Article 517 Course Final
Article 517 Course Final
4 hours
Article 517 Health Care Facilities
As stated in the 2011 Code, health care facilities are comprised of seven (7) different sections.
I. General,
V. X-Ray Installations,
VI. Communications, Signaling Systems, Data Systems, Fire Alarm Systems, and systems less than 120
volts, Nominal,
Parts I and II are the most general of the article. Part I gives a general scope and the definitions portion
of the entire article. Part II is the Wiring and Protection section for all patient care areas of health care
facilities. The other five (5) parts are dedicated to specific locations and/or systems through out Health
Care Facilities.
Article 517.1:
According to the 2011 Code, the provisions of this article shall apply to electrical construction and
installation criteria in health care facilities that provide services to humans. The requirements in part II
and III not only apply to single function buildings but also intended to be individually used to their
respective forms of occupancy with in a multifunction building. (e.g. a doctors examining room located
within a limited care facility would be required to meet the provisions of 517.10).
EXAM QUESTIONS:
1) Out of the seven (7) different parts of Article 517, where would you find the definitions
portion of the article?
A) VII. Isolated Power Systems
B) II. Wiring and Protection
C) I. General
D) V. X-Ray Installations
4) Would a doctor’s examining room located in a limited care facility be required to meet
the provisions of 517.10?
A) Yes
B) No
Equipment System is a system of circuits and equipment arranged for delayed, automatic, or manual
connection to a alternative power source and that serves mainly 3-phase power equipment.
Battery Powered Lighting Units are individual unit equipment for back up lighting consisting of the
following.
1) Rechargeable battery
2) Battery-charging means
3) Provisions for one or more lamps mounted on the equipment, or with terminals for remote
lamps or both.
4) Relaying device arranged to energize the lamps automatically upon failure of the power to
the unit or equipment.
Patient Bed Location: The area of a patients’ sleeping bed or the bed or procedure table of a critical
care area.
Patient Care Area is any portion of a health facility where patients are intended to be examined or
treated. Areas of a health care facility are determined by the governing body of the facility. The
governing body designates these areas in accordance with the type of patient care anticipated in each
area.
Informational note: Business offices, corridors, lounges, day rooms, dining rooms, or similar areas are
not classified as patient care areas.
Emergency System: is a system of circuitry and equipment specifically to supply alternate power to a
limited number of prescribed functions vital to the protection of life and safety.
Patient Equipment Grounding Point ‘s are jack’s or terminal’s that serve as the collection point for
redundant grounding of electrical appliances for patient care vicinity or for grounding other items in
order to eliminate electromagnetic interference problems.
Patient Care Vicinity is an area in which patients are cared for. It is a space with surfaces likely to be
contacted by the patient or an attendant who can come in contact with the patient. In a patient room, the
space within the room is not less than 6 ft. (1.8m) beyond the perimeter of the bed in its normal location,
and extending vertically no more than 7 ½ ft. ( 2.3 m) above the floor.
Task Illumination is provisions for the minimum lighting required to carry out necessary tasks in
certain areas, including but not limited to safe access to supplies and equipment, and access to exits.
7) Battery powered lighting units are individual equipment for back up illumination
consisting of all but one of the following:
A) Battery charging means
B) Rechargeable battery
C) Manual or automatic means of switching
D) Provisions for one or more lamp to be mounted on the equipment
8) The location of a sleeping bed, or procedure table in a critical care area is called a ____?
A) Nursing home
B) Limited facility
C) Patient care area
D) Patient bed location
11) A system of circuitry and equipment specifically to supply alternate power to a limited
number of prescribed functions vital to the protection of life and safety.
A) Emergency system
B) Critical branch
C) Alternate power source
D) Electrical life-support equipment
12) A jack or terminal that serves as the collection point for redundant grounding of
electrical appliances for patient care vicinity or for grounding other items in order to
eliminate electromagnetic interference problems.
A) Reference grounding point
B) Patient equipment grounding point
C) Selected receptacles
D) Psychiatric hospital
13) A patient care vicinity is an area in which the patient’s are cared for. It is a space where
the patient or attendant may come into contact with surfaces
A) True
B) False
14) In a patient room, the space within the room is not less than ________beyond the
perimeter of the bed in its normal location, and extending vertically no more than
________ above the floor.
A) 7 ½ ft; 6 ft
B) 8 ft; 7 ½ ft
C) 6 ft; 7 ½ ft
D) 5 ft; 8 ft
15) Selected receptacles are the orange with green dot receptacles designated for
emergency equipment in a patient care facility.
A) True
B) False
16) Does the installation of exit lights fall under the definition of Task Illumination?
A.) Yes
B.) No
II. Wiring and Protection
(A) Applicability – Part II shall apply to patient care areas of all health care facilities.
(1) Business offices, corridors, waiting rooms, and the areas in like in a clinic, medical or dental
office.
(2) Areas of a nursing home and limited care facilities wired in accordance with chapter one of
the code where the named areas are used solely as patient sleeping rooms.
As stated in the 2011 Code, the equipment grounding terminal buses of the normal and essential branch-
circuit panel boards serving the same individual patient care vicinity shall be connected together with an
insulated continuous copper conductor not smaller than 10 AWG. Where two or more panel boards
serving the same individual patient care vicinity are served from separate transfer switches on the
emergency system, the equipment grounding bus of those panels shall be connected together with an
insulated continuous copper conductor no smaller than a 10 AWG. This conductor shall be permitted to
be broken in order to terminate on the equipment grounding terminal bus in each panel board.
As described in the 2011 Code, receptacles with insulated grounding terminals, as described in
250.146(D), shall not be permitted in Health Care Facilities.
As required by the 2011 Code, each patient bed location shall be supplied by at least two branch circuits,
one from the emergency system and one from the normal system. All branch circuits from the normal
system shall originate in the same panel board. The branch circuits serving patient bed locations shall
not be part of a multi-wire branch circuit.
Exception NO 1: Branch circuits serving only special purpose outlets or receptacles, such as portable X-
ray outlets, shall not be required to be served from the same panel board or distribution panel.
Exception NO 2: Requirements of 517.18(A) shall not apply to patient bed locations in clinics, medical
and dental offices, and out patient facilities; psychiatric, substance abuse, and rehabilitation hospitals;
sleeping rooms of nursing homes and limited care facilities meeting the requirements of 517.10(B)(2)
Exception NO 3: A general care patient bed location served from two separate transfer switches on the
emergency system shall not be required to have circuits from the normal system.
17) Part II of this code ________ apply to business offices, corridors, waiting rooms, and
the areas in like in a clinic, medical or dental office.
