BWTS Maintenance - Alfa Laval - PureBallast
BWTS Maintenance - Alfa Laval - PureBallast
Published By:
Alfa Laval Tumba AB
SE-147 80 Tumba, Sweden
Contents
1 Introduction 7
1.1 Preparations and conditions 7
2 Maintenance schedule 9
2.1 Calibration schedule 12
2.2 Recommended spare parts on board 13
2.3 Serial number information 15
2.3.1 Indicating serial number 15
2.3.2 Example 15
3 UV reactor 19
3.1 Safety information 19
3.2 Replace UV lamp and quartz sleeve 20
3.2.1 Disassemble UV lamp 21
3.2.2 Disassemble quartz sleeve 22
3.2.3 Assemble quartz sleeve 23
3.2.4 Check for leaks after quartz sleeve assembly 24
3.2.5 Assemble UV lamp 24
3
TECHNICAL MANUAL - SECTION 1
4 Filter 27
4.1 Remove filter cover and filter element 30
4.2 Mount filter element and filter cover 32
4.3 Clean filter element and pre-filter 32
5 CIP 35
5.1 Change CIP liquid 35
6 Flow meter 37
6.1 Replace display and fuse 37
7 Pumps 39
7.1 Operate pumps manually 39
7.2 Repair drain pump 39
7.2.1 Clean drain pump 40
7.2.2 Disassemble drain pump 40
7.2.3 Assemble drain pump 42
8 Valves 45
8.1 Preparations and conditions 45
8.1.1 Tightening torques for actuators 46
4
TECHNICAL MANUAL - SECTION 1
9 Valve block 61
9.1 Change valve body 62
9.2 Connect electrical cables to valve block 62
9.3 Clean valve block 62
10 Level switch 63
10.1 Mount level switch 63
10.2 Dismount level switch 64
10.3 Test level switch 64
12 Control panel 67
12.1 Clean control panel 67
12.2 Replace control panel 67
1 Introduction
This chapter contains information and instructions about how to service the PureBallast system.
Instructions are sorted per component. The chapter is opened with a maintenance schedule
covering checks and services that must be performed with specified intervals.
NGE R
! DA
• Before maintaining the PureBallast system, the power supply must be switched off, to avoid
accidental starts. See instruction Shut down and deactivate the system in chapter 3. Operating
instructions and control system description.
NG
WARNI
!
• Read chapter 1. Safety.
• Installation must be done by a fully trained professional installer.
NOTE
• All maintenance and calibration activities must be recorded in the vessel’s maintenance log.
This is required by the ballast water convention. It is therefore recommended that the activities
in the maintenance and calibration schedules below are entered in the vessel’s general
maintenance system.
• Always read and follow the documentation that are included in shipment of components and
spare parts regarding handling, safety and disposal.
• Earth connection must be made before any welding is done.
• Follow local regulations for electrical installation and protective earthing.
• Electrical welding requirements: Connect the welding unit’s negative lead (work lead) to the
component you will weld, close to the welding area.
• Before maintaining the PureBallast system, the following valves must be locked in closed
position: V201-3 and V201-8. See instruction Lock valve in closed position on page 46.
• Follow local regulations for electrical installation and protective earth (ground).
• Follow rules when handling CIP liquid, regarding ventilation, personal protection etc.
• Point of contact: To order service or spare parts, contact your local Alfa Laval office. For
more information, see www.alfalaval.com.
Book No.9028175 02 7
TECHNICAL MANUAL - SECTION 1
2 Maintenance schedule
Follow this maintenance schedule to secure performance, safety and durability of the system and
its components. The schedule is sorted per component. The table refers to instructions usable
when performing the respective action.
General Testrun the Once a month. See 3. Operating If the system, for
system: Run a instructions and some reason, is not
ballast and/or control system operated by normal
deballast process. description. ballast operations,
Follow up with a it needs to be run
CIP process. Manual operation to verify that it is in
of valves: See good condition.
Note: If system is chapter 7. Service
used, but certain manual, section This will also
valves are not Valves. exercise the valves,
used, for example actuators and other
V212–31, those components to
should be opened keep them in good
and closed condition.
manually. For
relief valves,
see Calibration
schedule.
Electrical Check air filter Every six month. Upper filter: Filter mat: 9017400
cabinet Change filter mat 02.
when dirty.
Book No.9028175 02 9
TECHNICAL MANUAL - SECTION 1
2 Maintenance schedule
Filter Inspection and Once a year. See Remove filter Replace filter
cleaning of filter element. element, if
insert, including damaged.
filter element. Cleaning once a
year normally is See Spare parts
enough. But in catalogue for
exceptional cases service kit.
(vessels trading
very muddy
waters) it might
be necessary to
clean the more
often.
If the pressure
triggered
backflushing is
performed with
short intervals,
we suggest that
the filter element
manually cleaned
more often than
once year.
10 Book No.9028175 02
TECHNICAL MANUAL - SECTION 1
2 Maintenance schedule
CIP liquid CIP liquid level Rule of thumb: One can of CIP
check. Once every 3 liquid lasts for
months. approximately 50
Depending CIP processes.
on ballasting
frequency, the liquid
check might have to
be performed more
regularly.
Control opening Once a year. See chapter 7. Open and close the
and closing end Service manual, valves and inspect
stops. section Valves for visually.
instructions.
Book No.9028175 02 11
TECHNICAL MANUAL - SECTION 1
1. Connect a calibrated portable ultrasonic flow meter close to the flow meter.
2. Establish flow in the system.
3. Compare value indicated in control system and measure equipment.
5. Dismount the switch and place in water with temperature < 65 ˚C.
6. Check that alarm A104 is displayed in the control system.
12 Book No.9028175 02
TECHNICAL MANUAL - SECTION 1
UV reactor
Electrical cabinet
Filter
Book No.9028175 02 13
TECHNICAL MANUAL - SECTION 1
14 Book No.9028175 02
TECHNICAL MANUAL - SECTION 1
Serial numbers shall be used at error reporting and other contacts where a specific component is
discussed.
