Abstract
Most but not all fires emit smoke aerosols at some point during the combustion process. Therefore most
conventional fire detectors are based on the detection of smoke by light scattering. As every fire is
emitting specific gases it is reasonable to upgrade photoelectric fire detectors or even replace them for
specific environments with gas sensor based technologies. In this paper we present some gas detection
technologies which have the potential to be able to amend or replace existing systems for use especially in
residential fire detectors. But here some restrictions apply when using gas sensors. Among others these
are low cost, low power and long term requirements. We identified advantages but also some challenges
of gas detection technologies by testing colorimetric gas sensors, gas sensitive field effect transistors and
metal oxide sensors. As most technologies are not completely selective to the target gas and as there is
not “the” fire with one specific mixture of combustion gases it is helpful to combine different sensing
elements in sensor arrays where algorithms using pattern recognition methods like PLSDA, PCA etc. can
be used to increase the prediction reliability and the false alarm robustness. Here we focused on typical
combustion gases like CO, CO2, NO, NO2, NH3 and H2.
©©2012
2012
ThePublished by Elsevier
Authors. Published Ltd. Ltd. Selection and/or peer-review under responsibility of the Symposium Cracoviense
by Elsevier
Sp. z.o.o. Open access under CC BY-NC-ND license.
Keywords: Metal oxide, SnO2, GasFET, fire detection, PLS, pattern recognition, combustion.
1. Introduction
The first automatic smoke detector invented in 1940 was based on the measurement of the ionization
current using americium-241 as a radioactive source [1]. The alpha radiation emitted ionizes oxygen and
nitrogen in the air in the sensing chamber leading to a measurable ionization current which decreases
when smoke particles are present. Although these materials are relatively safe in use the acceptance at
* Corresponding author. Tel.: +41 41 724 5493; fax: +41 41 723 4980.
E-mail address: [email protected].
1877-7058 © 2012 The Authors. Published by Elsevier Ltd. Selection and/or peer-review under responsibility of the Symposium Cracoviense
Sp. z.o.o. Open access under CC BY-NC-ND license.
doi:10.1016/j.proeng.2012.09.430
Ulrich Hoefer and Daniel Gutmacher / Procedia Engineering 47 (2012) 1446 – 1459 1447
least in Europe decreased in the past. Environmental and health issues occurred and using radioactive
sources in fire detectors became undesirable. Although ionization detectors are still more sensitive as
conventional photoelectric detectors (“point detectors”) nowadays most residential fire detectors are
based on smoke detection by light scattering using forward scattering and/or backward scattering
combined with the detection of heat. Some use multiple wavelengths (IR and blue) to decrease the
detection limit and to suppress false alarms which in most cases are due to dust or water vapor. For
specific environments there are also alternative techniques in use like flame detectors, linear optical
detectors, aspirating smoke detectors and linear heat detectors (using raman scattering in optical fibers) –
to name just a few.
Not all fires are emitting smoke (pure ethanol fires for example do not) and especially some hot open
fires do not emit bigger quantities of smoke. But combustion gases are emitted from every fire and their
detection can be helpful for an early fire detection. There are numerous different gaseous compounds
which are emitted during a “normal” fire in buildings. Depending on the type of fire and the different
materials which are used in furniture, toys and the building construction, gases like CO, H2, NO2 and CO2
but also HCl, HBr, HCN, Ammonia, Acrolein, SO2 and many others may occur. Surprisingly during a fire
most people do not die from heat or flames but from poisonous gases [2]. For residential fire detection
some requirements apply restricting the choice of sensor technologies. Among others there are:
Therefore the number of different gas sensing technologies is very limited and several attempts have
been made in the past to develop and include gas sensors in fire detectors. For example in the past
electrochemical CO-cells have become small, cheap and robust enough and several products were
launched on the market. But not only technical reasons hindered the implementation of gas sensors. Due
to regulations and standards today according fire detectors are not allowed to work on gas sensors alone
(EN54 standard). In order to be robust against nuisance, gas-only based fire detectors should detect at
least two typical combustion gases simultaneously and there are several arguments to go for an according
development. With respect to photoelectric detectors most false alarms are due to dust and water vapor
and it can be expected that fire detectors using several gas sensors as basis for pattern recognition
algorithms will help to improve the overall detector performance like:
Providing additional information like air quality (humidity, carbon dioxide, volatile organic
compounds).