A) Shall
B) Shall not
C) Will
D) Will Not
18) The equipment grounding terminal buses of the normal and essential branch-circuit
panel boards serving the same individual patient care vicinity are required to be connected
together with an insulated continuous copper conductor not smaller than __________.
A) 8 AWG
B) 6 AWG
C) 4 AWG
D) 10 AWG
20) If two or more panel boards serving the same individual patient care vicinity are served
from separate _________________ on the emergency system, the equipment grounding bus
of those panels shall be connected together with an insulated continuous copper conductor
no smaller than a 10 AWG.
A) Panel boards
B) Transfer switches
C) Disconnects
D) Terminals
22) Each patient bed location shall be supplied by at least two branch circuits, one from the
_________________ and one from the normal system.
A) Isolated system
B) Emergency system
C) Essential electrical system
D) Life safety system
23) ____________ serving only special purpose outlets or receptacles, such as portable X-
ray outlets, shall not be required to be served from the same panel board or distribution
panel.
A) Emergency systems
B) Critical care systems
C) Branch circuits
D) Standby power
24) A general care patient bed location served from __________ separate transfer switches
on the emergency system shall not be required to have circuits from the normal system.
A) Two
B) Three
C) One
D) Five
517.19 Critical Care Areas (A) Patient Bed Location Branch Circuits.
As stated in the 2011 Code, each patient bed location shall be supplied by at least two circuits, one or
more from the emergency system and one or more from the normal system. At least one branch circuit
from the emergency panel shall supply a receptacle only at that bed location. Emergency system outlets
shall also indicate the panel board and circuit breaker number.
As required by the 2011 Code, each patient bed location must be supplied with at least six receptacles; at
least one shall be connected to either of the following:
(2) A emergency system circuit supplied by a different transfer switch than the other outlets at
the same patient bed location
517.19 Critical Care Areas (C) Patient care vicinity grounding and bonding (optional)
As stated in the 2011 Code, a patient care vicinity shall be permitted to have a patient equipment
grounding point. The patient equipment grounding point, where installed, shall be permitted to contain
one or more listed grounding and bonding jacks. An equipment bonding jumper no smaller than a 10
AWG shall be used to connect the grounding terminal of all ground type receptacles to the patient
equipment grounding point. The bonding conductor shall be permitted to be arranged in the center of or
looped as convenient.
As required by the 2011 Code, and where a grounded electrical distribution system is used and metal
feeder raceway or Type MC or MI cable that qualifies as an equipment grounding conductor in
accordance with 250.118 is installed, grounding of enclosures and equipment, such as panel boards and
switch boards, shall be ensured by one of the following bonding means at each termination or junction
point of the metal raceway or type MC or MI cable:
(1) A grounding bushing and a continuous copper bonding jumper, sized in accordance with
250.122, with the bonding jumper connected to the junction enclosure or the ground bus of the
panel.
(2) Connection of feeder raceway or type MC or MI cable to threaded hubs or busses on termination
enclosures.
(3) Other approved devices such as bonding type lock nuts or bushings.
25) At least one branch circuit from the emergency panel shall supply a ____________ only
at that bed location.
A) Luminaries
B) GFI
C) Receptacle
D) Outlet
26) Each patient bed location must be ________________ with at least six receptacles.
A) Supplied
B) Equipped
C) Connected
D) Energized
28) The patient equipment grounding point, if installed, is required to contain one or more
________ grounding and bonding jacks.
A) Labeled
B) Listed
C) Approved
D) All of the above
29) If a grounded electrical distribution system is used, the metal feeder raceway or type
MC or MI cable that is made as an equipment grounding conductor must be installed as
per ________.
A) 210.16
B) 250.66
C) 310.16
D) 250.118
As stated in the 2011 NEC, where an isolated ungrounded power source is used and limits the first fault
current to a low magnitude, the equipment grounding conductor associated with the secondary circuit
shall be permitted to run outside of the enclosure of the power conductors in the same circuit.
As stated in the 2011 Code, the equipment grounding conductor for special purpose outlets, such as
operation of mobile x-ray equipment, shall be extended to the reference grounding points of branch
circuits for all locations likely to be served from each outlet. Where such a circuit is served from an
isolated ungrounded system, the grounding conductor shall not be required to be run with the power
conductors; however the equipment grounding terminal of the special purpose outlet shall be connected
to the reference grounding point.
As required by the 2011 Code, wet procedure location patient care areas shall be provided with special
protection against electric shock by one of the following:
(1) Power distribution system that inherently limits the possible ground fault current due to the
first fault to a low value, without interrupting the power supply.
(2) Power distribution system in which the power supply is interrupted if the ground fault current
does, in fact, exceed a value of 6 mA.
As required by the 2011 Code where an isolated power system is utilized, the isolated power equipment
shall be listed as isolated power equipment, and the isolated power system shall be designed and
installed according to 517.160.
As stated in the 2011 Code, a ground fault circuit interrupter for protection of personnel shall not be
required for receptacles installed in those critical care areas where the toilet and basin are installed
within the patient room.
517.25 Scope
As stated in the 2011 Code, the essential electrical system for these facilities shall comprise a system
capable of supplying a limited amount of lighting and power service, which is considered essential for
life safety and orderly cessation of procedures during the time normal electrical service, is interrupted
for any reason. This includes clinics, medical and dental offices, out patient facilities, nursing homes,
limited care facilities, hospitals and other health care facilities serving patients.
31) The equipment grounding conductor used for critical care areas and associated with
the __________ circuit shall be permitted to run outside of the enclosure of the power
conductors in the same circuit.
A) Secondary
B) Primary
C) Line side
D) Load side
32) The grounding conductor for mobile x-ray equipment is not required to be run with the
_________ conductors.
A) Line
B) Load
C) Signal
D) Power
33) A Power distribution system in wet procedure location patient care areas that
inherently limits the possible ground fault current due to the first fault to a low value,
without ________ the power supply.
A) Spiking
B) Ground fault
C) Limiting
D) Interrupting
35) A ground fault circuit interrupter for ______________ of personnel shall not be
required for receptacles installed in critical care areas where the toilet and basin are
installed within the patient room.
A) Patients
B) Doctors
C) Protection
D) Nurses
36) The Scope of section III tells us that Essential Electrical Systems are required to do
what in all health care facilities?
A) Supply a limited amount of lighting and power service
B) Supply only equipment power
C) Supply emergency power to only hospitals
D) Supply emergency lighting to dental offices
As required by the 2011 Code, essential electrical systems for hospitals shall be comprised of two
separate systems capable of supplying a limited amount of lighting and power service that is considered
essential for life safety and effective hospital operation during the time the normal electrical service is
interrupted for any reason. These two systems shall be the emergency system and the equipment system.
