SPEC 46302

1/C CU 15KV 220 NL-EPR 133% TS SIMpull® PVC MV-105


Type MV-105 Single Conductor Copper, 220 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 133% Insulation Level, Tape
Shield, SIMpull® Polyvinyl Chloride (PVC) Jacket, Dual Rated UL/CSA

1 3 6

6 5 4 3 2 1

Images not to scale. See Table 1 for Dimensions

CONSTRUCTION:
1. Conductor: Class B compressed stranded bare copper per ASTM B3 and ASTM B8
2. Conductor Shield: Semi-conducting cross-linked copolymer
3. Insulation: 220 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 133% Insulation Level,
4. Insulation Shield: Stripable semi-conducting cross-linked copolymer
5. Copper Tape Shield: Helically wrapped 5 mil copper tape with 25% overlap
6. Overall Jacket: Polyvinyl Chloride (PVC)

APPLICATIONS AND FEATURES:


Southwire’s 15KV cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, and where su-
perior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not
in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated at -35°C
for cold bend. ST1 (low smoke) Rated for sizes 1/0 and larger. PVC jacket is made with SIM technology and has a coefficient of
friction COF of 0.2. Cable can be installed in conduit without the aid of lubrication. Rated for 1000 lbs./FT maximum sidewall
pressure.

SPECIFICATIONS:
• ASTM B3 Soft or annealed copper
• ASTM B8 Concentric-lay-standard copper
• UL 1072 - Medium Voltage Power Cables
• ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable & ICEA S-97-682 5-46 KV Utility
• UL 1685/FT4-ST1 Vertical-Tray Fire Propagation and Smoke Release Test (1/0 AWG and Larger)
• IEEE 1202 -Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 AWG and Larger)
• AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV
• CSA C68.10 - Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
• CSA C22.2 No.230 - Tray Cables - Rated TC-ER (1/0 AWG and Larger)
• CSA C22.2 No. 2556 / UL 2556 - Cable Test Methods

SAMPLE PRINT LEGEND:


SOUTHWIRE [SYMBOL - LIGHTING BOLT] #P# (UL/CSA) 1/C [#AWG or #kcmil] CU 220 MILS NL-EPR 15KV 133% INS LEVEL
25% TS MV-105 FOR CT USE SUN. RES. TC-ER(CSA 1/0 LARGER) FOR DIRECT BURIAL FT4 -ST1 YEAR (NESC) [SEQUENTIAL
FEET MARKS]

Southwire Company, LLC | One Southwire Drive, Carrollton, GA 30119 | www.southwire.com


Copyright © 2017 Southwire Company, LLC. All Rights Reserved SPEC 46302_PSS DIVISION DATE: 07/26/2018 Rev:2.0.07C
SPEC 46302

