SINGLE PHASE TRANSFORMERS - Notes
SINGLE PHASE TRANSFORMERS - Notes
What is a Transformer?
A transformer is a static piece of equipment used either for raising or lowering
the voltage of an AC supply with a corresponding decrease or increase in
current.
Fig.3-1
Principle of Operation
A transformer in its simplest form will consist of a rectangular laminated
magnetic structure on which two coils of different number of turns are wound as
shown in Figure 3.2a.
Fig.3-2a
1
Fig.3-2b
Depending upon the number of turns of the primary (N 1) and secondary (N2),
an alternating emf (E2) is induced in the secondary. This induced emf (E2) in
the secondary causes a secondary current I2. Consequently, terminal voltage V2
will appear across the load. If V2 > V1, it is called a step up-transformer. On
the other hand, if V2 < V1, it is called a step-down transformer.
When an alternating voltage V1 is applied to the primary, an alternating flux Φ
is set up in the core. This alternating flux links both the windings and induces
emfs E1 and E2 in them according to Faraday’s laws of electromagnetic
induction. The emf E1 is termed as primary emf and emf E2 is termed as
Secondary emf.
2
The following points may be noted carefully:
(i) The transformer action is based on the laws of electromagnetic
induction.
(ii) There is no electrical connection between the primary and secondary.
(iii) There is no change in frequency i.e., output power has the same
frequency as the input power.
Construction
We usually design a power transformer so that it approaches the characteristics
of an ideal transformer. To achieve this, following design features are
incorporated:
(i) The core is made of silicon steel which has low hysteresis loss and
high permeability. Further, core is laminated in order to reduce eddy
current loss. These features considerably reduce the iron losses and the
no-load current.
(ii) Instead of placing primary on one limb and secondary on the other, it
is a usual practice to wind one-half of each winding on one limb. This
ensures tight coupling between the two windings. Consequently,
leakage flux is considerably reduced.
(iii) The winding resistances are minimized to reduce Copper loss and
resulting rise in temperature and to ensure high efficiency.
3
Transformers are of two types: (i) core-type transformer (see Fig.3-3) and
(ii) shell-type transformer (see Fig.3-4).
Fig.3-3
Fig.3-4
4
Comparison of Core and Shell Type Transforms
The winding encircles the core. The core encircles most part of the windin
It has single magnetic circuit It has double magnetic circuit
The core has two limbs The core has three limbs
The multilayer disc or sandwich type
The cylindrical coils are used. coils are used.
The winding are uniformly distributed on two The natural cooling does not exist as the
limbs hence natural cooling is effective windings are surrounded by the core.
Preferred for low voltage transformers. Preferred for high voltage transformers.
As, shown in the fig., the flux rises sinusoidally to its maximum value Φm from 0. It
reaches to the maximum value in one quarter of the cycle i.e in T/4 sec (where, T is
time period of the sin wave of the supply = 1/f).
Therefore,
/
average rate of change of flux = Φm (T/4) = Φm (1/4f)/
Therefore,
average rate of change of flux = 4f Φm ....... (Wb/s).
Now,
Induced emf per turn = rate of change of flux per turn
5
Therefore, average emf per turn = 4f Φm ..........(Volts).
Now, we know, Form factor = RMS value / average value
Therefore, RMS value of emf per turn = Form factor X average emf per turn.
As, the flux Φ varies sinusoidally, form factor of a sine wave is 1.11
RMS value of induced emf in whole primary winding (E1) = RMS value of emf per
turn X Number of turns in primary winding
E1 = 4.44f N1 Φm ............................. eq 1
This is called the emf equation of transformer, which shows, emf / number of turns is
same for both primary and secondary winding.
= =K
Where, K = constant
This constant K is known as voltage transformation ratio.
If N2 > N1, i.e. K > 1, then the transformer is called step-up transformer.
If N2 < N1, i.e. K < 1, then the transformer is called step-down transformer
6
Concept of Ideal Transformer
NOTE:
For an ideal transformer, the primary applied voltage V1 is same as
the primary induced emf E1 as there are no voltage drops.
7
For ideal transformer:
Volt-Ampere Rating
Transformer rating is specified as the product of voltage and current and called
VA rating.
The full load primaty and secondary currents which indicate the safe maximum
values of currents which transformer windings can carry can be given as:
Consider an ideal transformer in Fig. 3-5. For no load I2 =0. I1 is just necessary
to produce flux in the core, which is called magnetising current
denoted as Im. Im is very small and lags V 1
by 900 as the winding is purely inductive.
8
According to Lenz's law, the induced e.m.f opposes the cause producing it
which is supply voltage V1. Hence E1 and E2 are in antiphase with V1 but equal
in magnitude and E1 and E2 are in phase.
Fig.3-5
The secondary emf E2 will cause a current I2 to flow through the load:
9
The Phasor diagram for the ideal transformer on load is shown in Figure (ii)
above.
The secondary current I2 lags behind V2 (or E2) by Φ . It causes a primary
10
Practical Transformer
A practical transformer differs from the ideal transformer in many respects. The
practical transformer has (i) iron losses (ii) winding resistances and (iii)
magnetic leakage, giving rise to leakage reactance.
(i) Iron losses. Since the iron core is subjected to alternating flux, there
occurs eddy current and hysteresis loss in it.
11
Practical Transformer on No Load
The primary will draw a small current I0 to supply (i) the iron losses and (ii) a
very small amount of copper loss in the primary. Hence the primary no load
current I0 is not 90° behind the applied voltage V1 but lags it by an angle Φ0 <
90° as shown in the phasor diagram.