517.30 Essential Electrical Systems for Hospitals (B)(2) General
As required by the 2011 Code, the emergency system shall be limited to circuits essential to life safety
and critical patient care. These are designated as the life safety branch and the critical branch.
As required by the 2011 Code, the equipment system shall supply major electrical equipment necessary
for patient care and basic hospital operations.
As required in the 2011 Code, the number of transfer switches to be used shall be based on reliability,
design, and load considerations. Each branch of both the emergency and equipment system shall have
more than one transfer switch. One transfer switch shall be permitted to serve one or more branches or
systems in a facility with a maximum demand on the essential electrical system of 150 kVA.
38) The Essential Electrical System is comprised of two different systems. What are they?
A) Normal and emergency systems
B) Emergency and equipment systems
C) Equipment and normal systems
D) Lighting and equipment systems
39) The emergency system is ___________ to circuits essential to life safety and critical
patient care.
A) Critical
B) Emergency
C) Limited
D) Branch circuits
40) The hospital emergency equipment is used to supply equipment _____________ for care
and hospital operation.
A) Necessary
B) Required
C) Needed
D) Wanted
41) The number of transfer switches to be used in hospitals shall be based on reliability,
design, and __________________ considerations.
A) Load
B) Manufacturer
C) Authority having jurisdiction
D) Contractor
42) One hospital transfer switch may be used to serve one or more branches or systems if
the demand on the essential electrical system does not exceed ___________.
A) 125 kVA
B) 200 kVA
C) 150 kVA
D) 100 kVA
517.30 Essential Electrical Systems for Hospitals (C) Wiring Requirements (1) Separation from
Other Circuits
The life safety branch and the critical branch of the emergency system shall be kept entirely independent
of all other wiring and equipment and shall not enter the same raceways, boxes, or cabinets with each
other or other wiring.
Wiring of the life safety branch and the critical branch shall be permitted to occupy the same raceways,
boxes, or cabinets of other circuits not part of the branch where such wiring complies with one of the
following:
4) Is for two or more emergency circuits supplied from the same branch and same transfer switch
The wiring of the equipment system shall be permitted to occupy the same raceways, boxes, or cabinets
of other circuits that are not part of the emergency system.
517.30 Essential Electrical Systems for Hospitals (C) Wiring Requirements (2) Isolated Power
Systems
Where isolated power systems are installed in any of the areas in 517.33 (A) (1) and
(A) (2), each system shall be supplied by an individual circuit serving no other load.
Mechanical Protection of the Emergency Circuits as required by the 2011 code, and the wiring of the
emergency systems in hospitals shall be mechanically protected. Where installed as branch circuits in
patient care areas, the installation shall comply with the requirements of 517.13(A) and (B). The
following wiring methods shall be permitted.
(1) Nonflexible metal raceways, type MI cable, or schedule 80 PVC conduits. Nonmetallic
raceways shall not be used for branch circuits that supply patient care areas.
(2) Where encased in not less than 50mm (2in) of concrete, Schedule 40 PVC conduit, flexible
nonmetallic or jacketed metallic raceways, or jacketed metallic cable assemblies listed for
installation in concrete. Nonmetallic raceways shall not be used for branch circuits that supply
patient care areas.
(3) Listed flexible metal raceways and listed metal sheathed cable assemblies in any of the
following:
c. Where fished into existing walls or ceilings, not otherwise accessible and not subject to
physical damage.
(4) Flexible power cords of appliances or other utilization equipment connected to the
emergency system.
(5) Cables for class 2 or class 3 systems permitted by Part IV of this article, with or without
raceways.
43) Which two branches of the hospital emergency system are required to be kept entirely
independent of all other wiring and equipment and shall not enter the same raceways,
boxes, or cabinets with each other or other wiring.
A) Equipment branch and critical branch
B) Life safety branch and emergency branch
C) Transfer switch and emergency branch
D) Life safety branch and the critical branch
44) The hospital wiring of the equipment systems shall be permitted to occupy the same
raceways, boxes, or cabinets of other circuits that are not part of the emergency system.
A) True
B) False
45) Where a isolated system is installed, each system will be served by a individual circuit
serving ______________ load.
A) One other
B) Two other
C) No other
D) Four other
46) Where installed as branch circuits in patient care areas, the installation shall comply
with the requirements of _________________ (A) and (B).
A) 517.13
B) 518.13
C) 514.13
D) 310.16
47) _____________ raceways shall not be used for branch circuits that supply patient care
areas.
A) Nonflexible
B) Type MI
C) Nonmetallic
D) Schedule 80 PVC
48) Where a raceway is in ________ of concrete for a patient care area, the assemblies must
be listed for installation in concrete.
A) 3 inches
B) 2 inches
C) 4 inches
D) 1 inches
49) Flexible metal raceways and listed metal sheathed cable assemblies for a patient care
area are allowed only in which of the following.
A) Where fished into existing walls or ceilings, not otherwise accessible and not subject to
physical damage.
B) Mechanical rooms
C) Between the emergency and normal power systems
D) Coming out of concrete
50) Cables for ______________ systems are permitted by Part IV of article 517, with or
without raceways.
A) Class 2 or class 3
B) Class 1 or class 3
C) Class 2 or class 4
D) Emergency
As stated in the 2011 Code, the essential electrical system shall have adequate capacity to meet the
demand for the operation of all functions and equipment to be served by each system branch.
Feeders shall be sized in accordance with Article 215 and 220. The generator set shall have sufficient
capacity and proper rating to meet the demand produced by the load of the essential electrical systems at
any given time.
Demand calculations for sizing of the generator set shall be based on any of the following
The sizing requirements in 700.4 and 701.4 shall not apply to hospital generator sets.
As required by this article in the 2011 Code, the cover plates for the electrical receptacles or the
electrical receptacles them selves, supplied from the emergency system shall have a distinctive color or
marking so as to be readily identifiable.
According to the 2011 Code, no function other than those listed in 517.32 (A) through (H) shall be
connected to the life safety branch. The life safety branch of the emergency system shall supply power
for the following lighting, receptacles, and equipment.
As described in the 2011 code, illumination of means of egress, such as lighting required for corridors,
passageways, stairways, and landings at exit doors, and all necessary ways of approach to exits.
Switching arrangements to transfer patient corridor lighting in hospitals from general illumination
circuits to night illumination circuits shall be permitted, provided only one of the two circuits can be
selected and both circuits cannot be extinguished at the same time.
As stated in the 2011 NEC, exit signs and directional signs will be connected to the life safety branch of
the emergency system.
51) Article 517 requires the essential electrical system shall have adequate capacity to meet
the demand for the operation of all _____________ and equipment to be served by each
system branch.
