Ethernet Manual (Embedded)
Ethernet Manual (Embedded)
www.schneider-electric.com
The information provided in this documentation contains general descriptions and/or technical character-
istics of the performance of the products contained herein. This documentation is not intended as a
substitute for and is not to be used for determining suitability or reliability of these products for specific user
applications. It is the duty of any such user or integrator to perform the appropriate and complete risk
analysis, evaluation and testing of the products with respect to the relevant specific application or use
thereof. Neither Schneider Electric nor any of its affiliates or subsidiaries shall be responsible or liable for
misuse of the information contained herein. If you have any suggestions for improvements or amendments
or have found errors in this publication, please notify us.
No part of this document may be reproduced in any form or by any means, electronic or mechanical,
including photocopying, without express written permission of Schneider Electric.
All pertinent state, regional, and local safety regulations must be observed when installing and using this
product. For reasons of safety and to help ensure compliance with documented system data, only the
manufacturer should perform repairs to components.
When devices are used for applications with technical safety requirements, the relevant instructions must
be followed.
Failure to use Schneider Electric software or approved software with our hardware products may result in
injury, harm, or improper operating results.
Failure to observe this information can result in injury or equipment damage.
© 2014 Schneider Electric. All rights reserved.
2 EAV64327 08/2014
Table of Contents
Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
About the Book. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Chapter 1 Presentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Hardware Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Software Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Chapter 2 Basics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
2.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Network Layer Supported Functions/Protocols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
TCP and UDP Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
2.2 Modbus TCP Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Modbus TCP Frames . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Modbus TCP Servers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Supported Modbus TCP Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Application Profile with Modbus TCP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Chapter 3 Hardware Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Hardware Presentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Firmware Version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Connection to the Adapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Electrical Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Cable Routing Practice . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Chapter 4 Software Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
4.1 Basic Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
IP Parameter Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
[Device Name] ( PAn) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
[IP mode Eth Embd] ( IM00) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
[IP Eth Embd] (IC01) (IC02) (IC03) (IC04) . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
[IP Mask Eth Embd] (IM01) (IM02) (IM03) (IM04) . . . . . . . . . . . . . . . . . . . . . . 39
[IP Gate Eth Embd] (IG01) (IG02) (IG03) (IG04) . . . . . . . . . . . . . . . . . . . . . . . 40
[MAC @] (MAC). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
[ETH emb Rx frames] ( ErXE) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
[ETH emb Tx frames] ( EtXE) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
[ETH emb error frames] ( EErE) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
[Ethernet Rate Data] ( ArdE) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
[Ethernet Embd cmd.] ( CMd5) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
[Ethernet Embd Ref Freq] ( LFr5) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
[Enable Web Services] ( EWEE) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
[Reset EmbWeb Passwd] ( rWPE) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
[Ethernet Timeout] ( ttOb) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
4.2 Additional Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
FDR Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
[Embedded Eth Com Interrupt] ( EtHF) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
[External Error] ( EPF1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Configuring I/O Scanning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
4.3 Fast Device Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Presentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Startup Detailed Behavior . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
FDR Operation Behavior . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Local Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Downloaded Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
EAV64327 08/2014 3
4.4 Communication Profile . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Definition of a Profile . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Functional Profiles Supported by the Drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Functional Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
CIA402 Operating State Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Description of Operating States . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Control Word ( CMd) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Stop Commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Assigning Control Word Bits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Status Word ( EtA) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Starting Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Sequence for a Drive Powered by the Power Stage Supply . . . . . . . . . . . . . . . . . . . . . . . . . 76
Sequence for a Drive with Separate Control Stage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Sequence for a Drive with Mains Contactor Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
4.5 Embedded Webserver . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Connection to the Webserver. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Chapter 5 Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
5.1 Operating States . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Configuring Communication Detected Error Response . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
5.2 Operating Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Configuring the Control Channel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Configuration of the Drive for Operation in I/O Profile . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Configuration of the Drive for Operation with CiA 402 Profile in Combined Mode. . . . . . . . . 89
Configuration of the Drive for Operation with CiA 402 Profile in Separate Mode. . . . . . . . . . 90
Chapter 6 Diagnostic and Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Fieldbus Status LEDs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
Connection for Fieldbus Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Fieldbus Functions Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
4 EAV64327 08/2014
Safety Information
Important Information
NOTICE
Read these instructions carefully, and look at the equipment to become familiar with the device before
trying to install, operate, or maintain it. The following special messages may appear throughout this
documentation or on the equipment to warn of potential hazards or to call attention to information that
clarifies or simplifies a procedure.
PLEASE NOTE
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel.
No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this
material.
A qualified person is one who has skills and knowledge related to the construction and operation of
electrical equipment and its installation, and has received safety training to recognize and avoid the
hazards involved.
Qualification Of Personnel
Only appropriately trained persons who are familiar with and understand the contents of this manual and
all other pertinent product documentation are authorized to work on and with this product. In addition, these
persons must have received safety training to recognize and avoid hazards involved. These persons must
have sufficient technical training, knowledge and experience and be able to foresee and detect potential
hazards that may be caused by using the product, by changing the settings and by the mechanical,
electrical and electronic equipment of the entire system in which the product is used. All persons working
on and with the product must be fully familiar with all applicable standards, directives, and accident
prevention regulations when performing such work.
