IntesisBox PA-AW-MBS-1 User Manual
IntesisBox PA-AW-MBS-1 User Manual
PA-AW-MBS-1 v.2.0
User Manual
Issue Date: 10/2016
r2.1
Order Code:
Information in this document is subject to change without notice. No part of this publication
may be reproduced, stored in a retrieval system or transmitted in any form or any means
electronic or mechanical, including photocopying and recording for any purpose other than
the purchaser’s personal use without the written permission of Intesis Software S.L.
TRADEMARKS
All trademarks and trade names used in this document are acknowledged to be the
copyright of their respective holders.
INDEX
1. Presentation .................................................................................................... 4
2. Connection ...................................................................................................... 5
2.1 Monobloc system. Aquarea Control Panel connection. ........................................ 5
2.2 Bibloc system. Aquarea indoor unit connection.................................................. 5
2.3 Connection to the EIA485 bus ......................................................................... 6
3. Modbus Interface Specification ........................................................................... 7
3.1 Modbus physical layer .................................................................................... 7
3.2 Modbus Registers .......................................................................................... 7
3.2.1 General System Control ........................................................................... 7
3.2.2 Climate Configuration .............................................................................. 8
3.2.3 Tank Configuration .................................................................................. 9
3.2.4 Consumption .......................................................................................... 9
3.2.5 Maintenance ......................................................................................... 10
3.2.6 Unit Configuration ................................................................................. 11
3.2.7 System Configuration ............................................................................ 12
3.3 Register dependencies ................................................................................. 13
3.4 DIP-switch Configuration Interface ................................................................ 15
3.5 Implemented Functions ................................................................................ 16
3.6 Device LED indicator .................................................................................... 17
3.7 EIA485 bus. Termination resistors and Fail Safe Biasing mechanism .................. 17
4. Technical Specifications ................................................................................... 19
5. List of supported Panasonic Aquarea Unit Types ................................................. 19
6. Error Codes ................................................................................................... 20
1. Presentation
FJ-RC-MBS-1 device
Reduced dimensions. 93 x 53 x 58 mm.
Modbus RTU
EIA485 network Modbus RTU
master
device
PA-AW-MBS-1
Up to 63
Panasonic PA-AW-MBS-1
SCADA
Aquarea
PLC
systems
DDC
BMS
HMI
Controller
etc
PA-AW-MBS-1
1
Values shown in the PA-AW-MBS-1 and the Control Panel may differ due to the non-synchronous behavior of the
Panasonic Aquarea system.
2. Connection
The interface comes with a cable and the corresponding connectors for direct connection to
the Aquarea system and with a plug-in terminal block of 2 poles for connection to a Modbus
RTU EIA485 network. If you have installed a Monobloc system, move to section 2.1. On
the other hand, if you have installed a Bibloc system, move to section 2.2.
AW Unit
IntesisBox®
PA-AW-MBS-1
EIA485
A+ B-
Modbus RTU
EIA485
Bus
Panasonic cable
AW Unit
IntesisBox®
PA-AW-MBS-1
EIA485
A+ B-
Supplied cable
Modbus RTU
EIA485
Bus
AW Unit
IntesisBox®
PA-AW-MBS-1
EIA485
A+ B-
Modbus RTU
EIA485 Bus
Important: Values shown in the PA-AW-MBS-1 and the Control Panel may differ
! due to the non-synchronous behavior of the Panasonic Aquarea system.
2
If a non valid value is sent, the value shown in the Modbus register is “-128” and in the remote controller is “---“.
3
Decidegrees or grades units can be selected using the S4 switch. See section1.1 for more details.
4
This mode will be only active when “Force Mode” or “Pump Down” registers are active. It can’t be set by the
user.
5
These working modes are only available through the Modbus registers of the PA-AW-MBS-1.
3.2.4 Consumption
6
If a non valid value is sent, the value shown in the Modbus register is “-128” and in the remote controller is “---“.
If tank is not connected, a value 0x8000 is sent and overwrites the “-128” value.
3.2.5 Maintenance
7
This register can be only activated through the remote controller.
0: Off
1: On
Heater Status
68 69 R Yes 0: Off
1: On
Heater Mode
69 70 R No 0: Off
1: On
Alarm Status
70 71 R N/A 0: No alarm
1: Alarm
Dry Concrete Temperature
71 72 R Yes
25ºC to 65ºC (x1 or x10 values)3
Air purge
72 73 R/W Yes 0: Off
1: On
Pump Speed
73 74 R/W Yes
1 to 7
ERP operation
74 75 R/W Yes 0: Normal
1 to 80
ERP parameters
0: Hz
75 76 R Yes 1: Td
2: FM
3: I1
ERP data
76 77 R Yes
-9 to 9
Slow/Fast test
0: Normal
1: Slow Time
77 78 R Yes
2: Fast Time
3: Slow Day
4: Fast Day
Thermoshift Presets are special functions designed to set a temperature offset in the HEAT,
COOL and TANK modes so user can adjust the temperature to their needs. These functions
are only configurable from the PA-AW-MBS-1 Modbus interface. They are not modifiable
from the remote controller of the Aquarea system.