• Serial number for the complete PureBallast system. See label on the side of the electrical
cabinet.
• Serial number for the component in question. If the component is installed on, or in, another
component, the number for the mother component shall be stated.
• Item number for the component. The item number identifies a unique component in the system.
It begins with a letter abbreviation indicating the component type, for example: LS (level switch)
or P (pump). A complete list of abbreviations is found in chapter 6. Installation description and
drawings, section Connection list.
2.3.2 Example
If the level switch is faulty, the following information shall be stated:
Book No.9028175 02 15
TECHNICAL MANUAL - SECTION 1
Electrical cabinet
7 SerialNrEC
7 SystemPlate
UV reactor
7 AOT SnrSkid
16 Book No.9028175 02
TECHNICAL MANUAL - SECTION 1
Filter
7 FilterSnr Filtrex
NOTE
7 LDC sernr
Book No.9028175 02 17
TECHNICAL MANUAL - SECTION 1
NOTE
Flow meter
NOTE
18 Book No.9028175 02
TECHNICAL MANUAL - SECTION 1
3 UV reactor
NGE R
! DA
• Always disconnect the PureBallast system from the power supply before disassembling, and
secure it from being switched on.
• Always lock valve V201–19 and V201–8 if you open the UV reactor in some way. See Lock
valve in closed position on page .
• UV lamps radiate ultraviolet radiation when lit. Only operate the UV lamp when correctly
installed inside the UV reactor with end caps properly closed.
• Never dismount or handle UV lamps before they are completely cooled down. A hot UV lamp is
under high internal pressure, and the risk of bursting exists. A hot lamp could also cause a
burn if it is touched.
• Before installation, check that the UV lamps and quartz sleeves are not broken.
• UV lamps and quartz sleeves are fragile and can easily become damaged. Exercise great care
when handling them. Do not apply vibrations or shock to the UV lamp. This can cause breakage
and shorten lamp life. Broken glass/quartz can also cause severe cuts. Always use protective
eye glasses and clean cotton gloves when handling UV lamps and quartz glass sleeves.
Book No.9028175 02 19
TECHNICAL MANUAL - SECTION 1
NGE R
! DA
• UV lamps contain a small amount of mercury (less than 0.2 grams per lamp) and must be
handled and disposed of with care. Used lamps UV can be handled and disposed of in the same
way as fluorescent lamps. Please refer to national regulations. If a UV lamp has accidentally
been broken, mercury could be spilt. Remove mercury with a special tool such as a syringe
(or use pure sulphure to bind the mercury for easy collection).
• Do not allow mercury to come in contact with your eyes or skin. Do not inhale mercury fumes.
• Free mercury must be kept in an airtight bottle, and must be disposed of according to
national regulations.
• In case of having inhaled mercury fumes, consult a doctor and follow medical instructions.
3.2 Replace UV lamp and quartz sleeve
7 AOTexploded
1. Cap
2. Cap nut
3. Bush
4. O-ring (inside bush)
5. Cable connector
6. Allen screw
7. Glass socket
8. O-ring
9. UV lamp
10. Quartz sleeve
20 Book No.9028175 02
TECHNICAL MANUAL - SECTION 1
• The PureBallast system must be turned off, and the power disconnected.
• After UV lamps have been changed, the runtime must be reset in page control system page 4.3
Timers. Requires login level Advanced operator.
• Wait at least 10 minutes after completed ballast or deballast process, to allow the UV reactor
to cool down to ambient temperature. If the UV lamps are hot they are under internal positive
pressure and may burst if broken.
NG
WARNI
!
• The UV reactor must not be under pressure when dismounting the UV lamps.
NG
WARNI
!
• Burn hazard: UV lamps can be hot and cause burns.
Follow the steps below
1. Unscrew the cap nuts (2) holding the caps (1). There is one nut on each side of the UV reactor
per UV lamp. If required, use a screwdriver on the nut, gently tapping with a hammer to release.
2. Carefully disconnect the two cable connectors (5) in both ends of the UV lamp (9).
Carefully draw out the UV lamp (3) with the electric cable, by holding the electric cables in
both ends. When pulled out, only hold the UV lamp by the ceramic ends. Immediately after
removal, place the lamp in its protective cover.
If required, use a screwdriver to press on the ceramic end of the lamp inside the bush on the
other side while carefully pulling the electric cable at the other end.
Book No.9028175 02 21
TECHNICAL MANUAL - SECTION 1
7UVBushScrewdriver
5. If the quartz sleeves is not broken, mount the new UV lamp according to the instruction
Assemble UV lamp on page 24. If broken see the Preparations and conditions section above.
2. Make sure that the following valves are closed: Control valve (V201-8), inlet valve (V201-9)
and UV reactor inlet (V201-19). If not, close them with control system set in manual mode.
3. Depressurize and drain the reactor by pressing the Drain function button in the control panel.
5. Disassemble the UV lamp according to the instruction Disassemble UV lamp on page 21.
6. Loosen the three Allen screws (6) of the glass socket (7) on both sides; just a few turns to
release them.
7. Unscrew the Allen screws completely at one side. Carefully remove the glass socket, to avoid
breaking the quartz sleeve. Then remove the glass socket on the other side.
8. Remove the O-rings (8) on both sides. The O-rings are firmly stuck in their seat, and will be
damaged during removal, but shall be replaced at assembly. Use an angled or hooked O-ring
tool to loosen and remove the O-ring. Be careful to avoid to break the glass.
If the O-ring is hard to remove, try the following:
– Moisten the O-ring with acetone or denatured alcohol.
