Sound Report AHU&PAU
Sound Report AHU&PAU
Octave: 63 125 250 500 1000 2000 4000 8000 Total Unit
Fan sound power level IN: SYQ-355C
Lw1 92 86 81 93 84 83 79 71 96.7 dB
LwA1 66 70 72 89 84 84 80 70 91.6 dB(A)
Fan sound power level OUT: SYQ-355C
Lw1 92 86 81 93 84 83 79 71 96.7 dB
LwA1 66 70 72 89 84 84 80 70 91.6 dB(A)
Inlet:sound power level in the inlet cross section.
Lw3 90.8 84.3 76.8 87.8 77.3 74.8 70.8 58.8 93.5 dB
LwA3 64.6 68.2 68.2 84.6 77.3 76 71.8 57.7 86.2 dB(A)
Outlet:sound power level in outlet cross section.
Lw4 92 86 81 93 84 83 79 71 96.7 dB
LwA4 65.8 69.9 72.4 89.8 84 84.2 80 69.9 92.1 dB(A)
Unit: sound power level emitted by the unit wall with ducted inlet and ducted outlet in according with BS EN 13053.
Lp2 65.7 53.8 49.9 60.9 52.8 47.5 28.1 15.1 67.4 dB
LpA2 39.5 37.7 41.3 57.7 52.8 48.7 29.1 14 59.5 dB(A)
Unit: sound pressure level emitted by the unit wall under free field condition in according with GB/T 9068, on a block-shaped
measurement surface that envelops the unit casing.
Octave: 63 125 250 500 1000 2000 4000 8000 Total Unit
Fan sound power level IN: SYD-355R
Lw1 89 95 86 86 85 82 80 76 97.3 dB
LwA1 63 79 77 83 85 83 81 75 90 dB(A)
Fan sound power level OUT: SYD-355R
Lw1 89 95 86 86 85 82 80 76 97.3 dB
LwA1 63 79 77 83 85 83 81 75 90 dB(A)
Inlet:sound power level in the inlet cross section.
Lw3 88.3 93.3 82.8 80.8 78.8 74.8 72.8 68.8 95.1 dB
LwA3 62.1 77.2 74.2 77.6 78.8 76 73.8 67.7 84.5 dB(A)
Outlet:sound power level in outlet cross section.
Lw4 89 95 86 86 85 82 80 76 97.3 dB
LwA4 62.8 78.9 77.4 82.8 85 83.2 81 74.9 90 dB(A)
Unit: sound power level emitted by the unit wall with ducted inlet and ducted outlet in according with BS EN 13053.
Lp2 60.5 62.7 54.1 53.8 53.5 46.2 28.8 19.4 65.7 dB
LpA2 34.3 46.6 45.5 50.6 53.5 47.4 29.8 18.3 56.8 dB(A)
Unit: sound pressure level emitted by the unit wall under free field condition in according with GB/T 9068, on a block-shaped
measurement surface that envelops the unit casing.
Lp2 72.2 78.2 69.2 69.2 68.2 65.2 63.2 59.2 80.5 dB
LpA2 46 62.1 60.6 66 68.2 66.4 64.2 58.1 73.2 dB(A)
Note:
1.It should be particularly noted that the noise levels outside the unit are significantly influenced by the installation location and acoustic
of the environment (for example, size, absorption capacity, and reflection of the space).
2.Furthermore, other noise sources(other units, fans, traffic noise,…) can add to the noise levels indicated above.
3.As for RU noise in EUROVENT certification, the "Lw3, Lw4, LwA2" parameters above represent "Octave Band In-duct INTLET in dB", "Octave Band
In-duct OUTLET in dB" and "AIRBORNE Sound Power - in dB(A)" respectively.
Octave: 63 125 250 500 1000 2000 4000 8000 Total Unit
Fan sound power level IN: SYD-500R
Lw1 90 91 86 89 83 82 80 75 96 dB
LwA1 63 75 77 86 83 83 81 74 90.1 dB(A)
Fan sound power level OUT: SYD-500R
Lw1 90 91 86 89 83 82 80 75 96 dB
LwA1 63 75 77 86 83 83 81 74 90.1 dB(A)
Inlet:sound power level in the inlet cross section.
Lw3 89.3 89.3 82.8 83.8 76.8 74.8 72.8 67.8 93.5 dB
LwA3 63.1 73.2 74.2 80.6 76.8 76 73.8 66.7 84.5 dB(A)
Outlet:sound power level in outlet cross section.
Lw4 90 91 86 89 83 82 80 75 96 dB
LwA4 63.8 74.9 77.4 85.8 83 83.2 81 73.9 90.1 dB(A)
Unit: sound power level emitted by the unit wall with ducted inlet and ducted outlet in according with BS EN 13053.
Lp2 72.3 73.3 68.3 71.3 65.3 64.3 62.3 57.3 78.3 dB
LpA2 46.1 57.2 59.7 68.1 65.3 65.5 63.3 56.2 72.4 dB(A)
Note:
1.It should be particularly noted that the noise levels outside the unit are significantly influenced by the installation location and acoustic
of the environment (for example, size, absorption capacity, and reflection of the space).
2.Furthermore, other noise sources(other units, fans, traffic noise,…) can add to the noise levels indicated above.
3.As for RU noise in EUROVENT certification, the "Lw3, Lw4, LwA2" parameters above represent "Octave Band In-duct INTLET in dB", "Octave Band
In-duct OUTLET in dB" and "AIRBORNE Sound Power - in dB(A)" respectively.
Octave: 63 125 250 500 1000 2000 4000 8000 Total Unit
Fan sound power level IN: SYD-450R
Lw1 86 87 82 86 80 79 77 72 92.3 dB
LwA1 60 71 74 83 80 80 78 71 87.1 dB(A)
Fan sound power level OUT: SYD-450R
Lw1 86 87 82 86 80 79 77 72 92.3 dB
LwA1 60 71 74 83 80 80 78 71 87.1 dB(A)
Inlet:sound power level in the inlet cross section.
Lw3 85.3 85.3 78.8 80.8 73.8 71.8 69.8 64.8 89.7 dB
LwA3 59.1 69.2 70.2 77.6 73.8 73 70.8 63.7 81.3 dB(A)
Outlet:sound power level in outlet cross section.
Lw4 86 87 82 86 80 79 77 72 92.3 dB
LwA4 59.8 70.9 73.4 82.8 80 80.2 78 70.9 87 dB(A)
Unit: sound power level emitted by the unit wall with ducted inlet and ducted outlet in according with BS EN 13053.
Lp2 68.8 69.8 64.8 68.8 62.8 61.8 59.8 54.8 75.1 dB
LpA2 42.6 53.7 56.2 65.6 62.8 63 60.8 53.7 69.8 dB(A)
Note:
1.It should be particularly noted that the noise levels outside the unit are significantly influenced by the installation location and acoustic
of the environment (for example, size, absorption capacity, and reflection of the space).
2.Furthermore, other noise sources(other units, fans, traffic noise,…) can add to the noise levels indicated above.
3.As for RU noise in EUROVENT certification, the "Lw3, Lw4, LwA2" parameters above represent "Octave Band In-duct INTLET in dB", "Octave Band
In-duct OUTLET in dB" and "AIRBORNE Sound Power - in dB(A)" respectively.
Octave: 63 125 250 500 1000 2000 4000 8000 Total Unit
Fan sound power level IN: SYD-280R
Lw1 96 93 90 84 83 81 79 75 98.8 dB
LwA1 70 77 82 81 83 82 80 74 89.2 dB(A)
Fan sound power level OUT: SYD-280R
Lw1 96 93 90 84 83 81 79 75 98.8 dB
LwA1 70 77 82 81 83 82 80 74 89.2 dB(A)
Inlet:sound power level in the inlet cross section.
Lw3 94.3 90.8 83.8 76.8 73.8 69.8 67.8 55.8 96.3 dB
LwA3 68.1 74.7 75.2 73.6 73.8 71 68.8 54.7 81.3 dB(A)
Outlet:sound power level in outlet cross section.
Lw4 96 93 90 84 83 81 79 75 98.8 dB
LwA4 69.8 76.9 81.4 80.8 83 82.2 80 73.9 89.1 dB(A)
Unit: sound power level emitted by the unit wall with ducted inlet and ducted outlet in according with BS EN 13053.
Lp2 77.5 74.5 71.5 65.5 64.5 62.5 60.5 56.5 80.3 dB
LpA2 51.3 58.4 62.9 62.3 64.5 63.7 61.5 55.4 70.6 dB(A)
Note:
1.It should be particularly noted that the noise levels outside the unit are significantly influenced by the installation location and acoustic
of the environment (for example, size, absorption capacity, and reflection of the space).
2.Furthermore, other noise sources(other units, fans, traffic noise,…) can add to the noise levels indicated above.
3.As for RU noise in EUROVENT certification, the "Lw3, Lw4, LwA2" parameters above represent "Octave Band In-duct INTLET in dB", "Octave Band
In-duct OUTLET in dB" and "AIRBORNE Sound Power - in dB(A)" respectively.
Octave: 63 125 250 500 1000 2000 4000 8000 Total Unit
Fan sound power level IN: SYD-225L
Lw1 96 87 85 80 80 78 77 75 97.1 dB
LwA1 70 71 76 76 80 79 78 73 85.6 dB(A)
Fan sound power level OUT: SYD-225L
Lw1 96 87 85 80 80 78 77 75 97.1 dB
LwA1 70 71 76 76 80 79 78 73 85.6 dB(A)
Inlet:sound power level in the inlet cross section.
Lw3 95.5 86.5 83 78 77.5 75 74 68 96.4 dB
LwA3 69.3 70.4 74.4 74.8 77.5 76.2 75 66.9 83.3 dB(A)
Outlet:sound power level in outlet cross section.
Lw4 96 87 85 80 80 78 77 75 97.1 dB
LwA4 69.8 70.9 76.4 76.8 80 79.2 78 73.9 85.8 dB(A)
Unit: sound power level emitted by the unit wall with ducted inlet and ducted outlet in according with BS EN 13053.
Lw2 83.4 67.2 68.8 62.3 63.3 57.3 40.9 35.5 83.7 dB
LwA2 57.2 51.1 60.2 59.1 63.3 58.5 41.9 34.4 67.3 dB(A)
Unit: sound pressure level emitted by the unit wall under free field condition in according with EN ISO 3744, on a block-shaped
measurement surface that envelops the unit casing.
Lp2 77.5 68.5 66.5 61.5 61.5 59.5 58.5 56.5 78.6 dB
LpA2 51.3 52.4 57.9 58.3 61.5 60.7 59.5 55.4 67.3 dB(A)
Note:
1.It should be particularly noted that the noise levels outside the unit are significantly influenced by the installation location and acoustic
of the environment (for example, size, absorption capacity, and reflection of the space).