EAV64327 08/2014 5
Intended Use
This product is a drive for three-phase synchronous and asynchronous motors and intended for industrial
use according to this manual.The product may only be used in compliance with all applicable safety
regulations and directives, the specified requirements and the technical data.Prior to using the product, you
must perform a risk assessment in view of the planned application. Based on the results, the appropriate
safety measures must be implemented.Since the product is used as a component in an entire system, you
must ensure the safety of persons by means of the design of this entire system (for example, machine
design). Any use other than the use explicitly permitted is prohibited and can result in hazards. Electrical
equipment should be installed, operated, serviced, and maintained only by qualified personnel.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
z Only appropriately trained persons who are familiar with and understand the contents of this manual
and all other pertinent product documentation and who have received safety training to recognize and
avoid hazards involved are authorized to work on and with this drive system. Installation, adjustment,
repair and maintenance must be performed by qualified personnel.
z The system integrator is responsible for compliance with all local and national electrical code
requirements as well as all other applicable regulations with respect to grounding of all equipment.
z Many components of the product, including the printed circuit boards, operate with mains voltage. Do
not touch. Use only electrically insulated tools.
z Do not touch unshielded components or terminals with voltage present.
z Motors can generate voltage when the shaft is rotated. Prior to performing any type of work on the
drive system, block the motor shaft to prevent rotation.
z AC voltage can couple voltage to unused conductors in the motor cable. Insulate both ends of unused
conductors of the motor cable.
z Do not short across the DC bus terminals or the DC bus capacitors or the braking resistor terminals.
z Before performing work on the drive system:
z Disconnect all power, including external control power that may be present.
z Place a Do Not Turn On label on all power switches.
z Lock all power switches in the open position.
z Wait 15 minutes to allow the DC bus capacitors to discharge. The DC bus LED is not an indicator
of the absence of DC bus voltage that can exceed 800 Vdc.
Measure the voltage on the DC bus between the DC bus terminals (PA/+, PC/-) using a properly
rated voltmeter to verify that the voltage is <42 Vdc
z If the DC bus capacitors do not discharge properly, contact your local Schneider Electric represen-
tative. Do not repair or operate the product.
z Install and close all covers before applying voltage.
Failure to follow these instructions will result in death or serious injury.
WARNING
UNEXPECTED MOVEMENT
Drive systems may perform unexpected movements because of incorrect wiring, incorrect settings,
incorrect data or other errors.
z Carefully install the wiring in accordance with the EMC requirements.
z Do not operate the product with unknown or unsuitable settings or data.
z Perform a comprehensive commissioning test.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Damaged products or accessories may cause electric shock or unanticipated equipment operation.
6 EAV64327 08/2014
DANGER
ELECTRIC SHOCK OR UNANTICIPATED EQUIPMENT OPERATION
Do not use damaged products or accessories.
Failure to follow these instructions will result in death or serious injury.
Contact your local Schneider Electric sales office if you detect any damage whatsoever.
WARNING
LOSS OF CONTROL
z The designer of any control scheme must consider the potential failure modes of control paths and,
for critical control functions, provide a means to achieve a safe state during and after a path failure.
Examples of critical control functions are emergency stop, overtravel stop, power outage and restart.
z Separate or redundant control paths must be provided for critical control functions.
z System control paths may include communication links. Consideration must be given to the
implications of unanticipated transmission delays or failures of the link.
z Observe all accident prevention regulations and local safety guidelines (1).
z Each implementation of the product must be individually and thoroughly tested for proper operation
before being placed into service.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
(1) For USA: Additional information, refer to NEMA ICS 1.1 (latest edition), Safety Guidelines for the
Application, Installation, and Maintenance of Solid State Control and to NEMA ICS 7.1 (latest edition),
Safety Standards for Construction and Guide for Selection, Installation and Operation of Adjustable-Speed
Drive Systems.
NOTICE
DESTRUCTION DUE TO INCORRECT MAINS VOLTAGE
Before switching on and configuring the product, verify that it is approved for the mains voltage
Failure to follow these instructions can result in equipment damage.
EAV64327 08/2014 7
8 EAV64327 08/2014
About the Book
At a Glance
Document Scope
The purpose of this document is to:
z Show you how to connect the Ethernet fieldbus on your drive.
z Show you how to set up the drive to use Ethernet for monitoring and control.
z Provide examples of setup using commissioning software
NOTE: Read and understand this document and all related documents (see below) before
installing,operating, or maintaining your drive.
Validity Note
This documentation is valid for the drive Ethernet fieldbus.
The technical characteristics of the devices described in this document also appear online. To access this
information online:
Step Action
1 Go to the Schneider Electric home page www.schneider-electric.com.
2 In the Search box type the reference of a product or the name of a product range.
z Do not include blank spaces in the model number/product range.
z To get information on grouping similar modules, use asterisks (*).
3 If you entered a reference, go to the Product Datasheets search results and click on the reference that
interests you.
If you entered the name of a product range, go to the Product Ranges search results and click on the
product range that interests you.
4 If more than one reference appears in the Products search results, click on the reference that interests
you.
5 Depending on the size of your screen, you may need to scroll down to see the data sheet.
6 To save or print a data sheet as a .pdf file, click Download XXX product datasheet.
The characteristics that are presented in this manual should be the same as those characteristics that
appear online. In line with our policy of constant improvement, we may revise content over time to improve
clarity and accuracy. If you see a difference between the manual and online information, use the online
information as your reference.
Related Documents
Use your tablet or your PC to quickly access detailed and comprehensive information on all our products
on www.schneider-electric.com
The Internet site provides the information you need for products and solutions
z The whole catalog for detailed characteristics and selection guides
z The CAD files to help design your installation, available in over 20 different file formats
z All software and firmware to maintain your installation up to date
z A large quantity of White papers, environment documents, application solutions, specifications... To
gain a better understanding of electrical systems and equipment or automation
z All the user guides related to your drive, listed below:
EAV64327 08/2014 9
Title of Documentation Reference Number
Altivar Process DeviceNet manual (VW3A3609) EAV64330
Altivar Process PROFINET manual (VW3A3627) EAV64333
Altivar Process CANopen Serial Link Manual (VW3A3608, 618, 628) EAV64331
Altivar Process Communication Parameters EAV64332
Altivar Process Safety Function Manual EAV64334
You can download these technical publications and other technical information from our website at
www.schneider-electric.com.