A) Systems
B) Functions
C) Electrical
D) Loads
52) Demand calculations in article 517 for sizing of the generator conductor set(s) shall be
based on any of the following.
A) Connected load
B) Feeder calculations based on Article 220
C) Prudent demand factors and historical data
D) All listed answers
53) Cover plates or the _____________ it’s self, supplied from the emergency system in
essential electrical systems for hospitals shall have a distinctive color or markings.
A) Wire
B) Switch
C) Device
D) Receptacle
54) The life safety branch of the emergency system shall supply power for the following
lighting, __________________, and equipment.
A) Devices
B) Switch
C) Receptacles
D) Enclosures
55) Illumination for means of egress which is connected to the life safety branch circuit for
the hospital emergency system lighting is _______________ for corridors, passageways,
stairways, and landings at exit doors, and all necessary ways of approach to exits.
A) Required
B) Selected
C) Any lighting
D) Approaches
56) Switching from day illumination to night illumination as stated in article 517 is allowed
as long as ________________.
A) Both are on
B) Both are off
C) Only one of the two circuits can be selected.
D) Both circuits can be switched simultaneously.
57) Exit and directional signs used in health care facilities will be connected to the
____________ of the emergency system.
A) Critical branch
B) Life safety branch
C) Source of power
D) Emergency branch
As stated in the 2011 Code, alarm and alerting systems including all of the following:
(2) Alarms required for systems used for the piping of non flammable medical gases.
(3) Mechanical, control, and other accessories required for effective life safety systems operation shall
be permitted to be connected to the life safety branch.
The 2011 Code Requires the critical branch of the emergency system to supply power for task
illumination, fixed equipment, selected receptacles, and special power circuits serving the following
areas and functions related to patient care:
(1) Critical care areas that utilize anesthetizing gases – task illumination, selected receptacles, and fixed
equipment.
(3) Patient care areas – task illumination and selected receptacles in the following areas:
(4) Additional specialized patient care task illumination and receptacles, where needed.
(9) Additional task illumination, receptacles, and selected power circuits needed for effective
hospital operation. Single-phase fractional horsepower motors shall be permitted to be connected
to the critical branch.
58) Mechanical, control, and other accessories required for effective life safety systems
operation in article 517 shall be permitted to be ________________ to the life safety
branch.
A) Hooked
B) Connected
C) Directed
D) In line
60) The critical branch of the emergency system shall supply power for patient care areas.
Which of the following is not a patient care area?
A) Medication preparation areas
B) General waiting rooms and corridors
C) Psychiatric bed areas
D) Infant nurseries
61) Task illumination, selected receptacles, and selected power circuits for General care
beds will have?
A) All lighting in patient rooms
B) All receptacles adjacent to bed location
C) Hallway receptacles closest to nurse’s station
D) At least one duplex receptacle in each patient bedroom
As required by this code, the equipment system shall be installed and connected to the alternate
power source such that the equipment described in 517.34(A) is automatically restored to
operation at appropriate time-lag intervals following the energizing of the emergency system. Its
arrangement shall also provide for the subsequent connection of equipment described in
517.34(B).
Exception: For essential electrical systems less than 150 kVA, deletion of the time-lag intervals
feature for delayed automatic connection to the equipment system shall be permitted.
517.34 Equipment System Connection to Alternate Power Source (A) Equipment for
Delayed Automatic Connection.
As stated in the 2011 Code, the following equipment shall be permitted to be arranged for
delayed automatic connection to the alternate power source:
1) Central suction systems serving medical and surgical functions, including controls. Such
suction systems shall be permitted on the critical branch.
(2) Sump pumps and other equipment required to operate for the safety of major apparatus,
including associated control systems and alarms.
(3) Compressed air systems serving medical and surgical functions, including controls. Such air
systems shall be permitted on the critical branch.
(5) Kitchen hood supply or exhaust systems, or both, if required to operate during a fire in or
under the hood.
(6) Supply, return, and exhaust ventilating systems for airborne infectious/isolation rooms,
protective environment rooms, exhaust fans for laboratory fume hoods, nuclear medicine areas
where radioactive material is used, ethylene oxide evacuation, and anesthesia evacuation. Where
delayed automatic connection is not appropriate; such ventilation systems shall be permitted to
be placed on the critical branch.
(7) Supply, return, and exhaust ventilating systems for operating and delivery rooms.
Exception: Sequential delayed automatic connection to the alternate power source to prevent
overloading the generator shall be permitted where engineering studies indicate it is necessary.
517.34 Equipment System Connection to Alternate Power Source (B) Equipment for
Delayed Automatic or Manual Connection
The 2011 Code describes the following equipment shall be permitted to be arranged for either
delayed automatic or manual connection to the alternate power source:
(1) Heating equipment to provide heating for operating, delivery, labor, recovery, intensive care,
coronary care, nurseries, infection/isolation rooms, emergency treatment spaces, and general
patient rooms and pressure maintenance (jockey or make-up) pump(s) for water based fire
protection systems.
Exception: Heating of general patient rooms and infection/isolation rooms during disruption of
the normal source shall not be required under any of the following
conditions:
(2) The outside design temperature is lower than −6.7°C (20°F), and where a selected
room(s) is provided for the needs of all confined patients, only such room(s) need be
heated.
Informational Note No. 1: The design temperature is based on the 971⁄2 percent design value as
shown in Chapter 24 of the ASHRAE Handbook of Fundamentals (1997).
Informational Note No. 2: For a description of a dual source of normal power, see 517.35(C)
Informational Note.
(2) An elevator(s) selected to provide service to patient, surgical, obstetrical, and ground floors
during interruption of normal power. In instances where interruption of normal power would
result in other elevators stopping
between floors, throw-over facilities shall be provided to allow the temporary operation of any
elevator for the release of patients or other persons who may be
confined between floors.
(3) Hyperbaric facilities.
(6) Minimal electrically heated autoclaving equipment shall be permitted to be arranged for
either automatic or manual connection to the alternate source.
(8) Other selected equipment shall be permitted to be served by the equipment system.
63) It shall be permitted to _____________ the health care facility critical branch circuit
into two or more branches.
A) Subdivide
B) Tap
C) Split
D) Narrow down
64) The health care facility equipment system shall be installed and connected to the
alternate power source such that the equipment described in ________ is automatically
restored to operation at appropriate time-lag intervals following the energizing of the
emergency system.
A) 517.12
B) 322.38
C) 517.34(A)
D) 240.12(A)(2)(b)
65) Which of the following equipment shall not be permitted to be arranged for delayed
automatic connection to the alternate power source with regards to health care facilities?
A) Lighting control panels in critical care areas.