2.Furthermore, other noise sources(other units, fans, traffic noise,…) can add to the noise levels indicated above.
3.As for RU noise in EUROVENT certification, the "Lw3, Lw4, LwA2" parameters above represent "Octave Band In-duct INTLET in dB", "Octave Band
In-duct OUTLET in dB" and "AIRBORNE Sound Power - in dB(A)" respectively.
Octave: 63 125 250 500 1000 2000 4000 8000 Total Unit
Fan sound power level IN: SYQ-450C
Lw1 89 87 85 98 90 88 82 75 99.9 dB
LwA1 63 71 77 94 90 89 83 74 96.6 dB(A)
Fan sound power level OUT: SYQ-450C
Lw1 89 87 85 98 90 88 82 75 99.9 dB
LwA1 63 71 77 94 90 89 83 74 96.6 dB(A)
Inlet:sound power level in the inlet cross section.
Lw3 88.3 85.3 81.8 92.8 83.8 80.8 74.8 67.8 95.4 dB
LwA3 62.1 69.2 73.2 89.6 83.8 82 75.8 66.7 91.4 dB(A)
Outlet:sound power level in outlet cross section.
Lw4 89 87 85 98 90 88 82 75 99.9 dB
LwA4 62.8 70.9 76.4 94.8 90 89.2 83 73.9 97.1 dB(A)
Unit: sound power level emitted by the unit wall with ducted inlet and ducted outlet in according with BS EN 13053.
Lp2 71.7 69.7 67.7 80.7 72.7 70.7 64.7 57.7 82.6 dB
LpA2 45.5 53.6 59.1 77.5 72.7 71.9 65.7 56.6 79.8 dB(A)
Note:
1.It should be particularly noted that the noise levels outside the unit are significantly influenced by the installation location and acoustic
of the environment (for example, size, absorption capacity, and reflection of the space).
2.Furthermore, other noise sources(other units, fans, traffic noise,…) can add to the noise levels indicated above.
3.As for RU noise in EUROVENT certification, the "Lw3, Lw4, LwA2" parameters above represent "Octave Band In-duct INTLET in dB", "Octave Band
In-duct OUTLET in dB" and "AIRBORNE Sound Power - in dB(A)" respectively.
Octave: 63 125 250 500 1000 2000 4000 8000 Total Unit
Fan sound power level IN: SYD-355K
Lw1 93 96 86 85 83 81 79 74 98.5 dB
LwA1 67 80 77 82 83 82 80 73 89 dB(A)
Fan sound power level OUT: SYD-355K
Lw1 93 96 86 85 83 81 79 74 98.5 dB
LwA1 67 80 77 82 83 82 80 73 89 dB(A)
Inlet:sound power level in the inlet cross section.
Lw3 92.3 94.3 82.8 79.8 76.8 73.8 71.8 66.8 96.8 dB
LwA3 66.1 78.2 74.2 76.6 76.8 75 72.8 65.7 83.9 dB(A)
Outlet:sound power level in outlet cross section.
Lw4 93 96 86 85 83 81 79 74 98.5 dB
LwA4 66.8 79.9 77.4 81.8 83 82.2 80 72.9 89 dB(A)
Unit: sound power level emitted by the unit wall with ducted inlet and ducted outlet in according with BS EN 13053.
Lp2 64.6 63.8 54.2 52.9 51.6 45.3 27.9 17.5 67.7 dB
LpA2 38.4 47.7 45.6 49.7 51.6 46.5 28.9 16.4 55.9 dB(A)
Unit: sound pressure level emitted by the unit wall under free field condition in according with GB/T 9068, on a block-shaped
measurement surface that envelops the unit casing.
Lp2 76.3 79.3 69.3 68.3 66.3 64.3 62.3 57.3 81.8 dB
LpA2 50.1 63.2 60.7 65.1 66.3 65.5 63.3 56.2 72.3 dB(A)
Note:
1.It should be particularly noted that the noise levels outside the unit are significantly influenced by the installation location and acoustic
of the environment (for example, size, absorption capacity, and reflection of the space).
2.Furthermore, other noise sources(other units, fans, traffic noise,…) can add to the noise levels indicated above.
3.As for RU noise in EUROVENT certification, the "Lw3, Lw4, LwA2" parameters above represent "Octave Band In-duct INTLET in dB", "Octave Band
In-duct OUTLET in dB" and "AIRBORNE Sound Power - in dB(A)" respectively.
Octave: 63 125 250 500 1000 2000 4000 8000 Total Unit
Fan sound power level IN: SYQ-400A
Lw1 90 89 87 99 91 89 84 77 101 dB
LwA1 64 73 79 96 91 91 85 76 98.4 dB(A)
Fan sound power level OUT: SYQ-400A
Lw1 90 89 87 99 91 89 84 77 101 dB
LwA1 64 73 79 96 91 91 85 76 98.4 dB(A)
Inlet:sound power level in the inlet cross section.
Lw3 89.3 87.3 83.8 93.8 84.8 81.8 76.8 69.8 96.6 dB
LwA3 63.1 71.2 75.2 90.6 84.8 83 77.8 68.7 92.5 dB(A)
Outlet:sound power level in outlet cross section.
Lw4 90 89 87 99 91 89 84 77 101 dB
LwA4 63.8 72.9 78.4 95.8 91 90.2 85 75.9 98.2 dB(A)
Unit: sound power level emitted by the unit wall with ducted inlet and ducted outlet in according with BS EN 13053.
Lp2 72.8 71.8 69.8 81.8 73.8 71.8 66.8 59.8 83.8 dB
LpA2 46.6 55.7 61.2 78.6 73.8 73 67.8 58.7 81 dB(A)
Note:
1.It should be particularly noted that the noise levels outside the unit are significantly influenced by the installation location and acoustic
of the environment (for example, size, absorption capacity, and reflection of the space).
2.Furthermore, other noise sources(other units, fans, traffic noise,…) can add to the noise levels indicated above.
3.As for RU noise in EUROVENT certification, the "Lw3, Lw4, LwA2" parameters above represent "Octave Band In-duct INTLET in dB", "Octave Band
In-duct OUTLET in dB" and "AIRBORNE Sound Power - in dB(A)" respectively.
Octave: 63 125 250 500 1000 2000 4000 8000 Total Unit
Fan sound power level IN: SYD-355R
Lw1 88 93 84 84 83 80 78 74 95.5 dB
LwA1 61 77 76 81 83 81 79 73 88.1 dB(A)
Fan sound power level OUT: SYD-355R
Lw1 88 93 84 84 83 80 78 74 95.5 dB
LwA1 61 77 76 81 83 81 79 73 88.1 dB(A)
Inlet:sound power level in the inlet cross section.
Lw3 87.3 91.3 80.8 78.8 76.8 72.8 70.8 66.8 93.4 dB
LwA3 61.1 75.2 72.2 75.6 76.8 74 71.8 65.7 82.5 dB(A)
Outlet:sound power level in outlet cross section.
Lw4 88 93 84 84 83 80 78 74 95.5 dB
LwA4 61.8 76.9 75.4 80.8 83 81.2 79 72.9 88 dB(A)
Unit: sound power level emitted by the unit wall with ducted inlet and ducted outlet in according with BS EN 13053.
Octave: 63 125 250 500 1000 2000 4000 8000 Total Unit
Fan sound power level IN: SYD-800K
Lw1 92 93 87 89 84 83 81 76 97.4 dB
LwA1 66 77 79 86 84 84 82 74 90.9 dB(A)
Fan sound power level OUT: SYD-800K
Lw1 92 93 87 89 84 83 81 76 97.4 dB
LwA1 66 77 79 86 84 84 82 74 90.9 dB(A)
Inlet:sound power level in the inlet cross section.
Lw3 91.3 91.3 83.8 83.8 77.8 75.8 73.8 68.8 95.2 dB
LwA3 65.1 75.2 75.2 80.6 77.8 77 74.8 67.7 85.2 dB(A)
Outlet:sound power level in outlet cross section.
Lw4 92 93 87 89 84 83 81 76 97.4 dB
LwA4 65.8 76.9 78.4 85.8 84 84.2 82 74.9 90.8 dB(A)
Unit: sound power level emitted by the unit wall with ducted inlet and ducted outlet in according with BS EN 13053.
Lp2 73 74 68 70 65 64 62 57 78.4 dB
LpA2 46.8 57.9 59.4 66.8 65 65.2 63 55.9 71.8 dB(A)
Note:
1.It should be particularly noted that the noise levels outside the unit are significantly influenced by the installation location and acoustic
of the environment (for example, size, absorption capacity, and reflection of the space).
2.Furthermore, other noise sources(other units, fans, traffic noise,…) can add to the noise levels indicated above.
3.As for RU noise in EUROVENT certification, the "Lw3, Lw4, LwA2" parameters above represent "Octave Band In-duct INTLET in dB", "Octave Band
In-duct OUTLET in dB" and "AIRBORNE Sound Power - in dB(A)" respectively.
Octave: 63 125 250 500 1000 2000 4000 8000 Total Unit
Fan sound power level IN: SYQ-280A
Lw1 91 97 91 95 92 88 86 78 101.3 dB
LwA1 65 81 82 92 92 89 87 76 96.8 dB(A)
Fan sound power level OUT: SYQ-280A
Lw1 91 97 91 95 92 88 86 78 101.3 dB
LwA1 65 81 82 92 92 89 87 76 96.8 dB(A)
Inlet:sound power level in the inlet cross section.
Lw3 89.3 94.8 84.8 87.8 82.8 76.8 74.8 58.8 97 dB
LwA3 63.1 78.7 76.2 84.6 82.8 78 75.8 57.7 88.4 dB(A)
Outlet:sound power level in outlet cross section.
Lw4 91 97 91 95 92 88 86 78 101.3 dB
LwA4 64.8 80.9 82.4 91.8 92 89.2 87 76.9 96.8 dB(A)
Unit: sound power level emitted by the unit wall with ducted inlet and ducted outlet in according with BS EN 13053.
Lp2 72.4 78.4 72.4 76.4 73.4 69.4 67.4 59.4 82.7 dB
LpA2 46.2 62.3 63.8 73.2 73.4 70.6 68.4 58.3 78.2 dB(A)
Note:
1.It should be particularly noted that the noise levels outside the unit are significantly influenced by the installation location and acoustic
of the environment (for example, size, absorption capacity, and reflection of the space).
2.Furthermore, other noise sources(other units, fans, traffic noise,…) can add to the noise levels indicated above.