10 EAV64327 08/2014
Presentation
Chapter 1
Presentation
EAV64327 08/2014 11
Presentation
Hardware Overview
General
The drive embeds an Ethernet communication port that can be used for Modbus TCP industrial
communication protocol.
In addition of the communication services provided by the protocol, the embedded adapter provides a set
of services at the Ethernet and TCP/IP level. The embedded adapter offers an embedded Web server
which offers comfortable displaying and commissioning functions directly from a standard web browser.
12 EAV64327 08/2014
Presentation
Software Overview
EAV64327 08/2014 13
Presentation
14 EAV64327 08/2014
Basics
Chapter 2
Basics
EAV64327 08/2014 15
Basics
Introduction
Section 2.1
Introduction
16 EAV64327 08/2014
Basics
Overview
Modbus TCP
The Modbus application layer is standard. Thousands of manufacturers are already implementing this
protocol. Many have already developed a Modbus TCP/IP connection and numerous products are
currently available. With the simplicity of its protocol and the fast Ethernet throughput data rate of
100 Mbit/s, Modbus TCP/IP achieves excellent performance.
Webserver
The standard Web server (six languages) provides access to the following pages:
z My dashboard: Customer defined view based on widgets
z Display
z Diagnostics
z Drive
z Setup
EAV64327 08/2014 17
Basics
ARP Protocol
The ARP (Address resolution protocol) is a protocol used by the IP (Internet protocol) network layer
protocol to map IP network addresses to hardware addresses (MAC address).
The protocol operates below the network layer as a part of the OSI link layer, and is used when IP is used
over Ethernet. A host, wishing to obtain a physical address, broadcasts an ARP request onto the TCP/IP
network. The host on the network that has the IP address in the request, then replies with its physical HA
(Hardware address).
There are four types of ARP messages which may be sent by the ARP protocol. They are identified by two
values in the “operation” field of an ARP message. The types of message are: ARP request; ARP reply.
0 8 15 16 31
Hardware type Protocol type
HLEN PLEN Operation
(Hardware address length) (Protocol address length)
Sender HA (bytes 0-3)
Sender HA (bytes 4-5) Sender IP (bytes 0-1)
Sender IP (bytes 2-3) Target HA (bytes 0-1)
Target HA (bytes 2-5)
Target IP (bytes 0-3)
ICPM Protocol
The embedded board manages the ICMP protocol.
z ICMP client: not supported
z ICMP server: the managed requests are the following:
Type Description
0 Echo reply (ping)
3 Destination unreachable
4 Sources quench
5 Redirect
6 Alternate host address
8 Echo request (ping)
9 Router advertisement
10 Router solicitation
11 Time exceeded
12 Parameter problem
13 Time stamp request
14 Time stamp reply
15 Information request
18 EAV64327 08/2014
Basics
Type Description
16 Information reply
17 Address mask request
18 Address mask reply
IP Protocol
The Ethernet adapter implements the IP protocols V4 and V6.
SNMP Services
The Ethernet adapter accepts the community name “private” for Writing and the community name “public”
for Reading.
MIB
EAV64327 08/2014 19
Basics
Connections
The Ethernet adapter supports up to 32 concurrent TCP/IP and/or TCP/UDP connection.
Field Description
op Message type DHCP request / DHCP reply
htype Address hardware type
hlen Hardware address length
hops Used by relay agent
xid Transaction identifier, random number chosen by the client allowing to associate the request and the
response
secs Time in seconds since the beginning of the transaction
flags First bit used for the broadcast reply flag
ciaddr Client IP address, only used if the client can respond to ARP request
yiaddr Client IP address, “your” IP address proposed by the server
siaddr IP address of the server
giaddr Gateway IP address, used when a relay agent needs to be crossed
sname Server name
file Location of boot file
options Optional parameters with DHCP extensions
20 EAV64327 08/2014
Basics
DHCP Message
The DHCP protocol uses 8 different types of message during the IP assigning process.
The table describes 8 messages:
Message Description
DISCOVER The client tries to discover the DHCP server using a broadcast
OFFER The server proposes a configuration
REQUEST The client chooses a DHCP server and declines other offers
ACK The chosen server assigns the IP configuration
NAK The server rejects the client request
DECLINE The client declines the assigned IP configuration
RELEASE The client releases Its IP address before the end of the lease
INFORM The client asks for network information (it already has an IP address)
Operating Modes
The choice between DHCP, BOOTP, and fixed configuration is made through one parameter:
z Fixed mode: the Ethernet adapter uses the address stored in parameter.
z BOOTP: the Ethernet adapter receives the addresses from BOOTP server.
z DHCP: if the device name [XXX] is valid, the Ethernet adapter receives the addresses from the DHCP
server.
EAV64327 08/2014 21
Basics
Section 2.2
Modbus TCP Features
22 EAV64327 08/2014
Basics
TCP Telegrams
Modbus TCP telegrams are not only Modbus standard requests and responses encapsulated in TCP
frames.
1 TCP header
2 MBPA: Modbus application protocol header
3 ADU: Application data unit
4 PDU: Protocol data unit (The Modbus message itself)
EAV64327 08/2014 23
Basics
Overview
24 EAV64327 08/2014
Basics
Identification
Id Value Comment
00 hex Schneider electric Device manufacturer
01 hex ATVXXX Drive commercial part number
02 hex 0101 Drive version
04 hex − −
05 hex − −
06 hex Customized Name Device name
This exchange is performed by implicit requests, thus avoiding the need to program the controller (PLC).
The I/O scanner periodically generates the read/write multiple registers (23 = 17 hex) request. The I/O
scanning service operates if it has been enabled in the PLC and the drive. The drive parameters assigned
to I/O scanning have been selected by default. This assignment can be modified by configuration.