– Loose the O-ring in a couple of places before removing it.
– Perforate the O-ring to get a good grip.
22 Book No.9028175 02
TECHNICAL MANUAL - SECTION 1
10. Carefully clean the surface and remove any small parts, for example glass or rubber.
2. Wet the O-rings (8) with water and slip them over respective side of the quartz sleeve.
Check that the O-ring are positioned evenly on both sides. If not, they may be damaged
and cause leaks.
The O-rings shall not be pressed into position, the glass socket will press them into position
when fastened later.
3. Carefully mount the first glass socket on the quartz sleeve with three Allen screws evenly, but
do not tighten the screws. Note that the waxed screws must be used to avoid seizing.
7QuartzSleeve
4. Once the Allen screws (6) are evenly entered, carefully tighten them evenly to a torque of 7 Nm.
7. Follow the instruction Check for leaks after quartz sleeve assembly.
Book No.9028175 02 23
TECHNICAL MANUAL - SECTION 1
1. Pressurize the UV reactor with water to between 2 and 4 bar (0.2 and 0.4 MPa).
• A leakage check must have been performed according to the instruction Check for leaks after
quartz sleeve assembly.
• Use waxed screws.
• New heat resistant O-rings must be used in the two bushes. Always replace used O-rings.
• Keep the UV lamp in its protective cover as long as possible. Do not touch the glass of the
lamp; hold the lamp by its ceramic end parts.
• Glass sockets and bushes must be dry and clean before mounting.
• After UV lamps have been changed, the runtime must be reset in control system page 4.3
Timers.
Follow the steps below
1. Mount the new heat resistant O-rings in the two lamp bushes (3).
5. Make sure that the connection is clean to ensure good electric connection (no rust, burning or
fading on the connectors). Reconnect the two cable connectors for the UV lamp.
6. Mount the UV lamp caps and tighten the cap nut at both ends of the UV lamp, by hand only.
Make sure that the electric cable is not squeezed between the cap and the bush when the cap
is mounted. Slack can be pushed into the bush.
7. Control the control system page 3.1 Alarm list, to make sure there is no alarm when after the
lamp power supply is on.
24 Book No.9028175 02
TECHNICAL MANUAL - SECTION 1
NG
WARNI
!
• Switch off the main breaker on the cabinet door. The LPS has high voltage/power (600 V)
inside and on the lamp power connector, even when UV lamps are not lit.
• The cabinet contains a fan, which can cause injury if in operation.
Follow the steps below
7 LPSmaint
1. Dismount LPS
Release two power connectors at the bottom of the LPS and the signal cable connector
at the top.
2. Loosen the nuts at the bottom (1) of the arc holding the LPS.
NOTE
Make sure not to drop the washer into the LPS. It may cause short circuit.
4. Mount LPS
Set the DIP switches on the LPS according to chapter 4. Parameters, section Lamp power
supply (LPS) parameters.
6. Reconnect the three connectors. Make sure the connectors sit tight.
Book No.9028175 02 25
TECHNICAL MANUAL - SECTION 1
9. Switch on the main breaker on the cabinet door and check that LPS:s function correctly
according to instruction Test LPS installation below.
NG
WARNI
!
• This instruction must be performed after cable connection. If not hazardous situation may arise
which, if not avoided, will result in death or serious injury.
DANGER
!
• Before operating the UV reactor, make sure that there is water in the UV reactor. Check the
LED on the level switch: Steady yellow light indicates that there is water in the UV reactor.
Follow the steps below
1. Switch on the main breaker on the electrical cabinet door. Switch on the power to the UV
reactor using the switches on the breaker cabinet.
2. Set the control system in manual mode (requires login level Advanced operator).
3. Go to page 1.2 Reactor and start LPS 1. Make sure that two UV lamps are lit.
Note: It can take up to 90 seconds for the lamp to start.
6. Check that no error indication on the LPS and that there are no alarms in page 2.1 Alarm
list in the control system.
26 Book No.9028175 02
TECHNICAL MANUAL - SECTION 1
4 Filter
• Disconnect the power to the filter, using the main switch on the control cabinet.
• Always lock valve V201–3 and V201–19 if you open the filter in some way.
• Only perform maintenance and servicing work when the filter is cooled, depressurized and
drained.
• Shut off the air supply to the filter.
• Visually inspect gasket during maintenance. Replace if necessary.
Tightening torques for filter bolts
M4 3
M6 7
M8 12
M10 18
M12 25
M14 35
M16 45
M18 60
M20 75
M22 90
M24 105
Book No.9028175 02 27
TECHNICAL MANUAL - SECTION 1
4 Filter
28 Book No.9028175 02
7 FiltrexExploded
TECHNICAL MANUAL - SECTION 1
4 Filter
1 Gear reducer
2 Gear shaft
3 Electric motor
4 Thrust bearing flange fixing bolt
5 Gear reducer flange / cover fixing bolt
6 Thrust bearing
7 Backflush shaft bushing gasket
7a Backflush shaft bushing asket
8 Filter vent plug
9 Filter cover
10 Cover bolt
11 Backflush shaft bushing
12 Filter element fixing bolt
13 Filter cover gasket
14 Filter body
15 Filter element
16 Backflush nozzle
17 Filter element gasket
18 Backflush shaft bushing
19 Filter drain plug
20 Backflush line gasket
22 Pressure transmitter
29 Junction box
30 Backflush nozzle support
31 Backflush nozzle fixing bolt
32 Backflush nozzle support gasket
33 Base frame
34 Base frame fixing bolt
40 Ring spear
41 Thrust bearing upper flange
42 Thrust bearing lower flange
43 Seeger
44 Cover lifting lug
45 Rotation indicator
70 Nameplate
80 Prefilter
Book No.9028175 02 29
TECHNICAL MANUAL - SECTION 1
2. Depressurize and drain the filter by pressing the Drain function button in the control panel.
3. Close the following valves: V201-1 and V201-32 according to the instruction in the Open and
close valves manually on page 46 and Lock valve in closed position on page .