3.As for RU noise in EUROVENT certification, the "Lw3, Lw4, LwA2" parameters above represent "Octave Band In-duct INTLET in dB", "Octave Band
In-duct OUTLET in dB" and "AIRBORNE Sound Power - in dB(A)" respectively.
Octave: 63 125 250 500 1000 2000 4000 8000 Total Unit
Fan sound power level IN: SYD-280R
Lw1 98 89 87 81 82 80 79 76 99.1 dB
LwA1 71 73 78 78 82 81 80 75 87.6 dB(A)
Fan sound power level OUT: SYD-280R
Lw1 98 89 87 81 82 80 79 76 99.1 dB
LwA1 71 73 78 78 82 81 80 75 87.6 dB(A)
Inlet:sound power level in the inlet cross section.
Lw3 97.5 88.5 85 79 79.5 77 76 69 98.4 dB
LwA3 71.3 72.4 76.4 75.8 79.5 78.2 77 67.9 85.1 dB(A)
Outlet:sound power level in outlet cross section.
Lw4 98 89 87 81 82 80 79 76 99.1 dB
LwA4 71.8 72.9 78.4 77.8 82 81.2 80 74.9 87.7 dB(A)
Unit: sound power level emitted by the unit wall with ducted inlet and ducted outlet in according with BS EN 13053.
Lw2 85.4 69.2 70.8 63.3 65.3 59.3 42.9 36.5 85.7 dB
LwA2 59.2 53.1 62.2 60.1 65.3 60.5 43.9 35.4 69.2 dB(A)
Unit: sound pressure level emitted by the unit wall under free field condition in according with EN ISO 3744, on a block-shaped
measurement surface that envelops the unit casing.
Lp2 66.4 50.2 51.8 44.3 46.3 40.3 23.9 17.5 66.7 dB
LpA2 40.2 34.1 43.2 41.1 46.3 41.5 24.9 16.4 50.2 dB(A)
Unit: sound pressure level emitted by the unit wall under free field condition in according with GB/T 9068, on a block-shaped
measurement surface that envelops the unit casing.
Lp2 79.4 70.4 68.4 62.4 63.4 61.4 60.4 57.4 80.5 dB
LpA2 53.2 54.3 59.8 59.2 63.4 62.6 61.4 56.3 69.1 dB(A)
Note:
1.It should be particularly noted that the noise levels outside the unit are significantly influenced by the installation location and acoustic
of the environment (for example, size, absorption capacity, and reflection of the space).
2.Furthermore, other noise sources(other units, fans, traffic noise,…) can add to the noise levels indicated above.
3.As for RU noise in EUROVENT certification, the "Lw3, Lw4, LwA2" parameters above represent "Octave Band In-duct INTLET in dB", "Octave Band
In-duct OUTLET in dB" and "AIRBORNE Sound Power - in dB(A)" respectively.
Octave: 63 125 250 500 1000 2000 4000 8000 Total Unit
Fan sound power level IN: SYQ-400A
Lw1 90 88 86 98 91 88 83 76 100.2 dB
LwA1 63 72 77 95 91 90 84 75 97.6 dB(A)
Fan sound power level OUT: SYQ-400A
Lw1 90 88 86 98 91 88 83 76 100.2 dB
LwA1 63 72 77 95 91 90 84 75 97.6 dB(A)
Inlet:sound power level in the inlet cross section.
Lw3 89.3 86.3 82.8 92.8 84.8 80.8 75.8 68.8 95.8 dB
LwA3 63.1 70.2 74.2 89.6 84.8 82 76.8 67.7 91.7 dB(A)
Outlet:sound power level in outlet cross section.
Lw4 90 88 86 98 91 88 83 76 100.2 dB
LwA4 63.8 71.9 77.4 94.8 91 89.2 84 74.9 97.4 dB(A)
Unit: sound power level emitted by the unit wall with ducted inlet and ducted outlet in according with BS EN 13053.
Lp2 73.1 71.1 69.1 81.1 74.1 71.1 66.1 59.1 83.3 dB
LpA2 46.9 55 60.5 77.9 74.1 72.3 67.1 58 80.5 dB(A)
Note:
1.It should be particularly noted that the noise levels outside the unit are significantly influenced by the installation location and acoustic
of the environment (for example, size, absorption capacity, and reflection of the space).
2.Furthermore, other noise sources(other units, fans, traffic noise,…) can add to the noise levels indicated above.
3.As for RU noise in EUROVENT certification, the "Lw3, Lw4, LwA2" parameters above represent "Octave Band In-duct INTLET in dB", "Octave Band
In-duct OUTLET in dB" and "AIRBORNE Sound Power - in dB(A)" respectively.
Octave: 63 125 250 500 1000 2000 4000 8000 Total Unit
Fan sound power level IN: SYD-225L
Lw1 96 91 88 82 82 79 77 75 98 dB
LwA1 70 75 80 79 82 80 78 73 87.5 dB(A)
Fan sound power level OUT: SYD-225L
Lw1 96 91 88 82 82 79 77 75 98 dB
LwA1 70 75 80 79 82 80 78 73 87.5 dB(A)
Inlet:sound power level in the inlet cross section.
Lw3 94.8 88.8 82.8 74.8 73.3 68.8 66.8 60.8 96.1 dB
LwA3 68.6 72.7 74.2 71.6 73.3 70 67.8 59.7 80.2 dB(A)
Outlet:sound power level in outlet cross section.
Lw4 96 91 88 82 82 79 77 75 98 dB
LwA4 69.8 74.9 79.4 78.8 82 80.2 78 73.9 87.4 dB(A)
Unit: sound power level emitted by the unit wall with ducted inlet and ducted outlet in according with BS EN 13053.
Lw2 86.8 76.8 74.5 67.7 68.3 60.9 43.5 36.3 87.5 dB
LwA2 60.6 60.7 65.9 64.5 68.3 62.1 44.5 35.2 72.4 dB(A)
Unit: sound pressure level emitted by the unit wall under free field condition in according with EN ISO 3744, on a block-shaped
measurement surface that envelops the unit casing.
Lp2 77.6 72.6 69.6 63.6 63.6 60.6 58.6 56.6 79.6 dB
LpA2 51.4 56.5 61 60.4 63.6 61.8 59.6 55.5 69 dB(A)
Note:
1.It should be particularly noted that the noise levels outside the unit are significantly influenced by the installation location and acoustic
of the environment (for example, size, absorption capacity, and reflection of the space).
2.Furthermore, other noise sources(other units, fans, traffic noise,…) can add to the noise levels indicated above.
3.As for RU noise in EUROVENT certification, the "Lw3, Lw4, LwA2" parameters above represent "Octave Band In-duct INTLET in dB", "Octave Band
In-duct OUTLET in dB" and "AIRBORNE Sound Power - in dB(A)" respectively.
Octave: 63 125 250 500 1000 2000 4000 8000 Total Unit
Fan sound power level IN: SYD-225L
Lw1 94 87 85 78 79 76 75 72 95.5 dB
LwA1 68 71 76 75 79 78 76 71 84.6 dB(A)
Fan sound power level OUT: SYD-225L
Lw1 94 87 85 78 79 76 75 72 95.5 dB
LwA1 68 71 76 75 79 78 76 71 84.6 dB(A)
Inlet:sound power level in the inlet cross section.
Lw3 93.5 86.5 83 76 76.5 73 72 65 94.8 dB
LwA3 67.3 70.4 74.4 72.8 76.5 74.2 73 63.9 81.9 dB(A)
Outlet:sound power level in outlet cross section.
Lw4 94 87 85 78 79 76 75 72 95.5 dB
LwA4 67.8 70.9 76.4 74.8 79 77.2 76 70.9 84.4 dB(A)
Unit: sound power level emitted by the unit wall with ducted inlet and ducted outlet in according with BS EN 13053.
Lw2 81.4 67.2 68.8 60.3 62.3 55.3 38.9 32.5 81.9 dB
LwA2 55.2 51.1 60.2 57.1 62.3 56.5 39.9 31.4 66.2 dB(A)
Unit: sound pressure level emitted by the unit wall under free field condition in according with EN ISO 3744, on a block-shaped
measurement surface that envelops the unit casing.
Lp2 75.6 68.6 66.6 59.6 60.6 57.6 56.6 53.6 77.1 dB
LpA2 49.4 52.5 58 56.4 60.6 58.8 57.6 52.5 66 dB(A)
Note:
1.It should be particularly noted that the noise levels outside the unit are significantly influenced by the installation location and acoustic
of the environment (for example, size, absorption capacity, and reflection of the space).
2.Furthermore, other noise sources(other units, fans, traffic noise,…) can add to the noise levels indicated above.
3.As for RU noise in EUROVENT certification, the "Lw3, Lw4, LwA2" parameters above represent "Octave Band In-duct INTLET in dB", "Octave Band
In-duct OUTLET in dB" and "AIRBORNE Sound Power - in dB(A)" respectively.
Octave: 63 125 250 500 1000 2000 4000 8000 Total Unit
Fan sound power level IN: SYD-225L
Lw1 96 91 88 82 82 80 78 75 98.1 dB
LwA1 70 75 80 79 82 81 79 74 87.9 dB(A)
Fan sound power level OUT: SYD-225L
Lw1 96 91 88 82 82 80 78 75 98.1 dB
LwA1 70 75 80 79 82 81 79 74 87.9 dB(A)
Inlet:sound power level in the inlet cross section.
Lw3 94.8 88.8 82.8 74.8 73.3 69.8 67.8 60.8 96.1 dB
LwA3 68.6 72.7 74.2 71.6 73.3 71 68.8 59.7 80.4 dB(A)
Outlet:sound power level in outlet cross section.
Lw4 96 91 88 82 82 80 78 75 98.1 dB
LwA4 69.8 74.9 79.4 78.8 82 81.2 79 73.9 87.8 dB(A)
Unit: sound power level emitted by the unit wall with ducted inlet and ducted outlet in according with BS EN 13053.
Lw2 86.8 76.8 74.5 67.7 68.3 61.9 44.5 36.3 87.6 dB
LwA2 60.6 60.7 65.9 64.5 68.3 63.1 45.5 35.2 72.5 dB(A)
Unit: sound pressure level emitted by the unit wall under free field condition in according with EN ISO 3744, on a block-shaped
measurement surface that envelops the unit casing.
Lp2 77.6 72.6 69.6 63.6 63.6 61.6 59.6 56.6 79.7 dB
LpA2 51.4 56.5 61 60.4 63.6 62.8 60.6 55.5 69.4 dB(A)
Note:
1.It should be particularly noted that the noise levels outside the unit are significantly influenced by the installation location and acoustic
of the environment (for example, size, absorption capacity, and reflection of the space).
2.Furthermore, other noise sources(other units, fans, traffic noise,…) can add to the noise levels indicated above.