Serving additional life-safety applications (i.e. CO-detection)
One additional advantage of using gas sensors might be the comparably fast diffusion of gases through
heat layers when compared to smoke aerosols. In this paper we focus on the investigation of three
different gas sensor technologies which meet at least some of the above requirements. As an example,
temperature cycled metal oxide sensors (SnO2-hotplate), gas sensitive field effect transistors (GasFETs),
colorimetric gas sensors (optodes) will be presented. The technologies are intended to work also as a fire
detection system on its own – without the support of photoelectric systems.
Metal oxide sensors are well known since several decades and still are basis for comprehensive
research activities. Among their advantages are their strong sensitivity to all type of gaseous compounds
and their overall stability. Generally their limited selectivity can be a critical point for some applications.
Since they have to be heated up to temperatures between 150°C and 350°C the power consumption was
rather high. With the development of membrane setups (hotplate) and a resulting very low thermal mass it
is now possible to operate them with a comparably low power consumption – even continuously.
Changing the operation temperature leads to changing ad- and desorption characteristics with respect to
different gases. By applying short heat pulses the power consumption can be drastically decreased and
additional information can be derived out of the signals. Gases can be identified even in the presence of
others also reacting with the sensor surface [3], [4], [5].
Table 1: EN54 test fires and according gaseous compounds. Main target gases are in bold.
Table 1 lists standardized test fires (EN-54) and their main gaseous compounds. Gases like CO2, CO, H2,
H2O, NO and NO2 can be found in any fire. Main compounds are CO and H2 in smoldering fires whereas
CO2, and NO2 are emitted in hot and complete combustion processes (open or flaming fires). Using
appropriate sensors makes it possible to distinguish between those fire types. One apparent problem of
metal oxides which often is stated is the different signal direction when exposed to reducing and
oxidizing gases (CO and NO2) because during fires both gases can be present and the signals could be
Ulrich Hoefer and Daniel Gutmacher / Procedia Engineering 47 (2012) 1446 – 1459 1449
counterbalanced resulting in a zero signal. But by applying heat pulses to the sensor and using subsequent
recognition algorithms – for example based on PLSDA (Partial Least Squares Discriminant Analysis) this
problem can be solved. In this work we worked with SnO2 hotplate metal oxide sensors (Applied Sensor,
www.appliedsensor.com), applied heat pulses of 0.9s length and sampled 100 times per pulse.
Figure 1: Left: applied voltage, right: resistance (a.u.) during a fire event. 2.7V corresponds to 350°C. One cycle lasts 0.9s..
Figure 1 shows the applied heating voltage and the transient signal of the hotplate SnO2-metal oxide
sensor during a fire event as shown for example in Figure 2. After measuring a complete set of test fires
we developed a suitable model for PLSDA by pre-extracting the most pronounced differences of signal
shape. We were able to successfully test the model with respect to discrimination between open and
smoldering fires. These signal evaluation algorithms need limited computation power in operation, so that
it can be easily done by a low-power microcontroller (basically it is only one multiplication of a fixed
matrix with an input vector containing measurement data). Figure 3 and Figure 4 show the according
results. The strong sensor signal to solvent vapors (not shown here) which impose high requirements to
the signal evaluation, however open up the possibility to the detection of accelerants giving the possibility
to announce an according pre-alarm.
1450 Ulrich Hoefer and Daniel Gutmacher / Procedia Engineering 47 (2012) 1446 – 1459
Figure 2: SnO2-metal oxide sensor resistance at heatpoint 69 (refer to Figure 1) during different test fires (refer to
Table 1) and nuisance events. Influence of ageing on sensor response.
Figure 3: Prediction of test data as “no fire” using a PLSDA-model. Very few of the fires get misinterpreted as no
fire. Legend: red no fire – “no fire” before ignition and during weekend, green smoldering – TF2, blue smoldering –
TF2 reduced intensity, light blue smoldering – TF3, grey smoldering – TF3 reduced intensity, red flaming – TF4,
green flaming – TF4 reduced intensity.