5. Remove the motor (using a lifting device, if necessary). Be careful not to harm the motor
fitting when lifting it from it’s seat.
7 FilterMotor
6. Remove the cover bolts (10) and the lifting lugs (44).
7. Screw two filter cover bolts in the lifting lugs holes until the cover raises slightly from the filter
house.
7 LiftingBolt
30 Book No.9028175 02
TECHNICAL MANUAL - SECTION 1
8. Remove the cover bolts and fasten the lifting lugs in their holes again.
7 LiftingLug
9. If not present: Fasten the lifting device of the winch on the filter cover. Fasten it in the same
holes as the motor, using the same bolts.
Use the winch to lift the filter cover with the filter element out of the filter. Be careful not to
harm the filter element.
Note: The filter should be lifted in one continuous movement, without sudden jerks – even if
the filter element is slightly stuck in the filter house.
11. Remove bolts to the bottom shaft support that holds the shaft inside the filter element (15).
Remove it carefully.
12. Remove the seeger ring (43) from the backflush shaft bushing (11).
7 FiltrexSeeger
13. Pull out the backflush shaft bushing. If it is stuck, give a couple of light blows with a wooden
hammer on the top of the shaft to release it.
Book No.9028175 02 31
TECHNICAL MANUAL - SECTION 1
15. Unscrew the four Allen screws inside the element to loosen the filter cover.
7 FiltrexAllenS
17. Lift the pre-filter (80) from the bottom of the filter house.
Note:
• Clean the upper inside of the house at the top of the. The area where the O rings meet the
housing should be clean.
• No force should be used to fit the filter element in the filter house or to fit the motor in its seat.
• Check the O rings. Replace if necessary.
• Fill up the filter with technical water / potable water after it is mounted. Use the Fill function
button in the control panel. Requires login as Advanced operator or higher.
• There is not need to de-air the filter when it is filled up.
4.3 Clean filter element and pre-filter
Follow this instruction to clean the filter element. At the same time, check that the filter element
is in good condition.
• Alpacon descalant offshore may be used as cleaning agent. See Safety data sheet / CIP liquid
in chapter 6. Installation description and drawings.
• Mixing ratio for Alpacon descalant offshore is 1 part concentrated Alpacon descalant to 20 parts
technical water / potable water. Follow this mixing ratio, regardless of recommendation on label.
• Alpacon descalant offshore storage temperature: 0 °C to +55 °C.
32 Book No.9028175 02
TECHNICAL MANUAL - SECTION 1
NG
WARNI
!
• Risk for eye and skin irritation. Avoid contact with eyes and wear protective gloves and goggles.
Follow rules when handling CIP liquid agent, regarding ventilation, personal protection etc.
NG
WARNI
!
• If Alpacon descalant offshore comes in contact with eyes or skin, rinse thoroughly with cold
water.
• The pH value should be approximately 2.0–3.0.
• Proceed with the utmost caution when transporting, assembling, disassembling and cleaning
the filter element.
Follow the steps below
1. Follow the instructions Remove filter element (page 30) to remove the filter element.
4. Soak the filter element in the cleaning agent with the opening facing upwards. Leave it to soak
for 1–4 hours. Let the element dip dry before next step.
5. Place the element in so it does not fall over when cleaning it.
6. Spray the filter element with water (60–80 °C) from the outside, using a flat nozzle. Note: If a
high-pressure cleaner is used, the pressure must not exceed a maximum of 15 bar. If a cleaner
with higher capacity is used, compensate by increasing the distance, minimum 30 cm.
7. Blow the filter element with instrument air (with 10 micron filter or finer), from the outside.
8. 8. Inspect the filter element from the outside with a magnifier to make sure that it is clean. If
needed, repeat the procedure. This time it is enough to let the element soak for 5 minutes.
10. Put the filter element gasket back. Reassemble the rest of the filter.
Book No.9028175 02 33
TECHNICAL MANUAL - SECTION 1
5 CIP
Alpacon descalant is used as cleaning agent for the CIP process. It contains no solvents and no
inorganic acids and it is non-flammable. See Safety data sheet / CIP liquid in chapter 6. Installation
description and drawings.
• Avoid letting the CIP cap with the pipe be out of the can for too long, to avoid loosing CIP
liquid in the pipe and hose.
ON
CAUTI
!
• Risk for eye and skin irritation. Avoid contact with eyes and wear protective gloves and goggles.
Follow rules when handling CIP liquid agent, regarding ventilation, personal protection etc.
ON
CAUTI
!
• If Alpacon descalant offshore comes in contact with eyes or skin, rinse thoroughly with cold
water.
• Alpacon descalant offshore storage temperature: 0 °C to +55 °C.
3. Replace the old can with a new. Remove the cap from the new CIP liquid can.
5. Remove the small cap on the cip liquid can, throw it away and cut a hole in the membrane
under the cap. The purpouse is to let air into the can to let CIP liquid out.
Book No.9028175 02 35
TECHNICAL MANUAL - SECTION 1
7. Go to control system page 1.5 CIP and make sure that level switch LS320 indicates wet
condition (green).
8. Go to control system page 4.3 Timers. Reset CIP Number of cleaned UV reactors. If this is
done each time the CIP liquid is changed, it is possible to build up experience on how many
CIP processes it is possible to perform before it is time to change CIP liquid. Requires login
level Advanced operator.
36 Book No.9028175 02
TECHNICAL MANUAL - SECTION 1
6 Flow meter
NG
WARNI
!
• Risk of electric shock! Exposed components carry dangerous voltages.