3.As for RU noise in EUROVENT certification, the "Lw3, Lw4, LwA2" parameters above represent "Octave Band In-duct INTLET in dB", "Octave Band
In-duct OUTLET in dB" and "AIRBORNE Sound Power - in dB(A)" respectively.
Octave: 63 125 250 500 1000 2000 4000 8000 Total Unit
Fan sound power level IN: SYD-225L
Lw1 94 87 85 78 79 76 75 72 95.5 dB
LwA1 68 71 76 75 79 78 76 71 84.6 dB(A)
Fan sound power level OUT: SYD-225L
Lw1 94 87 85 78 79 76 75 72 95.5 dB
LwA1 68 71 76 75 79 78 76 71 84.6 dB(A)
Inlet:sound power level in the inlet cross section.
Lw3 93.5 86.5 83 76 76.5 73 72 65 94.8 dB
LwA3 67.3 70.4 74.4 72.8 76.5 74.2 73 63.9 81.9 dB(A)
Outlet:sound power level in outlet cross section.
Lw4 94 87 85 78 79 76 75 72 95.5 dB
LwA4 67.8 70.9 76.4 74.8 79 77.2 76 70.9 84.4 dB(A)
Unit: sound power level emitted by the unit wall with ducted inlet and ducted outlet in according with BS EN 13053.
Lw2 81.4 67.2 68.8 60.3 62.3 55.3 38.9 32.5 81.9 dB
LwA2 55.2 51.1 60.2 57.1 62.3 56.5 39.9 31.4 66.2 dB(A)
Unit: sound pressure level emitted by the unit wall under free field condition in according with EN ISO 3744, on a block-shaped
measurement surface that envelops the unit casing.
Lp2 75.6 68.6 66.6 59.6 60.6 57.6 56.6 53.6 77.1 dB
LpA2 49.4 52.5 58 56.4 60.6 58.8 57.6 52.5 66 dB(A)
Note:
1.It should be particularly noted that the noise levels outside the unit are significantly influenced by the installation location and acoustic
of the environment (for example, size, absorption capacity, and reflection of the space).
2.Furthermore, other noise sources(other units, fans, traffic noise,…) can add to the noise levels indicated above.
3.As for RU noise in EUROVENT certification, the "Lw3, Lw4, LwA2" parameters above represent "Octave Band In-duct INTLET in dB", "Octave Band
In-duct OUTLET in dB" and "AIRBORNE Sound Power - in dB(A)" respectively.
Octave: 63 125 250 500 1000 2000 4000 8000 Total Unit
Fan sound power level IN: SYD-225L
Lw1 96 91 88 82 81 79 77 74 98 dB
LwA1 70 75 79 78 81 80 78 73 86.9 dB(A)
Fan sound power level OUT: SYD-225L
Lw1 96 91 88 82 81 79 77 74 98 dB
LwA1 70 75 79 78 81 80 78 73 86.9 dB(A)
Inlet:sound power level in the inlet cross section.
Lw3 94.8 88.8 82.8 74.8 72.3 68.8 66.8 59.8 96.1 dB
LwA3 68.6 72.7 74.2 71.6 72.3 70 67.8 58.7 80 dB(A)
Outlet:sound power level in outlet cross section.
Lw4 96 91 88 82 81 79 77 74 98 dB
LwA4 69.8 74.9 79.4 78.8 81 80.2 78 72.9 87.1 dB(A)
Unit: sound power level emitted by the unit wall with ducted inlet and ducted outlet in according with BS EN 13053.
Lw2 86.8 76.8 74.5 67.7 67.3 60.9 43.5 35.3 87.5 dB
LwA2 60.6 60.7 65.9 64.5 67.3 62.1 44.5 34.2 72.1 dB(A)
Unit: sound pressure level emitted by the unit wall under free field condition in according with EN ISO 3744, on a block-shaped
measurement surface that envelops the unit casing.
Lp2 77.7 72.7 69.7 63.7 62.7 60.7 58.7 55.7 79.7 dB
LpA2 51.5 56.6 61.1 60.5 62.7 61.9 59.7 54.6 68.8 dB(A)
Note:
1.It should be particularly noted that the noise levels outside the unit are significantly influenced by the installation location and acoustic
of the environment (for example, size, absorption capacity, and reflection of the space).
2.Furthermore, other noise sources(other units, fans, traffic noise,…) can add to the noise levels indicated above.
3.As for RU noise in EUROVENT certification, the "Lw3, Lw4, LwA2" parameters above represent "Octave Band In-duct INTLET in dB", "Octave Band
In-duct OUTLET in dB" and "AIRBORNE Sound Power - in dB(A)" respectively.
Octave: 63 125 250 500 1000 2000 4000 8000 Total Unit
Fan sound power level IN: SYD-225L
Lw1 94 87 85 78 79 76 75 72 95.5 dB
LwA1 68 71 76 75 79 78 76 71 84.6 dB(A)
Fan sound power level OUT: SYD-225L
Lw1 94 87 85 78 79 76 75 72 95.5 dB
LwA1 68 71 76 75 79 78 76 71 84.6 dB(A)
Inlet:sound power level in the inlet cross section.
Lw3 93.5 86.5 83 76 76.5 73 72 65 94.8 dB
LwA3 67.3 70.4 74.4 72.8 76.5 74.2 73 63.9 81.9 dB(A)
Outlet:sound power level in outlet cross section.
Lw4 94 87 85 78 79 76 75 72 95.5 dB
LwA4 67.8 70.9 76.4 74.8 79 77.2 76 70.9 84.4 dB(A)
Unit: sound power level emitted by the unit wall with ducted inlet and ducted outlet in according with BS EN 13053.
Lw2 81.4 67.2 68.8 60.3 62.3 55.3 38.9 32.5 81.9 dB
LwA2 55.2 51.1 60.2 57.1 62.3 56.5 39.9 31.4 66.2 dB(A)
Unit: sound pressure level emitted by the unit wall under free field condition in according with EN ISO 3744, on a block-shaped
measurement surface that envelops the unit casing.
Lp2 62.7 48.5 50.1 41.6 43.6 36.6 20.2 13.8 63.2 dB
LpA2 36.5 32.4 41.5 38.4 43.6 37.8 21.2 12.7 47.5 dB(A)
Unit: sound pressure level emitted by the unit wall under free field condition in according with GB/T 9068, on a block-shaped
measurement surface that envelops the unit casing.
Lp2 75.7 68.7 66.7 59.7 60.7 57.7 56.7 53.7 77.2 dB
LpA2 49.5 52.6 58.1 56.5 60.7 58.9 57.7 52.6 66.1 dB(A)
Note:
1.It should be particularly noted that the noise levels outside the unit are significantly influenced by the installation location and acoustic
of the environment (for example, size, absorption capacity, and reflection of the space).
2.Furthermore, other noise sources(other units, fans, traffic noise,…) can add to the noise levels indicated above.
3.As for RU noise in EUROVENT certification, the "Lw3, Lw4, LwA2" parameters above represent "Octave Band In-duct INTLET in dB", "Octave Band
In-duct OUTLET in dB" and "AIRBORNE Sound Power - in dB(A)" respectively.
Octave: 63 125 250 500 1000 2000 4000 8000 Total Unit
Fan sound power level IN: SYD-225L
Lw1 96 91 89 82 82 80 78 75 98.2 dB
LwA1 70 75 80 79 82 81 79 74 87.9 dB(A)
Fan sound power level OUT: SYD-225L
Lw1 96 91 89 82 82 80 78 75 98.2 dB
LwA1 70 75 80 79 82 81 79 74 87.9 dB(A)
Inlet:sound power level in the inlet cross section.
Lw3 94.8 88.8 83.8 74.8 73.3 69.8 67.8 60.8 96.1 dB
LwA3 68.6 72.7 75.2 71.6 73.3 71 68.8 59.7 80.6 dB(A)
Outlet:sound power level in outlet cross section.
Lw4 96 91 89 82 82 80 78 75 98.2 dB
LwA4 69.8 74.9 80.4 78.8 82 81.2 79 73.9 87.9 dB(A)
Unit: sound power level emitted by the unit wall with ducted inlet and ducted outlet in according with BS EN 13053.
Lw2 86.8 76.8 75.5 67.7 68.3 61.9 44.5 36.3 87.6 dB
LwA2 60.6 60.7 66.9 64.5 68.3 63.1 45.5 35.2 72.8 dB(A)
Unit: sound pressure level emitted by the unit wall under free field condition in according with EN ISO 3744, on a block-shaped
measurement surface that envelops the unit casing.
Lp2 77.6 72.6 70.6 63.6 63.6 61.6 59.6 56.6 79.8 dB
LpA2 51.4 56.5 62 60.4 63.6 62.8 60.6 55.5 69.5 dB(A)
Note:
1.It should be particularly noted that the noise levels outside the unit are significantly influenced by the installation location and acoustic
of the environment (for example, size, absorption capacity, and reflection of the space).
2.Furthermore, other noise sources(other units, fans, traffic noise,…) can add to the noise levels indicated above.
3.As for RU noise in EUROVENT certification, the "Lw3, Lw4, LwA2" parameters above represent "Octave Band In-duct INTLET in dB", "Octave Band
In-duct OUTLET in dB" and "AIRBORNE Sound Power - in dB(A)" respectively.
Octave: 63 125 250 500 1000 2000 4000 8000 Total Unit
Fan sound power level IN: SYD-225L
Lw1 94 87 85 78 79 76 75 72 95.5 dB
LwA1 68 71 76 75 79 78 76 71 84.6 dB(A)
Fan sound power level OUT: SYD-225L
Lw1 94 87 85 78 79 76 75 72 95.5 dB
LwA1 68 71 76 75 79 78 76 71 84.6 dB(A)
Inlet:sound power level in the inlet cross section.
Lw3 93.5 86.5 83 76 76.5 73 72 65 94.8 dB
LwA3 67.3 70.4 74.4 72.8 76.5 74.2 73 63.9 81.9 dB(A)
Outlet:sound power level in outlet cross section.
Lw4 94 87 85 78 79 76 75 72 95.5 dB
LwA4 67.8 70.9 76.4 74.8 79 77.2 76 70.9 84.4 dB(A)
Unit: sound power level emitted by the unit wall with ducted inlet and ducted outlet in according with BS EN 13053.
Lw2 81.4 67.2 68.8 60.3 62.3 55.3 38.9 32.5 81.9 dB
LwA2 55.2 51.1 60.2 57.1 62.3 56.5 39.9 31.4 66.2 dB(A)
Unit: sound pressure level emitted by the unit wall under free field condition in according with EN ISO 3744, on a block-shaped
measurement surface that envelops the unit casing.
