Lightning Protection Device For Filed Instruments
Lightning Protection Device For Filed Instruments
INSTALLATION
Operating temperature:
No Safety approval: -40 to +85°C (-40 to +185°F)
FM approval:
-40 to +80°C (-40 to +176°F) (T6)
ATEX approval:
MODEL: MD6N–24–[1][2][3] -40 to +80°C (-40 to +176°F) (T5)
■ SELECTABLE WIRING CONDUITS SPECIFIC TO EACH APPROVAL -40 to +75°C (-40 to +167°F) (T6)
‘N’ marked combinations are not selectable.
Mounting: Screwed into an electrical conduit of outdoor
APPROVAL
0 3 4 enclosures
WIRING CONDUIT
0 Y N N Weight: 330 g (0.73 lb)
1 Y Y Y
2 Y N Y
PERFORMANCE
Discharge voltage (peak voltage)
Line to line: 30 V min.
ORDERING INFORMATION
Line to ground: ±160 V min.
• Code number: MD6N–24–[1][2][3]
Max. surge voltage
Specify a code from below for each of [1] through [3].
Line to line: 40 V max.
(e.g. MD6N-24-00B)
Line to ground: ±650 V max.
For the safety approval code 4, specify the product’s
(The maximum voltage that could pass through the surge
destination country using Ordering Information Sheet (No.
protector. Protected equipment must be able to withstand
ESU-8284).
this voltage for a very short time period.)
Response time:
[1] SAFETY APPROVAL Line to line: ≤ 4 nsec.
0: None Line to ground: ≤ 20 nsec.
3: FM explosion-proof Leakage current:
4: ATEX flameproof Line to line: ≤ 5 μA @ 30 V DC
Confirm selectable combinations of approval and wiring Line to ground: ≤ 5 μA @ ±160 V DC
conduit types in the table. Discharge current capacity: 10000 A (8/ 20 μsec.)
Max. load current: 100 mA
https://www.m-system.co.jp/
MODEL: MD6N-24
Internal series resistance: Approx. 22 Ω including return
Max. line voltage
Without safety approval: 30 V DC
With safety approval: 28 V DC
Capacitance @ 1 kHz:
Line to line: ≤ 2500 pF
Line to ground: ≤ 100 pF
CONNECTION EXAMPLES
Field (Protected Equipment Enclosure) Conduit Mount Central Station
Type SPD
Protected Equipment MDP-24-1 Current Loop Supply
+ yellow red + + From Field
S S S+ P+ +
blue black
Cable IN
– – –
S S S– P– –
To Central Station
G
green (Protected Equiment)
G
Connect the Conduit Mount Type SPD’s green leadwire to the ground terminal inside the protected equipment enclosure to
ground through the enclosure’s outside ground terminal.
If the enclosure does not have an inside ground terminal, connect the green leadwire directly to the outside ground wire
pulled inside the enclosure. Keep the ground wire as short as possible.
https://www.m-system.co.jp/
MODEL: MD6N-24
EXTERNAL DIMENSIONS unit: mm [inch]
2–G 1/2, 1/2 NPT or M20x1.5
32 [1.26]
leadwires
22Ω
+ red yellow +
black blue
– –
green To Equipment
*2
G Ground
*1. The zenor diode has polarity. Zero-cross signal cannot be connected.
*2. Use only when the signal line requires functional grounding.
This is NOT for surge protection.