8
Default value will be the maximum: 5ºC for Climate and 10ºC for Tank.
9
When this signal is set to 1, the gateway is reset and all values in the remote controller are set in the Modbus
registers losing all previous configuration.
18 19 Outdoor Temp for Heating off (Min) Selection N/A N/A Protocol10: 2.01 - - -
C
l
19 20 Outdoor Temp for Heating off (Min) N/A N/A Protocol10: 2.01 - - -
i
m 21 22 Heater Capacity Selection N/A N/A Protocol10: 2.01 - - -
a
t 22 23 Max Heater Capacity N/A N/A Protocol10: 2.01 - - -
e Indoor unit has
23 24 Cooling Setpoint Temperature N/A N/A - - -
Cool mode
Tank Connection
30 31 Tank On/Off 81 82 - - -
0xAA: On
Tank Connection
31 32 Tank Working Mode 81 82 - - -
0xAA: On
Tank Connection
32 33 Tank Water Temp 81 82 - - -
0xAA: On
Tank Connection Heating Priority
T 34 35 Tank Heat-up Interval 81 82 83 84
0xAA: On 0x55: Off
a Tank Connection Heating Priority
n 35 36 Operation Interval 81 82 83 84
0xAA: On 0x55: Off
k Tank Connection Booster Heater
36 37 Booster Delay Time 81 82 88 89
0xAA: On On: 0xAA (Protocol: 2.01)
Tank Connection Sterilization
37 38 Sterilization On 81 82 85 86
0xAA: On 0xAA: On
Tank Connection Sterilization
38 39 Sterilization Boiling Temp 81 82 85 86
0xAA: On 0xAA: On
Tank Connection Sterilization
39 40 Sterilization Continuing Time 81 82 85 86
0xAA: On 0xAA: On
M
a 56 57 Warning Tank Temp. Status N/A N/A Protocol10: 2.01 - - -
i
n 57 58 Defrost Status N/A N/A Protocol10: 2.01 - - -
t
e
62 63 Pump Down N/A N/A Protocol10: 1.01 - - -
n
a
64 65 Force Deice N/A N/A Protocol10: 2.01 - - -
n
c
65 66 Service SW Code N/A N/A Protocol10: 2.01 - - -
e
Tank Connection
82 83 Solar Priority 81 82 - - -
0xAA: On
U 83 84 Heating Priority 81 82
Tank Connection
- - -
n 0xAA: On
i Indoor Unit has Cool
84 85 Cooling Priority N/A N/A Protocol10: 2.01 N/A N/A
t mode
Tank Connection
c 85 86 Sterilization 81 82 - - -
0xAA: On
o
n 86 87 Base Pan Heater N/A N/A Protocol10: 2.01 - - -
f
i 87 88 Anti-Freezing N/A N/A Protocol10: 2.01 - - -
g
Tank Connection
88 89 Booster Heater N/A N/A Protocol10: 2.01 81 82
0xAA: On
If conditions specified in this table are not matched for each signal, the register shows a not valid value (0x8000) and the register’s entry
is blocked.
10
Modbus protocol communication version used by the Aquarea system.
© Intesis Software S.L. - All rights reserved URL http://www.intesis.com 14 / 20
This information is subject to change without notice Email [email protected]
IntesisBox® is a registered trademark of Intesis Software SL tel +34 938047134
IntesisBox® PA-AW-MBS-1 User’s Manual r2.0 eng
They are DIP-switches S1*, S3 and S4 on the device, in the following location:
S1*
S1*
ON 1 2 3 4
AW Unit * DIP-Switch S1 is
not used by current
version of PA-AW-
IntesisBox® MBS-1
PA-AW-MBS-1
EIA485
A+ B-
ON 1 2 3 4 5 6 7 8 ON 1 2 3 4
P7 P5
S3 S4
S3 S4
The following tables apply for configuration of the interface through these DIP-switches:
11
Default value
Binary
Switches
value Decimal value Description
1 2 3 4 5 6 7 8
b0…b8
xxxxxx00 0 x x x x x x 2400bps
xxxxxx10 1 x x x x x x 4800bps
xxxxxx01 2 x x x x x x 9600bps (- default value)
xxxxxx11 3 x x x x x x 19200bps
Table 3.3 S4 Switch - Other: Degrees/Decidegress (x10) and EIA485 termination resistor
Binary
Decimal Switches
value Description
value 1 2 3 4
b0…b4
16: Write Multiple Registers (Although this function is allowed, the interface does not
allow write operations on more than 1 register with the same request, this means
that length field should always be 1 when using this function for writes).
12
Only in the interfaces connected at both ends of the bus must be activated the termination resistor. More
information can be found in section 3.7.
L1 (yellow)
Operation ON OFF Meaning
Blinking 500 ms 500 ms Communication error
Flashing 100 ms 1900 ms Normal operation (configured and working)
In order to prevent fail status detections by the receivers "listening" the bus when all the
transmitters outputs are in three-state (high impedance), it is also required a fail-safe
biasing mechanism. This mechanism provides a safe status (a correct voltage level) in the
bus when all the transmitters’ outputs are in three-state.