B) Sump pumps and other equipment required to operate for the safety of major apparatus.
C) Smoke control and stair pressurization systems, or both.
D) Central suction systems serving medical and surgical functions, including controls
67) Article 517 allows the following equipment shall be permitted to be arranged for either
delayed automatic or manual connection to the alternate power source.
As required by the 2011 Code, generator accessories, including but not limited to, the transfer
fuel pump, electrically operated louvers, and other generator accessories essential for generator
operation, shall be arranged for automatic connection to the alternate power source.
517.35 Sources of Power (A) Two Independent Sources of Power
As required by the 2011 Code, the essential electrical systems shall have a minimum of two
independent sources of power: a normal source generally supplying the entire electrical system
and one or more alternate sources for use when the normal source is interrupted.
517.35 Sources of Power (B) Alternate Source of Power.
As stated in this code, the alternate source of power shall be one of the following:
(1) Generator(s) driven by some form of prime mover(s) and located on the premises
(2) Another generating unit(s) where the normal source consists of a generating unit(s) located
on the premises
(3) An external utility service when the normal source consists of a generating unit(s) located on
the premises
As required by the 2011 Code, careful consideration shall be given to the location of the spaces
housing the components of the essential electrical system to minimize interruptions caused by
natural forces common to the area (e.g., storms, floods, earthquakes, or hazards created by
adjoining structures or activities). Consideration shall also be given to the possible interruption
of normal electrical services resulting from similar causes as well as possible disruption of
normal electrical service due to internal wiring and equipment failures.
517.40 Essential Electrical Systems for Nursing Homes and Limited Care Facilities
(B) Inpatient Hospital Care Facilities
The 2011 code states that those nursing homes and limited care facilities that admit patients who
need to be sustained by electrical life support equipment, the essential electrical system from the
source to the portion of the facility where such patients are treated shall comply with the
requirements of Part III, 517.30 through 517.35.
68) _____________ accessories not limited to the transfer fuel pump, electrically operated
louvers, and other generator accessories as described in article 517.
A) Emergency
B) Generator
C) Equipment
D) Fixed equipment
69) Essential health care facility electrical systems shall have a minimum of __________
independent sources of power
A) Three
B) One
C) Five
D) Two
70) In Article 517.35 (B), all alternate power sources have one main thing in common
A) All are green energy
B) All are generator power
C) Must be on premises
D) Utility driven
71) Article 517 requires careful consideration to be given to the location of the spaces
housing the components of the ____________ electrical system to minimize interruptions
caused by natural forces common to the area
A) Essential
B) Emergency
C) Isolated
D) Life safety
72) Nursing homes and limited care facilities that admit patients who need to be sustained
by _____________ life support equipment.
A) Emergency
B) Essential
C) Required
D) Electrical
517.35 Sources of Power (C) Facilities Contiguous or Located on the Same Site with
Hospitals
As stated in the 2011 Code, careful consideration shall be given to the location of the spaces
housing the components of the essential electrical system to minimize interruptions caused by
natural forces common to the area (e.g., storms, floods, earthquakes, or hazards created by
adjoining structures or activities). Consideration shall also be given to the possible interruption
of normal electrical services resulting from similar causes as well as possible disruption of
normal electrical service due to internal wiring and equipment failures.
Informational Note: Facilities in which the normal source of power is supplied by two or more
separate central station-fed services experience greater than normal electrical service reliability
than those with only a single feed. Such a dual source of normal power consists of two or more
electrical services fed from separate generator sets or a utility distribution network that has
multiple power input sources and is arranged to provide mechanical and electrical separation so
that a fault between the facility and the generating sources is not likely to cause an interruption
of more than one of the facility service feeders.
517.40 Essential Electrical Systems for Nursing Homes and Limited Care Facilities. (A)
Applicability.
In the 2011 Code, the requirements of Part III, 517.40(C) through 517.44, shall apply to nursing
homes and limited care facilities.
Exception: The requirements of Part III, 517.40(C) through 517.44, shall not apply to
freestanding buildings used as nursing homes and limited care facilities, provided that the
following apply:
(a) Admitting and discharge policies are maintained that preclude the provision of care
for any patient or resident who may need to be sustained by electrical life support
equipment.
517.40 Essential Electrical Systems for Nursing Homes and Limited Care Facilities (B)
Inpatient Hospital Care Facilities.
The 2011 Code states that for those nursing homes and limited care facilities that admit patients
who need to be sustained by electrical life support equipment, the essential electrical system
from the source to the portion of the facility where such patients are treated shall comply with
the requirements of Part III, 517.30 through 517.35.
517.40 Essential Electrical Systems for Nursing Homes and Limited Care Facilities (C)
Facilities Contiguous or Located on the Same Site with Hospitals.
As described in the 2011 Code, nursing homes and limited care facilities that are contiguous or
located on the same site with a hospital shall be permitted to have their essential electrical
systems supplied by that of the hospital.
As required by the 2011 Code, the essential electrical systems for nursing homes and limited care
facilities shall be comprised of two separate branches capable of supplying a limited amount of
lighting and power service, which is considered essential for the protection of life safety and
effective operation of the institution during the time normal electrical service is interrupted for
any reason. These two separate branches shall be the life safety branch and the critical branch.
73) Article 517 requires careful consideration to be given to the location of the essential
electrical system to minimize interruptions created by natural ____________ common to
the area.
A) Elements
B) Forces
C) Hazards
D) Human
75) If a limited care facility admits patients who need to be sustained by electrical life
support equipment, the _____________ electrical system from the source to the portion of
the facility where patients are treated must comply with part III of article 517.
A) Essential
B) Emergency
C) Life safety
D) Normal
76) A _______________ that is contiguous or on same site as a hospital is allowed to have its
essential system supplied by the hospital.
A) Hospital
B) Nursing home
C) ICU
D) Entry way
77) Essential electrical systems for nursing homes and limited care facilities shall be
comprised of two separate branches capable of supplying a ______________ amount of
lighting and power service.
A) Limited
B) Maximum
C) Small
D) Selected
As stated in the 2011 Code, the number of transfer switches to be used shall be based on
reliability, design, and load considerations. Each branch of the essential electrical system shall be
served by one or more transfer switches. One transfer switch shall be permitted to serve one or
more branches or systems in a facility with a maximum demand on the essential electrical system
of 150 kVA.
As required by the 2011 NEC, the essential electrical system shall have adequate capacity to
meet the demand for the operation of all functions and equipment to be served by each branch at
one time.