Make sure that the power supply is switched off before you remove the cover of the electronics
compartment.
Follow the steps below
4. Remove the screws and remove the cover from the electronics compartment.
Book No.9028175 02 37
TECHNICAL MANUAL - SECTION 1
5. Remove the power supply board. Insert a suitable tool into the hole, provided for the purpose
and pull the board clear of its holder.
Replacing the device fuse on the power supply board (step 5–6)
1. Protective cap
2. Device fuse
7 Re-assembly
Re-assembly
38 Book No.9028175 02
TECHNICAL MANUAL - SECTION 1
7 Pumps
This section contain instructions for the CIP and drain pumps.
1. Look at the signal plate on the valve block to identify which button that controls the pump.
See page for an illustration.
2. Press the button on the valve body with a pointy object to start the pump. The pump remains
running as long as the button is pressed.
ON
CAUTI
!
• Always wear protective eye glasses and gloves while working on the pump.
NG
WARNI
!
• Always disconnect the PureBallast system from the power supply before disassembling, tand
secure it from being switched on.
• Before disassembling the pump, the pneumatic hoses must be disconnected, and the extension
pipe must be removed and blocked.
• Drain the pump from liquids.
• The pump should be placed horizontally on a work bench.
Book No.9028175 02 39
TECHNICAL MANUAL - SECTION 1
7 CIP pump
1. Remove the drain pump from the skid and place it on a work bench.
3. Place the pump on the side that still has the nuts (the pump lays on the nuts) on a stable ground.
5. Carefully lift up the suction and discharge connections (13). You have the centre block (12)
and one of the housings with pin screws (14) left.
40 Book No.9028175 02
TECHNICAL MANUAL - SECTION 1
6. Upend the pump and carefully pull out the pin screws (14). Be careful not to damage the
diaphragms (15).
1. Put the house wall with the flat side down on a plane surface.
4. Place one of the pin screws on the inside (behind) the valve ball stopper on the lower valve
seat (21). Carefully pull out the valve seat in the housing.
5. Remove the valve ball (23) from the valve seat, buy using a pin screw: Press out the valve ball
stopper (22), which will release the valve ball.
• Have backup spares of the sealing (36) and backup O-ring (47). There is a risk that these parts
get damaged during this operation.
Follow the steps below
1. Press the diaphragms (15) to their neutral position (both have the same distance to the
centre block).
2. Hold one of the diaphragms (15) and unscrew the other. Then pull out the remaining diaphragm
with the diaphragm shaft (16).
3. Disassemble the circlips (27) which keep the air valve (61) on its place.
4. Press out the air valve. A wood shaft of a hammer can be used. Be careful not to damage the
sealing edges towards the diaphragm or the air valve.
5. If the shaft sealings (36) seem to be worn out, carefully remove them with a pointed tool.
Book No.9028175 02 41
TECHNICAL MANUAL - SECTION 1
2. Apply some soft soap solution on the air valve O-rings (30).
3. Push the air valve (61) into the housing. Make sure that the O-rings (30) remain in the right
position. Put the circlip (27) on the other side.
4. Put the diaphragm (15) with shaft (16) into the centre block. Screw the next diaphragm (15)
onto the shaft (16) and fix the holes.
1. Make sure that the O-rings (18) are placed on the in/outlet (13) before assembling of pump.
3. Make sure all pin screws (14) have one nut (37) and one washer (38) each. Nut should only be
put on one or two threads.
4. Put all the pin screws through the housing and then turn the housing so it rests on the nuts.
5. Put the centre block (12) to the housing with screws through the centre block. Be careful not to
damage the diaphragms.
6. Place suction and discharge connections (13) in their positions in the housing. Be careful not
to damage the O-rings (18).
7. Put the second housing (11) onto the pin screws (14). Make sure that suction/discharge
connections are in right direction. Be careful with the O-rings.
8. Fasten the nuts (37) crosswise by hand, with or without washers depending on how much of
the thread comes out. Turn the nuts gently with a tool to close the pump. If some of the nuts
were fastened without washer, unscrew those and put washers underneath. After a few weeks
operation a follow up draft of the nuts is recommended.
42 Book No.9028175 02
TECHNICAL MANUAL - SECTION 1
2. Check that there is water in the UV reactor (LS201-29). Check the LED on the level switch:
Steady yellow light indicates that there is water in the UV reactor.
If not, press the Fill function button in the control system and wait for the UV reactor to be filled.
4. Observe if the motor sound and functions OK. If not, check installation and connections and
attend to and test again.
5. Observe if the pump sounds OK and that it strikes the number or times set in p403 with hertz
as set in p405. If not: Check/change parameter settings.
1. Pull the pipe from the CIP liquid can and stick it to a bottle filled with at least 3 dl of water.(This
is to avoid waisting CIP liquid during the test.)
2. Go to page 1.5 CIP and press the Run CIP pump button.
3. Observe if the pump sounds OK and that it strikes 26 times with 2 hz (approximately 2 times
per second).
If not: Check settings for parameter p403 and p405.
Book No.9028175 02 43
TECHNICAL MANUAL - SECTION 1
8 Valves
7 Actuator
1. Safety cover
2. Pad lock
3. Lower position for indicator screw
4. Upper position for indicator screw — with screw
5. Position indicator
6. Center screw
7. Bracket
8. Puck
9. Locking bolt
10. End stop bolt.
Book No.9028175 02 45
TECHNICAL MANUAL - SECTION 1
M5 05–06
M6 10–11
M8 23–25
M10 48–52
M12 82–86
M14 132–138
M16 200–210
M20 390–410
1. Look at the signal plate on the valve block to identify which button that controls the valve.
2. Press the button on the valve body with a pointy object to open the valve. The valve remains
open as long as the button is pressed.
• Note that the end positions of the end stop bolts are factory adjusted and should normally not
be readjusted.