Ulrich Hoefer and Daniel Gutmacher / Procedia Engineering 47 (2012) 1446 – 1459 1451
Figure 4: Prediction of test data as “smoldering fire” using Model 1. The discrimination works well. Even
the low-intensity fires are detected correctly. Legend: red no fire – “no fire” before ignition and during
weekend, green smoldering – TF2, blue smoldering – TF2 reduced intensity, light blue smoldering – TF3,
grey smoldering – TF3 reduced intensity, red flaming – TF4, green flaming – TF4 reduced intensity.
A background concentration of interfering gases and even the change of the environmental temperature
changes the sensitivity to the target gases. As cross sensitivities to solvent vapors are pronounced a
product development therefore needs a detailed investigation of interfering gases but also on drift, long
term behavior of sensitivity and stability, humidity and temperature influence. The lack of discrimination
power using just one sensor can be solved by using different sensing layers. Nevertheless power
consumption has to be considered.
1452 Ulrich Hoefer and Daniel Gutmacher / Procedia Engineering 47 (2012) 1446 – 1459
Another approach to cost effective fire gas detection is given by materials which change their color
during gas exposure. Compared to the well known materials which are used by the police to check
alcohol content in breath the requirements in fire detection are different. Most of these applications use
one-time disposable sensors whereas for fire detectors the change of color has to be fully reversible. For
passing approval and certification procedures but also during regular tests of fire detectors in buildings a
reversible reaction and stability for many years is indispensable. An according system needs a color
changing chemical complex reversibly binding the target gas, a polymer matrix in which the complex is
embedded and a substrate on which the color dye is deposited. The optical readout then can be done by
using cost effective LED’s emitting in the appropriate wavelength (or nearby) and a photo detector. A
wide range of different chemical complexes like azobenzoles, corrines, porphyrines, phtalocyanines,
macrolides are described in literature for the detection of NH3, CO2, NOX, CO and other gases. Several
investigations have been made and many patents were filed also for fire detection applications [6], [7],
[8].
In this work we used a rhodium complex as the basic indicator substance for CO which is shown in Figure
5. Based on previous works [9] we exchanged the ligands with fluorathetic acid groups in order to make
the complex less sensitive to humidity [10].
Figure 5: rhodium complex which was used as CO indicator (left). Absorption in the UV-VIS range of the Rh-
complex in solution without and with exposure to 100% CO (right).
During exposure to CO there is an exchange of the axial ligands. Both fluorathetic acid groups can be
replaced by one CO-molecule leading to a colour change. The most pronounced change of absorption was
measured at 405nm and 562nm. The indicator substance then was embedded into a PVC matrix for
stabilization and in order to be able to coat a glass substrate used as waveguide. The principal
measurement setup and the measured change of absorption are shown in Figure 6. When embedded in the
PVC-matrix the change of absorption at 405 nm nearly disappears. One half of a conventional glass
substrate then was coated with the PVC-matrix stabilized complex where the second, non coated half was
used as a reference channel. The layer thickness was between 50 nm and 300 nm. In order to be close to a
Ulrich Hoefer and Daniel Gutmacher / Procedia Engineering 47 (2012) 1446 – 1459 1453
low cost future detector design we chose a conventional yellow LED (peak wavelength 590 nm) as
emitter and a conventional photodiode (BPW 32) as detector (spectral range 350 to 1100nm). Figure 7
shows the results obtained using this measurement setup during different test fires in a 1m3 test chamber.
Figure 6: principle measurement setup comprising a conventional yellow LED, a glass waveguide and two photo
diodes (left). Change of absorption in the UV-VIS range of the Rh-complex in a PVC-based matrix during exposure
to 100% CO (right).
Figure 7: measurement results of the detector setup shown in Figure 6 using the PVC matrix embedded Rh-complex
during different test fires. The spike at 30 min is due to switching on the room light – after that the system was
immediately covered by a protection.
