This document provides tables with information for current-carrying capacity and voltage drop of 60°C thermosetting insulated flexible cables. Table 4F1A lists the current ratings in amperes for single-phase AC or DC, three-phase AC, and two single-core cables touching, based on conductor cross-sectional area and operating temperature. Table 4F1B gives the voltage drop in mV/A/m for various cable configurations, also based on cross-sectional area and operating temperature. Notes provide additional guidance on reducing ratings if cables are wound on drums or may be covered.

Uploaded by

Eddie Twe
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
71 views

Table 4f1a and 4f1b

This document provides tables with information for current-carrying capacity and voltage drop of 60°C thermosetting insulated flexible cables. Table 4F1A lists the current ratings in amperes for single-phase AC or DC, three-phase AC, and two single-core cables touching, based on conductor cross-sectional area and operating temperature. Table 4F1B gives the voltage drop in mV/A/m for various cable configurations, also based on cross-sectional area and operating temperature. Notes provide additional guidance on reducing ratings if cables are wound on drums or may be covered.

Uploaded by

Eddie Twe
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

TABLE 4F1A

Ambient temperature: 30°C


CURRENT-CARRYING CAPACITY (amperes) Conductor operating temperature: 60°C
Conductor cross- Single-phase AC or DC Three-phase AC Single-phase AC or DC
60oC thermosetting insulated flexible cables with sheath, sectional area
non-armoured
(COPPER CONDUCTORS) 1 two-core cable with or without 1 three-core, four-core or five-core 2 single-core cables, touching
protective conductor cable
Reproduced from BS7671:2018 Wiring Regulations
NOTES: 1 2 3 4
1.The current ratings tabulated are for cables in free air but may also be
used for cables resting on a surface. If the cable is to be wound on a
mm2 (A) (A) (A)
drum on load the ratings should be reduced in accordance with NOTE 2 4 30 26 -
below and for cables which may be covered, NOTE 3 below.
6 39 34 -
2.Flexible cables wound on reeling drums:
The current ratings of cables used on reeling drums are to be reduced by
IO 51 47 -
the following factors: 16 73 63 -
a) Radial type drum b) Ventilated cylindrical type drum
ventilated: 85% 1 layer of cable: 85% 25 97 83 -
unventilated: 75% 2 layers of cable: 65% 35 - 102 140
3 layers of cable: 45%
4 layers of cable: 35% 50 - 124 175
A radial type drum is one where spiral layers of cable are accommodated 70 - 158 216
between closely spaced flanges; if fitted with solid flanges the ratings
given above should be reduced and the drum is described as non-
95 - 192 258
ventilated. If the flanges have suitable apertures the drum is described 120 - 222 302
as ventilated.
150 - 255 347
A ventilated cylindrical cable drum is one where layers of cable are 185 - 291 394
accommodated between widely spaced flanges and the drum and end
flanges have suitable ventilating apertures. 240 - 343 471
3.Where cable may be covered over or coiled up whilst on load, or the air 300 - 394 541
movement over the cable restricted, the current rating should be 400 - - 644
reduced.
It is not possible to specify the amount of reduction but the table of 500 - - 738
rating factors for reeling drums can be used as a guide. 861
630 - -

UK T 020 7241 8787 | F 020 7241 8700 | [email protected] | www.elandcables.com


International T +44 20 7241 8740 | F +44 20 7241 8700 | [email protected]
TABLE 4F1B

VOLTAGE DROP (per ampere per metre) Conductor operating temperature: 60°C
60°C thermosetting insulated flexible 2 single-core cables, touching
Conductor cross- Two-core Two-core cable, 1 three-core, four-core
cables with sheath, non-armoured sectional area cable DC single-phase AC or five-core cable,
(COPPER CONDUCTORS) DC Single-phase AC*
three-phase AC

Reproduced from BS7671:2018 Wiring 1 2 3 4 5 6


Regulations (mm2) (mV/A/m) (mV/A/m) (mV/A/m) (mV/A/m) (mV/A/m)
4 12 12 10 - -
6 7.8 7.8 6.7 - -
10 4.6 4.6 4.0 - -
16 2.9 2.9 2.5 - -
R X Z R X Z R X Z
25 1.80 1.80 0.175 1.85 1.55 0.150 1.55 - - - -
35 - - - - 1.10 0.150 1.15 1.31 1.31 0.21 1.32
50 - - - - 0.83 0.145 0.84 0.91 0.91 0.21 0.93
70 - - - - 0.57 0.140 0.58 0.64 0.64 0.20 0.67
95 - - - - 0.42 0.135 0.44 0.49 0.49 0.195 0.53
120 - - - - 0.33 0.135 0.36 0.38 0.38 0.190 0.43
150 - - - - 0.27 0.130 0.30 0.31 0.31 0.190 0.36
185 - - - - 0.22 0.130 0.26 0.25 0.25 0.190 0.32
240 - - - - 0.170 0.130 0.21 0.190 0.195 0.185 0.27
300 - - - - 0.135 0.125 0.185 0.150 0.155 0.180 0.24
400 - - - - - - - 0.115 0.120 0.175 0.21
500 - - - - - - - 0.090 0.099 0.170 0.20
630 - - - - - - - 0.068 0.079 0.170 0.185
Note: *A larger voltage drop will result if the cables are spaced.