Lp2 75.6 68.6 66.6 59.6 60.6 57.6 56.6 53.6 77.1 dB
LpA2 49.4 52.5 58 56.4 60.6 58.8 57.6 52.5 66 dB(A)
Note:
1.It should be particularly noted that the noise levels outside the unit are significantly influenced by the installation location and acoustic
of the environment (for example, size, absorption capacity, and reflection of the space).
2.Furthermore, other noise sources(other units, fans, traffic noise,…) can add to the noise levels indicated above.
3.As for RU noise in EUROVENT certification, the "Lw3, Lw4, LwA2" parameters above represent "Octave Band In-duct INTLET in dB", "Octave Band
In-duct OUTLET in dB" and "AIRBORNE Sound Power - in dB(A)" respectively.
Octave: 63 125 250 500 1000 2000 4000 8000 Total Unit
Fan sound power level IN: SYD-225L
Lw1 97 92 90 83 83 81 79 76 99.2 dB
LwA1 71 76 81 80 83 82 80 75 88.9 dB(A)
Fan sound power level OUT: SYD-225L
Lw1 97 92 90 83 83 81 79 76 99.2 dB
LwA1 71 76 81 80 83 82 80 75 88.9 dB(A)
Inlet:sound power level in the inlet cross section.
Lw3 95.3 89.8 83.8 75.8 73.8 69.8 67.8 56.8 96.7 dB
LwA3 69.1 73.7 75.2 72.6 73.8 71 68.8 55.7 81.1 dB(A)
Outlet:sound power level in outlet cross section.
Lw4 97 92 90 83 83 81 79 76 99.2 dB
LwA4 70.8 75.9 81.4 79.8 83 82.2 80 74.9 88.9 dB(A)
Unit: sound power level emitted by the unit wall with ducted inlet and ducted outlet in according with BS EN 13053.
Lp2 78.6 73.6 71.6 64.6 64.6 62.6 60.6 57.6 80.8 dB
LpA2 52.4 57.5 63 61.4 64.6 63.8 61.6 56.5 70.5 dB(A)
Note:
1.It should be particularly noted that the noise levels outside the unit are significantly influenced by the installation location and acoustic
of the environment (for example, size, absorption capacity, and reflection of the space).
2.Furthermore, other noise sources(other units, fans, traffic noise,…) can add to the noise levels indicated above.
3.As for RU noise in EUROVENT certification, the "Lw3, Lw4, LwA2" parameters above represent "Octave Band In-duct INTLET in dB", "Octave Band
In-duct OUTLET in dB" and "AIRBORNE Sound Power - in dB(A)" respectively.
Octave: 63 125 250 500 1000 2000 4000 8000 Total Unit
Fan sound power level IN: SYD-225L
Lw1 94 87 85 78 79 76 75 72 95.5 dB
LwA1 68 71 76 75 79 78 76 71 84.6 dB(A)
Fan sound power level OUT: SYD-225L
Lw1 94 87 85 78 79 76 75 72 95.5 dB
LwA1 68 71 76 75 79 78 76 71 84.6 dB(A)
Inlet:sound power level in the inlet cross section.
Lw3 93.5 86.5 83 76 76.5 73 72 65 94.8 dB
LwA3 67.3 70.4 74.4 72.8 76.5 74.2 73 63.9 81.9 dB(A)
Outlet:sound power level in outlet cross section.
Lw4 94 87 85 78 79 76 75 72 95.5 dB
LwA4 67.8 70.9 76.4 74.8 79 77.2 76 70.9 84.4 dB(A)
Unit: sound power level emitted by the unit wall with ducted inlet and ducted outlet in according with BS EN 13053.
Lw2 81.4 67.2 68.8 60.3 62.3 55.3 38.9 32.5 81.9 dB
LwA2 55.2 51.1 60.2 57.1 62.3 56.5 39.9 31.4 66.2 dB(A)
Unit: sound pressure level emitted by the unit wall under free field condition in according with EN ISO 3744, on a block-shaped
measurement surface that envelops the unit casing.
Lp2 75.6 68.6 66.6 59.6 60.6 57.6 56.6 53.6 77.1 dB
LpA2 49.4 52.5 58 56.4 60.6 58.8 57.6 52.5 66 dB(A)
Note:
1.It should be particularly noted that the noise levels outside the unit are significantly influenced by the installation location and acoustic
of the environment (for example, size, absorption capacity, and reflection of the space).
2.Furthermore, other noise sources(other units, fans, traffic noise,…) can add to the noise levels indicated above.
3.As for RU noise in EUROVENT certification, the "Lw3, Lw4, LwA2" parameters above represent "Octave Band In-duct INTLET in dB", "Octave Band
In-duct OUTLET in dB" and "AIRBORNE Sound Power - in dB(A)" respectively.
Octave: 63 125 250 500 1000 2000 4000 8000 Total Unit
Fan sound power level IN: SYD-225L
Lw1 97 92 89 83 82 80 78 75 99 dB
LwA1 71 76 81 80 82 81 79 74 88.2 dB(A)
Fan sound power level OUT: SYD-225L
Lw1 97 92 89 83 82 80 78 75 99 dB
LwA1 71 76 81 80 82 81 79 74 88.2 dB(A)
Inlet:sound power level in the inlet cross section.
Lw3 95.8 89.8 83.8 75.8 73.3 69.8 67.8 60.8 97.1 dB
LwA3 69.6 73.7 75.2 72.6 73.3 71 68.8 59.7 81 dB(A)
Outlet:sound power level in outlet cross section.
Lw4 97 92 89 83 82 80 78 75 99 dB
LwA4 70.8 75.9 80.4 79.8 82 81.2 79 73.9 88.1 dB(A)
Unit: sound power level emitted by the unit wall with ducted inlet and ducted outlet in according with BS EN 13053.
Lw2 87.8 77.8 75.5 68.7 68.3 61.9 44.5 36.3 88.5 dB
LwA2 61.6 61.7 66.9 65.5 68.3 63.1 45.5 35.2 73.1 dB(A)
Unit: sound pressure level emitted by the unit wall under free field condition in according with EN ISO 3744, on a block-shaped
measurement surface that envelops the unit casing.
Lp2 78.6 73.6 70.6 64.6 63.6 61.6 59.6 56.6 80.6 dB
LpA2 52.4 57.5 62 61.4 63.6 62.8 60.6 55.5 69.7 dB(A)
Note:
1.It should be particularly noted that the noise levels outside the unit are significantly influenced by the installation location and acoustic
of the environment (for example, size, absorption capacity, and reflection of the space).
2.Furthermore, other noise sources(other units, fans, traffic noise,…) can add to the noise levels indicated above.
3.As for RU noise in EUROVENT certification, the "Lw3, Lw4, LwA2" parameters above represent "Octave Band In-duct INTLET in dB", "Octave Band
In-duct OUTLET in dB" and "AIRBORNE Sound Power - in dB(A)" respectively.
Octave: 63 125 250 500 1000 2000 4000 8000 Total Unit
Fan sound power level IN: SYD-225L
Lw1 94 87 85 78 79 76 75 72 95.5 dB
LwA1 68 71 76 75 79 78 76 71 84.6 dB(A)
Fan sound power level OUT: SYD-225L
Lw1 94 87 85 78 79 76 75 72 95.5 dB
LwA1 68 71 76 75 79 78 76 71 84.6 dB(A)
Inlet:sound power level in the inlet cross section.
Lw3 93.5 86.5 83 76 76.5 73 72 65 94.8 dB
LwA3 67.3 70.4 74.4 72.8 76.5 74.2 73 63.9 81.9 dB(A)
Outlet:sound power level in outlet cross section.
Lw4 94 87 85 78 79 76 75 72 95.5 dB
LwA4 67.8 70.9 76.4 74.8 79 77.2 76 70.9 84.4 dB(A)
Unit: sound power level emitted by the unit wall with ducted inlet and ducted outlet in according with BS EN 13053.
Lw2 81.4 67.2 68.8 60.3 62.3 55.3 38.9 32.5 81.9 dB
LwA2 55.2 51.1 60.2 57.1 62.3 56.5 39.9 31.4 66.2 dB(A)
Unit: sound pressure level emitted by the unit wall under free field condition in according with EN ISO 3744, on a block-shaped
measurement surface that envelops the unit casing.
Lp2 75.6 68.6 66.6 59.6 60.6 57.6 56.6 53.6 77.1 dB
LpA2 49.4 52.5 58 56.4 60.6 58.8 57.6 52.5 66 dB(A)
Note:
1.It should be particularly noted that the noise levels outside the unit are significantly influenced by the installation location and acoustic
of the environment (for example, size, absorption capacity, and reflection of the space).
2.Furthermore, other noise sources(other units, fans, traffic noise,…) can add to the noise levels indicated above.
3.As for RU noise in EUROVENT certification, the "Lw3, Lw4, LwA2" parameters above represent "Octave Band In-duct INTLET in dB", "Octave Band
In-duct OUTLET in dB" and "AIRBORNE Sound Power - in dB(A)" respectively.
Octave: 63 125 250 500 1000 2000 4000 8000 Total Unit
Fan sound power level IN: SYD-225L
Lw1 97 93 91 84 84 82 79 77 99.6 dB
LwA1 71 77 82 81 84 83 80 76 89.7 dB(A)
Fan sound power level OUT: SYD-225L
Lw1 97 93 91 84 84 82 79 77 99.6 dB
LwA1 71 77 82 81 84 83 80 76 89.7 dB(A)
Inlet:sound power level in the inlet cross section.
Lw3 95.8 90.8 85.8 76.8 75.3 71.8 68.8 62.8 97.4 dB
LwA3 69.6 74.7 77.2 73.6 75.3 73 69.8 61.7 82.5 dB(A)
Outlet:sound power level in outlet cross section.
Lw4 97 93 91 84 84 82 79 77 99.6 dB
LwA4 70.8 76.9 82.4 80.8 84 83.2 80 75.9 89.8 dB(A)
Unit: sound power level emitted by the unit wall with ducted inlet and ducted outlet in according with BS EN 13053.
Lw2 87.8 78.8 77.5 69.7 70.3 63.9 45.5 38.3 88.8 dB
LwA2 61.6 62.7 68.9 66.5 70.3 65.1 46.5 37.2 74.7 dB(A)
Unit: sound pressure level emitted by the unit wall under free field condition in according with EN ISO 3744, on a block-shaped
measurement surface that envelops the unit casing.
Lp2 78.7 74.7 72.7 65.7 65.7 63.7 60.7 58.7 81.3 dB
LpA2 52.5 58.6 64.1 62.5 65.7 64.9 61.7 57.6 71.5 dB(A)
Note:
1.It should be particularly noted that the noise levels outside the unit are significantly influenced by the installation location and acoustic
of the environment (for example, size, absorption capacity, and reflection of the space).