The PA-AW-MBS-1 device includes an on-board terminator resistor of 120Ω that can be
connected to the EIA485 bus by using DIP-switch P5 (see below).
A fail safe biasing circuit has also been included in the board of PA-AW-MBS-1, it can be
connected to the EIA485 bus by placing the internal jumper JP1 (see details below).
This fail safe biasing of the EIA485 bus must only be supplied by one of the devices
connected to the bus. As this fail safe biasing circuit also provides a termination resistance,
only one of both must be selected in the PA-AW-MBS-1 device, fail safe biasing (jumper JP1
placed) or terminator resistor (DIP-switch P5 position 4 to ON).
The device providing fail safe biasing or terminator resistor should be the one connected at
one end of the bus. At the other end of the bus, if there is also a PA-AW-MBS-1 device,
select the 120Ω terminator resistor through DIP-switch P5, or if there is a master device not
providing internal 120Ω terminator resistor, connect an external 120Ω resistor in the bus
terminal block connection of such master device.
Some Modbus RTU EIA485 master devices can provide also internal 120Ω terminator
resistor and/or fail safe biasing (consult the technical documentation of the master device
connected to the EIA485 network in every case).
Location of jumpers and DIP-switches for EIA485 bus Termination resistor or Fail Safe
Biasing selection:
K2 K1
JP1
ON
1 2 3 4
P5
4. Technical Specifications
Enclosure ABS (UL 94 HB). 2,5mm thickness. Size: 93 x 53 x 58 mm. Weight: 85g
Color Light Grey
Power supply Supplied through Modbus bus.
1 x Device status
LED indicators 1 x Error indicator
Per terminal: solid wires or stranded wires (twisted or with ferrule)
Terminal wiring (for 1 core: 0.75 … 1.25mm2
low-voltage signals) 2 cores: 0.75 … 1.25mm2
3 cores: not permitted
AW system K1 (Aquarea unit) (4 x 0.22 - Shielded)
connection K2 (Remote controller) (4 x 0.22 - Shielded)
Modbus RTU port
1 x Serial EIA485 (Plug-in screw terminal block 2 poles). SELV
(EIA485 Port)
Operating
From 0ºC to 40ºC
Temperature
Operating Humidity <95% RH, non-condensing
Isolation Voltage 1000 VDC
Isolation Resistance 1000 MΩ
RoHS conformity Compliant with RoHS directive (2002/95/CE).
CE conformity to EMC directive (2004/108/EC) and Low-voltage directive
Certifications (2006/95/EC)
EN 61000-6-2; EN 61000-6-3; EN 60950-1; EN 50491-3; EN 50090-2-2;
AW System LED
connection Indicator
DIP
Switches
DIP
Switches
58 mm
EIA485
Port
93 mm
53 mm
6. Error Codes
Error in
Error Code
Remote Error Description
(Modbus)
Controller
000 H00 No abnormality detected
042 H12 Indoor / outdoor capacity unmatched
224 H15 Outdoor compressor temperature sensor abnormality
225 H23 Indoor refrigerant liquid temperature sensor abnormality
226 H24 Unknown
227 H38 Indoor / outdoor mismatch
232 H42 Compressor low pressure abnormality
228 H61 Unknown
229 H62 Water flow switch abnormality
230 H63 Refrigerant low pressure abnormality
231 H64 Refrigerant high pressure abnormality
236 H70 Indoor backup heater OLP abnormality
038 H72 Tank temperature sensor abnormality
156 H76 Indoor - control panel communication abnormality
020 H90 Indoor / outdoor abnormal communication
002 H91 Tank booster heater OLP abnormality
222 H95 Indoor / outdoor wrong connection
233 H98 Outdoor high pressure overload protection
036 H99 Indoor heat exchanger freeze prevention
193 F12 Pressure switch activate
195 F14 Outdoor compressor abnormal rotation
196 F15 Outdoor fan motor lock abnormality
197 F16 Total running current protection
200 F20 Outdoor compressor overheating protection
202 F22 IPM overheating protection
203 F23 Outdoor DC peak detection
204 F24 Refrigerant cycle abnormality
234 F25 Cooling / heating cycle changeover abnormality
205 F27 Pressure switch abnormality
208 F36 Outdoor air temperature sensor abnormality
209 F37 Indoor water inlet temperature sensor abnormality
013 F38 Unknown
212 F40 Outdoor discharge pipe temperature sensor abnormality
214 F41 PFC control
215 F42 Outdoor heat exchanger temperature sensor abnormality
216 F43 Outdoor defrost temperature sensor abnormality
210 F45 Indoor water outlet temperature sensor abnormality
207 F46 Outdoor current transformer open circuit
237 F48 Outdoor EVA outlet temperature sensor abnormality
238 F49 Outdoor bypass outlet temperature sensor abnormality
235 F95 Cooling high pressure overload protection
65535 N/A Communication error between PA-AW-MBS-1 and the AW unit
In case you detect an error code not listed, contact your nearest Panasonic technical
support service.