The signals follow well the measured CO-concentration. The complex reacts reversibly, nevertheless a
slight drift, which is possibly due to changes in ambient temperature influencing the electronics, can be
observed. The sensitivity seems to be good enough for fire detection purposes. For a future product
1454 Ulrich Hoefer and Daniel Gutmacher / Procedia Engineering 47 (2012) 1446 – 1459
development detailed investigations have to be performed especially on long term stability and the
influence of humidity and temperature. It is known that such complexes suffer from bleaching effects
which lead to premature ageing. One possibility to increase lifetime might be the use of very short light
pulses for optical readout followed by longer inactive periods. As a reliable fire gas detection needs the
ability of detecting additional gases like NO2 the setup can be extended by using additional sensitive
layers.
Another gas sensing technology for low power applications is the work function readout using field effect
devices. Whereas first introduced with the hydrogen-sensitive field effect transistor with a heated Pd-gate
by Lundström, recent developments focus on CMOS compatible suspended gate FETs (“GasFET”) [12],
[13], [14]. The electrical potential that arises from gas adsorption at the sensitive material which is
deposited on the gate is directly used to control the transistor characteristics. To allow gas access the gate
is suspended by several μm from the isolating passivation layer to allow gas access. A schematic cross
section is shown in Figure 8. Using appropriate sensing layers, these GasFETs work at room temperature
and therefore have a low power consumption. In our case we used a floating gate device which recently
has been industrialized by Micronas (www.micronas.com). As the FET is processed using standard
CMOS manufacturing procedures all the needed readout electronic can be included on the same chip and
even a microprocessor could be included in future.
Figure 8: Schematic cross section of a floating gate FET (FGFET) using a suspended gate. Gas molecules are
able to enter the gap between sensitive layer and the passivation-layer above the floating gate electrode.
Several GasFETs channels can be operated in parallel and therefore different gases can be detected
simultaneously which is the basis to implement pattern recognition algorithms. Materials which were
tested here as sensitive layers were Pt, Ga2O3 (“GaOx”) copper phthalocyanine (CuPC),
heteropolysiloxane (HPS) and TiN films, whereas also materials like BaTiO3/CuO, SnO2/Pd,
polyvinylpyrrolidone (PVP), polyamide (PA) and others were reported [15]. We identified CO, H2, NO2
and NH3 as a set of suitable fire gases to be tested. CO and H2 are typical gases emitted during smoldering
fires. They can be detected by Ga2O3- or Pt-films. NO2 is mainly emitted from open fires and can be
detected by the CuPC-films. NH3 can be found in cigarette smoke as well as in acrylic wool combustion
gases. CO2 also is a typical combustion product but as it can be found also in human breath in higher
concentrations we decided to not consider it for fire detection.
Ulrich Hoefer and Daniel Gutmacher / Procedia Engineering 47 (2012) 1446 – 1459 1455
Figure 9: response of Pt-, Ga2O3- (GaOx), CuPC-, HPS- and TiN layers equipped GasFET’s to CO, NO2, H2, ethanol
(EtOH) and CO2.
Figure 9 shows the response of 4 different GasFET’s to CO, NO2, H2, ethanol (EtOH) and CO2. None of
the layers is responding to ethanol which is important for minimizing the false alarm rate. The CuPC-
layer only shows response to NO2, whereas the TiN-layer is not responding to any of the measured gases
but to NH3 (not shown here). The Pt-layer behaves similar to the GaOx-layer but with a higher overall
response. Both are responding to CO, H2, NO2 but not to CO2 and ethanol. Beside the response of the
HPS-layer to NO2 in opposite direction to Pt and GaOx, an interesting result is its response to CO2.