Follow the steps below
1. Set the valve to closed position from the control system. Control the position indicator, to make
sure. The yellow position indicator is in line with the valve throttle (indicating open when
the position indicator is in line with the pipe).
2. Disconnect power and instrument air. Verify that the valve is not under pressure.
46 Book No.9028175 02
TECHNICAL MANUAL - SECTION 1
3. Open the padlock (2) on the actuator and remove the safety cover (1) from the bolts (3, 4).
7 576075_lock_manual
4. Measure exactly how far out the end stop bolt (4) is from a reference surface, for example the
actuator house. Make a note of the distance. This information is needed when unlocking
the valve.
5. Open the locking bolt (3) and turn them a couple of turns.
6. Screw the end stop bolt (4) to its bottom position and tighten the locking bolt.
8. Slide the safety cover over the end bolts and lock the safety cover with the pad lock.
• Note that the end positions of the end stop bolts are factory adjusted and should normally not
be readjusted.
Follow the steps below
1. Disconnect all power and instrument air. Verify that the valve is not under pressure.
Book No.9028175 02 47
TECHNICAL MANUAL - SECTION 1
2. Open the padlock (2) on the actuator and remove the safety cover (1) from the bolts (3, 4).
7 576075_lock_manual
4. Adjust the end stop bolt (4) to the same position (distance from reference surface) as before
locking the valve, according to the notes made during locking.
NOTE
• It is important to adjust the ends stop bolt to the correct position. Otherwise the actuator
may be damaged.
5. Tighten the locking bolt (3).
7. Slide the safety cover in position over the end stop bolts. Lock the safety cover with the pad
lock.
48 Book No.9028175 02
TECHNICAL MANUAL - SECTION 1
1. Remove the DIN connector to disconnect the power. Let the air connection remain.
Result: Valve goes to closed position (due to the air connection). The yellow indicators on the
puck shows position of valve: closed. The yellow position indicators are in line with the valve
throttle (indicating closed when the position indicators are in opposite line with the pipe).
2. Disconnect the air hose to the pilot valve. Verify that the actuator is not pressurized. Always
use caution and double-check that ports 2 and 4 are vented and are free from any accessory
and/or device.
3. If the actuator have a switch box at the top: Loosen the four screws holding the switch box to
the actuator. Remove the switch box together with its bracket.
4. Loosen the four hexagonal screws holding the actuator to the valve.
5. If the actuator is mounted on the valve with a bracket and coupling (dimension 400): Loosen
the screws holding the bracket to the valve. Make sure not to loose the coupling between the
valve and actuator when lifting the actuator.
ON
CAUTI
!
• The actuator must not be pressurized at any time during installation as it may result in injury.
• The valve must be in closed position.
• The valve position must not be adjusted during the routine.
• The utmost cleanliness is required during air supply connection to the actuator, that is, the
connecting pipe thread, fittings and seals must be clean and dirt-free.
• Before fitting onto the valve, make sure the actuator/valve is correctly orientated, depending on
which direction of rotation is required.
Follow the steps below
1. Note the position of the groove (2) of the valve stem (3). It indicates the position of the valve
throttle. The illustration shows a square variant, but octagonal versions exist.
Book No.9028175 02 49
TECHNICAL MANUAL - SECTION 1
7 ValveStem
2. Make sure that the lock pin (inside the valve stem) only travels in the allowed sector (1) and
that it does not pass the opening (5).
3. If the actuator is mounted on the valve with a bracket and coupling (dimension 400): First fit
the coupling on the valve stem. Make sure that the red position indicator on the coupling is in
line with the pipe when the valve is open.
4. Fit the actuator onto the valve stem (or the coupling). The actuator may only be positioned in
even 90° intervals in relation to the valve. It is not allowed to adjust the position by turning the
actuator by hand after it is fitted on the valve stem.
5. Mount the actuator on the valve with the four hexagonal screws. For each screw, one washer
and one spring washer shall be used. Tighten with torque according to the table Tightening
torques for actuators on page 46.
6. If the actuator have a switch box at the top: Make sure that the yellow position indicator under
the switch box is in line with the throttle (according to the groove in the valve stem). The yellow
position indicator shall be in line with the valve throttle (indicating open when the position
indicator is in line with the pipe). If not, remove the position indicator, turn it 90° and refit it.
Mount the switch box with the bracket on the actuator, using the four bolts.
8. Operate the valve to make sure it operates in the desired direction of rotation.
50 Book No.9028175 02
TECHNICAL MANUAL - SECTION 1
7 576075_lock_manual
1. Note the exact position of the position indicator for reference after adjustment.
2. Open the padlock (2) on the actuator and remove the safety cover (1).
Result: Two sets of bolts are displayed. The right set adjusts closing position and the left
set adjusts open position.
4. Adjust end position by turning the end stop blot (4) with small turns.
– Clockwise decrease the end position.
– Counterclockwise increase the end position.
NOTE
6. Tighten the locking bolt (3) to fixate the position of the end stop bolt (4).
Book No.9028175 02 51
TECHNICAL MANUAL - SECTION 1
7 201-8Positioner4
7 201-8Positioner
52 Book No.9028175 02
TECHNICAL MANUAL - SECTION 1
1. Make sure that the transmission ratio selector (6) is set to 90° according to sticker on the
component. If not: Adjust by pressing the bar with a screw driver.
2. Make sure that the Arrestor device wheel (1) is set to 90°. If not: Adjust by turning.
4. Make sure that Menu 1 is displyaed. If not: Press HAND button repeatedly until it is.
Make sure that “turn” is displayed in the menu. If not: press + or – repeatedly until it is.
Note: Do not choose “– turn”.
7 201-8Positioner2
- Use a screw driver to loosen the yellow locking wheel (counter clockwise).