When the I/O scanning service has been enabled in the drive:
z A TCP connection is assigned to it.
z The parameters assigned in the periodic variables are exchanged cyclically between the Ethernet
adapter and the drive.
z The parameters assigned to the periodic output variables are reserved for I/O scanning. They cannot
be written by other Modbus services, even if the I/O scanner is not sending its periodic output variables.
EAV64327 08/2014 25
Basics
Description
The profiles managed with the drive when it is controlled through Modbus TCP are:
z Native profile (CiA402 - IEC 61800-7),
z I/O profile.
For details, refer to CiA®402 - IEC61800-7 functional profile (see page 63)
26 EAV64327 08/2014
Hardware Setup
Chapter 3
Hardware Setup
EAV64327 08/2014 27
Hardware Setup
Hardware Presentation
28 EAV64327 08/2014
Hardware Setup
Firmware Version
Compatibility
The drive firmware and embedded communication adapter are provided in a common package for
updating the drive.
EAV64327 08/2014 29
Hardware Setup
Apply the following instructions to remove the front cover of the drive:
Step Action
1 Unscrew the four screws attaching the front cover
2 Slide down the front cover
3 Remove the front cover
4 Plug the Ethernet cable in the Ethernet port
30 EAV64327 08/2014
Hardware Setup
Electrical Installation
Pin Layout
The figure shows the RJ45 socket for the Ethernet connection:
The table provides the pin out details of each RJ45 connector:
Cable Specification
Cable specifications are as follows:
z Minimum Cat 5e,
z Use equipotential bonding conductors
z Connector RJ45
z Shield: both ends grounded
z Twisted-pair cable
z Cable: 8 x 0.25 mm² (8 x AWG 22)
z Use pre-assembled cables to reduce the wiring mistakes,
z Verify that wiring, cables, and connected interfaces meet the PELV requirements.
z Maximum cable length per segment = 100 m (328 ft)
EAV64327 08/2014 31
Hardware Setup
Installation Topology
The following figure shows the connection between the drive and PC through an Ethernet switch.
The following figure shows the direct connection between the drive and PC.
32 EAV64327 08/2014
Software Setup
Chapter 4
Software Setup
EAV64327 08/2014 33
Software Setup
Basic Settings
Section 4.1
Basic Settings
34 EAV64327 08/2014
Software Setup
IP Parameter Settings
Assigning IP Parameters
If not using IPV6 functionalities, following parameters shall be configured:
z The drive IP address.
z The subnet mask.
z The gateway IP address.
These IP addresses can be entered using the display terminal, the embedded webserver, or the DTM-
based PC software.
They can be also provided by:
z A BOOTP server (correspondence between the MAC address and the IP addresses).
z Or a DHCP server (correspondence between device name [DEVICE NAME] (PAn) and the IP
addresses).
If an IP address other than 0.0.0.0 has been entered manually, assignment using a server is disabled.
Regardless of the type of IP address assignment, if the address is modified, then the IP address is effective
the next time the drive is turned on (control voltage if a separate power supply is being used).
Configuring BOOTP
The BOOTP service is used to assign IP addresses based on the MAC address. The MAC address
consisting of 6 hexadecimal digits (MM-MM-MM-XX-XX-XX) must be entered in the BOOTP server. The
MAC address appears on the fieldbus adapter dedicated menu on the display terminal.
In the [Communication] ( COM-) , [Comm parameters] ( CMP-) menu and [Ethernet Embd]
( EtE-) submenu:
z Leave the IP address [IP Eth Embd] ( IC01) ( IC02) ( IC03) ( IC04) at the value[0.0.0.0]
( 0) ( 0) ( 0) ( 0) .
z Do not enable the FDR service.
Configuring DHCP
The DHCP service is used to assign IP addresses and FDR configuration file path based on the device
name [DEVICE NAME] (PAn).
The device name consisting of an alphanumeric string must be entered in both the DHCP server and the
drive.
In the [Communication] ( COM-) , [Comm parameters] ( CMP-) menu and [Ethernet Embd]
( EtE-) submenu, enter the [DEVICE NAME] (PAn)
EAV64327 08/2014 35
Software Setup
Access
This parameter is accessible via [Communication] ( COM-) , [Comm parameters] ( CMP-) menu
and [Ethernet Embd] ( EtE-) submenu.
This is a read/write parameter
Possible Settings
The FDR (Fast Device Replacement) service is based on identification of the device by a Device Name.
In the case of the Altivar drive, this is represented by the [Device Name] ( PAn) parameter. Verify that
all the network devices have different Device Name.
36 EAV64327 08/2014
Software Setup
Access
This parameter is accessible via [Communication] ( COM-) , [Comm parameters] ( CMP-) menu
and [Ethernet Embd] ( EtE-) submenu.
This is a read/write parameter
The parameter number is 64400.
Possible Settings
The table presents the parameter settings:
EAV64327 08/2014 37
Software Setup
Access
This parameter is accessible via [Communication] ( COM-) , [Comm parameters] ( CMP-) menu
and [Ethernet Embd] ( EtE-) submenu.
This is a read/write parameter
The parameter number for IC01 is 64401
The parameter number for IC02 is 64402
The parameter number for IC03 is 64403
The parameter number for IC04 is 64404
Possible Settings
The table presents the parameter settings:
38 EAV64327 08/2014
Software Setup
Access
This parameter is accessible via [Communication] ( COM-) , [Comm parameters] ( CMP-) menu
and [Ethernet Embd] ( EtE-) submenu.