During fire tests, concentrations of the gases of interest were recorded simultaneously using commercial
gas analyzing systems. In addition, the optical absorbance (SICK) and an ionisation chamber (MIC, not
shown here) were used as a reference. Figure 10 shows the signals of Pt-, GaOx-, CuPC- and TiN
equipped GasFETs during a smoldering PVC-cable and an open (flaming) beech wood fire (TF1). The
differences in signal strength and direction are due to the different gases which are emitted. It is likely
that PVC emits HCl during combustion which causes a signal on the CuPC- and also on TiN-layer. The
open beech wood fire mainly emits NO2. Figure 11 shows the response of the sensors to polyurethane fire
(TF4) and to a smoldering fire (TF2). As during TF4 CO concentration is low (9 ppm after 90s) and that
of NO2 (1 ppm after 90s) comparably high, the Pt and CuPC layers are reacting in the opposite direction
compared to the smoldering fire (TF2) where the CO concentration is comparably high and that of NO 2
low. By interpreting the different signals it becomes possible to identify different fire events. As
elementary signal evaluation algorithms only may take signal slope and direction into account, PLSDA-
based algorithms might give a deeper understanding of the fire situation and/or atmospheric conditions.
1456 Ulrich Hoefer and Daniel Gutmacher / Procedia Engineering 47 (2012) 1446 – 1459
Figure 10: response of 4 different GasFETs, to smoldering PVC-cable (left) and TF1 (right) open beech wood fire.
Figure 11: response of 3 GasFETs to TF2 (right) smoldering beech wood and TF4 (left) polyurethane fire. The actual
NO2- and CO concentration is shown below. The optical attenuation is recorded by a SICK reference measurement
system.
For the model creation we took the information from 4 layers (refer to Figure 10) and performed first of all
a smoothing of all signals (Savitzky-Golay with a window of 40s). Afterwards the 1st derivative was taken
to become independent of sensor baseline. Finally smoothing of the resulting data was performed with a
window of 20s. The values of the derivative for each sensor channel together with additional information
like r.h. or temperature were then used as input for the model. The plots below show the prediction as a
certain class within the model. We tested the algorithm with other data from open- and smoldering fires
as well as cigarette smoke (as nuisance). Figure 12 shows the prediction with respect to no fire, open
(flaming) fire, smoldering fire and cigarette smoke. Some smoker events were misinterpreted as
smoldering fires which of course is due to its nature.
Ulrich Hoefer and Daniel Gutmacher / Procedia Engineering 47 (2012) 1446 – 1459 1457
Figure 12: Results of Model 1 (calculation performed by taking signals of 4 layers). The graphs show the prediction
of the different events (flaming fire, smoldering fire and smoker) for flaming fires (top left), smoldering fires (top
right) and smoking (bottom left). Higher prediction values mean better recognition. The red dotted line is the
threshold above which the events are recognized
The prediction algorithm could be implemented into a real time fire detection graphical user interface
giving an according alarm after identifying fire and its classification. This setup was tested about 6
months later again with no remarkable change of prediction power.
5. Summary
Detecting fires alternatively with gas sensors or gas sensor arrays can improve the detection performance
with respect to time to alarm and nuisance robustness. Most false alarms using photoelectric detectors are
due to dust and water vapor and it can be expected that the investigated technologies at least do not
respond to dust. A cross sensitivity on changes in humidity could be observed regarding to all sensor
technologies but according cross sensitivities might be compensated by using an additional humidity
sensor. The most important requirements for gas sensors to be used in fire gas detectors (point detectors)
1458 Ulrich Hoefer and Daniel Gutmacher / Procedia Engineering 47 (2012) 1446 – 1459
are their long term stability, low price, low power requirements and limited cross sensitivities. PLSDA is
an appropriate method for the recognition of fire and non-fire events for metals oxide sensors as well as
for GasFETs. Metal oxide sensors show a strong cross sensitivity to ethanol and other solvent vapors,
which implies that with respect to false alarm robustness signal processing is more challenging. Optodes
may be a suitable technology but long-term stability has to be proven (bleaching). Due to the heat, smoke
particles are mainly transported by convection with a minor contribution of diffusion whereas gas is
transported by both convection and presumably with a higher fraction of diffusion. First results indicate
that this is true at least for so called “heat layers” beneath ceilings [16]. These layers can occur during
smoldering fires and are due to a temperature difference between near ceiling positions and the room.
Aerosols are then not able to pass this layer for several minutes. Gas sensors used in this work responded
some minutes earlier than conventional photoelectric detectors. Generally it can be stated that all of the
presented technologies are able to reliably detect fires but one of the main issues is to suppress false
alarms by identification of other situations which pretend fires. Accordingly, the used pattern recognition
models and algorithms have to be tested extensively and have to be continually improved using field data
– like this was also the case for photoelectric detectors in the past.