2.Furthermore, other noise sources(other units, fans, traffic noise,…) can add to the noise levels indicated above.
3.As for RU noise in EUROVENT certification, the "Lw3, Lw4, LwA2" parameters above represent "Octave Band In-duct INTLET in dB", "Octave Band
In-duct OUTLET in dB" and "AIRBORNE Sound Power - in dB(A)" respectively.
Octave: 63 125 250 500 1000 2000 4000 8000 Total Unit
Fan sound power level IN: SYD-225L
Lw1 96 88 86 80 80 78 77 74 97.3 dB
LwA1 70 72 77 77 80 79 78 73 85.9 dB(A)
Fan sound power level OUT: SYD-225L
Lw1 96 88 86 80 80 78 77 74 97.3 dB
LwA1 70 72 77 77 80 79 78 73 85.9 dB(A)
Inlet:sound power level in the inlet cross section.
Lw3 95.5 87.5 84 78 77.5 75 74 67 96.6 dB
LwA3 69.3 71.4 75.4 74.8 77.5 76.2 75 65.9 83.4 dB(A)
Outlet:sound power level in outlet cross section.
Lw4 96 88 86 80 80 78 77 74 97.3 dB
LwA4 69.8 71.9 77.4 76.8 80 79.2 78 72.9 86 dB(A)
Unit: sound power level emitted by the unit wall with ducted inlet and ducted outlet in according with BS EN 13053.
Lw2 83.4 68.2 69.8 62.3 63.3 57.3 40.9 34.5 83.8 dB
LwA2 57.2 52.1 61.2 59.1 63.3 58.5 41.9 33.4 67.5 dB(A)
Unit: sound pressure level emitted by the unit wall under free field condition in according with EN ISO 3744, on a block-shaped
measurement surface that envelops the unit casing.
Lp2 64.7 49.5 51.1 43.6 44.6 38.6 22.2 15.8 65.1 dB
LpA2 38.5 33.4 42.5 40.4 44.6 39.8 23.2 14.7 48.8 dB(A)
Unit: sound pressure level emitted by the unit wall under free field condition in according with GB/T 9068, on a block-shaped
measurement surface that envelops the unit casing.
Octave: 63 125 250 500 1000 2000 4000 8000 Total Unit
Fan sound power level IN: SYD-225L
Lw1 96 91 88 82 82 79 77 75 98 dB
LwA1 70 75 80 79 82 80 78 73 87.5 dB(A)
Fan sound power level OUT: SYD-225L
Lw1 96 91 88 82 82 79 77 75 98 dB
LwA1 70 75 80 79 82 80 78 73 87.5 dB(A)
Inlet:sound power level in the inlet cross section.
Lw3 94.8 88.8 82.8 74.8 73.3 68.8 66.8 60.8 96.1 dB
LwA3 68.6 72.7 74.2 71.6 73.3 70 67.8 59.7 80.2 dB(A)
Outlet:sound power level in outlet cross section.
Lw4 96 91 88 82 82 79 77 75 98 dB
LwA4 69.8 74.9 79.4 78.8 82 80.2 78 73.9 87.4 dB(A)
Unit: sound power level emitted by the unit wall with ducted inlet and ducted outlet in according with BS EN 13053.
Lw2 86.8 76.8 74.5 67.7 68.3 60.9 43.5 36.3 87.5 dB
LwA2 60.6 60.7 65.9 64.5 68.3 62.1 44.5 35.2 72.4 dB(A)
Unit: sound pressure level emitted by the unit wall under free field condition in according with EN ISO 3744, on a block-shaped
measurement surface that envelops the unit casing.
Lp2 77.6 72.6 69.6 63.6 63.6 60.6 58.6 56.6 79.6 dB
LpA2 51.4 56.5 61 60.4 63.6 61.8 59.6 55.5 69 dB(A)
Note:
1.It should be particularly noted that the noise levels outside the unit are significantly influenced by the installation location and acoustic
of the environment (for example, size, absorption capacity, and reflection of the space).
2.Furthermore, other noise sources(other units, fans, traffic noise,…) can add to the noise levels indicated above.
3.As for RU noise in EUROVENT certification, the "Lw3, Lw4, LwA2" parameters above represent "Octave Band In-duct INTLET in dB", "Octave Band
In-duct OUTLET in dB" and "AIRBORNE Sound Power - in dB(A)" respectively.
Octave: 63 125 250 500 1000 2000 4000 8000 Total Unit
Fan sound power level IN: SYD-225L
Lw1 94 87 85 78 79 76 75 72 95.5 dB
LwA1 68 71 76 75 79 78 76 71 84.6 dB(A)
Fan sound power level OUT: SYD-225L
Lw1 94 87 85 78 79 76 75 72 95.5 dB
LwA1 68 71 76 75 79 78 76 71 84.6 dB(A)
Inlet:sound power level in the inlet cross section.
Lw3 93.5 86.5 83 76 76.5 73 72 65 94.8 dB
LwA3 67.3 70.4 74.4 72.8 76.5 74.2 73 63.9 81.9 dB(A)
Outlet:sound power level in outlet cross section.
Lw4 94 87 85 78 79 76 75 72 95.5 dB
LwA4 67.8 70.9 76.4 74.8 79 77.2 76 70.9 84.4 dB(A)
Unit: sound power level emitted by the unit wall with ducted inlet and ducted outlet in according with BS EN 13053.
Lw2 81.4 67.2 68.8 60.3 62.3 55.3 38.9 32.5 81.9 dB
LwA2 55.2 51.1 60.2 57.1 62.3 56.5 39.9 31.4 66.2 dB(A)
Unit: sound pressure level emitted by the unit wall under free field condition in according with EN ISO 3744, on a block-shaped
measurement surface that envelops the unit casing.
Lp2 75.6 68.6 66.6 59.6 60.6 57.6 56.6 53.6 77.1 dB
LpA2 49.4 52.5 58 56.4 60.6 58.8 57.6 52.5 66 dB(A)
Note:
1.It should be particularly noted that the noise levels outside the unit are significantly influenced by the installation location and acoustic
of the environment (for example, size, absorption capacity, and reflection of the space).
2.Furthermore, other noise sources(other units, fans, traffic noise,…) can add to the noise levels indicated above.
3.As for RU noise in EUROVENT certification, the "Lw3, Lw4, LwA2" parameters above represent "Octave Band In-duct INTLET in dB", "Octave Band
In-duct OUTLET in dB" and "AIRBORNE Sound Power - in dB(A)" respectively.
Octave: 63 125 250 500 1000 2000 4000 8000 Total Unit
Fan sound power level IN: SYD-225L
Lw1 97 91 89 82 82 80 78 75 98.8 dB
LwA1 70 75 80 79 82 81 79 74 87.9 dB(A)
Fan sound power level OUT: SYD-225L
Lw1 97 91 89 82 82 80 78 75 98.8 dB
LwA1 70 75 80 79 82 81 79 74 87.9 dB(A)
Inlet:sound power level in the inlet cross section.
Lw3 95.8 88.8 83.8 74.8 73.3 69.8 67.8 60.8 96.9 dB
LwA3 69.6 72.7 75.2 71.6 73.3 71 68.8 59.7 80.7 dB(A)
Outlet:sound power level in outlet cross section.
Lw4 97 91 89 82 82 80 78 75 98.8 dB
LwA4 70.8 74.9 80.4 78.8 82 81.2 79 73.9 87.9 dB(A)
Unit: sound power level emitted by the unit wall with ducted inlet and ducted outlet in according with BS EN 13053.
Lw2 87.8 76.8 75.5 67.7 68.3 61.9 44.5 36.3 88.5 dB
LwA2 61.6 60.7 66.9 64.5 68.3 63.1 45.5 35.2 72.8 dB(A)
Unit: sound pressure level emitted by the unit wall under free field condition in according with EN ISO 3744, on a block-shaped
measurement surface that envelops the unit casing.
Lp2 78.6 72.6 70.6 63.6 63.6 61.6 59.6 56.6 80.4 dB
LpA2 52.4 56.5 62 60.4 63.6 62.8 60.6 55.5 69.5 dB(A)
Note:
1.It should be particularly noted that the noise levels outside the unit are significantly influenced by the installation location and acoustic
of the environment (for example, size, absorption capacity, and reflection of the space).
2.Furthermore, other noise sources(other units, fans, traffic noise,…) can add to the noise levels indicated above.
3.As for RU noise in EUROVENT certification, the "Lw3, Lw4, LwA2" parameters above represent "Octave Band In-duct INTLET in dB", "Octave Band
In-duct OUTLET in dB" and "AIRBORNE Sound Power - in dB(A)" respectively.
Octave: 63 125 250 500 1000 2000 4000 8000 Total Unit
Fan sound power level IN: SYD-225L
Lw1 94 87 85 78 79 76 75 72 95.5 dB
LwA1 68 71 76 75 79 78 76 71 84.6 dB(A)
Fan sound power level OUT: SYD-225L
Lw1 94 87 85 78 79 76 75 72 95.5 dB
LwA1 68 71 76 75 79 78 76 71 84.6 dB(A)
Inlet:sound power level in the inlet cross section.
Lw3 93.5 86.5 83 76 76.5 73 72 65 94.8 dB
LwA3 67.3 70.4 74.4 72.8 76.5 74.2 73 63.9 81.9 dB(A)
Outlet:sound power level in outlet cross section.
Lw4 94 87 85 78 79 76 75 72 95.5 dB
LwA4 67.8 70.9 76.4 74.8 79 77.2 76 70.9 84.4 dB(A)
Unit: sound power level emitted by the unit wall with ducted inlet and ducted outlet in according with BS EN 13053.
Lw2 81.4 67.2 68.8 60.3 62.3 55.3 38.9 32.5 81.9 dB
LwA2 55.2 51.1 60.2 57.1 62.3 56.5 39.9 31.4 66.2 dB(A)
Unit: sound pressure level emitted by the unit wall under free field condition in according with EN ISO 3744, on a block-shaped
measurement surface that envelops the unit casing.
Lp2 75.6 68.6 66.6 59.6 60.6 57.6 56.6 53.6 77.1 dB
LpA2 49.4 52.5 58 56.4 60.6 58.8 57.6 52.5 66 dB(A)
Note:
1.It should be particularly noted that the noise levels outside the unit are significantly influenced by the installation location and acoustic
of the environment (for example, size, absorption capacity, and reflection of the space).
2.Furthermore, other noise sources(other units, fans, traffic noise,…) can add to the noise levels indicated above.