This is a read/write parameter
The parameter number for IPM1 is 64405
The parameter number for IPM2 is 64406
The parameter number for IPM3 is 64407
The parameter number for IPM4 is 64408
Possible Settings
The table presents the parameter settings:
EAV64327 08/2014 39
Software Setup
Access
This parameter is accessible via [Communication] ( COM-) , [Comm parameters] ( CMP-) menu
and [Ethernet Embd] ( EtE-) submenu.
This is a read/write parameter
The parameter number for IG01 is 64409
The parameter number for IG02 is 64410
The parameter number for IG03 is 64411
The parameter number for IG04 is 64412
Possible Settings
The table presents the parameter settings:
40 EAV64327 08/2014
Software Setup
[MAC @] (MAC)
Access
This parameter is accessible via [Display] ( MON-) , [Communication map] ( CMM-) menu and
[Ethernet Embd Diag] ( MPE-) submenu.
This is a read-only parameter
Possible Settings
The table presents the parameter settings:
EAV64327 08/2014 41
Software Setup
Access
This parameter is accessible via [Display] ( MON-) , [Communication map] ( CMM-) menu and
[Ethernet Embd Diag] ( MPE-) submenu.
This is a read-only parameter
The parameter numbers is 64416
42 EAV64327 08/2014
Software Setup
Access
This parameter is accessible via [Display] ( MON-) , [Communication map] ( CMM-) menu and
[Ethernet Embd Diag] ( MPE-) submenu.
This is a read-only parameter
The parameter numbers is 64418
EAV64327 08/2014 43
Software Setup
Access
This parameter is accessible via [Display] ( MON-) , [Communication map] ( CMM-) menu and
[Ethernet Embd Diag] ( MPE-) submenu.
This is a read-only parameter
The parameter numbers is 64420
44 EAV64327 08/2014
Software Setup
Access
This parameter is accessible via [Display] ( MON-) , [Communication map] ( CMM-) menu and
[Ethernet Embd Diag] ( MPE-) submenu.
This is a read-only parameter
The parameter numbers is 64413
Possible Settings
The table presents the parameter settings:
EAV64327 08/2014 45
Software Setup
Access
This parameter is accessible via [Display] ( MON-) , [Communication map] ( CMM-) menu and
[Command word image] ( CWI-) submenu.
This is a read-only parameter
The parameter numbers is 8515
46 EAV64327 08/2014
Software Setup
Access
This parameter is accessible via [Display] ( MON-) , [Communication map] ( CMM-) menu and
[Command word image] ( CWI-) submenu.
This is a read-only parameter
The parameter numbers is 8525
EAV64327 08/2014 47
Software Setup
Access
This parameter is accessible via [My preferences] ( MYP-) menu and [Webserver] ( WbS-)
submenu.
This is a read/write parameter
The parameter numbers is 6693
Possible Settings
The table presents the parameter settings:
48 EAV64327 08/2014
Software Setup
Access
This parameter is accessible via [My preferences] ( MYP-) menu and [Webserver] ( WbS-)
submenu.
This is a read/write parameter
Possible Settings
The table presents the parameter settings:
EAV64327 08/2014 49
Software Setup
Access
This parameter is accessible via fieldbus using the Modbus address.
This is a read/write parameter
The parameter number is 64415.
Possible Settings
The table presents the parameter settings:
Settings Description
0.1...30 sec Factory setting: 10 sec
50 EAV64327 08/2014
Software Setup
Additional Settings
Section 4.2
Additional Settings
EAV64327 08/2014 51
Software Setup
FDR Settings
Access
The parameters are accessible via the webserver or the DTM-based PC software
FDR Configuration
The following figure shows FDR settings via webserver:
52 EAV64327 08/2014
Software Setup
Access
This is a read-only parameter
The parameter number is 7132.
Possible Settings
The table presents the parameter settings:
EAV64327 08/2014 53
Software Setup
Access
This is a read-only parameter
The parameter number is 7143.
Possible Settings
The table presents the parameter settings:
54 EAV64327 08/2014
Software Setup
Description
The drive I/O scanning service can be enabled or disabled with the DTM-based PC software.
It is not possible to modify the assignment of the I/O scanning periodic variables using the display terminal.
To configure I/O scanning, use the DTM-based PC software.
EAV64327 08/2014 55
Software Setup
Section 4.3
Fast Device Replacement
56 EAV64327 08/2014
Software Setup
Presentation
FDR Service
The FDR (Fast Device Replacement) service is used to simplify the maintenance of drives connected on
the Ethernet network. In the event of drive not functioning correctly, this service automatically reconfigures
its replacement.
The new drive (FDR client) retrieves:
z Its IP addresses and the FDR file path from a DHCP server
z The FDR file from an FTP server, if the drive is not configured in local configuration
In practice, the DHCP server and the FTP server are the same device (PAC M580, M340 PLC, or
dedicated PCs).
The FDR file contains:
z The Ethernet parameters (configuration of I/O scanning, FDR, and so on)
z The drive parameters (drive, functions, application, and so on)
The FDR service is based on identification of the device by a Device Name. In the case of the Altivar
process drive, this is represented by the [DEVICE NAME] ( PAn) parameter.
The configuration of the FDR service is accessible via embedded webserver or DTM-based software.
NOTE: Check that all the network devices have different Device Name.
NOTE: The FDR server controls duplication of Device Name (it does not assign an IP address that has
already been assigned and is active).
If the same IP address is supplied on 2 devices, the second should trigger an IP address duplication
(network management detected error which triggers an [External Error] ( EPF1) by default).
If the FDR service has been enabled, the Ethernet adapter attempts to restore its IP addresses on each
power-up. Each time the procedure has detected error, the Ethernet adapter reiterates its FDR requests
(DHCP).
Where the configuration also needs to be downloaded by the FDR server:
After assigning the Ethernet card IP addresses, if the configuration download has detected error, the
Ethernet card detects a network management detected error (triggers an [External Error] ( EPF1) by
default).