- Turn the adjustment wheel (5) by hand until a 0 is displayed between the “d” and the “U” as
shown in the illustration. Normally this is when the value in the screen is close to 0.
7 201-8Positioner3
Book No.9028175 02 53
TECHNICAL MANUAL - SECTION 1
10. Press the hand button for 5 seconds until a number or “VER” is displayed, then let go of the
button.
Result: “MAN” is displayed”.
54 Book No.9028175 02
TECHNICAL MANUAL - SECTION 1
Trouble shooting
- Reset to factory settings: Press HAND button repeatedly until menu 50 is displayed.
- Press + button until “oCAY” is displayed.
- Restart instruction Calibrate positioner on V201-8 from step 4.
- Set the parameters according to Alfa Laval software settings. See table above.
Book No.9028175 02 55
TECHNICAL MANUAL - SECTION 1
Hint: A multimeter can be used to indicate position of the cam wheels, if it is hard to hear the click
from the micro switch, or if it is inconvenient to see valve position in control panel. Connect a
multimeter to connection point 41 and 42 in the positioner.
3. Close it to approximately 10 %.
4. On the positioner: Adjust both cam wheels to same position. Cam wheels are above the
adjustment wheel (5) on page 51.
5. Turn the cam wheels in any direction until it valve indicates steady green in the control panel.
Miltimeter indicate circuit closed.
6. Turn the cam wheel slowly counter clock wise until you hear a click from the micro switch in
the positioner. Stop directly after the click. Stop directly after the multimeter changes to
indicate circuit open.
7. Check that the valve is indicated as open (steady green) in the control panel.
Result 2: Valve indicated as red. Cam wheels are in wrong position, for example due to the
wheels been turned too much after the click). Miltimeter indicate circuit open. Repeat from
step 2 until setting is OK.
56 Book No.9028175 02
TECHNICAL MANUAL - SECTION 1
Valve actuator with switch box for position feedback to control system
1. Switch box
2. Bracket
3. Actuator
4. Pilot valve
5. Bracket - Used for valves with dimension 400
6. Coupling with position indicator - Used for valves
with dimension 400
7. DIN connector
8. Position indicator
Book No.9028175 02 57
TECHNICAL MANUAL - SECTION 1
3. Before mounting the switch box, change the position of the yellow position indicator, so it
is in line with the throttle.
7 MountPilote
1. Check that the O-rings are fitted on the pilot valve, on the side facing the actuator.
2. Fit the pilot valve on in the actuator, so that the pin on the actuator fits the hole on the pilot
valve. The throttle valves (2 and 4) shall be directed downwards.
3. Mount the pilot valve with two Allen screws in the holes (1).
5. Fit the DIN connector (5) on the coil, including gasket. Then fasten the connector with the
screw (6).
58 Book No.9028175 02
TECHNICAL MANUAL - SECTION 1
7 AdjustTravel
1. Operate the valve manually to check traveling speed according to the instruction in the Operate
valves manually on page 46.
Book No.9028175 02 59
TECHNICAL MANUAL - SECTION 1
9 Valve block
• The valve bodies does not have individual placing, they can be placed in any order.
NGE R
! DA
• Always disconnect the PureBallast system from the power and air supply before disassembling,
and secure it from being switched on.
7 Valve block
Valve block
Book No.9028175 02 61
TECHNICAL MANUAL - SECTION 1
1. Remove the screws holding the valve bodies (2) and the signal plate (4).
4. Attach a new sealing on the new valve body and fasten the valve body to the valve block.
2. Attach the cables according to electrical drawing Electrical cabinet / interconnection diagram in
chapter 6. Installation description and drawings.
2. Operate the service air according to instruction Open and close valves manually on page 46
to blow out the dust.
62 Book No.9028175 02
TECHNICAL MANUAL - SECTION 1
10 Level switch
This section contains information about the level switch LS201-29 installed in the UV reactor. For
information about status indications, see chapter 5. Alarms and faultfinding, section Level switch.
7LS Component
Level switch
NOTE
2. Seal the level switch with lock tight or equivalent pipe seal.
4. Identify the sensor align mark (▼) on the component. Make sure that it is positioned on the
upper side of the level switch.
Book No.9028175 02 63
TECHNICAL MANUAL - SECTION 1
5. Complete the seal carefully by tightening the component with a spanner. Use the spanner on
the hexagon flats, but not on the level switch body.
• The external surface may be hot. Care must be taken to avoid possible burns.
Follow the steps below
2. Loosen the component with a spanner. Use the spanner on the hexagon flats, but not on
the level switch body.
3. Remove the level switch and remove the old seal from the threads.
1. Make sure that the component i powered (the green LED shall be lit).
2. Hold a magnet to the test point indicated on the on the level switch, indicated below.
7LS Test
3. Make sure the level switch reacts to the magnet. The component is OK if the green and
yellow LED is lit.
64 Book No.9028175 02
TECHNICAL MANUAL - SECTION 1
This section contains information about the temperature switch TS201-60 and the temperature
transmitter TT201–33 installed in the UV reactor. The two components are similar in design, so
the same instructions can be used.
7 TS and TT
NOTE
1. Seal the component’s threads using lock tight or equivalent pipe seal.
3. Tighten the component with a spanner. Use the spanner on the hexagon flats, but not on
the components body.
Book No.9028175 02 65
TECHNICAL MANUAL - SECTION 1
• The external surface may be hot. Care must be taken to avoid possible burns.
Follow the steps below
2. Loosen the component with a spanner. Use the spanner on the hexagon flats, but not on
the components body.
3. Remove the level switch and remove the old seal from the threads.
66 Book No.9028175 02
TECHNICAL MANUAL - SECTION 1
12 Control panel
NOTE
• Control panels may only be cleaned when set in wipe mode. This is to prevent unintended
functions from being triggered by buttons pressed during cleaning.