517.41 Essential Electrical Systems (D) Separation from Other Circuits.
It states in the 2011 Code that the life safety branch shall be kept entirely independent of all other
wiring and equipment and shall not enter the same raceways, boxes, or cabinets with other
wiring except as follows:
(3) In a common junction box attached to exit or emergency luminaries supplied from
two sources
The wiring of the critical branch shall be permitted to occupy the same raceways, boxes,
or cabinets of other circuits that are not part of the life safety branch.
78) The number of transfer switches to be used for essential electrical systems shall be
based on reliability, design, and _______________ considerations.
A) Line
B) Power
C) Sustainability
D) Load
79) The essential electrical system shall have adequate capacity to meet the______________
for the operation of all functions and equipment to be served by each branch at one time.
A) Liability
B) Authority having jurisdiction
C) Demand
D) Leverage
80) The life safety branch of an essential electrical system shall be kept entirely
______________ of all other wiring and equipment.
A) Separated
B) Combined
C) Independent
D) Together
81) The wiring of the _______________branch shall be permitted to occupy the same
raceways, boxes, or cabinets of other circuits that are not part of the life safety branch.
A) Critical
B) Emergency
C) Life support
D) Life safety
82) All receptacle cover plates or receptacles them selves will have a distinctive
______________ or marking.
A) Color
B) Circuit
C) Identifiable
D) Etched
83) The life safety branch circuit is required to be installed and connected to the alternate
source of power so that all functions specified herein shall be automatically restored to
operation within __________ seconds after the interruption of the normal source.
A) 20
B) 10
C) 30
D) 5
517.42 Automatic Connection to Life Safety Branch (A) Illumination of Means of Egress
Required by the 2011 Code, the illumination of means of egress as is necessary for corridors,
passageways, stairways, landings, and exit doors and all ways of approach to exits. Switching
arrangement to transfer patient corridor lighting from general illumination circuits shall be
permitted, providing only one of two circuits can be selected and both circuits cannot be
extinguished at the same time.
The 2011 Code states that exit signs and exit directional signs shall be connected to the life
safety branch.
517.42 Automatic Connection to Life Safety Branch (C) Alarm and Alerting Systems
As stated in the 2011 Code for health care facilities, the alarm and alerting systems connected to
the life safety branch circuit including the following:
(2) Alarms required for systems used for the piping of nonflammable medical gases
As required by the 2011 Code, the communications systems, where used for issuing instructions
during emergency conditions.
517.42 Automatic Connection to Life Safety Branch (E),(F), and (G) Dining and Recreation
Areas
Sufficient lighting in dining and recreation areas to provide illumination to exit ways. Task
illumination and selected receptacles in the generator set location.
Elevator cab lighting, control, communications, and signal systems shall be automatically
connected to the life safety branch.
85) The fire alarm, exit signs and nonflammable medical gases alarm are not required to be
connected to the life safety branch.
A) True
B) False
86) Where used for issuing instructions during emergency conditions, the _____________
system will be connected to the life safety branch circuit.
A) Communications
B) Telecom
C) Intercom
D) Telegraph
87) Which of the following is not required to be connected to the life safety?
A) Generator set
B) Elevators
C) Parking lot lights
D) Dining and recreation
88) As allowed in article 517 for essential electrical systems under ___________, deleting
the time-lag intervals feature shall be permitted.
A) 150 kVA
B) 200 kVA
C) 100 kVA
D) 500 kVA
As stated in this code, the following equipment shall be permitted to be connected to the critical
branch and shall be arranged for delayed automatic connection to the alternate power source:
(1) Patient care areas — task illumination and selected receptacles in the following:
(2) Sump pumps and other equipment required to operate for the safety of major
apparatus and associated control systems and alarms
(4) Supply, return, and exhaust ventilating systems for airborne infectious isolation rooms
As stated in the 2011 Code, the following equipment shall be permitted to be connected to the
critical branch circuit and shall be arranged for either delayed automatic or manual connection to
the alternate power source:
Exception: Heating of general patient rooms during disruption of the normal source shall not be
required under any of the following conditions:
(2) The outside design temperature is lower than −6.7°C (20°F) and where a selected
room(s) is provided for the needs of all confined patients, only such room(s) need be
heated.
(3) The facility is served by a dual source of normal power as described in 517.44(C),
Informational Note.
Informational Note: The outside design temperature is based on the 971⁄2 percent design values
as shown in Chapter 24 of the ASHRAE Handbook of Fundamentals (1997).
(2) Elevator service — in instances where disruption of power would result in elevators
stopping between the temporary operations of any elevator for the release of passengers.
For elevator cab lighting, control, and signal system requirements, see 517.42(G).
As required by the 2011 Code, the essential electrical systems shall have a minimum of two
independent sources of power: a normal source generally supplying the entire electrical system
and one or more alternate sources for use when the normal source is interrupted.
89) Which of the following does not have to be connected to the delayed automatic
connection of the critical branch circuit?
A) Waiting rooms
B) Pharmacy dispensing areas
C) Medication preparation areas
D) Nurses’ stations (unless adequately lighted by corridor luminaries)
90) Supply and return air, Kitchen hood supply, smoke control system, and sump pumps
are some equipment permitted to be connected to the _____________ and arranged for
auto delay.
A) Life safety
B) Critical branch
C) Emergency power
D) Battery back up system
91) For either delayed automatic or manual connection to the alternate power source for
heating equipment to provide heating for patient rooms as long as the temperature is
higher or lower than _________.
A) 35 F
B) 15 F
C) 20 F
D) 25 F
93) The essential electrical systems for health care facilities will have a _____________ of
two independent sources of power.
A) No more than
B) Maximum
C) At least
D) Minimum
As required by the 2011 Code, the alternate source of power shall be a generator(s) driven by
some form of prime mover(s) and located on the premises.
Exception No. 1: Where the normal source consists of generating units on the premises, the
alternate source shall be either another generator set or an external utility service.
Exception No. 2: Nursing homes or limited care facilities meeting the requirement of 517.40(A)
and other health care facilities meeting the requirement of 517.45 shall be permitted to use a
battery system or self-contained battery integral with the equipment.
As stated in the 2011 Code, careful consideration shall be given to the location of the spaces
housing the components of the essential electrical system to minimize interruptions caused by
natural forces common to the area (e.g., storms, floods, earthquakes, or hazards created by
adjoining structures or activities). Consideration shall also be given to the possible interruption
of normal electrical services resulting from similar causes as well as possible disruption of
normal electrical service due to internal wiring and equipment failures.
Informational Note: Facilities in which the normal source of power is supplied by two or more
separate central station-fed services experience greater than normal electrical service reliability
than those with only a single feed. Such a dual source of normal power consists of two or more
electrical services fed from separate generator sets or a utility distribution network that has
multiple power input sources and is arranged to provide mechanical and electrical separation so
that a fault between the facility and the generating sources will not likely cause an interruption of
more than one of the facility service feeders.
