Earth Fault Protection Guide 2022 Part 1
Earth Fault Protection Guide 2022 Part 1
Protection
How to design efficient earth fault protection
with Residual Current Devices (RCD)
Guide 2022
se.com
The aim of this guide is to provide advice for the
selection and implementation of Residual Current
Devices according to international series of standards
IEC 60364 and based on Schneider Electric best
practices and products.
The information provided in this guide contains general descriptions and/or technical characteristics of the
performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or
reliability of these products for specific user applications. It is the duty of the reader to perform the
appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant
specific application or use thereof.
Neither Schneider Electric nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of
the information contained herein. If you have any suggestions for improvements or amendments or have
found errors in this publication, please notify us.
No part of this document may be reproduced in any form or by any means, electronic or mechanical,
including photocopying, without express written permission of Schneider Electric.
Any work performed on an electrical installation must comply with all applicable local, regional and national
regulations.
Selectors....................................................................... 54 F
Appendix....................................................................... 55 G
Acronyms...................................................................... 61 H
Current flow time Residual Current Devices (RCD) are designed to provide protection against
hazardous earth fault current.
A
t (ms)
C1
10000
5000
The principles of the protection of persons against electric shock refer to the serious
physiological risks (respiratory paralysis, ventricular fibrillation) that can occur in the
2000 AC-4
1000 hazardous zone event of contact with a live part, causing an excessively high current to flow through
500 the human body for too long a time.
AC-1 to AC-3
The IEC 60479-1 publications updated in 2016 define the limit (C1) below which
200 non-hazardous zone
100
these principles must be come into play.
50
20
10 Ib (mA) Protection of persons in low-voltage installations must comply with standards,
0.1 0.2 0.5 1 2 5 10 20 50 100 200 500 2000 10000 installation rules, best practices, official guides, circulars, etc.
1000 5000
Current through i.e.IEC 61140, IEC 60364, IEC 60479, IEC 61008, IEC 61009, IEC 60947-2, etc.
body In accordance with IEC 61140, in low voltage installations, the triple level of
protection is mandatory:
Insulation
DB429095.eps
barrier Level 1
(cable trough)
Hazardous live-parts shall not be accessible
This level applies to any "normally" live part (for example electrical cable) to prevent
any person to come into contact with it (direct contact).
The type of protection to be implemented is called "basic protection".
An insulation barrier such as cable insulation, a cover, housing, cable protection
troughs, etc. is required to ensure protection.
Level 2
Accessible-conductive-parts shall not become hazardous
This level applies to any accessible conductive part that is not "normally" live but
DB428058.eps
which may become hazardous due to a failure of the basic protection that is not
visible to the user (indirect contact) (for example metallic casing of a machine).
The type of protection to be implemented under these circumstances is called "fault
IΔn = 300 mA protection".
This protection can be ensured by bonding and connection to earth of the accessible
conductive parts and the use of an earth fault protection device. In the TT method of
earthing, this earth fault protection device shall be a residual current device with
Ra max = 166 Ω adequate sensitivity.
A second insulation barrier also ensures protection.
Level 3
DB428057.eps
2- Fault Indirect
DB428076.eps
Fire outbreak Many fires of electrical origin are caused by the creation and propagation of electric
A arcs in building materials, in the presence of moisture, dust, pollution, etc.
These arcs appear and develop due to the wear and tear or ageing of the insulating
materials. The fire hazard occurs when the leakage currents reach a few hundred
milliamps for a few seconds.
For fault currents of this magnitude, residual current devices with a sensitivity of
300 mA or 500 mA trip in less than a second, whether they be instantaneous,
selective or time-delayed.
Id < 300 mA IEC 60364-4-42 (subclause 422.3.10) states that it is mandatory to install a residual
current device with a sensitivity less than or equal to 300 mA:
Wet dust
b on premises with a risk of explosion (BE3)
b on premises with a risk of fire (BE2)
b in agricultural and horticultural buildings
b for circuits supplying fair, exhibitions and entertainment equipment
b on temporary outdoor leisure facilities.
In some countries, installation rules and/or local safety regulations require a
sensitivity of 300 mA.
DB428083.eps
The basic characteristics of the operation of a RCD are shown opposite:
b a magnetic toroid surrounds all the active conductors, including the neutral
conductor, if present, supplying an electrical circuit. The magnetic flux generated in
V V the magnetic toroid depends at all times on the vector sum of the currents in the
I1 I2 active conductors ➡
b in the case of a single-phase circuit, the incoming current I1 (from source to use) is
V considered to be positive, while the outgoing
➡
current I2 is considered to be negative
I3 ➡ ➡
b for a healthy electrical circuit, I1 + I2 = 0, there is no magnetic flux:
no electromotive force created in the secondary winding
B
➡
b in case of earth leakage, a fault current Id flows through the magnetic toroid from
source to use but returns through the protective conductors (TN method of earthing)
or via the earth (TT method of earthing).
➡ ➡
Consequently,
➡
the sum of the incoming and
outgoing currents is not zero, i.e. I1 + I2 = Id, and this difference in current creates a
magnetic flux. The difference in current is called "residual current"
b the resulting alternating flux in the magnetic toroid consequently ➡
induces an
V electromotive force in the secondary winding so that a current I3 flows through the
V V I3
I1 I2 tripping control winding➡
of the device.
If the residual current Id exceeds the value (the threshold) required to trip the device
V directly or via an electronic relay, this will cause the associated disconnection device
Id (switch or circuit breaker) to open
With the Voltage Dependent (VD) technology, the summation current transformer
measures residual current. An electronic circuit detects the tripping level and then
sends an order to tripping unit to open the protected circuit
b in this case, the power supply of electronic circuit and energy for tripping unit come
from the line voltage
b with this technology, the RCD will be able to detect but not to trip if the line voltage
is too low, because the electronic circuit and tripping units needs to be powered.
DB428278.eps
Compact Vigirex
NSXm160H
Vigi NG125
Socket
Toroid
PB113740-90.eps
High-sensitivity relay
Test button
Electronic interface
Tripping mechanism
N
DB406620.eps
1 3
High-sensitivity
relay
T
Toroid Electronic
circuit
b The toroid provides information on the leakage current and the power required to
trip the device.
b The electronic circuit and the relay are not connected to the electrical network.
Power is provided only by the leakage current.
b Even if there is an accidental break of the neutral conductor or a voltage drop, the
entire electromechanical system will continue to operate, allowing the residual
current device to trip.