Table 1 – Weights & Measurements


Diameter over
Cond. Insul. Insul. Jacket Approx. OD Approx. Max Pull Min Bend- Conduit
Stock Cond. Size (1) (3) Shield Thickness¹ (6) Weight Tension ing Radius Size*
Code AWG inches inches inches mils inches lbs./MFT lbs. inches inches
953638 ◊
2 0.283 0.760 0.820 80 1.000 639 531 12.0 3
955104 1 0.322 0.799 0.859 80 1.039 715 670 12.5 3
955989◊ 1/0 0.362 0.839 0.899 80 1.079 809 845 12.9 3
955997 ◊
2/0 0.405 0.882 0.942 80 1.122 922 1065 13.5 3.5
956003 3/0 0.456 0.933 0.993 80 1.173 1063 1342 14.1 3.5
956011 ◊
4/0 0.512 0.989 1.049 80 1.229 1235 1693 14.7 3.5
956029 ◊
250 0.558 1.044 1.104 80 1.284 1390 2000 15.4 4
956037◊ 350 0.661 1.147 1.207 80 1.387 1767 2800 16.6 4
956045 ◊
500 0.789 1.275 1.335 80 1.515 2314 4000 18.2 5
643755 ◊
600 0.866 1.361 1.421 80 1.601 2680 4800 19.2 5
956052◊ 750 0.968 1.463 1.523 80 1.703 3210 6000 20.4 5
956060 ◊
1000 1.117 1.612 1.672 110 1.912 4183 8000 22.9 6
581886 1250 1.250 1.767 1.827 110 2.067 5074 10000 24.8 6
550811 2000 1.583 2.138 2.198 110 2.438 7682 16000 29.3
All dimensions are nominal and subject to normal manufacturing tolerances
* Conduit size based on 3 phase 40% fill-factor without ground
¹ Comply with ICEA S-93-639 Appendix C for jacket thickness determination
◊ Standard stock item
Table 2 – Electrical and Engineering Data
Shield Short Allowable Ampacities
Resistance Reactance Positive Zero Circuit 900C/1050C
Cond. DC AC XC XL Sequence Sequence Current
Size @ 250C @ 900C @ 60Hz @ 60Hz Impedance* Impedance* 6 Cycles In Duct † In Air ‡
Stock Code AWG Ω/MFT Ω/MFT MΩ*MFT Ω/MFT Ω/MFT Ω/MFT Amps Amps Amps
953638◊ 2 0.162 0.203 0.053 0.051 0.203 + j0.051 0.573 + j0.418 2700 155 / 165 195 / 215
955104 1 0.129 0.161 0.049 0.049 0.162 + j0.049 0.531 + j0.400 2827 175 / 185 225 / 250
955989 ◊
1/0 0.102 0.128 0.045 0.047 0.128 + j0.047 0.496 + j0.383 2957 200 / 215 260 / 290
955997◊ 2/0 0.081 0.101 0.042 0.045 0.102 + j0.045 0.467 + j0.366 3097 230 / 245 300 / 335
956003 3/0 0.064 0.080 0.039 0.043 0.081 + j0.043 0.443 + j0.346 3263 260 / 275 345 / 385
956011◊ 4/0 0.051 0.064 0.036 0.042 0.065 + j0.042 0.423 + j0.327 3445 295 / 315 400 / 445
956029 ◊
250 0.043 0.054 0.034 0.041 0.055 + j0.041 0.409 + j0.309 3624 325 / 345 445 / 495
956037 ◊
350 0.031 0.039 0.030 0.039 0.040 + j0.039 0.384 + j0.279 3959 390 / 415 550 / 610
956045◊ 500 0.022 0.028 0.026 0.037 0.029 + j0.037 0.361 + j0.248 4376 465 / 500 685 / 765
643755 ◊
600 0.018 0.024 0.024 0.036 0.348 + j0.229 0.024 + j0.036 4655 505 / 544 765 / 855
956052 ◊
750 0.014 0.019 0.022 0.035 0.020 + j0.035 0.334 + j0.210 4987 565 / 610 885 / 990
956060◊ 1000 0.011 0.015 0.020 0.034 0.016 + j0.034 0.315 + j0.185 5472 640 / 690 1060 / 1185
581886 1250 0.009 0.013 0.019 0.033 0.014 + j0.033 0.298 + j0.165 5976 715 / 770 1210 / 1350
550811 2000 0.005 0.010 0.016 0.032 0.011 + j0.032 0.263 + j0.127 7183 940 / 1010 1575 / 1755
* Calculations are based on three cables triplexed / 5 mil 25 % over lapping copper tape shield / Conductor temperature of 90°C / Shield temperature of 45°C /
Earth resistivity of 100 ohms-meter
† Ampacities are based on TABLE 310.60(C)(77) Detail 1. of the 2014 National Electrical Code (20°C Ambient Earth Temperature, Thermal Resistance ROH of 90)
‡ Ampacities are based on TABLE 310.60(C)(69) of the 2014 National Electrical Code (40°C Ambient Air Temperature)
◊ Standard stock item

Southwire Company, LLC | One Southwire Drive, Carrollton, GA 30119 | www.southwire.com


Copyright © 2017 Southwire Company, LLC. All Rights Reserved SPEC 46302_PSS DIVISION DATE: 07/26/2018 Rev:2.0.07C