EAV64327 08/2014 57
Software Setup
Presentation
58 EAV64327 08/2014
Software Setup
EAV64327 08/2014 59
Software Setup
Local Configuration
Presentation
IP Assignment Save
If the drive parameter configuration is local, the FDR server only assigns the following IP addresses:
z Card IP address,
z Subnet mask,
z Gateway IP address.
On connection to the network, the drive automatically saves its parameters in the FDR server.
60 EAV64327 08/2014
Software Setup
Downloaded Configuration
Presentation
IP Assignment Save
If the drive parameter configuration has been downloaded, the FDR server assigns the following
addresses:
z Card IP address,
z Subnet mask,
z Gateway IP address,
z FDR server IP address.
Periodic Saving
Periodic saving of the drive configuration can be configured on the FDR server in either local configuration
or downloaded configuration mode
Using the embedded webserver or the DTM-based software:
z Set FDR synchronization to automatic mode
z Set the synchronization cycle time
NOTE: Saving too often risks overburdening the fieldbus and adversely affecting its performance (factory
setting: 2.560 s.).
Limitations
The FDR service is able to store the current configuration of the drive, but does not provide the possibility
to store multi-parameters configurations.
EAV64327 08/2014 61
Software Setup
6 Check that the system is operational If the save operation has not been successful, the adapter
detects a communication error which, in factory settings
mode, triggers an [External Error]( EPF1)
Replacing a Drive
For replacing a drive, it is necessary to follow the procedure below:
62 EAV64327 08/2014
Software Setup
Communication Profile
Section 4.4
Communication Profile
EAV64327 08/2014 63
Software Setup
Definition of a Profile
Types of Profiles
There are 3 types of profile:
z Communication profiles
z Functional profiles
z Application profiles
Communication Profile
A communication profile describes the characteristics of the bus or network:
z Cables
z Connectors
z Electrical characteristics
z Access protocol
z Addressing system
z Periodic exchange service
z Messaging service
z ...
A communication profile is unique to a type of fieldbus (such as Modbus, PROFIBUS DP, and so on) and
is used by various different types of device.
Functional Profile
A functional profile describes the behavior of a type of device:
z Functions
z Parameters (such as name, format, unit, type, and so on.)
z Periodic I/O variables
z State chart
z ...
A functional profile is common to all members of a device family (such as variable speed drives, encoders,
I/O modules, displays, and so on).
They can feature common or similar parts. The standardized (IEC 61800-7) functional profiles of variable
speed drives are:
z CiA402
z PROFIDRIVE
z CIP
Application Profile
Application profile defines the services to be provided by the devices on a machine. For example, CiA DSP
417-2 V 1.01 part 2: CANopen application profile for lift control systems - virtual device definitions.
Interchangeability
The aim of communication and functional profiles is to achieve interchangeability of the devices connected
via the fieldbus.
64 EAV64327 08/2014
Software Setup
I/O Profile
Using the I/O profile simplifies PLC programming.
The I/O profile mirrors the use of the terminal strip for control by utilizing 1 bit to control a function.
The I/O profile for the drive can also be used when controlling via a fieldbus.The drive starts up as soon as
the run command is sent.15 bits of the control word (bits 1...15) can be assigned to a specific function.
This profile can be developed for simultaneous control of the drive via:
z The terminals
z The Modbus control word
z The CANopen control word
z Ethernet Modbus TCP embedded
z The fieldbus module control word
The I/O profile is supported by the drive itself and therefore in turn by all the communication ports
(integrated Modbus, CANopen, Ethernet, PROFIBUS DP, PROFINET, and DeviceNet fieldbus modules).
CiA402 Profile
The drive only starts up following a command sequence.
The control word is standardized.
5 bits of the control word (bits 11...15) can be assigned to a function.
The CiA402 profile is supported by the drive itself and therefore by all the communication ports (Modbus,
CANopen, Ethernet, PROFIBUS DP, PROFINET, and DeviceNet).
The drive supports the velocity mode of CiA402 profile.
In the CiA402 profile, there are two modes that are specific to the drive and characterize commands and
references value management:
z Separate [Separate] (SEP)
z Not separate [Not separ.] (SIN),
EAV64327 08/2014 65
Software Setup
Functional Description
Introduction
Drive operation involves two main functions, which are illustrated in the diagrams below.
CiA402
The main parameters are shown with their CiA402 name and their CiA402/Drivecom index (the values in
brackets are the CANopen addresses of the parameter).
The following figure shows the control diagram for drive operation:
Altivar Process
These diagrams translate as follows for the Altivar process system.
The following figure shows the control diagram for drive operation:
66 EAV64327 08/2014
Software Setup
State Diagram
After switching on and when an operating mode is started, the product goes through a number of operating
states.
The state diagram (state machine) shows the relationships between the operating states and the state
transitions. The operating states are internally monitored and influenced by monitoring functions.
The following figure shows the CIA402 state diagram:
EAV64327 08/2014 67
Software Setup
68 EAV64327 08/2014
Software Setup
7 - Fault reaction Transient state during which the drive performs an action corresponding to the
active selected error response.
8 - Fault Error response terminated. Power stage is disabled.
The drive is locked, no power is supplied to the motor.
EAV64327 08/2014 69
Software Setup
Summary
Operating State Power Stage Supply for Power Supplied to Modification of Configuration
Separate Control Stage Motor Parameters
1 - Not ready to Not required No Yes
switch on
2 - Switch on Not required No Yes
disabled
3 - Ready to Not required No Yes
switch on
4 - Switched on Required No Yes, return to 2 - Switch on
disabled operating state
5 - Operation Required Yes No
enabled
6 - Quick stop Required Yes, during fast stop No
active
7 - Fault reaction Depends on error response Depends on error −
active configuration response configuration
8 - Fault Not required No Yes
70 EAV64327 08/2014
Software Setup
Bit Mapping
EAV64327 08/2014 71
Software Setup
Stop Commands
Halt Command
The Halt command enables movement to be interrupted without having to leave the 5 - Operation
enabled state. The stop is performed in accordance with the [Type of stop] ( Stt) parameter.