Preparations and conditions
• Never use aggressive solvents, chemicals, scouring agents, pressurized air or steam jet.
Follow the steps below
2. Clean the display and surrounding front cover with a soft cloth and mild detergent. Do not
spray detergent directly on the control panel.
Book No.9028175 02 67
TECHNICAL MANUAL - SECTION 1
If included in order, 1 or 2 remote control panels can be mounted in wall, worktop etc. at an optional
location, for example the bridge, cargo control room or back office.
• Remote control panel is mounted according to according to drawing Remote control panel /
Dimension drawing. Note the clearance area.
• Use a 24 VDC, 2 amp power supply cable with minimum cross section of 0.75 mm2, preferably
halogen free and flexible. Connect power cable to terminal X1 in remote control panel.
• Communication cable (W501) between the remote control panel and electrical cabinet can be
either Ethernet or optical fiber. Cable requirements and connection points below:
- Ethernet cable – Type: Cat 5e (or better), shielded. Max length: 100 meters. One remote
control panel: From terminal X2 in remote control panels to terminal X7 in the electrical
cabinet. Two remote control panels: From terminal X2 in second remote control panel to
either switch SW1 in electrical cabinet or to switch SW1 in the first remote control panel.
- Optical fiber cable – Type: Multi-mode optical fiber cable with LC connector. Max length:
500 meters. From remote control panel’s switch SW1 to switch SW1 in electrical cabinet.
See Remote control panel / Circuit diagram.
Book No.9028175 02 69
TECHNICAL MANUAL - SECTION 1
13.1 Mount and connect remote control panel 13 Remote control panel (optional)
TECHNICAL MANUAL - SECTION 1
14 Electrical cabinet
1. Hold down the plastic clip on the top of the terminal block and pivot the block towards you.
7IO1_X025002A
3. Hold down the triangle on the top of the I/O board and loosen the board.
7IO2_X025003A
Book No.9028175 02 71
TECHNICAL MANUAL - SECTION 1
4. Pull the board straight out (otherwise it can fasten in one of its guides).
7IO3_X025004A
5. Compare the part number of the new I/O board to the old board, to make sure it is correct.
6. If changing more than one board at a time, check with the electrical diagram to ensure that
the boards are mounted in the right places.
7. Mount the new I/O board by pressing it straight into place. Make sure the board is firmly in
place, otherwise it will be impossible to mount the cable terminal.
7IO4_X025005A
8. Remount the terminal block. Make sure the clip on the bottom of the block fastens properly in
place on the axel on the bus holder.
7IO5_X025007A
72 Book No.9028175 02
TECHNICAL MANUAL - SECTION 1
9. Pivot the terminal block on the axel until the clip on the terminal block top fastens into place in
the I/O board.
7IO6_X025006A
Book No.9028175 02 73
Version OPEX2018 TECHNICAL MANUAL - SECTION 2
Compliance :: USCG
Product :: PureBallast 3.1-85 USCG FLEX
Capacity :: 32 - 85 m3/hr
FlexPic
Lamp power supply 10000 hours CIP pump spare part set 2 yr
Quartz sleeve set 131040 hours UV sensor 1 yr
UV lamp set 3000 hours Filter Insert 7 yr
Filter maintenance kit 1 yr
OPEX WorkUp for Art Anderson Associates's NOAA Vessels over 10 years
1 of 4
Version OPEX2018 TECHNICAL MANUAL - SECTION 2
Power Factor based upon system Type Approval and UVT 80%
2 of 4
Version OPEX2018 TECHNICAL MANUAL - SECTION 2
Compliance :: USCG
Product :: PureBallast 3.1-85 USCG FLEX
Capacity :: 32 - 85 m3/hr
OPEX Summary
3 of 4
Version OPEX2018 TECHNICAL MANUAL - SECTION 2
Annual OPEX overview for Art Anderson Associates's NOAA Vessels over 10 years
Evaluation based upon 1 PureBallast 3.1-85 USCG FLEX systems installed, excludes labor estimates.
Item \ Year 1 2 3 4 5
CIP liquid € - € 84 € 84 € 84 € 84
Lamp power supply € - € - € - € - € -
Quartz sleeve set € - € - € - € - € -
UV lamp set € - € - € - € - € -
Filter maintenance kit € - € 473 € 473 € 473 € 473
CIP pump spare kit € - € - € 1,313 € - € 1,313
UV sensor € - € 611 € 611 € 611 € 611
Filter Insert € - € - € - € - € -
Service € - € - € - € - € -
TOTAL € - € 1,169 € 2,482 € 1,169 € 2,482
Item \ Year 6 7 8 9 10
CIP liquid € 84 € 84 € 84 € 84 € 84
Lamp power supply € - € - € - € - € -
Quartz sleeve set € - € - € - € - € -
UV lamp set € - € - € - € - € -
Filter maintenance kit € 473 € 473 € 473 € 473 € 473
CIP pump spare kit € - € 1,313 € - € 1,313 € -
UV sensor € 611 € 611 € 611 € 611 € 611
Filter Insert € - € - € 5,927 € - € -
Service € - € - € - € - € -
TOTAL € 1,169 € 2,482 € 7,096 € 2,482 € 1,169
4 of 4
TECHNICAL MANUAL - SECTION 3
ART
ANDERSON
202 PACIFIC AVE, BREMERTON, WA 98337
® (360) 479-5600
TECHNICAL MANUAL - SECTION 3
TECHNICAL MANUAL - SECTION 3
TECHNICAL MANUAL - SECTION 3
TECHNICAL MANUAL - SECTION 3
TECHNICAL MANUAL - SECTION 3
TECHNICAL MANUAL - SECTION 3
TECHNICAL MANUAL - SECTION 3
TECHNICAL MANUAL - SECTION 3