The no-load primary current I0 can be resolved into two rectangular
components:
12
ii)
Fig. above shows a practical transformer with the assumption that resistances
and leakage reactances of the windings are negligible. With this assumption, V 2
= E2 and V1 = E1.
13
Let us take the usual case of inductive load which causes the I2 to lag V2 by Φ2.
14
Phasor Diagram:
Note that counter emf that opposes the applied voltage
V1 is -E1. Therefore, if we add I1R1 (in phase with I1)
and I1 X1 (90° ahead of I1) to -E1, we get the applied
primary voltage V1. The phasor E2 represents the
induced emf in the secondary by the mutual flux. The
secondary terminal voltage V2 will be what is left over
after subtracting I2R2 and I2X2 from E2.
15
Modelling and Equivalent Circuits of Single Phase Transformers
The term equivalent circuit of a transformer means the combination of fixed and
variable resistances and reactances, which exactly simulates performance and
working of the transformer.
Impedance Ratio
16
Shifting Impedances in a Transformer
NOTE:
We can transfer the parameters from one winding to the other. Thus:
NOTE:
17
A- Referred to primary
18
B- Referred to secondary
V2 = KV1
19
What the Importance of Shifting Impedances?
If we shift all the impedances from one winding to the other, the transformer is
eliminated and we get an equivalent electrical circuit. Various voltages and
currents can be readily obtained by solving this electrical circuit.
The equivalent circuit for the transformer can be represented as shown in the
figure.
Where:
Ro: represents the core losses (hysteresis and eddy current losses)
20
Iw: active current (required to supply the core losses)
■ NOTE2: The equivalent circuit has created two normal electrical circuits
separated only by an ideal transformer whose function is to change
values according to the equation:
21
Simplified Equivalent Circuit of a Loaded Transformer
If all the secondary quantities are referred to the primary, we can get the
simplified equivalent circuit of the transformer referred to the primary as shown
below
22
From the above circuits:
where
► The referred value of load voltage V'2 is chosen as the reference phasor.
► I'2 R01 is in phase with I'2 and the voltage drop I'2 X01, leads I'2 by 90°.
23
If all the primary quantities are referred to the secondary, we can get the
simplified equivalent circuit of the transformer referred to the secondary as
shown below
Where
24
Hence the phasor diagram can be obtained as:
► I2 R02 is in phase with I2 and the voltage drop I2 X02, leads I2 by 90°.
► I'W is in phase with V'1 while I'm lags behind V'1 by 90°.
25
Approximate Equivalent Circuit of a Loaded Transformer
The no-load current I0 in a transformer is only 1-3% of the rated primary current
and may be neglected without any serious error. The transformer can then be
shown as in the figure below:
If all the secondary quantities are referred to the primary, we can get the
approximate equivalent circuit of the transformer referred to the primary as
shown below
If all the primary quantities are referred to the secondary, we can get the
approximate equivalent circuit of the transformer referred to the secondary as
shown below
26
Approximate Voltage Drop in a Transformer
At no-load, the secondary voltage is K V1. When a load having a lagging p.f.
cos 2 is applied, the secondary carries a current I2 and voltage drops occur in
(R2 + K2R1) and (X2 + K2 X1). Consequently, the secondary voltage falls from
KV1 to V2.
Hence, we have,
It is clear from the phasor diagram below that drop in secondary voltage is AC
= I2 Z02.
27
Approximate drop in secondary voltage
Note: If the circuit is referred to primary, then it can be easily established that
28
Testing, Efficiency, and Voltage Regulation
where
The +ve sign is for lagging p.f. and -ve sign for leading p.f.
NOTE: It may be noted that % voltage regulation of the transformer will be the
same whether primary or secondary side is considered.
Losses in a Transformer
NOTE: The above losses appear in the form of heat and produce (i) an increase
in temperature and (ii) a drop in efficiency.
29
A- Core or Iron losses (Pi)
These consist of hysteresis and eddy current losses and occur in the transformer
core due to the alternating flux. These can be determined by open-circuit test
(see next sections).
► Supply frequency f.
NOTE: The hysteresis loss can be minimized by using steel of high silicon
content whereas eddy current loss can be reduced by using core of thin
laminations.
30
B- Copper losses (PC)
These losses occur in both the primary and secondary windings due to their
ohmic resistance. These can be determined by short-circuit test
Efficiency of a Transformer
In practice, open-circuit and short-circuit tests are carried out to find the
efficiency,
31
Condition for Maximum Efficiency
For a load of given pf, efficiency depends upon load current I2. Hence, the
efficiency to be maximum the denominator should be minimum i.e.
32
NOTE: In a transformer, iron losses are constant whereas copper losses are
variable. In order to obtain maximum efficiency, the load current should be
such that total Cu losses become equal to iron losses.
or
⟹Output kVA corresponding to maximum efficiency:
All-Day Efficiency
The ratio of output in kWh to the input in kWh of a transformer over a 24-hour
period is known as all-day efficiency i.e.:
33
Transformer Tests
Open-Circuit Test
In this test (see Figure below), the rated voltage is applied to the primary
(usually low-voltage winding) while the secondary is left open-circuited.
As the normal rated voltage is applied to the primary, therefore, normal iron
losses will occur in the transformer core.
34
⟹
In this test (see Figure below), the secondary (usually low-voltage winding) is
short-circuited by a thick conductor and variable low voltage is applied to the
primary.
The low input voltage is gradually raised till at voltage V SC, full-load current I1
flows in the primary. Then I2 in the secondary also has full-load value since
I1/I2 = N2/N1. Under such conditions, the copper loss in the windings is the
same as that on full load.
35
where R01 is the total resistance of transformer referred to primary
Short-circuit pf
36