(A) Essential Electrical Distribution. The essential electrical distribution system shall be a
battery or generator system.
(B) Electrical Life Support Equipment. Where electrical life support equipment is
required, the essential electrical distribution system shall be as described in 517.30
through 517.35
(C) Critical Care Areas. Where critical care areas are present, the essential electrical
distribution system shall be as described in 517.30 through 517.35.
(D) Power Systems. Battery systems shall be installed in accordance with the
requirements of Article 700, and generator systems shall be as described in 517.30
through 517.35.
517.60 Anesthetizing Location Classification (A) Hazardous (Classified) Location. The 2011
Code requires Anesthetizing Location Classifications to be classified as listed below.
(1) Use Location: In a location where flammable anesthetics are employed, the entire area
shall be considered to be a Class I, Division 1 location that extends upward to a level 1.52
m (5 ft) above the floor. The remaining volume up to the structural ceiling is considered
to be above a hazardous (classified) location.
(2) Storage Location: Any room or location in which flammable anesthetics or volatile
flammable disinfecting agents are stored shall be considered to be a Class I, Division 1
location from floor to ceiling.
94) The alternate source of power with regards to health care facilities shall be a generator
and located on the_________.
A) Block
B) Site
C) Premises
D) with in sight
95) According to the article 517 exceptions, if already using a generator as the normal
source, you may also use another generator or an external.____________.
A) Battery
B) Power source
C) Inverter
D) Utility
96) The location of essential electrical systems must be chosen to minimize the affects
caused by ____________ common to the area.
A) Natural forces
B) Short circuiting
C) Over current suppressors
D) Surging
97) The essential electrical systems with regards to article 517 shall be a __________ or
generator set.
A) Solar
B) Battery
C) Steam generation
D) Nuclear
98) Battery systems as stated in article 517 shall be installed in accordance with the
requirements of Article _______.
A) 754
B) 700
C) 517
D) 310
99) In an area where flammable anesthetics are used, the entire area shall be considered a
_________________ location.
A) Class 1, Division 2
B) Class 2, Division 2
C) Class 2, Division 1
D) Class 1, Division 1
As required by the 2011 Code, any inhalation anesthetizing location designated for the exclusive
use of nonflammable anesthetizing agents shall be considered to be an other-than-hazardous
(classified) location.
517.61 Wiring and Equipment (A) Within Hazardous (Classified) Anesthetizing Locations.
100) Any inhalation anesthetizing location used for the exclusive use of _______________
anesthetizing agents shall be considered to be an other-than-hazardous (classified) location.
A) Fast acting
B) Bottled
C) Nonflammable
D) IV induced
104) Receptacles and attaching plugs in a hazardous location shall be listed for use in a
________ location, and shall have a provision for a grounding conductor.
A) Class 2, Group D
B) Class 1, Group C
C) Class 1, Group A
D) Class 2, Group C
105) If a 60 amp receptacle and attachment plug are used above hazardous locations, the 60
amp plug will be allowed to receive what amps.
A) 60 ampere only
B) 50 ampere only
C) Both 50 & 60 ampere
D) Neither
(1) Wiring for grounded and isolated circuits does not occupy the same raceway or cable.
(2) All conductive surfaces of the equipment are connected to an equipment grounding
conductor.
(3) Equipment (except enclosed X-ray tubes and the leads to the tubes) is located at least
2.5 m (8 ft) above the floor or outside the anesthetizing location.
(4) Switches for the grounded branch circuit are located outside the hazardous (classified)
location.
517.63 Grounded Power Systems in Anesthetizing Location (C) Fixed Lighting Branch
Circuits.
As required by the 2011 Code, the branch circuits supplying only fixed lighting shall be
permitted to be supplied by a normal grounded service provided the following apply:
(1) Such luminaries are located at least 2.5 m (8 ft) above the floor.
(3) Wiring for circuits supplying power to luminaries does not occupy the same raceway
or cable for circuits supplying isolated power.
(4) Switches are wall-mounted and located above hazardous (classified) locations.
As required by the 2011 Code, wall-mounted remote-control stations for remote-control switches
operating at 24 volts or less shall be permitted to be installed in any anesthetizing location.
517.63 Grounded Power Systems in Anesthetizing Location (E) Location of Isolated Power
Systems.
As stated in the 2011 Code, and where an isolated power system is utilized, the isolated power
equipment shall be listed as isolated power equipment. Isolated power system equipment and its
supply circuit shall be permitted to be located in an anesthetizing location, provided it is installed
above a hazardous (classified) location or in other-than-hazardous (classified) location.
106) How many battery powered lighting units are required in anesthetizing locations?
A) One
B) Three
C) Two
D) Five
107) Which of the following do not apply to article 517.63, the grounded power systems in
anesthetizing locations.
A) All conductive surfaces of the equipment are connected to an equipment grounding
conductor
B) Switches for the grounded branch circuit are located outside the hazardous (classified)
location
C) Equipment is located at least 3ft above the floor or outside the anesthetizing location.
D) Wiring for grounded and isolated circuits does not occupy the same raceway or cable.
108) Fixed luminaries in anesthetizing locations powered by a normal grounded service
must be at least __________ above the floor.
A) 10ft
B) 6ft
C) 9ft
D) 8ft
110) When an isolated power system is used, the isolated power equipment is required to be
listed as _________________.
A) Emergency equipment
B) Safety equipment
C) Isolated power equipment
D) Anesthetizing equipment
The 2011 Code requires low-voltage equipment that is frequently in contact with the bodies of
persons or has exposed current-carrying elements to comply with one of the following:
The 2011 Code requires power that is to be supplied to low-voltage equipment to comply with
one of the following:
(1) Approved means for insulating the secondary circuit from the primary circuit
As stated in the 2011 Code, resistance or impedance devices shall be permitted to control low-
voltage equipment but shall not be used to limit the maximum available voltage to the
equipment.
As required by the 2011 NEC, battery-powered appliances shall not be capable of being charged
while in operation unless their charging circuitry incorporates an integral isolating-type
transformer.
The 2011 Code requires any receptacle or attachment plug used on low-voltage circuits to be of a
type that does not permit interchangeable connection with circuits of higher voltage.
Informational Note: Any interruption of the circuit, even circuits as low as 10 volts, either by any
switch or loose or defective connections anywhere in the circuit, may produce a spark that is
sufficient to ignite flammable anesthetic agents.
111) Which of the following is not a requirement for low voltage equipment in health care
facilities.
A) Be moisture resistant
B) Operate on an electrical potential of 10 volts or less
C) Be listed and labeled as an exposed device
D) Be approved as intrinsically safe or double-insulated equipment
112) Article 517 requires low voltage power for instruments and equipment to not be
supplied by _____________________.