Acknowledgements
The authors would like to thank the group of Maximilian Fleischer (Siemens), Danick Briand and
Jerome Courbat (EPFL). Part of this work was funded by the Swiss government (KTI).
References
[1] Hans J. Tobler. Ionisationsfeuermelder: technische und wirtschaftliche Bedeutung, Bulletin SEV/VSE 23/06, 2006, 13-15
[2] Peter Basmer, Gerhard Zwick. Messung des Giftgascocktails bei Bränden, Forschungsstelle für Brandschutztechnik an der
Universität Karlsruhe (TH), 2004
[3] Tekin A. Kunt, Thomas J. McAvoy, Richard E. Cavicchi, Steve Semancik. Optimization of temperature programmed
sensing for gas identification using micro-hotplate sensors. Sensors & Actuators B53 (1998) 24-43.
[4] Zafer Ankara, Andreas Schütze. Low power virtual sensor systems based on a micromachined gas sensor for security
applications and warning systems. Presented at EUROSENSORS XXII Conference 2008, Dresden, Germany, September
07-10, 2008
[5] Peter Reimann. Early fire detection in coal mines based on sub-ppm level ethene detection with a T-cycled semiconductor.
Gas sensor Safety and Security Systems in Europe Conference 2008, Potsdam, Germany, June 19 - 20, 2008.
[6] Ursula E. Spichiger-Keller. Chemical Sensors and Biosensors for Medical and Biological Applications. Wiley-VCH,
Weinheim, 1998.
[7] Andreas Hensel: Untersuchung von Optoden zur selektiven Gaserkennung für die Brandmeldetechnik, Richard Pflaum
Verlag, 2002.
[8] J. Schneider, A. Hensel, U. Oppelt. Optoelectronic Gas Sensor Based on Opodes. United States Patent US 6,704,470 B1,
2004.
[9] Esteban, J.V. Ros-Lis, R. Martinez-Manez, M.D. Marcos, M. Moragues. J. Soto, F. Sancenon, Angew. Chem. Int. Ed.
2010, 49, 4934 – 4937.
[10] J. Courbat, M. Pascu, D. Gutmacher, D. Briand, J. Wöllenstein, U. Hoefer, K. Severin, N.F. de Rooij. A
COLORIMETRIC CO SENSOR FOR FIRE DETECTION. Eurosensors XXV conference, Athens, September 2011.
[11] R. Pohle, E. Simon, R. Schneider, M. Fleischer, R. Sollacher, H. Gao, K. Müller, P. Jauch, M. Loepfe, H.-P. Frerichs, C.
Wilbertz. Fire detection with low power fet gas sensors. Sensors and Actuators B 120 (2007) 669–672.
[12] Lundtström, I.; Shivaraman, M.S.; Svenson, C.M. Hydrogen-sensitive Pd-gate MOS-transistor. J. Appl. Phys. 1975, 46,
3876-3881.
[13] Flietner, B.; Doll, T.; Eisele, I. Reliable hybrid GasFETs for work-function measurements with arbitrary materials. Sens.
Actuat. B-Chem. 1994, 22, 109-113.
[14] Fleischer, M.; Ostrick, B.; Pohle, R.; Simon, E.; Meixner, H.; Bilger, C.; Daeche, F. .Low-power gas sensors
based on work function measurement in low-cost hybrid flip-chip technology. Sens. Actuat. B-Chem. 2001, 80,
169-173.
Ulrich Hoefer and Daniel Gutmacher / Procedia Engineering 47 (2012) 1446 – 1459 1459
[15] Ralf Moos, Kathy Sahner, Maximilian Fleischer, Ulrich Guth, Nicolae Barsan and Udo Weimar. Solid State Gas Sensor
Research in Germany – a Status Report. Sensors 2009, 9, 4323-4365.
[16] D. Gutmacher, U. Hoefer, J. Wöllenstein, Gas sensor technologies for fire detection, Sens. Actuators B: Chem. (2011),
doi:10.1016/j.snb.2011.11.053