If the Halt command is active, no power is supplied to the motor and no torque is applied.
Regardless of the assignment of the [Type of stop] ( Stt) parameter [Fast stop assign]
( FSt) ,[Ramp stop] ( rMP) , [Freewheel] ( nSt) , or [DC injection assign.] ( dCI) ), the drive
remains in the 5 - Operation enabled state.
Freewheel Command
A Freewheel Stop command using a digital input of the terminal or a bit of the control word assigned
to Freewheel Stop causes a change to operating state 2 - Switch on disabled.
72 EAV64327 08/2014
Software Setup
Function Codes
In the CiA402 profile, fixed assignment of a function input is possible using the following codes:
For example, to assign the DC injection braking to bit13 of embedded Ethernet, simply configure the[ DC
injection assign.] ( dCI) parameter with the [C513] ( C513) value.
Bit 11 is assigned by default to the operating direction command [Reverse assign.] ( rrS) .
EAV64327 08/2014 73
Software Setup
Bit Mapping
74 EAV64327 08/2014
Software Setup
Starting Sequence
Description
The command sequence in the state diagram depends on how power is being supplied to the drive.
There are 3 possible scenarios:
EAV64327 08/2014 75
Software Setup
Description
Both the power and control stages are powered by the power stage supply.
If power is supplied to the control stage, it has to be supplied to the power stage as well.
The following sequence must be applied:
Step 1
Apply the 2 - Shut down command
Step 2
z Check that the drive is in the operating state 3 - Ready to switch on.
z Then apply the 4 - Enable operation command.
z The motor can be controlled (send a reference value not equal to zero).
NOTE: It is possible, but not necessary to apply the 3 - Switch on command followed by the 4 -
Enable Operation command to switch successively into the operating states 3 - Ready to Switch
on, 4 - Switched on and then 5 - Operation Enabled. The 4 - Enable operation command
is sufficient.
76 EAV64327 08/2014
Software Setup
Description
Power is supplied separately to the power and control stages.
If power is supplied to the control stage, it does not have to be supplied to the power stage as well.
The following sequence must be applied:
Step 1
z The power stage supply is not necessarily present.
z Apply the 2 - Shut down command
Step 2
z Check that the drive is in the operating state 3 - Ready to switch on.
z Check that the power stage supply is present (Voltage enabled of the status word).
EAV64327 08/2014 77
Software Setup
Step 3
z Check that the drive is in the operating state 4 - Switched on.
z Then apply the 4 - Enable operation command.
z The motor can be controlled (send a reference value not equal to zero).
z If the power stage supply is still not present in the operating state 4 - Switched on after a time delay
[Mains V. time out] ( LCt) , the drive triggers an error [input contactor] ( LCF) .
78 EAV64327 08/2014
Software Setup
Description
Power is supplied separately to the power and control stages.
If power is supplied to the control stage, it does not have to be supplied to the power stage as well. The
drive controls the mains contactor.
The following sequence must be applied:
Step 1
z The power stage supply is not present as the mains contactor is not being controlled.
z Apply the 2 - Shutdown command.
Step 2
z Check that the drive is in the operating state 3 - Ready to switch on.
z Apply the 3 - Switch on command, which closes the mains contactor and switch on the power stage
supply.
EAV64327 08/2014 79
Software Setup
Embedded Webserver
Section 4.5
Embedded Webserver
80 EAV64327 08/2014
Software Setup
Overview
Webserver
The Ethernet adapter provides an integrated Web server which allows several functions like: display,
parameter settings, and diagnostics. This chapter describes the services provided by this webserver.
The webserver can be accessed from standard browsers like Internet Explorer, chrome, safari, or Firefox.
EAV64327 08/2014 81
Software Setup
Access
The webserver can be accessed from standard browsers.
In the following example, the drive has received the IP address 10.0.0.5:
First connect the computer to the drive by typing http:// followed by the drive IP address.
You are asked to first enter a User Name and a Password.
By default the user name is ADMIN and the password is also ADMIN.
Once connected, the webserver home page is displayed.
Using IPV6 network discovery service, there is no need to set IP parameters. The drive appears
automatically in the network explorer of the PC while physically connected.
The drive is identified as ATV6ppppppp-MMMM where MMMM is the two last bytes of the MAC address.
Right-click and select Display device web page to open the webserver.
82 EAV64327 08/2014
Operations
Chapter 5
Operations
EAV64327 08/2014 83
Operations
Operating States
Section 5.1
Operating States
Description
The response of the drive in the event of an Ethernet communication interruption can be configured.
Configuration can be performed using the display terminal from the [Complete settings] (CSt-),
[Error/warning handling] (CSWM) menu, [Fieldbus monitoring] ( CLL-) submenu, via the [Eth
Error Response] ( EtHL) .
The values of the [Eth Error Response] ( EtHL) parameter, which triggers a drive detected error
[Embedded Eth Com Interrupt] (EtHF) , are:
Value Meaning
[Freewheel] (YES) Freewheel stop (factory setting)
[Ramp stop] (rMP) Stop on ramp
[Fast stop] ( FSt) Fast stop
[DC injection] ( dCI) DC injection stop
The values of the [Eth Error Response] ( EtHL) parameter, which does not trigger a drive detected
error, are:
Value Meaning
[Ignore] (nO) Detected error ignored
[Per STT] (Stt) Stop according to configuration of [Type of stop] (Stt)
[fallback spd] (LFF) Change to fallback speed, maintained as long as the detected error persists
and the run command has not been removed
[Spd maint.] (rLS) The drive maintains the speed at the time the detected error occurred, as
long as the detected error persists, and the run command has not been
removed
The fallback speed can be configured in the [Complete settings] (CSt-), [Error/warning handling]
(CSWM) menu, [Fallback speed] ( LFF-) submenu, using the [Fallback speed] (LFF) parameter.