A) Autotransformers
B) Dry cell batteries
C) Batteries made up of storage cells
D) Chord and attachment plugs
113) Isolation type transformers used for supplying low voltage circuits in health care
facilities are required to have the core and ___________ connected to an equipment
grounding conductor.
A) Delta
B) Wye
C) Line
D) Case
114) Resistance or impedance devices used in health care facilities are permitted to control
_______________ equipment but not to limit their maximum allowable voltage.
A) Line voltage
B) Load voltage
C) Low-voltage
D) Control voltage
116) When used in health care facilities, receptacles or attachment plugs used on low
voltage equipment are not permitted to interchange with _________ voltage circuits.
A) Lower
B) Same
C) Higher
D) Transformed
V. X-Ray Installations
As required by the 2011 Code, any fixed and stationary X-ray equipment shall be connected to
the power supply by means of a wiring method complying with applicable requirements of
Chapters 1 through 4 of this Code, as modified by this article.
Exception: Equipment properly supplied by a branch circuit rated at not over 30 amperes shall be
permitted to be supplied through a suitable attachment plug and hard service cable or cord.
517.71 Connection to Supply Circuit (B) Portable, Mobile, and Transportable Equipment.
As required by the 2011 Code, individual branch circuits shall not be required for portable,
mobile, and transportable medical X-ray equipment requiring a capacity of not over 60 amperes.
As required by the 2011 Code, the disconnecting means of adequate capacity for at least 50
percent of the input required for the momentary rating or 100 percent of the input required for
the long-time rating of the X-ray equipment, whichever is greater, shall be provided in the supply
circuit.
As stated in the 2011 Code, the disconnecting means shall be operable from a location readily
accessible from the X-ray control.
517.72 Disconnecting Means (C) Portable Equipment.
As stated by the 2011 Code for equipment connected to a 120-volt branch circuit of 30 amperes
or less, a grounding type attachment plug and receptacle of proper rating shall be permitted to
serve as a disconnecting means.
517.73 Rating of Supply Conductors and Over current Protection (B) Therapeutic
Equipment.
As required by the 2011 Code, the ampacity of conductors and rating of over current protective
devices shall not be less than 100 percent of the current rating of medical X-ray therapy
equipment.
Informational Note: The ampacity of the branch-circuit conductors and the ratings of
disconnecting means and over current protection for X-ray equipment are usually designated by
the manufacturer for the specific installation.
The 2011 Code allows size 18 AWG or 16 AWG fixture wires as specified in 725.49 and flexible
cords shall be permitted for the control and operating circuits of X-ray and auxiliary equipment
where protected by not larger than 20-ampere over current devices.
117) X ray equipment properly supplied by a circuit not over 30 amps can use an
attachment plug and hard service ___________ or chord.
A) Wire
B) Type MC cable
C) Cable
D) Non-metallic liquid tight
118) Individual _________ circuits shall not be required for portable x-ray equipment
requiring a capacity of not over 60 amps.
A) Safety
B) Emergency
C) Supplemental
D) Branch
119) ______ or ______ percent of the input voltage will be required for the X-ray
disconnecting means in a health care facility, whichever is greater according to the
equipment.
A) 50 / 100
B) 25 / 75
C) 100 / 125
D) 35 / 95
120) An X-ray machine disconnect is required to be operable from a location readily
____________ from the control room.
B) Line of sight
A) Accessible
C) With in 25 feet
D) Close to
121) A grounding attachment plug can be used as a disconnect for portable equipment in
health care facilities if the current is ________ amps or less.
A) 20
B) 40
C) 30
D) 25
122) Over current protection for therapeutic equipment shall not be less than _________
percent of the current rating of medical X-ray machine.
A) 125
B) 50
C) 95
D) 100
123) ____________ chords are permitted for the operating and control circuits of auxiliary
and x-ray equipment if the circuit is no larger than 20 amps.
A) Flexible
B) Solid
C) Small
D) Heavy
Required by the 2011 Code for new X-ray installations and all used or reconditioned X-ray
equipment moved to and reinstalled at a new location shall be of an approved type.
As stated in the 2011 Code, transformers and capacitors that are part of X-ray equipment shall
not be required to comply with Articles 450 and 460. Capacitors shall be mounted within
enclosures of insulating material or grounded metal.
The 2011 Code states that the cables with grounded shields connecting X-ray tubes and image
intensifiers shall be permitted to be installed in cable trays or cable troughs along with X-ray
equipment control and power supply conductors without the need for barriers to separate the
wiring.
As required by the 2011 Code, all high-voltage parts, including X-ray tubes, shall be mounted
within grounded enclosures. Air, oil, gas, or other suitable insulating media shall be used to
insulate the high-voltage from the grounded enclosure. The connection from the high-voltage
equipment to X-ray tubes and other high-voltage components shall be made with high-voltage
shielded cables.
As stated in the 2011 code, the low-voltage cables connecting to oil-filled units that are not
completely sealed, such as transformers, condensers, oil coolers, and high-voltage switches, shall
have insulation of the oil-resistant type.
Required by the 2011 Code for non–current carrying metal parts of X-ray and associated
equipment (controls, tables, X-ray tube supports, transformer tanks, shielded cables, X-ray tube
heads, etc.) shall be connected to an equipment grounding conductor in the manner specified in
Part VII of Article 250, as modified by 517.13(A) and (B).
The 2011 Code requires wire-pulling compounds that increase the dielectric constant
must not be used on the secondary conductors of the isolated power supply
125) Transformers that are part of x-ray equipment are not required to comply with
Articles 450 and _________.
A) 425
B) 460
C) 310
D) 255
126) Cables with grounded shields connecting x-ray tubes and image intensifiers are
allowed to be installed in ___________ or troughs.
A) Cable tray
B) Raceway
C) Rigid conduit
D) PVC pipe
127) All __________ parts, including x-ray tubes, shall be installed within a grounded
enclosures.
A) Low-Voltage
B) High impedance
C) High-Voltage
D) Electrical
128) Low-voltage cables used for equipment in health care facilities that connect to oil filled
units which are not sealed completely are required to have _______________ of the oil
resistant type.
A) Coating
B) Covering
C) Copper
D) Insulation
129) Non current carrying metal parts of x-ray and associated equipment shall be
connected to an ___________ grounding conductor in the proper manner.
A) Main
B) Grounded
C) Service
D) Equipment
130) When pulling in the secondary conductors for isolated power systems used in health
care facilities, the pulling compound must not ________ the conductor dielectric constant.
A) Increase
B) Decrease
C) Absorbs
D) Produces