3.As for RU noise in EUROVENT certification, the "Lw3, Lw4, LwA2" parameters above represent "Octave Band In-duct INTLET in dB", "Octave Band
In-duct OUTLET in dB" and "AIRBORNE Sound Power - in dB(A)" respectively.
Octave: 63 125 250 500 1000 2000 4000 8000 Total Unit
Fan sound power level IN: SYD-250L
Lw1 99 94 91 85 85 82 81 78 101 dB
LwA1 73 78 83 82 85 84 82 76 90.8 dB(A)
Fan sound power level OUT: SYD-250L
Lw1 99 94 91 85 85 82 81 78 101 dB
LwA1 73 78 83 82 85 84 82 76 90.8 dB(A)
Inlet:sound power level in the inlet cross section.
Lw3 97.3 91.8 84.8 77.8 75.8 70.8 69.8 58.8 98.6 dB
LwA3 71.1 75.7 76.2 74.6 75.8 72 70.8 57.7 82.7 dB(A)
Outlet:sound power level in outlet cross section.
Lw4 99 94 91 85 85 82 81 78 101 dB
LwA4 72.8 77.9 82.4 81.8 85 83.2 82 76.9 90.6 dB(A)
Unit: sound power level emitted by the unit wall with ducted inlet and ducted outlet in according with BS EN 13053.
Lp2 80.3 75.3 72.3 66.3 66.3 63.3 62.3 59.3 82.3 dB
LpA2 54.1 59.2 63.7 63.1 66.3 64.5 63.3 58.2 71.9 dB(A)
Note:
1.It should be particularly noted that the noise levels outside the unit are significantly influenced by the installation location and acoustic
of the environment (for example, size, absorption capacity, and reflection of the space).
2.Furthermore, other noise sources(other units, fans, traffic noise,…) can add to the noise levels indicated above.
3.As for RU noise in EUROVENT certification, the "Lw3, Lw4, LwA2" parameters above represent "Octave Band In-duct INTLET in dB", "Octave Band
In-duct OUTLET in dB" and "AIRBORNE Sound Power - in dB(A)" respectively.
Octave: 63 125 250 500 1000 2000 4000 8000 Total Unit
Fan sound power level IN: SYD-250L
Lw1 97 89 86 81 81 79 78 75 98.2 dB
LwA1 71 73 78 78 81 80 79 74 86.9 dB(A)
Fan sound power level OUT: SYD-250L
Lw1 97 89 86 81 81 79 78 75 98.2 dB
LwA1 71 73 78 78 81 80 79 74 86.9 dB(A)
Inlet:sound power level in the inlet cross section.
Lw3 96.5 88.5 84 79 78.5 76 75 68 97.5 dB
LwA3 70.3 72.4 75.4 75.8 78.5 77.2 76 66.9 84.3 dB(A)
Outlet:sound power level in outlet cross section.
Lw4 97 89 86 81 81 79 78 75 98.2 dB
LwA4 70.8 72.9 77.4 77.8 81 80.2 79 73.9 86.8 dB(A)
Unit: sound power level emitted by the unit wall with ducted inlet and ducted outlet in according with BS EN 13053.
Lw2 84.4 69.2 69.8 63.3 64.3 58.3 41.9 35.5 84.8 dB
LwA2 58.2 53.1 61.2 60.1 64.3 59.5 42.9 34.4 68.3 dB(A)
Unit: sound pressure level emitted by the unit wall under free field condition in according with EN ISO 3744, on a block-shaped
measurement surface that envelops the unit casing.
Lp2 65.3 50.1 50.7 44.2 45.2 39.2 22.8 16.4 65.7 dB
LpA2 39.1 34 42.1 41 45.2 40.4 23.8 15.3 49.2 dB(A)
Unit: sound pressure level emitted by the unit wall under free field condition in according with GB/T 9068, on a block-shaped
measurement surface that envelops the unit casing.
Lp2 78.3 70.3 67.3 62.3 62.3 60.3 59.3 56.3 79.5 dB
LpA2 52.1 54.2 58.7 59.1 62.3 61.5 60.3 55.2 68.1 dB(A)
Note:
1.It should be particularly noted that the noise levels outside the unit are significantly influenced by the installation location and acoustic
of the environment (for example, size, absorption capacity, and reflection of the space).
2.Furthermore, other noise sources(other units, fans, traffic noise,…) can add to the noise levels indicated above.
3.As for RU noise in EUROVENT certification, the "Lw3, Lw4, LwA2" parameters above represent "Octave Band In-duct INTLET in dB", "Octave Band
In-duct OUTLET in dB" and "AIRBORNE Sound Power - in dB(A)" respectively.
Octave: 63 125 250 500 1000 2000 4000 8000 Total Unit
Fan sound power level IN: SYD-315K
Lw1 96 99 88 87 85 83 81 76 101.4 dB
LwA1 70 83 80 84 85 84 82 75 91.2 dB(A)
Fan sound power level OUT: SYD-315K
Lw1 96 99 88 87 85 83 81 76 101.4 dB
LwA1 70 83 80 84 85 84 82 75 91.2 dB(A)
Inlet:sound power level in the inlet cross section.
Lw3 94.3 96.8 81.8 79.8 75.8 71.8 69.8 56.8 98.9 dB
LwA3 68.1 80.7 73.2 76.6 75.8 73 70.8 55.7 84.2 dB(A)
Outlet:sound power level in outlet cross section.
Lw4 96 99 88 87 85 83 81 76 101.4 dB
LwA4 69.8 82.9 79.4 83.8 85 84.2 82 74.9 91.1 dB(A)
Unit: sound power level emitted by the unit wall with ducted inlet and ducted outlet in according with BS EN 13053.
Lp2 77 80 69 68 66 64 62 57 82.4 dB
LpA2 50.8 63.9 60.4 64.8 66 65.2 63 55.9 72.1 dB(A)
Note:
1.It should be particularly noted that the noise levels outside the unit are significantly influenced by the installation location and acoustic
of the environment (for example, size, absorption capacity, and reflection of the space).
2.Furthermore, other noise sources(other units, fans, traffic noise,…) can add to the noise levels indicated above.
3.As for RU noise in EUROVENT certification, the "Lw3, Lw4, LwA2" parameters above represent "Octave Band In-duct INTLET in dB", "Octave Band
In-duct OUTLET in dB" and "AIRBORNE Sound Power - in dB(A)" respectively.
Octave: 63 125 250 500 1000 2000 4000 8000 Total Unit
Fan sound power level IN: SYD-355R
Lw1 84 90 81 81 80 77 76 71 92.3 dB
LwA1 58 74 73 78 80 79 77 70 85.4 dB(A)
Fan sound power level OUT: SYD-355R
Lw1 84 90 81 81 80 77 76 71 92.3 dB
LwA1 58 74 73 78 80 79 77 70 85.4 dB(A)
Inlet:sound power level in the inlet cross section.
Lw3 83.5 89.5 79 79 77.5 74 73 64 91.4 dB
LwA3 57.3 73.4 70.4 75.8 77.5 75.2 74 62.9 82.7 dB(A)
Outlet:sound power level in outlet cross section.
Lw4 84 90 81 81 80 77 76 71 92.3 dB
LwA4 57.8 73.9 72.4 77.8 80 78.2 77 69.9 85.2 dB(A)
Unit: sound power level emitted by the unit wall with ducted inlet and ducted outlet in according with BS EN 13053.
Lw2 71.4 70.2 64.8 63.3 63.3 56.3 39.9 31.5 75.1 dB
LwA2 45.2 54.1 56.2 60.1 63.3 57.5 40.9 30.4 66.5 dB(A)
Unit: sound pressure level emitted by the unit wall under free field condition in according with EN ISO 3744, on a block-shaped
measurement surface that envelops the unit casing.
Lp2 65 71 62 62 61 58 57 52 73.3 dB
LpA2 38.8 54.9 53.4 58.8 61 59.2 58 50.9 66.2 dB(A)
Note:
1.It should be particularly noted that the noise levels outside the unit are significantly influenced by the installation location and acoustic
of the environment (for example, size, absorption capacity, and reflection of the space).
2.Furthermore, other noise sources(other units, fans, traffic noise,…) can add to the noise levels indicated above.
3.As for RU noise in EUROVENT certification, the "Lw3, Lw4, LwA2" parameters above represent "Octave Band In-duct INTLET in dB", "Octave Band
In-duct OUTLET in dB" and "AIRBORNE Sound Power - in dB(A)" respectively.
Octave: 63 125 250 500 1000 2000 4000 8000 Total Unit
Fan sound power level IN: SYD-225L
Lw1 97 92 89 83 83 80 78 75 99 dB
LwA1 71 76 81 80 83 81 79 74 88.5 dB(A)
Fan sound power level OUT: SYD-225L
Lw1 97 92 89 83 83 80 78 75 99 dB
LwA1 71 76 81 80 83 81 79 74 88.5 dB(A)
Inlet:sound power level in the inlet cross section.
Lw3 95.8 89.8 83.8 75.8 74.3 69.8 67.8 60.8 97.1 dB
LwA3 69.6 73.7 75.2 72.6 74.3 71 68.8 59.7 81.2 dB(A)
Outlet:sound power level in outlet cross section.
Lw4 97 92 89 83 83 80 78 75 99 dB
LwA4 70.8 75.9 80.4 79.8 83 81.2 79 73.9 88.4 dB(A)
Unit: sound power level emitted by the unit wall with ducted inlet and ducted outlet in according with BS EN 13053.
Lw2 87.8 77.8 75.5 68.7 69.3 61.9 44.5 36.3 88.5 dB
LwA2 61.6 61.7 66.9 65.5 69.3 63.1 45.5 35.2 73.4 dB(A)
Unit: sound pressure level emitted by the unit wall under free field condition in according with EN ISO 3744, on a block-shaped
measurement surface that envelops the unit casing.
Lp2 69.2 59.2 56.9 50.1 50.7 43.3 25.9 17.7 69.9 dB
LpA2 43 43.1 48.3 46.9 50.7 44.5 26.9 16.6 54.8 dB(A)
Unit: sound pressure level emitted by the unit wall under free field condition in according with GB/T 9068, on a block-shaped
measurement surface that envelops the unit casing.
Lp2 78.8 73.8 70.8 64.8 64.8 61.8 59.8 56.8 80.8 dB
LpA2 52.6 57.7 62.2 61.6 64.8 63 60.8 55.7 70.2 dB(A)
Note:
1.It should be particularly noted that the noise levels outside the unit are significantly influenced by the installation location and acoustic
of the environment (for example, size, absorption capacity, and reflection of the space).
2.Furthermore, other noise sources(other units, fans, traffic noise,…) can add to the noise levels indicated above.
