. Earthing Isolator Open/Close
4. Status (Running/Stop)

• Analog Inputs:
1. Active Power
2. Current
3. Temperature (for GT-703)
ELMS Software
• HMI of ELMS is developed in Siemens SICAM 230.
• HMI provides following capabilities:
– The load selection lists
– Event List
– Status of generators, motors, bus-ties and transformers
– Trends
– Status of ELMS equipment
Thank You