WARNING
LOSS OF CONTROL
If this parameter is set to nO, Modbus communication monitoring is disabled.
z Only use this setting after a thorough risk assessment in compliance with all regulations and standards
that apply to the device and to the application.
z Only use this setting for tests during commissioning.
z Verify that communication monitoring has been re-enabled before completing the commissioning
procedure and performing the final commissioning test.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
84 EAV64327 08/2014
Operations
Detected Errors
EAV64327 08/2014 85
Operations
Operating Modes
Section 5.2
Operating Modes
86 EAV64327 08/2014
Operations
Overview
This chapter explains how to configure the drive for operation from communication network through three
following examples.
z I/O mode - a simple command word (based on forward, reverse, and reset binary commands).
z Combined mode (with native profile CiA 402) - Both reference value and command word come from the
communication network.
z Separate (with native profile CiA 402) - reference value and command come from separate sources: for
example, the command (in CiA 402) comes from the communication network and the reference value
from the HMI.
EAV64327 08/2014 87
Operations
Description
The I/O profile, here is a simple example, which can be extended with additional features. The command
word is made of run forward (bit 0 of CMd), run reverse (bit 1 of CMd), and the function fault reset (bit 7 of
CMd).
In the [Error/warning handling] ( CSWM) menu, [Fault Reset] ( rSt-) submenu, configure:
88 EAV64327 08/2014
Operations
Configuration of the Drive for Operation with CiA 402 Profile in Combined Mode
Description
This section describes how to configure the settings of the drive if it is controlled in CiA 402 mode. The
example focuses on the not separate mode. Additional modes are detailed in the drive programming
manual.
In the [Complete settings] ( CSt-) menu, [Command and reference] ( CrP-) submenu:):
z [Ref.1 Channel] (Fr1): is set on according to the communication source you can choose in the
following table:
z [Profile] (CHCF): defines if the drive operates in combined mode (reference value and command from
the same channel).
EAV64327 08/2014 89
Operations
Configuration of the Drive for Operation with CiA 402 Profile in Separate Mode
Description
Alternate combinations are possible, see the drive programming manual for the list of possible settings.
For example:
The drive is controlled from the communication (Ethernet) but the reference value is adjusted on display
terminal. The control word comes from the controller and is written according to CiA 402 profile.
The settings are as shown in the table:
90 EAV64327 08/2014
Diagnostic and Troubleshooting
Chapter 6
Diagnostic and Troubleshooting
EAV64327 08/2014 91
Diagnostic and Troubleshooting
LED Indicators
The following figure describes the LEDs status for fieldbus monitoring
LED Description
92 EAV64327 08/2014
Diagnostic and Troubleshooting
LED Behaviour
LED behavior
EAV64327 08/2014 93
Diagnostic and Troubleshooting
Description
If the product cannot be addressed via the fieldbus, first check the connections. The product manuals
contains the technical data of the device and information on fieldbus and device installation.
Verify the following:
z Power connections to the device
z Fieldbus cable and fieldbus wiring
z Fieldbus connection to the device
94 EAV64327 08/2014
Diagnostic and Troubleshooting
EAV64327 08/2014 95
Diagnostic and Troubleshooting
If a communication warning is sent (in accordance with the protocol criteria) by a monitored port or fieldbus
module, the drive triggers a communication interruption.
The drive reacts according to the communication interruption configuration (operating state Fault,
maintenance, fallback, and so on)
If a communication warning occurs on a channel that is not being monitored, the drive does not trigger a
communication interruption.
96 EAV64327 08/2014
Glossary
A
Abbreviations
Req. = Required
Opt. = Optional
D
Display terminal
The display terminal menus are shown in square brackets.
For example: [Communication]
The codes are shown in round brackets.
For example: (CON-)
Parameter names are displayed on the display terminal in square brackets.
For example: [fallback spd]
Parameter codes are displayed in round brackets.
For example: (LFF)
E
Error
Discrepancy between a detected (computed, measured, or signaled) value or condition and the specified
or theoretically correct value or condition.
F
Factory setting
Factory settings when the product is shipped
Fault
Fault is an operating state. If the monitoring functions detect an error, a transition to this operating state is
triggered, depending on the error class. A "Fault reset" is required to exit this operating state after the
cause of the detected error has been removed. Further information can be found in the pertinent standards
such as IEC 61800-7, ODVA Common Industrial Protocol (CIP).
Fault Reset
A function used to restore the drive to an operational state after a detected error is cleared by removing
the cause of the error so that the error is no longer active.
M
Monitoring function
Monitoring functions acquire a value continuously or cyclically (for example, by measuring) in order to
check whether it is within permissible limits. Monitoring functions are used for error detection.
P
Parameter
Device data and values that can be read and set (to a certain extent) by the user.
PELV
Protective Extra Low Voltage, low voltage with isolation. For more information: IEC 60364-4-41
PLC
Programmable logic controller
EAV64327 08/2014 97
Glossary
Power stage
The power stage controls the motor. The power stage generates current for controlling the motor.
Q
Quick Stop
The Quick Stop function can be used for fast deceleration of a movement as a response to a detected error
or via a command.
W
Warning
If the term is used outside the context of safety instructions, a warning alerts to a potential problem that
was detected by a monitoring function. A warning does not cause a transition of the operating state.
98 EAV64327 08/2014
Altivar_Ethernet Manual(Embedded)_EN_EAV64327_01
08/2014