3.As for RU noise in EUROVENT certification, the "Lw3, Lw4, LwA2" parameters above represent "Octave Band In-duct INTLET in dB", "Octave Band
In-duct OUTLET in dB" and "AIRBORNE Sound Power - in dB(A)" respectively.
Octave: 63 125 250 500 1000 2000 4000 8000 Total Unit
Fan sound power level IN: SYD-225L
Lw1 94 87 85 78 79 76 75 72 95.5 dB
LwA1 68 71 76 75 79 78 76 71 84.6 dB(A)
Fan sound power level OUT: SYD-225L
Lw1 94 87 85 78 79 76 75 72 95.5 dB
LwA1 68 71 76 75 79 78 76 71 84.6 dB(A)
Inlet:sound power level in the inlet cross section.
Lw3 93.5 86.5 83 76 76.5 73 72 65 94.8 dB
LwA3 67.3 70.4 74.4 72.8 76.5 74.2 73 63.9 81.9 dB(A)
Outlet:sound power level in outlet cross section.
Lw4 94 87 85 78 79 76 75 72 95.5 dB
LwA4 67.8 70.9 76.4 74.8 79 77.2 76 70.9 84.4 dB(A)
Unit: sound power level emitted by the unit wall with ducted inlet and ducted outlet in according with BS EN 13053.
Lw2 81.4 67.2 68.8 60.3 62.3 55.3 38.9 32.5 81.9 dB
LwA2 55.2 51.1 60.2 57.1 62.3 56.5 39.9 31.4 66.2 dB(A)
Unit: sound pressure level emitted by the unit wall under free field condition in according with EN ISO 3744, on a block-shaped
measurement surface that envelops the unit casing.
Lp2 62.8 48.6 50.2 41.7 43.7 36.7 20.3 13.9 63.3 dB
LpA2 36.6 32.5 41.6 38.5 43.7 37.9 21.3 12.8 47.6 dB(A)
Unit: sound pressure level emitted by the unit wall under free field condition in according with GB/T 9068, on a block-shaped
measurement surface that envelops the unit casing.
Lp2 75.8 68.8 66.8 59.8 60.8 57.8 56.8 53.8 77.3 dB
LpA2 49.6 52.7 58.2 56.6 60.8 59 57.8 52.7 66.2 dB(A)
Note:
1.It should be particularly noted that the noise levels outside the unit are significantly influenced by the installation location and acoustic
of the environment (for example, size, absorption capacity, and reflection of the space).
2.Furthermore, other noise sources(other units, fans, traffic noise,…) can add to the noise levels indicated above.
3.As for RU noise in EUROVENT certification, the "Lw3, Lw4, LwA2" parameters above represent "Octave Band In-duct INTLET in dB", "Octave Band
In-duct OUTLET in dB" and "AIRBORNE Sound Power - in dB(A)" respectively.
Octave: 63 125 250 500 1000 2000 4000 8000 Total Unit
Fan sound power level IN: SYQ-500C
Lw1 87 85 83 96 88 85 80 73 97.8 dB
LwA1 61 69 75 92 88 87 81 72 94.6 dB(A)
Fan sound power level OUT: SYQ-500C
Lw1 87 85 83 96 88 85 80 73 97.8 dB
LwA1 61 69 75 92 88 87 81 72 94.6 dB(A)
Inlet:sound power level in the inlet cross section.
Lw3 86.3 83.3 79.8 90.8 81.8 77.8 72.8 65.8 93.4 dB
LwA3 60.1 67.2 71.2 87.6 81.8 79 73.8 64.7 89.3 dB(A)
Outlet:sound power level in outlet cross section.
Lw4 87 85 83 96 88 85 80 73 97.8 dB
LwA4 60.8 68.9 74.4 92.8 88 86.2 81 71.9 95 dB(A)
Unit: sound power level emitted by the unit wall with ducted inlet and ducted outlet in according with BS EN 13053.
Lp2 69.7 67.7 65.7 78.7 70.7 67.7 62.7 55.7 80.5 dB
LpA2 43.5 51.6 57.1 75.5 70.7 68.9 63.7 54.6 77.7 dB(A)
Note:
1.It should be particularly noted that the noise levels outside the unit are significantly influenced by the installation location and acoustic
of the environment (for example, size, absorption capacity, and reflection of the space).
2.Furthermore, other noise sources(other units, fans, traffic noise,…) can add to the noise levels indicated above.
3.As for RU noise in EUROVENT certification, the "Lw3, Lw4, LwA2" parameters above represent "Octave Band In-duct INTLET in dB", "Octave Band
In-duct OUTLET in dB" and "AIRBORNE Sound Power - in dB(A)" respectively.
Octave: 63 125 250 500 1000 2000 4000 8000 Total Unit
Fan sound power level IN: SYD-200L
Lw1 98 91 88 82 82 80 78 75 99.4 dB
LwA1 72 75 79 79 82 81 79 74 87.7 dB(A)
Fan sound power level OUT: SYD-200L
Lw1 98 91 88 82 82 80 78 75 99.4 dB
LwA1 72 75 79 79 82 81 79 74 87.7 dB(A)
Inlet:sound power level in the inlet cross section.
Lw3 97.3 89.3 84.8 76.8 75.8 72.8 70.8 67.8 98.2 dB
LwA3 71.1 73.2 76.2 73.6 75.8 74 71.8 66.7 82.6 dB(A)
Outlet:sound power level in outlet cross section.
Lw4 98 91 88 82 82 80 78 75 99.4 dB
LwA4 71.8 74.9 79.4 78.8 82 81.2 79 73.9 87.8 dB(A)
Unit: sound power level emitted by the unit wall with ducted inlet and ducted outlet in according with BS EN 13053.
Lp2 82.4 75.4 72.4 66.4 66.4 64.4 62.4 59.4 83.8 dB
LpA2 56.2 59.3 63.8 63.2 66.4 65.6 63.4 58.3 72.2 dB(A)
Note:
1.It should be particularly noted that the noise levels outside the unit are significantly influenced by the installation location and acoustic
of the environment (for example, size, absorption capacity, and reflection of the space).
2.Furthermore, other noise sources(other units, fans, traffic noise,…) can add to the noise levels indicated above.
3.As for RU noise in EUROVENT certification, the "Lw3, Lw4, LwA2" parameters above represent "Octave Band In-duct INTLET in dB", "Octave Band
In-duct OUTLET in dB" and "AIRBORNE Sound Power - in dB(A)" respectively.
Octave: 63 125 250 500 1000 2000 4000 8000 Total Unit
Fan sound power level IN: SYD-225L
Lw1 97 91 88 82 82 79 78 75 98.7 dB
LwA1 71 75 79 78 82 81 79 74 87.6 dB(A)
Fan sound power level OUT: SYD-225L
Lw1 97 91 88 82 82 79 78 75 98.7 dB
LwA1 71 75 79 78 82 81 79 74 87.6 dB(A)
Inlet:sound power level in the inlet cross section.
Lw3 96.3 89.3 84.8 76.8 75.8 71.8 70.8 67.8 97.4 dB
LwA3 70.1 73.2 76.2 73.6 75.8 73 71.8 66.7 82.4 dB(A)
Outlet:sound power level in outlet cross section.
Lw4 97 91 88 82 82 79 78 75 98.7 dB
LwA4 70.8 74.9 79.4 78.8 82 80.2 79 73.9 87.6 dB(A)
Unit: sound power level emitted by the unit wall with ducted inlet and ducted outlet in according with BS EN 13053.
Lp2 69.5 59.7 57.1 50.8 51.5 44.2 27.8 19.4 70.3 dB
LpA2 43.3 43.6 48.5 47.6 51.5 45.4 28.8 18.3 55.4 dB(A)
Unit: sound pressure level emitted by the unit wall under free field condition in according with GB/T 9068, on a block-shaped
measurement surface that envelops the unit casing.
Lp2 81.2 75.2 72.2 66.2 66.2 63.2 62.2 59.2 82.9 dB
LpA2 55 59.1 63.6 63 66.2 64.4 63.2 58.1 71.8 dB(A)
Note:
1.It should be particularly noted that the noise levels outside the unit are significantly influenced by the installation location and acoustic
of the environment (for example, size, absorption capacity, and reflection of the space).
2.Furthermore, other noise sources(other units, fans, traffic noise,…) can add to the noise levels indicated above.
3.As for RU noise in EUROVENT certification, the "Lw3, Lw4, LwA2" parameters above represent "Octave Band In-duct INTLET in dB", "Octave Band
In-duct OUTLET in dB" and "AIRBORNE Sound Power - in dB(A)" respectively.
Octave: 63 125 250 500 1000 2000 4000 8000 Total Unit
Fan sound power level IN: SYD-280R
Lw1 97 90 86 80 80 78 76 73 98.3 dB
LwA1 71 74 78 77 80 79 77 72 86 dB(A)
Fan sound power level OUT: SYD-280R
Lw1 97 90 86 80 80 78 76 73 98.3 dB
LwA1 71 74 78 77 80 79 77 72 86 dB(A)
Inlet:sound power level in the inlet cross section.
Lw3 96.3 88.3 82.8 74.8 73.8 70.8 68.8 65.8 97.2 dB
LwA3 70.1 72.2 74.2 71.6 73.8 72 69.8 64.7 80.8 dB(A)
Outlet:sound power level in outlet cross section.
Lw4 97 90 86 80 80 78 76 73 98.3 dB
LwA4 70.8 73.9 77.4 76.8 80 79.2 77 71.9 85.9 dB(A)
Unit: sound power level emitted by the unit wall with ducted inlet and ducted outlet in according with BS EN 13053.
Lp2 69.2 58.4 54.8 48.5 49.2 42.9 25.5 17.1 69.8 dB
LpA2 43 42.3 46.2 45.3 49.2 44.1 26.5 16 53.5 dB(A)
Unit: sound pressure level emitted by the unit wall under free field condition in according with GB/T 9068, on a block-shaped
measurement surface that envelops the unit casing.
Lp2 80.9 73.9 69.9 63.9 63.9 61.9 59.9 56.9 82.2 dB
LpA2 54.7 57.8 61.3 60.7 63.9 63.1 60.9 55.8 69.8 dB(A)
Note:
1.It should be particularly noted that the noise levels outside the unit are significantly influenced by the installation location and acoustic
of the environment (for example, size, absorption capacity, and reflection of the space).
2.Furthermore, other noise sources(other units, fans, traffic noise,…) can add to the noise levels indicated above.
3.As for RU noise in EUROVENT certification, the "Lw3, Lw4, LwA2" parameters above represent "Octave Band In-duct INTLET in dB", "Octave Band
In-duct OUTLET in dB" and "AIRBORNE Sound Power - in dB(A)" respectively.